Evaluasi Kinerja Ozone Generator

Utility Oncology Plant


Spesifikasi Mesin Ozone Generator
 Max. water flow rate to be treated = 2,5 m3/h
 Max. water pressure to be treated = 3 bar
 Max ozone Production = 2,5 g/h
 Dry air flow rate to ozone generator = 300 NL/h
 Flow rate ozone to sanitization = 1 g/m3
Kondisi di Utility Oncology
 Konsentrasi Ozone dalam PW = 0,04 mg/L
 Debit PW Looping = 2 m3/h
 Debit dry air to ozone generator = 240 NL/h
 Pressure return PW looping = 2,07 bar
Evaluasi Kapasitas Produksi Ozone
Produksi Ozone = Debit PW Looping x Kons. Ozone dalam PW + 25% safety factor
Capacity Ozone Output Capacity Ozone Output
Speed Pompa Frekuensi Debit
in Operation in Sanitization
(%) (Hz) (L/h)
(g/h) (g/h)
50 30,1 1600 0,80 1,6
60 34,1 1800 0,90 1,8
70 38,2 2000 1,00 2,0
80 42,2 2200 1,10 2,2
90 45 2500 1,25 2,5
Debit PW Oncology Non
4000 2,00 4,0
sterile
Monitoring PW Generator

 Brand = Remoin
 Type = OSMO-REM 3000
 Kapasitas mesin = 3 m3/h
 Kapasitas tangki PW = 2 m3
 Efisiensi performa mesin = 90%

Running Hours PW Total produksi PW Total Konsumsi DRW


Bulan
Generator (m3) (m3)

Oktober 135,70 366,39 435,21

November 141,52 382,10 463,75

Desember 128,71 347,52 421,36

Januari 120,50 325,35 388,01

Februari 118,58 320,18 381,84

Maret 120,50 325,35 388,01

PW Generator
500
450
400
350
300
250
200
150
100
50
0
Oktober November Desember Januari Februari Maret

Mesin Beroperasi (jam) Produksi DRW (m3) Total Penggunaan DRW (m3)
Monitoring Pompa PW Looping

Frekuensi (Hz) Speed Pompa (%) Debit (L/h)


30.1 50 1600
34.1 60 1800
38.2 70 2000
42.2 80 2200
45 90 2500

Debit PW Looping
4500
4000
3500
Debit PW (L/h)

3000
2500
2000
1500
1000
500
0
50 60 70 80 90
Speed pompa (%)

Debit PW non sterile Debit PW Looping

Ket: Debit PW untuk oncology non sterile 4000 L/h