200 ⇔ 240V
+α
Now-a-days, control panel cooling units are built to
have no non-flon-gas emissions. At Apiste, we not only
eliminate the cost of flon-gas by using non-flon-gas, we
also provide a line-up of products with features that reduce
our customers' workload.
2
Uses the minimum
required energy
4
Has no fin and doesn't require a filter
5
Resistant to water
3
Reasons for non-flon-gas coolers
Flon-gas was used in air conditioning units as a refrigerant. It was commonly used because it
was chemically stable, had low toxicity and was not explosive. But, it is now regulated due to the
harmful effects it has on the global environment.
1. Install products in an appropriate location and properly maintain 4. Take appropriate measures in case of flon-gas leakage
the environment
2. Regular, thorough product inspections 5. Report leakage (if it is more than 1000 CO2-t/year)
3. Keep records and maintain product maintenance history 6. Contract loading and collection of flon-gas during device maintenance
6
Use non-flon-gas from now on.
Non-flon-gas refrigerants have 0 Ozone depletion potential and their potential to contribute to global
warming is much lower than alternative flon-gases.
Non-flon-gas refrigerants with low Global warming potential are not required to be collected and
disposed off by specific companies.
There are also no obligations for regular inspections and they do not fall under the Act Concerning
the Recovery and Destruction of Fluorocarbons.
Our control panel cooling units can cut the costs incurred by flon-gases by using non-flon-gases in
the ENC-GR-SUS/GR-eco/GR series.
HFC-134a
Refrigerant CO 2 HFO-1234yf
(Substitute Flon-gas)
Ozone depletion
potential 0 0 0
Global warming
potential
1 4 1300
7
Non-flon-gas &
SUS
Model The ENC-GR-SUS series eliminates
flon-gas costs and can also be used in wet
ENC-GR-SUS series
or humid environments.
Outdoors or in wet/humid
environments
HFO-1234yf Refrigerant
200 ⇔ 240V
*Safety standards as of
February 2017, application in process.
4 70W 2480W
Side-mount type
8
Non-flon-gas & SUS model ENC-GR-SUS series
Panels are made fully of stainless steel so that the unit can be used for a long time in harsh environments
such as wet/humid environments or outdoors. The unit is durable and highly weather resistant. Also, in the
inner structure of the unit, the condenser is coated with Cathodic Electrodeposition and the refrigerant pipes
are coated with modified epoxy resin-based coating*, making the unit a highly reliable non-flon-gas Control
panel cooling unit.
*Only the condenser side refrigerant pipes.
Cathodic
Electrodeposition
Coating composed of epoxy
resin is applied using an
electrochemical reaction for
extremely high anti-corrosion
performance without any
unevenness in the coat.
9
ENC-GR-SUS series Non-flon-gas & SUS model
Ultra-slim body
Compact installation with very little protrusion
Depth is only 99 mm
For compact spaces. To install in locations after considering the floor design to make the unit
inconspicuous. The ENC-GRSUS series was made to be slimmer as requested by users. Our large
model is 150 mm deep and our smallest model is only 99 mm with an ultra-slim body.
Depth is only
99 ※
mm
Energy-saving model
Cools only the required sections
800 WLRQ
)RSHUD
212)
700
3RZHUFRQVXPSWLRQUDWLR
600
500
HQHUJ\VDYLQJ
400
300
RQWURO
200 YHUWHUF ENC-GR1500L-SUS
'&LQ ENC-AR1620HD
100
0
0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
/RDGUDWHORDGUDWHGFRROLQJFDSDFLW\
$PELHQWWHPSHUDWXUH&6HWWLQJWHPSHUDWXUH&0HDVXUHPHQWPRGHO(1&*5/HFR(1&*/
10
Non-flon-gas & SUS model ENC-GR-SUS series
Toughness
For longer service life.
Dry mode
The cooling mode of the GR-eco Series features a dry mode that can be switched on when operating in high
humidity locations or environments. Please change the dry mode when, for example, equipments start up
with moisture interference.
Cooling outdoor utility panels Cooling food product ETC rack heat measures
inspection devices
11
Non-flon-gas &
Energy saving
model The ENC-GR-eco series eliminates
flon-gas costs and can also reduce
ENC-GR-eco series electricity costs.
HFO-1234yf Refrigerant
200 ⇔ 240V
*Safety standards as of
February 2017, application in process.
450W 2500 W
Side-mount type
12
Non-flon-gas & Energy saving model ENC-GR-eco series
While ON/OFF control has been adopted for existing series, with ENC-GR-eco series, compressor and fan
in which DC motor is incorporated are controlled by inverter. Not running at full power until reaching 100%
load ratio reduces running costs. Moreover, the temperature does not change when if worksnormally like as
ON/OFF control, so the stress on an electric device can be reduced.
DC cooling fan
DC compressor
DC radiator fan
500 WLRQ
)RSHUD
450 212)
400
3RZHUFRQVXPSWLRQUDWLR
350
HQHUJ\VDYLQJ
300
250
QWURO
UWHUFR
200
YH
150 '&LQ ENC-GR1000EX-eco
100
ENC-G1120EX
50
0
0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%
/RDGUDWHORDGUDWHGFRROLQJFDSDFLW\
$PELHQWWHPSHUDWXUH&6HWWLQJWHPSHUDWXUH&0HDVXUHPHQWPRGHO(1&*5/HFR(1&*/
13
ENC-GR-eco series Non-flon-gas & Energy saving model
Highly durable
6XSSUHVVLQJWKHQXPEHURI 2/5RSHUDWHVWR radiator fan
UHYROXWLRQVWRFRQWLQXH Abolishment of
VWRSFRROLQJRSHUDWLRQ
WKHFRROLQJRSHUDWLRQ
contact relay
equivalent to IP68.
Long-life DC fan
7HPSHUDWXUHRIFRPSUHVVRUKHDG
equivalent to IP68
provides long-time
([LVWLQJPRGHO reassurance.
7HPSHUDWXUHRI
FRPSUHVVRUKHDG
Surface coated
board.
light weight 15 kg
Easy to install
within the
measurement slim body 115 mm
line!
14
Non-flon-gas & Energy saving model ENC-GR-eco series
200 ⇔ 240V
Dry mode
The cooling mode of the GR-eco Series features a dry mode that can be switched on when operating in
humid locations or climates.
15
Non-flon-gas &
Maintenance-free
model The ENC-GR series
eliminates flon-gas costs and can also
ENC-GR series reduce maintenance.
CO 2 Refrigerant
200 ⇔ 240V
450W 1500W
ENC-GR500LE ENC-GR1100LE
Non-drain 460/480W 970/1100W
Top-mount type
16
Non-flon-gas & Maintenance-free model ENC-GR series
Maintenance-free
Finless and filter-less with no clogging*
Conventional Control panel cooling units dissipated heat using fin and tube condensers. So when they were
clogged by oil mist and dust, their cooling capacity dropped significantly, requiring frequent maintenance.
The ENC-GR series has a finless condenser so there are no clogging points on the unit and filters are
unnecessary. Our unit can maintain its cooling capacity for a long period of time without frequent
maintenance. *Excluding non-drain types
Conventionally...
Troublesome filter
replacement was required
Cooling capacity = thermal conductivity x surface area xΔt (air/refrigerant temperature gap)
Flon-gas refrigerant and fin & tube condenser CO2 refrigerant and fin-less condenser
Refrigerant temperature:90°C
⊿t=55℃
⊿t=30℃
temperature:65°C
Refrigerant
Δt 1.8
Air temperature
Air temperature
35°C
35°C
times of
flon-gas!
While the flon-gas refrigerant of older models has a temperature of about 65ºC under
compression, compressed CO2 refrigerant can operate in temperatures as high as 90ºC.
This greatly increases the temperature (Δt) component of refrigerant capacity, thus maintaining
the same level of cooling capacity without enlarging aluminum fin surface area. Eliminating aluminum
fins eliminates clogged sections to essentially achieve a filter-less maintenance-free cooler.
17
ENC-GR series Non-flon-gas & Maintenance-free model
100
95
ENC-GR series
90 Paraffinum liquidum spray
85
Conventional Fin & tube type
80
75
Default values Oil mist deposit Oil mist + dirt
• Product Model: ENC-GR1100L • Measurement Conditions: Air enthalpy test based on JIS B-8615-1 Powder dust mist
• Oil mist deposit conditions: Mineral oil spray
• Dust deposit conditions: JIS Z-8901 test powder. 24 hours in diffused dust
200 ⇔ 240V
18
Non-flon-gas & Maintenance-free model ENC-GR series
Non-drain type
Primary dryer
Secondary
dryer
Primary dryer Heats the water Secondary dryer Heats the air
Correlation between drain water temperature Correlation of environment temperature and
and evaporation rate drying rate
8
(kg/m2•h) comparison
Evaporation rate from the water surface
9
8 7
7 6
6
5
5
4.6 4
4 Approximately Approximately
3
3 4.6 times the 5.0 times the
2 evaporation 2 evaporation
rate rate
1 1
0 0
20 25 30 35 40 45 50 55 60 20 25 30 35 40 45 50 55 60 65 70
Drain water temp (°C) Environment temp (°C)
Evaporation rate when the water is at 50°C is 4.6 times Evaporation rate when the temperature in the
than that when the water is at 30°C. evaporization filter is at 60°C, is 5.0 times than that when
the temperature is at 40°C.
*When external air temperature is at 35°C and humidity is at 85%.
19
A Complete "Non-flon-gas" series Lineup ENC-GR-SUS / GR-eco/ GR series
*Safety standards as of February 2017,
application in process.
Side-mount type
SUS
model
Energy
saving
model
Maintenance-
free model
ENC-GR500L E ENC-GR1100LE
460/480W 970/1100W
Non-
drain
Top-mount type
Maintenance-
free model
20
*Safety standards as of February 2017,
Specification application in process.
50/60Hz
* Cooling Capacity : Rated capacity value when ambient temperature is 35° C and ambient humidity is 40%RH , power source & voltage : 200V.
(Measuring specification :JIS B 8615-1 the inside of a air enthalpy test method)
* Use area temperature / humidity : Use area temperature / humidity is not meant to satisfy all conditions in temperature and humidity.
* Rating Value : 35°
C ambient temperature, ambient humidity RH 40%, power source & voltage : 200V.
* Maximum Value : The ambient temperature at MAX value has specification separately.
* Use the product keeping the use power supply and voltage; within ±10% of rated power supply and rated voltage.
* Consumption current and wattage are values during cooling operation.
* Dust prevention / dust proof protection class : Excluding drain pipe section
* Reading an instruction manual well certainly before use and please use it right.
■ ENC-GR500L-SUS ■ ENC-GR1000L-SUS
900 1800
Internal setting temperature [°C]
700 1400
600 1200
500 1000
400 800
45 45
300 600
35 35
200 400
25
100 200
25
0 0
20 25 30 35 40 45 50 55 20 25 30 35 40 45 50 55
Ambient temperature [°
C] Ambient temperature [°
C]
■ ENC-GR1500L-SUS ■ ENC-GR2500L-SUS
Internal setting temperature [°C]
2500 4000
Internal setting temperature [°C]
3500
Cooling capacity [W]
2000
3000
1500 2500
2000
45
1000 1500 45
35
35
25 1000 25
500
500
0 0
20 25 30 35 40 45 50 55 20 25 30 35 40 45 50 55
Ambient temperature [°
C] Ambient temperature [°
C]
21
*Safety standards as of February 2017,
Specification application in process.
50/60Hz
Consumption
Current (A) Rating :2.3/2.1 Rating :2.0/1.8 Rating :3.0/2.8 Rating :3.9/3.7 Rating :4.5/4.3 Rating :6.6/6.4
Cooling
MAX:2.5/2.3 MAX:2.5/2.4 MAX:4.3/4.1 MAX:6.0/5.7 MAX:5.8/5.7 MAX:6.9/6.6
Ventilation 26 22 38 40 48 93
Consumption
wattage (W) Rating :330 Rating :280 Rating :455 Rating :625 Rating :725 Rating :1090
Cooling
MAX:364 MAX:382 MAX:678 MAX:952 MAX:950 MAX:1130
Vibration Resistance Equivalent to JIS Z 0200 Level1
Refrigerant Protection
Dust prevention / dust proof protection class Equivalent to IP54 (internal circulation route)
Type HFO-1234yf
Fill ration (g) 150 150 240 600 700 680
Noise (dB (A)) Approx. 69 Approx. 69 Approx. 72 Approx. 72 Approx. 73 Approx. 76
External Output Alarm output (No-voltage/normal open: resistive load 250V 2A) Can be switched to no-voltage/normal close by setting
Display Internal temperature/Error/RUN
Environmental Response RoHS Directive
* Cooling Capacity : Rated capacity value when ambient temperature is 35° C and ambient humidity is 40%RH , power source & voltage : 200V.
(Measuring specification :JIS B 8615-1 the inside of a air enthalpy test method)
* Use area temperature / humidity : Use area temperature / humidity is not meant to satisfy all conditions in temperature and humidity.
* Rating Value : 35°
C ambient temperature, ambient humidity RH 40%, power source & voltage : 200V.
* Maximum Value : The ambient temperature at MAX value has specification separately.
* Use the product keeping the use power supply and voltage; within ±10% of rated power supply and rated voltage.
* Consumption current and wattage are values during cooling operation.
* Dust prevention / dust proof protection class : Excluding drain pipe section
* Reading an instruction manual well certainly before use and please use it right.
700 1400
800 600 1200
500 1000
600
400 800
400 300 45 600 45
200 400 35
200 45 35 25
35 100 200
0 25 0 25 0
20 25 30 35 40 45 50 55 20 25 30 35 40 45 50 55 20 25 30 35 40 45 50 55
Ambient temperature [°
C] Ambient temperature [°
C] Ambient temperature [°
C]
3000 4000
2000
Cooling capacity [W]
3500
2500
3000
1500 2000 2500
45 1500 45 2000
1000
35 45
35 1500
1000 35
500 25 1000
25 25
500
500
0 0 0
20 25 30 35 40 45 50 55 20 25 30 35 40 45 50 55 20 25 30 35 40 45 50 55
Ambient temperature [°
C] Ambient temperature [°
C] Ambient temperature [°
C]
22
*Safety standards as of February 2017,
Specification application in process.
50/60Hz
Consumption
Current (A) 定格:1.8/1.6 Rating :2.9/2.8 Rating :4.0/3.8 Rating :4.8/4.6 Rating :6.8/6.6
Cooling
MAX:2.3/2.1 MAX:4.1/4.0 MAX:6.2/6.0 MAX:5.7/5.5 MAX:6.9/6.7
Ventilation 24 47 41 64 110
Consumption
wattage (W) 定格:250 Rating :455 Rating :625 Rating :765 Rating :1135
Cooling
MAX:346 MAX:659 MAX:984 MAX:920 MAX:1155
Vibration Resistance Equivalent to JIS Z 0200 Level1
Refrigerant Protection
Dust prevention / dust proof protection class Equivalent to IP54 (internal circulation route)
Type HFO-1234yf
Fill ration (g) 210 250 650 740 720
Noise (dB (A)) Approx. 64 Approx. 70 Approx. 70 Approx. 77 Approx. 81
External Output Alarm output (No-voltage/normal open: resistive load 250V 2A) Can be switched to no-voltage/normal close by setting
Display Internal temperature/Error/RUN
Environmental Response RoHS Directive
* Cooling Capacity : Rated capacity value when ambient temperature is 35° C and ambient humidity is 40%RH , power source & voltage : 200V.
(Measuring specification :JIS B 8615-1 the inside of a air enthalpy test method)
* Use area temperature / humidity : Use area temperature / humidity is not meant to satisfy all conditions in temperature and humidity.
* Rating Value : 35°
C ambient temperature, ambient humidity RH 40%, power source & voltage : 200V.
* Maximum Value : The ambient temperature at MAX value has specification separately.
* Use the product keeping the use power supply and voltage; within ±10% of rated power supply and rated voltage.
* Consumption current and wattage are values during cooling operation.
* Dust prevention / dust proof protection class : Excluding drain pipe section
* Reading an instruction manual well certainly before use and please use it right.
800 2000
1200
700
600 1000 1500
500 800
45 45
400 600 1000
35
300 45 35
400 25
200 35 500
100 25 200 25
0 0 0
20 25 30 35 40 45 50 55 20 25 30 35 40 45 50 55 20 25 30 35 40 45 50 55
Ambient temperature [°
C] Ambient temperature [°
C] Ambient temperature [°
C]
■ ENC-GR2000EX-eco ■ ENC-GR2500EX-eco
Internal setting temperature [°C]
3500 4500
4000
3000
Cooling capacity [W]
3500
2500
3000
2000 2500
1500 2000
45 45
1500
1000 35
1000 35
500 25 500 25
0 0
20 25 30 35 40 45 50 55 20 25 30 35 40 45 50 55
Ambient temperature [°
C] Ambient temperature [°
C]
23
Specification
50/60Hz
Dust prevention / dust proof protection class Equivalent to IP54 (Internal circulation route)
Type R744
Fill ration (g) 210 330 440 200 390 400
Noise (dB (A)) Approx. 62/62 Approx. 65/65 Approx. 67/67 Approx. 62/62 Approx. 65/65 Approx. 67/67
External Output Alarm output (No-voltage/normal open: resistive load 250V 2A) Can be switched to no-voltage/normal close by setting
Display Display Internal temperature/Error/RUN
Environmental Response RoHS Directive
* Rated capacity value when external temperature / humidity is 35° C -40%RH, internal temperature / humidity is 35°
C -40%RH.
* Use area temperature / humidity : Use area temperature / humidity is not meant to satisfy all conditions in temperature and humidity.。
* Rateing Value : 35°C ambient temperature, ambient humidity RH 40%, power source & voltage : 200V.
* Maximum Value : The ambient temperature at MAX value has specification separately.
* Use the product keeping the use power supply and voltage; within ±10% of rated power supply and rated voltage.
* Consumption current and wattage are values during cooling operation.
* Dust prevention / dust proof protection class : Excluding drain pipe section
* Reading an instruction manual well certainly before use and please use it right.
C]
C]
C]
650 750 600 650
Internal setting temperature [°
550
Cooling capacity [W]
600 700
550 650 500 550
500 600 450 500
45 45
450 40 550 45 400 450 45
40 40
400 35 350 35 400 40
500 35 35
30 30 30
350 450 30 300 350
25 25 25
25
300 400 250 300
20 25 30 35 40 45 50 20 25 30 35 40 45 50 20 25 30 35 40 45 50 20 25 30 35 40 45 50
Ambient temperature [°
C] Ambient temperature [°
C] Ambient temperature [°
C] Ambient temperature [°
C]
C]
C]
C]
C]
C]
C]
1700 1700
Cooling capacity [W]
1600 1600
1500 1600 1500 1600
1500 1500
1400 1400
1400 1400
1300 45 45 1300 45
1300 1300
40 40 45 40
1200 1200 1200 40 1200
35 35 35
1100 30 1100 35 1100 30
30 1100 30
1000 25 1000 25 1000 25 1000 25
20 25 30 35 40 45 50 20 25 30 35 40 45 50 20 25 30 35 40 45 50 20 25 30 35 40 45 50
Ambient temperature [°
C] Ambient temperature [°
C] Ambient temperature [°
C] Ambient temperature [°
C]
24
Specification
50/60Hz
Dust prevention / dust proof protection class Equivalent to IP54 (Internal circulation route)
Type R744
Fill ration (g) 230 320
Noise (dB (A)) Approx. 62/62 Approx. 65/65
External Output Alarm output (No-voltage/normal open: resistive load 250V 2A) Can be switched to no-voltage/normal close by setting
Display Display Internal temperature/Error/RUN
Environmental Response RoHS Directive
* Rated capacity value when external temperature / humidity is 35° C -40%RH, internal temperature / humidity is 35°
C -40%RH.
* Use area temperature / humidity : Use area temperature / humidity is not meant to satisfy all conditions in temperature and humidity.。
* Rateing Value : 35°C ambient temperature, ambient humidity RH 40%, power source & voltage : 200V.
* Maximum Value : The ambient temperature at MAX value has specification separately.
* Use the product keeping the use power supply and voltage; within ±10% of rated power supply and rated voltage.
* Consumption current and wattage are values during cooling operation.
* Dust prevention / dust proof protection class : Excluding drain pipe section
* Reading an instruction manual well certainly before use and please use it right.
■ ENC-GR500LE
50Hz 60Hz
C]
C]
650
600 600
Cooling capacity [W]
Cooling capacity [W]
550 550
500 500
450 45 450 45
400 400 40
40
35
350 35 350
30
300 30 300 25
250 25 250
200 200
20 25 30 35 40 45 50 20 25 30 35 40 45 50
Ambient temperature [°
C] Ambient temperature [°
C]
■ ENC-GR1100LE
50Hz 60Hz
C]
C]
1600 1600
Internal setting temperature [°
Internal setting temperature [°
1400 1400
Cooling capacity [W]
Cooling capacity [W]
1200 1200
1000 1000 45
40
800 45 800
35
40
30
600 35 600
30 25
400 25 400
20 25 30 35 40 45 50 20 25 30 35 40 45 50
Ambient temperature [°
C] Ambient temperature [°
C]
25
External Dimensions〈Non-Flon-Gas & SUS〉
50
28 Power supply and
alarm output terminal
300
11.2
Air outlet Air outlet
700
Air inlet
Air direction louver Diagram of Panel Cutout
(Radiation side) Air inlet [Figure seen from control board outside]
300
(Cooling side)
350
10 330 10
9 312 9 6-φ10
50
50
21
29
Drain pipe
(Outer diameter φ9.5)
400
300
103.3 Air inlet
700
(Radiation side)
43.4
300
279
50
Side-mount type / ENC-GR1000L-SUS (Unit : mm)
Power supply
and alarm
71.2 output terminal
485
Air outlet
(Cooling side)
Air direction louver
1070
50
29
50
485
Drain pipe
580
1070
485
469
50
26
Side-mount type / ENC-GR1500L-SUS (Unit : mm)
50
Nut for attachment to
Power supply main unit 6-M8
71.2
and alarm
output terminal
635
Air outlet
(Cooling side)
Air direction louver
Air outlet
1370
(Radiation side)
Diagram of Panel Cutout
Air inlet [Figure seen from control board outside]
(Cooling side) 400
10 380 10
Air inlet
(Radiation side) 9 362 9 6-φ11
635
21
50
29
635
685
50
Drain pipe
(Outer diameter φ16)
107.2
Air inlet (Radiation side)
1370
63.4
635
664
50
Side-mount type / ENC-GR2500L-SUS (Unit : mm)
Power supply
675
and alarm
output terminal
Air outlet
Air outlet (Cooling side)
Diagram of Panel Cutout
1450
21
50
29
675
795
50
675
634
50
27
External Dimensions〈Non-Flon-Gas & Energy saving〉
25 103
115 10
(Packing) 11.3 277.4 11.3
300
30
Power supply
41.3
and alarm
output connector
173
Air outlet
(Cooling side)
300 Air direction louver
36
11
600
300
11.3 277.4 11.3
41.3
10 257.4 10
6-∅10
41.3
Air inlet Air outlet
171.3
(Radiation side) (Radiation side)
Filter
Drain pipe
300
(Outer diameter φ9.6)
130
600
370
34
217.4
58.7
41.3
Side-mount type / ENC-GR500L-eco (Unit : mm)
350
Air outlet Air inlet 114 216 20
(Radiation side) (Cooling side)
20
4-M8
82
20 310 20
45
168
361
450
220
190
121
Drain pipe
69
79
65 6-φ10
10 329 11
28
Side-mount type / ENC-GR1000L-eco (Unit : mm)
45
Air outlet
(Radiation side)
Air outlet
(Cooling side)
415
Air inlet Air direction louver
(Radiation side)
Filter Air inlet
730
(Cooling side)
300
and alarm
35 230 35
output terminal
35
45
45
23 254 23
53
45.2
415
530
730
208
200
4-M8
225
14.8
165
Drain pipe
(Outer diameter φ16)
45
10 280 10 6-φ10
(Mounting hole)
10.5 10.5
30
35
Air outlet
475
(Radiation side)
465
510
Filter
Drain pipe
47.5
50
160
475
4-M8
20
20 360 20
30
23 354 23
6-φ11
12.5 375 12.5
29
External Dimensions〈Non-Flon-Gas & Energy saving〉
Hole for
attachment to
10 main unit 6-M8
450 230 (Packing) 11 428 11
71.2
50
Air outlet
550
(Cooling side)
Air direction louver
1200
450
Power supply 428
Air outlet
and alarm 19 390 19
(Radiation side)
20
output terminal
50
Air inlet
730
(Radiation side)
550
Filter
1200
50
70
160
550
4-M8
20
20 410 20
50
Hole for
attachment to
main unit 6-M8
450 230 10
(Packing) 11 428 11
71.2
50
550
Air outlet
(Cooling side)
Air direction louver
1200
730
Drain pipe
47.5 (Outer diameter φ16)
6-φ11
50
1200
70
160
550
4-M8
20
20 410 20
50
30
Top-mount type / ENC-GR500EX-eco (Unit : mm)
25 550 25 270 36
A
76
(Radiation side)
47
Air inlet A
(39.2)
15 25 175 25 30
Main drain pipe
(Outer diameter φ16)
Air inlet
(Cooling side) Air outlet (Cooling side) Power supply and 10 300 250 10
Section View A-A
Air direction louver alarm output terminal 30 4-Ø10
25 600 25 353 36
A
348
62.7
75 158.5
(52.4)
41
272
62
Air inlet Air outlet (Cooling side) Power supply and 36 378 236
40
31
External Dimensions〈Non-Flon-Gas & Energy saving〉
50
250
20
30 590 30 350 36
Air outlet
(Radiation side)
61.5
[Figure seen from control board outside]
620
Air inlet
43.6
(39.5)
350
330
250
Main drain pipe
Power supply and (Outer diameter φ16)
alarm output terminal
Main unit
15 380
15 590 15
Air inlet
(Cooling side) Air outlet (Cooling side)
Air direction louver
Air outlet
30 650 30 400 36 (Radiation side)
4-φ10
40
60
42
50
Air inlet
(41)
300
320
Filter
58 203.5
Main drain pipe
Power supply and
(Outer diameter φ16)
50
15 55 425 200 15
710
Air inlet
(Cooling side)
Air outlet (Cooling side)
Air direction louver
32
Top-mount type / ENC-GR2500EX-eco (Unit : mm)
50
300
20
Air outlet
30 650 30 400 36 (Radiation side)
4-φ10
40
60
50
42
Air inlet Sub drain pipe
(41)
400
300
320
Filter
Main drain pipe
(Outer diameter φ16)
50
Power supply and
alarm output terminal
40
15 55 425 200 15
710
Air inlet
(Cooling side)
Air outlet (Cooling side)
Air direction louver
33
External Dimensions〈Non-Flon-Gas & Maintenance-free〉
350
220
30
250 72 11 329 10
10 6-M6
34.5
Power supply
82
and alarm Air outlet
Air outlet output connector
(Radiation side) (Cooling side)
121 168
Air inlet
40
450
(Cooling side)
Diagram of Panel Cutout
162
178
89.6
26
350
130
178.7 Air inlet 114 216 20
20
(Radiation side)
82
Main
168
unit
361
450
4-M6
79 121
6-φ10
69
17.7
(Mounting hole)
62.8 10 329 11
Drain pipe
(Outer diameter φ16)
300
250
10 280 10
30
280 72
6-M6
46
10
Air outlet
44
(Cooling side)
157
Air inlet
(Cooling side)
415
Air outlet
(Radiation side) Power supply
730
162
and alarm
output connector
Air inlet
125 Diagram of Panel Cutout
(Radiation side)
225
274.8
300
35 230 35
34
46
47 174
44
415
530
730
Main unit
18
63 Drain pipe
(Outer diameter φ16)
225
166
6-φ10
46
(Mounting hole)
10 280 10
34
Side-mount type / ENC-GR1500L (Unit : mm)
400
374 13
100 79
4-M8
250
280 72
30
30
67
10
(Cooling side)
Air direction louver
Air inlet
157
(Cooling side)
Air outlet
465
(Radiation side) Power supply
and alarm
750
162
output connector
Air inlet Diagram of Panel Cutout
120 155 (Radiation side)
[Figure seen from control board outside]
275
209
168
400
23 354 23
46
35
30
41
69 240
465
510
4-M6
Main unit
750
197
27
18
63 Drain pipe
( Outer diameter φ16)
209
205
46
6-φ10
12.5 375 12.5
(Mounting hole)
10 480 10
38 424
150 40
34
170 34
170
240
30
Drain pipe
(Outer diameter φ16)
49.1
22.6
25 450 25 71.7
Main unit
10 480 10
450 4-φ10
280 (Mounting hole)
Power supply and 454
5
170
Air inlet
(Cooling side)
60
Air outlet
35
(Cooling side)
35 440 15
500
35
External Dimensions〈Non-Flon-Gas & Maintenance-free〉
10 630 10
574 38
41
272 41
50
4-M8
323
223
272
30
Air outlet
Air inlet (Radiation side)
(Radiation side)
Drain pipe
69
18.6
55.2
230 284 26 92 [Figure seen from control board outside]
353 34.1
25 600 25
Main unit 4-φ10
118 10 630 (Mounting hole)
12
36
41
Power supply 604
279
and alarm
353
272
output connector
40
62
378
10 620 10
564 38
50
220 50
4-M8
250
320
Air outlet
(Radiation side)
30
20
Air inlet
(Radiation side)
19
Drain pipe
( Outer diameter φ16)
438
478
475
55
19
15
Power supply 594
50
and alarm
output connector
350
250
330
50
36
External Dimensions〈Non-Flon-Gas & Nondrain〉
350
30 220
72 11 10
10
82
Filter
Air outlet (Cooling side)
121 168
Evaporation fi lter Air inlet (Radiation side)
Air inlet (Cooling side)
570
199
6-M6
[Figure seen from control board outside]
180 8 350
114 216 20
20
82
Main
unit
168
361
21
570
121
63
Drain pipe
(Outer diameter φ16)
6-φ10
189
(Mounting hole)
199
10 329 11
300
250
30
72
10 10 10
44
6-M6 300
35 230 35
34
46
44
8
220
415
530
730
Main unit
Drain pipe
18
46
6-φ10
(Mounting hole)
10 280 10
37
<Related products guide>
Chosen by customers using control panel cooling units
http://www.apiste-global.com/