IEC 60364-5-52
Electrical installations of buildings –
Part 5-52:
Selection and erection of electrical
equipment – Wiring systems
Standard prescriptions
www.lpqi.org
Standard prescriptions
www.lpqi.org
IlThe worldè…
mondo cambiato per sempre
www.lpqi.org
… changed forever!
www.lpqi.org
Theorethical background
www.lpqi.org
Theorethical background
Balanced linear loads
www.lpqi.org
Theorethical background
Unbalanced linear loads
www.lpqi.org
Theorethical background
Non linear unbalanced loads
www.lpqi.org
Theorethical background
3rd order harmonics
www.lpqi.org
Sizing criteria
www.lpqi.org
Example
installation method C
Phases 3
design load 37,5 A
Number of cores 4
Insulation EPR
Installation method Clipped to a wall
www.lpqi.org
Example
Harmonics free environment
– ⇒ 4 mm2
www.lpqi.org
Example
Office # 1
3 h = 22%
www.lpqi.org
Example
Office # 2
3 h = 40%
− IN = 37,5 · 0,4 · 3 = 45 A
− IF = 37.5 A
− IN > IF size related to neutral
current
− Equivalent neutral current:
45
= 52,3
0,86
− ⇒ 10 mm2
www.lpqi.org
Example
Lighting equipment FLC
3 h = 72% + 9 h = 33,9% + …
146,2
= 146,2
1
− ⇒ 35 mm2
www.lpqi.org