This manual covers the following item:

Model Reference Part Number

PDD24 031-1055
Use of DANGER, WARNING, CAUTION, and NOTE
This publication includes, DANGER, WARNING, CAUTION, and NOTE information where appropriate to point out safety
related or other important information.
DANGER Hazards which could result in severe personal injury or death
WARNING Hazards which could result in personal injury
CAUTION Hazards which could result in equipment or property damage
NOTE Alerts user to pertinent facts and conditions
Although DANGER and WARNING hazards are related to personal injury, and CAUTION hazards are associated with
equipment or property damage, it should be understood that operation of damaged equipment could, under certain operational
conditions, result in degraded process performance leading to personal injury or death. Therefore, comply fully with all
DANGER, WARNING, and CAUTION notices.

TRADEMARKS
All trade references are duly acknowledged.

008-5104-04
PDD24 Power Distribution Panel User Manual
Table of Contents

TABLE OF CONTENTS
Chapter 1 - Introduction and technical data
1.1 Purpose..................................................................................................................... 1-1
1.2 Specification ............................................................................................................ 1-2
1.3 Environmental specifications................................................................................... 1-3
1.4 Transport and handling ............................................................................................ 1-3

Chapter 2 - Technical description


2.1 Physical .................................................................................................................... 2-1
2.1.1 External connectors................................................................................. 2-1
2.2 Theory of operation ................................................................................................. 2-2

Chapter 3 - Servicing
3.1 Scope........................................................................................................................ 3-1
3.2 Diode testing and replacement................................................................................. 3-1
3.2.1 Diode testing and replacement with the system shut down .................... 3-1
3.2.2 Diode testing and replacement with the system live............................... 3-2
3.2.3 Relay testing and replacement ................................................................ 3-2
3.3 Preventive maintenance ........................................................................................... 3-3

Chapter 4 - Service support


4.1 Spare parts................................................................................................................ 4-1
4.2 List of spares ............................................................................................................ 4-1

Chapter 5 - Glossary of terms


5.1 Glossary of terms ..................................................................................................... 5-1

008-5104-04 i
PDD24 Power Distribution Panel User Manual
Table of Contents

ii 008-5104-04
PDD24 Power Distribution Panel User Manual
Section 1.1 Purpose

Chapter 1 Introduction and technical data

1.1 Purpose
The Power Distribution Panel (PDD24) provides diode auctioneering of 24Vdc field supplies to
give a redundant supply for field devices via termination cards, or any suitable SC300E remote
devices. The redundant supply is distributed using standard plug-to-plug two-core power cables
from 48 indicating/alarm monitored fuse outputs.

Figure 1-1. PDD24 - Front view

Figure 1-2. PDD24 - Rear view

008-5104-04 1-1
PDD24 Power Distribution Panel User Manual
Chapter 1 Introduction and technical data

A fuse blown LED on the PDD24 indicates the failure of any of the fuses. A fuse blown alarm
signal from two sets of volt free changeover relay contacts is available at the rear of the PDD24.
Optionally, the fuse blown alarm for up to 24 termination cards can be combined, making the
fuse blown LED a single fuse blown indicator for an entire cabinet.
This document is intended to provide a general understanding of the function of the Power
Distribution Panel, sufficient to enable basic maintenance operations to be effected in the field.

1.2 Specification

Model PDD24
Power inputs Dual 24Vdc nominal, 33V maximum
Fuse fault inputs 24 x fuse fault inputs
Outputs 24Vdc via 48 individually fused outlets
Power rating 30A maximum distributed over the 48 outlets with
a maximum temperature of +60°C and a 6A
continuous maximum per outlet
Diode pack Replaceable spare
Fuse rating All fuses 7.5A
Indication Common ‘fuse blown’ LED and volt-free contacts
Alarm relay contacts 100V ac/dc 1A resistive load
30W 60VA reactive load
Replaceable spare
Overall size (mm) 133(3U)H x 483W x 90D
Overall size (inches) 5.24H x 19W x 3.54D
Weight 2kg

1-2 008-5104-04