You are on page 1of 7

Everything You

M
NEED to KNOW
About TXVs
}
With the higher
SEER air conditioners,
technicians need to
reacquaint themselves
with thermostatic
TXV does this by keeping the coil sup-
plied with enough refrigerant to main-
tain the right superheat of the suction
gas leaving the evaporator coil.
There are three forces that govern
the TXV operation. Refer to Figure 1,
which shows the basic force balance
diagram of a TXV. In the chart:
P1: Power element and remote
bulb pressure.
needed to initiate movement of the
valve pin to just start to move. This is
defined as .002-inch of stroke.
® Gradient. The amount of super-
heat required to move the pin from
the static set point to the rated stroke
is called gradient. Figure 2 depicts
how a TXV regulates flow in
response to changing superheat.
Starting from the origin, no
expansion valves P2: Evaporator pressure. change in valve stroke occurs as the
P3: Superheat spring equivalent superheat slowly increases. It is not
pressure. until the static setpoint is reached
BY AL MAIER For the valve to be stable, the that the valve begins to open. From
forces need to be balanced, or P1 = this point forward, further increase
P2 + P3. in superheat results in a proportional
efore the 13 SEER mini-

B mum efficiency standard,


thermostatic expansion
valves (TXVs) were rarely
seen in residential air-con-
ditioning systems. They
were used on some high SEER sys-
tems and on heat pumps (usually on
the outdoor coil), but these repre-
sented a relatively small portion of
Figure 1
In a TXV, the forces
need to be balanced
for it to be stable.

As the evaporator outlet temperature


the overall market. becomes warmer, the pressure (P1)
However, that has changed dra- increases, causing the diaphragm to flex
matically now that virtually all new in a downward direction. This forces
13 SEER equipment will be manu- the valve pin in an open position, result-
factured with TXVs. As a result, there ing in increased refrigerant flow.
is a growing need for many service The underside of the diaphragm
technicians to reacquaint themselves always senses the evaporator pressure
with TXVs in terms of operation, (P2). As this pressure increases, it
troubleshooting and replacement. forces the diaphragm in an upward, or
closing position, decreasing refrigerant
Refrigerant flow flow.
Metering the flow of refrigerant to the The spring pressure (P3) also acts on
evaporator is the sole function of a the underside of the diaphragm. This
TXV. It must meter this flow at pre- spring is adjusted to provide static
cisely the same rate the refrigerant is superheat for the valve. The static P1 = P2 + P3
being vaporized by the heat load. The superheat is the amount of superheat
Thermostatic expansion valves

L
duced in this manner are termed
internally equalized valves.
In most a/c systems, the evapora-
tors are quite large and, therefore,
have significant pressure drop across
them. For the TXV to sense the evap-
orator outlet pressure, a separate
line is needed from the suction line
(near the TXV bulb location) to the
external equalizer connection on the
valve body.
If a distributor is used to supply
refrigerant to various evaporator cir-
cuits, an externally equalized valve
must be used. Distributors typically
have between 15 psi and 30 psi pres-
sure drop across them. Hence, use
them only with externally equalized
valves.
Figure 2 ® Balanced-ported valves. With
A TXV regulates flow in response to charging superheat. a conventional TXV, the pressure dif-
ferential across the valve results in a
force that tends to “open” the valve.
increase in valve stroke until the suction gas temperature measured in As operating conditions vary, this
maximum stroke position is attained. step 3. The difference is the operat- pressure differential changes and
Gradient is an important aspect to ing superheat. results in a variation of the original
TXV performance in a system. Too ® Internally and externally equal- superheat. Engineers have developed
low a gradient and the valve will be ized TXVs. In a system with a rela- the balance-ported TXV to compen-
unstable and tend to “hunt” (more tively small evaporator, the pressure sate for this (Figure 4).
on this later). If the gradient is too drop across that evaporator is so In this design, the inlet pressure is
high, more superheat will be needed small you can assume it is zero. applied across the valve pin as well
for the valve to open, resulting in Therefore, the TXV outlet pressure as an undercut on the push-rod.
high operating superheat and poor Since these forces are in opposite
evaporator efficiency. directions, they cancel or balance
® Measuring superheat. Since one another resulting in no change
good superheat control is the criteri- In most a/c systems, in superheat, regardless of operating
on of TXV performance, accurate conditions.
measurement of the superheat is the evaporators Balanced-ported valves are ideal
vital. This involves four steps, as for use in systems that operate over
shown in Figure 3. They are: are quite large and, large changes in operating condi-
1. Measure the suction pressure at tions. An example of this is a com-
the evaporator outlet with an accu- therefore, have mercial a/c system that must operate
rate gauge. If a gauge connection is both winter and summer, resulting
significant pressure
GRAPHICS COURTESY OF EMERSON CLIMATE TECHNOLOGIES

not available, a tee can be installed in system operation under widely


in the equalizer line. varying head pressures.
2. Referring to a P/T chart for the drop across them
refrigerant used in the system, find Troubleshooting TXVs
the saturation temperature that cor- There are really only three failure
responds to the pressure observed in modes that a TXV can experience:
step 1. and evaporator outlet pressure are 1. Starving. This is defined as
3. Measure the temperature of the equal. insufficient refrigerant flow causing
suction line at the remote sensing By drilling a small bleed passage high superheat at the evaporator out-
bulb. This can be done with a strap- between the underside of the let. Symptoms include high super-
on type thermometer or an electron- diaphragm and the outlet of the heat at the compressor inlet, high
ic device. valve, you can sense the pressure discharge temperature and possibly
4. Subtract the saturation temper- internally and eliminate the need for compressor overheating (the protec-
ature determined in step 2 from the an external connection. Valves pro- tor trips).
for that particular model. As a rule of
thumb, operating superheats between
8º F to 12º F is considered normal.
Some “tips” to help in troubleshoot-
ing TXV performance follow:
• Check the bulb to assure it is
properly connected to the suction line.
If you can move the bulb by hand,
then it is not secured adequately.
• Some manufacturers insulate
the bulb to protect it from the effects
of an airstream. If this was done by
the oem, make sure the insulation is
still intact.
• Check the equalizer line for
restrictions (kinks) or signs of frost.
Figure 3 A frosted equalizer line indicates
Four steps are required to accurately measure superheat. internal leakage and will require
replacement of the valve. You will
need to repair or replace a kinked
2. Flooding. This occurs when the equalizer as well for the valve to
refrigerant flow to the evaporator is operate properly.
so high that all of it can’t evaporate A TXV is designed to meter the
within the coil. The result is liquid flow of liquid refrigerant. If the refrig-
refrigerant getting back to the erant at the valve inlet contains flash
compressor. Symptoms include low gas the capacity of the valve will be
evaporator superheat, diluted oil and reduced. Make certain the system is
noisy compressors. If not corrected, properly charged and that some sub-
this can lead to permanent compres- cooling exists at the inlet of the valve
sor damage. before condemning the TXV.
3. Hunting. When the superheat in With the use of R-410A and POE
an operating system is constantly oils, there is a greater risk of dirt and
changing from little or no superheat contaminants being circulated with-
to very high superheat, it is called in the system. Some manufacturers
hunting. You can easily recognize use inlet strainers or screens to pre-
this by noting extreme cyclic changes vent debris from clogging the valve.
Figure 4 in the evaporator or suction pressure. If such a condition is found, clean
The balanced port TXV compen- Hunting is caused by many fac- and replace the strainer. It would
sates for varying operating tors, but usually occurs when the also be wise to install a large fil-
conditions. valve is oversized for the load. Before ter/drier at the inlet of the TXV to
condemning a valve for this symp- prevent a recall.
tom, make certain the evaporator is
clear of frost and has proper airflow Replacing a TXV
since these conditions will result in If you determine that you need to
very low loads potentially resulting replace the valve after checking the
in a “good” valve hunt. superheat, here are some tips to
assure proper replacement:
Checking TXV operation 1. Whenever possible, use the
If a TXV is suspected of working valve recommended by the manufac-
properly, checking the superheat is turer of the equipment. If this is not
the only way to know for sure. Do possible, be sure the replacement
this with accurate instrumentation has the same:
Figure 5 to get meaningful results. • Rated capacity.
Wrap the valve with wet rags to Check the a/c equipment manufac- • Refrigerant designation.
avoid overheating. turer’s installation and service manu- • Charge type.
al to verify the acceptable superheat • Internal/external equalizer style.
Thermostatic expansion valves

L
• Internal check valve (if supplied
on original valve).
• Inlet/outlet connection size and
type.
2. To maintain system cleanliness,
replace the filter-drier whenever
opening the sealed system. While this
always has been a recommended
service procedure, it is of even greater
importance with HFC/POE systems
due to the hygroscopic nature of the
POE oils and their greater solvency.
3. Do not overheat the valve dur-
ing the brazing process. Overheating
can cause deterioration of the inter-
nal seals, which could lead to frosted
equalizer lines. To avoid this:
• Wrap the valve with wet rags as
shown in Figure 5. Figure 6
• Keep the torch flame pointed Here is a diagram of an internal check valve.
away from the valve body.
• Never allow the torch to come
in contact with the bulb. the ball against the seat, forcing it Systems using TXVs are quickly
closed. All the flow must then pass becoming the norm in this post 13-
TXVs in heat pumps through the main valve port and the SEER world. Understanding their
In heat pump applications, the liquid valve operates as a normal valve. function and operation will enable
refrigerant must flow through or When the flow is reversed the inlet you to properly service systems
around the TXV when operating in pressure pushes the ball up, allowing using these devices. Follow the
the reverse direction. Historically, flow through the check port. In this basic troubleshooting and replace-
this was accomplished by installing a mode, the flow bypasses the main port ment guidelines discussed here, to
check valve around the valve. and liquid will flow through the valve ensure optimal system performance
However, in recent years TXV with only a small pressure drop. and prevent permanent compressor
manufacturers have modified their When replacing a valve in a heat damage.N
products with internal check valves. pump verify if the original valve had
Many oems have adopted these since an internal check. If it did, be sure Al Maier has over 30 years of refriger-
they eliminate joints and the poten- the replacement has one too. If none ation system and component design
tial for leaks. is available, use a standard valve. experience. He is currently vice presi-
Figure 6 is a cross-sectional draw- You must install a check valve to dent of application engineering for
ing of one such valve. In the forward bypass the TXV when reverse flow is Emerson Climate Technologies, Flow
flow direction, inlet pressure pushes encountered. Controls Division.

Emerson Climate Technologies


Flow Controls Division
11911 Adie Rd.,
St. Louis, MO 63043
314.569.4500; fax: 314.569.4593
www.emersonclimate.com/flowcontrols
Form No. 2006FC-174R1

Reprinted from August 2006 - RSES Journal


TROUBLESHOOTING
Thermal Expansion
Valves
ith the advent of the 13 SEER regulations in

W January 2007, nearly every manufacturer of


split residential air-conditioning equipment
changed their designs from using flow raters to
using thermal expansion valves (TXVs) for con-
trolling the rate at which refrigerant is fed to the evaporator.
The TXV enables a more energy-efficient system because it
Here is the correct way to diagnose

P1
and troubleshoot a system with a
TXV as its flow control device.


maintains the evaporator closer to the optimum superheat at
all operating conditions, and it enables the system to pull- BY AL MAIER
down to optimum conditions faster after an off cycle.

TXV function
➦ P2
and operation valve is in
Although TXVs offer many oper- balance when
ating advantages, they are viewed
as a somewhat mysterious device
P1=P2+P3
by those not familiar with them
and as a result are often replaced
needlessly. The TXV has only one
function. It meters the flow of liquid refrigerant into the evap-
orator in exact proportion to the evaporation rate of the
refrigerant in the evaporator. By responding to the tempera-
ture of the refrigerant gas leaving the evaporator and the bulb decreases and the valve pin
pressure of the evaporator, the TXV can control the gas leav- then moves in a “closing” direction.
ing the evaporator at a predetermined superheat. A TXV’s factory superheating set-
Superheat is the temperature of a vapor above its satura- ting is made with the valve pin just
tion temperature. It is found by measuring the actual temper- starting to move away from the seat.
ature at the outlet of the evaporator and subtracting the tem- A further increase in superheat is

perature corresponding to the evaporating pressure from it. needed for the valve to open to its
In order to correctly troubleshoot a TXV, first under- rated position. This is an important
stand how the valve works. There are three forces shown concept to understand since it means
that govern a TXV’s operation. These are P1, the pressure that a valve with a factory setting of
created by the remote bulb and power assembly; P2, the
evaporator or equalizer pressure; and P3, the equivalent
P3 8° will not maintain an 8° super-
heat at a rated load. Additional
spring pressure of the superheat spring. superheat is needed to get the valve
The pressure in the remote bulb assembly (P1) corre- to “stroke” to its rated capacity.
sponds to the refrigerant temperature leaving the evaporator.
As this pressure increases, it tends to move the valve in an Troubleshooting TXVs
“opening” direction. Opposed to this force on the diaphragm’s There are three principle modes of failure of a TXV. The
underside and acting in a closing direction is the force exert- valve may feed too much refrigerant (flooding); it may not
ed by the evaporator pressure and the pressure exerted by the feed enough refrigerant (starving); or can alternately feed
superheat spring. The valve will assume a stable position too much and then too little (hunting). Each of these will
when these forces are in equilibrium (P1=P2+P3). be discussed in greater detail:
As the temperature of the refrigerant leaving the evapora-
tor increases above its saturation temperature—correspon- Flooding
ding to the evaporator pressure—the pressure in the remote Flooding occurs when the refrigerant amount being fed to
bulb in-creases, causing the valve pin to move in an “open- the evaporator is more than can be evaporated, resulting
ing” direction. Conversely, as the refrigerant gas temperature in liquid refrigerant going back to the compressor.
leaving the evaporator decreases, the pressure in the remote Symptoms of flooding include frosting of the compressor

18 RSES Journal ~ Januar y 2008


shell, noisy compressors, low super-
heat at the evaporator, and normal- or Measuring/adjusting superheat steps
higher-than-normal suction pressures.
Causes of flooding include: To measure superheat:
• Undersized or inefficient com- 1. Determine suction pressure at the evaporator outlet;
pressor. If the compressor capacity is 2. Use a pressure/temperature chart for the appropriate refrigerant,
low, the suction pressure will be higher and determine the saturation temperature corresponding to the pressure
than normal and the superheat will be measured in step 1;
low. If this condition is suspected, con- 3. Measure the temperature of the suction line at the remote bulb
sult with the compressor manufacturer; location; and
• Low superheat setting. On 4. Subtract the saturation temperature determined in step 2 from the
externally adjustable valves, turn the temperature measured in step 3. The difference is the superheat.
adjusting stem clockwise to increase
the superheat; Adjusting superheat for externally adjustable TXVs only:
• Moisture. Any moisture in the 1. Remove the seal cap from the bottom of the valve, exposing the
system can freeze in the TXV, prevent- adjusting stem;
ing the valve from functioning as 2. Rotate the stem clockwise to increase the superheat—decreases
intended. If this is suspected, install a flow of refrigerant; and
high-quality liquid-line filter drier. It 3. Rotate the stem counterclockwise to decrease the superheat—
also is advisable to install a liquid-line increases flow of refrigerant.
moisture indicator to enable the tech-
nician to monitor the moisture level
within the operating system;
• Dirt or debris. Any foreign Starving • Undercharged system. If a sys-
material that gets past the inlet strain- Starving occurs when the refrigerant tem is low on charge then the super-
er can become lodged between the pin amount feeding the evaporator is fully heat will be high, the suction pressure
and the port of the TXV, preventing it evaporated long before the outlet. low, but the system still will not provide
from properly closing. Here again, a Symptoms of starving include insuffi- sufficient cooling. A sight glass
high-quality filter drier should be cient refrigeration effect—warmer installed in the liquid line immediately
installed in the system to prevent the than desired load temperature—high before the TXV is the best way to deter-
circulation of dirt and debris and superheat at the evaporator outlet and mine this. “Bubbles” in the sight glass
cause system malfunctions; low-suction pressure. Causes of starv- are a clear indication that the system is
• TXV seat leak. If the pin and ing include: low on charge. On residential A/C sys-
port do not seat properly, liquid refrig- • Moisture. Any moisture in the tems, the manufacturers include a
erant will flow through the valve when system can freeze in the TXV, pre- chart indicating what the correct pres-
there should be none. Inspecting the venting the valve from functioning as sures are in different operating condi-
valve may reveal dirt and debris, in intended. If this is suspected, install a tions. These tables can be used to
which case the TXV can be cleaned high-quality liquid-line filter drier. It determine if the system charge is cor-
and put back into service. Inspection is also advisable to install a liquid-line rect. Additionally, measure the sub-
may also reveal damage to the pin or moisture indicator so the technician cooling at the inlet of the TXV. If there
port due to wire drawing or erosion of can monitor the moisture level within is no subcooling, that too is an indica-
the pin. In such a case, the valve the operating system; tion that the system charge is low;
should be replaced; • Dirt or debris. Any foreign • Flash gas at inlet to TXV. Any
• Oversized valve. Make certain material that gets past the inlet strain- restrictions in the liquid line leading
the correct valve specified by the er can become lodged between the to the TXV inlet will cause a pressure
equipment manufacturer is installed pin and the TXV’s port, preventing it drop and result in flash-gas forma-
in the system. A valve too large for the from correctly closing. Here again, a tion. Because the gas density is much
capacity of the system will tend to high-quality filter drier should be less than that of liquid refrigerant,
overfeed; and installed in the system to prevent the having flash gas feeding the TXV will
• Incorrect bulb position. Ideally, circulation of dirt and debris that reduce the valve’s capacity and cause
the power element bulb should be cause system malfunctions; high superheat and starving. Flash gas
attached to a horizontal run of suction • Insufficient Delta P across can be found in the following ways:
line—immediately after the evapora- valve. If the pressure drop across the 1. Look for frost or moisture on
tor outlet. It should be in close proxim- valve is too low the valve’s capacity is the liquid line. As the flash gas is
ity to the equalizer connection, but reduced. This sometimes happens dur- formed, it causes a refrigeration effect
upstream of it. The bulb needs to be ing low ambient operation when the making the area around it cold. Since
firmly attached to the suction line to head pressure is allowed to “float” with the liquid line is normally warm to the
maintain good thermal contact. the ambient. To correct for this, raise touch, a cold spot is usually a sure sign
Additionally, the bulb must not be the head pressure or replace the valve that a restriction exists at that point;
influenced by external sources of heat. with one that has a larger capacity; 2. If a sight glass is installed,

Januar y 2008 ~ RSES Journal 19


look for bubbles. A steady stream of bubbles indicates • Strainer clogged. Dirt or debris in the refrigerant
either a low charge or vapor in the liquid line; and leading to the valve can result in the strainer becoming
3. Check for subcooling. If subcooled liquid is pres- clogged. Remove and clean the strainers and add a high-
ent at the outlet of the condenser, but not at the inlet of capacity liquid-line filter drier to prevent recurrence.
the evaporator, then determine where you have lost the
subcooling. In some cases, the liquid line may be under- Hunting
sized, or liquid-to-suction heat exchange may have been Hunting occurs when the TXV alternately opens and clos-
lost, resulting in a loss of subcooling. es, causing large fluctuations in superheat. This can be
• Plugged equalizer line. If the equalizer line is plugged, caused by the difference in the time response of the system
the pressure underneath the diaphragm can be higher than versus the TXV. Different type charges have been designed
the actual evaporator pressure, resulting in a valve that tends with various time constants to minimize this effect, but
to be in a more “closed” position. To correct this, replace or other factors—such as sudden changes in load or operation
repair the equalizer line; at low-load conditions—also can impact this. Causes of
• Valve too small. Check that the valve is correctly hunting include:
sized for the system. Replace with the proper sized valve; • Valve oversized for application. A valve that is too
• Superheat adjusted too high. On externally large for the application will tend to hunt. If this is suspect-
adjustable valves, turn the adjusting stem counterclock- ed, replace the valve with one that is correctly sized for the
wise to decrease the superheat; application;
• Power assembly failure or partial loss of charge. If • Bulb location. Verify that the bulb is not located down-
the power assembly has lost all or part of its charge, it will stream of a P trap on the suction line. Relocate the bulb if this
not generate sufficient pressure to cause the valve to “open.” is found. It may also be helpful to insulate the bulb to make
A tech can verify this in the field by holding the bulb in his certain it is not affected by an air stream;
hand while monitoring the system operating conditions. • Refrigerant distribution. On systems with distribu-
Hand warmth should cause the pressure to increase, result- tors, it is not uncommon to have different circuits with
ing in increased refrigerant flow and an increase in suction largely differing loads. This can result in some circuits occa-
pressure. If no change is noted, the valve may have lost its sionally overfeeding sufficiently to allow liquid to reach the
charge. This technique is only valid if the system is correct- bulb. This, of course, will force the TXV closed until super-
ly charged and the valve has high-quality liquid refrigerant heat is again achieved; at which time it will open. To correct
at its inlet. If it is found that the valve has lost its charge, the this requires elimination of the distribution problem;
power assembly must be replaced. In some cases, the power • Superheat adjustment. TXVs have their superheat
assembly is an integral part of the TXV, in which case the set at the factory to operate correctly on most systems. At
entire valve must be replaced. times, however, the factory setting may need to be adjust-
• Cross ambient effect. Some TXVs have special ed. In most cases, increasing the superheat will minimize
charges designed to limit the maximum operating pres- hunting. Turning the adjustment screw clockwise will
sure of the system. These are designated with a “W” in increase the superheat; and
the charge code followed by a number—for example • Moisture. Any moisture in the system can freeze in
HW100. With charges of this type, the bulb must always the TXV, preventing the valve from functioning as intend-
be colder than the power element or the valve’s body. If ed. As the moisture freezes and then thaws, the superheat
not, the charge can migrate from the bulb to the power will vary erratically. The use of a high-quality liquid-line
element with a resultant loss of control. If this is suspect- filter drier is recommended to prevent this.N
ed, replace the valve with a non-maximum evaporator
pressure type charge—in this example, an R-22 refriger- Al Maier is vice president of application engineering at Emerson
ant medium temperature (HC) or R-22 heat pump Climate Technologies Flow Controls Div. For more information
(HCA); and call 314-569-4680 or e-mail al.maier@emersonclimate.com.

Emerson Climate Technologies


Flow Controls Division
11911 Adie Rd.,
St. Louis, MO 63043
314.569.4500; fax: 314.569.4593
www.emersonclimate.com/flowcontrols
Form No. 2008FC-21
Reprinted from January 2008 - RSES Journal

You might also like