Neutral conductor sizing


LPQIves has been co-financed by

LPQI is a member of Angelo Baggini – angelo.baggini@unibg.it


Franco Bua - franco.bua@ecd.it

IEC 60364-5-52
Electrical installations of buildings –
Part 5-52:
Selection and erection of electrical
equipment – Wiring systems

Standard prescriptions

www.lpqi.org
Standard prescriptions

IEC 60364-5-52 Art. 524.3


ƒ For polyphase circuits where each phase conductor has a
cross-sectional area greater than 16 mm2 in copper or 25
mm2 in aluminium, the neutral conductor may have a
smaller cross-sectional area than that of the line conductors
if the following conditions are simultaneously fulfilled:
– the expected maximum current including harmonics,
if any, in the neutral conductor during normal service is
not greater than the current-carrying capacity of the
reduced cross sectional area of the neutral conductor;
– the neutral conductor is protected against overcurrents
according to the rules of 431.2 of IEC 60364-4-43;
– the size of the neutral conductor is at least equal to 16
mm2 in copper or 25 mm2 in aluminium.

www.lpqi.org
IlThe worldè…
mondo cambiato per sempre

www.lpqi.org
… changed forever!

www.lpqi.org
Theorethical background

www.lpqi.org
Theorethical background
Balanced linear loads

www.lpqi.org
Theorethical background
Unbalanced linear loads

www.lpqi.org
Theorethical background
Non linear unbalanced loads

www.lpqi.org
Theorethical background
3rd order harmonics

www.lpqi.org
Sizing criteria

IEC 60364-5-52 Annex D


Reduction factors
for harmonic currents in four-core and five-core cables

Third harmonic Size selection is Size selection is


content of phase based on phase based on neutral
current current current
(%)
0-15 1,00 -
15-33 0,86 -
33-45 - 0,86
45 - 1,00

www.lpqi.org
Example

installation method C

Phases 3
design load 37,5 A
Number of cores 4
Insulation EPR
Installation method Clipped to a wall

www.lpqi.org
Example
ƒ Harmonics free environment

– Cable size related to phase currents

– ⇒ 4 mm2
www.lpqi.org
Example

Office # 1

3 h = 22%

− IN = 37,5 · 0,22 · 3 = 24,7 A


− IF = 37.5 A
− IN < IF size related to phase
current
− Equivalent phase current:
37,5
= 43,6
0,86
− ⇒ 6 mm2

(IEC 60364-5-52 tab. A.52-5 )

www.lpqi.org
Example
Office # 2

3 h = 40%

− IN = 37,5 · 0,4 · 3 = 45 A
− IF = 37.5 A
− IN > IF size related to neutral
current
− Equivalent neutral current:

45
= 52,3
0,86
− ⇒ 10 mm2

(IEC 60364-5-52 tab. A.52-5 )

www.lpqi.org
Example
Lighting equipment FLC

3 h = 72% + 9 h = 33,9% + …

− IN = 37,5 · 1,30 · 3 = 146,2 A


− IF = 37.5 A
− IN > IF size related to neutral
current
− Equivalent neutral current:

146,2
= 146,2
1
− ⇒ 35 mm2

(IEC 60364-5-52 tab. A.52-5 )

www.lpqi.org