Preface
In order to avoid harm for man and unit, please obey below safety precaution
during installation, setting, operation and maintenance:
1) Make sure tools do not leave in fan motor before operating.
2) Make sure fan motor is stopped before opening the access door
3) Make sure correct connection before starting
4) Do not enter into unit when operating. Switching off the power before inspection
5) Make sure Connecting copper tube welded well and has good air tightness in the
finished connecting tube between the indoor and outdoor unit, Can not exist the
Weld and drain welding phenomenon.
6) The indoor and outdoor unit should be vacuumize after connection and than to
charge the refrigerant; In order to ensure that the return pipe back to the trachea
and external insulation, the connecting pipe should cover with heat preservation
cotton.
7) Make sure manually-operated gate is closed before humidifier.
8) Unit with heater should series connect the heater power on fan motor main power,
interlock with fan motor, or install switch off device without wind close to air outlet
pipeline to avoid fire due to lack of wind.
2
1. Loading and Transportation
(1) Unit would be packed and transported integrally or separately as per its type
and size.
(2) Please user proper transportation instrument as per unit’s size and weight,
like forklift, platform truck, and etc, as show in drawing 1-1
2. Storage
If the time between unit arrival and installation is over 2 weeks, please take
following protection measures:
A. Storage the unit in even and dry area, and avoid shaking and pressing to
damage the unit or parts.
B. When leaving factory, the unit is packed with plastic film, which might be
damaged in transportation or inspection, so please use tent cloth or plastic film
to cover the whole unit until to the bottom.
C. If the unit would be stored for a long time, it is recommended to enter the unit
through service door or fan section, and rotate the fan and motor once a
month. And this will be helpful to bearing lubrication and rustproof.
3
3. Installation and Connection
3.1、Installation
Before installation, please make sure that the field is ready well, and then the
unit could be unpacked. The machine room shall be clean, and the unit basement
shall be even and ready well, and the size shall be fir for the unit.
When unpacking, please check accessories as per packing list
Before installation, please also check the unit’s outlook and main parts, like
panel, service door, main components and etc.
For purge unit, it is also need to check and clean the filter bracket, coil &
heater and fan motor.
Relative staff shall carefully learn the shop drawing, installation instruction
and warning labels before installation.
The above checking procedure shall be conducted by supplier and user
together.
After the above checking, the unit can be installed:
1)Check if there is enough servicing space around (especially the side where
to draw out the filter). Show as drawing 3-1:
Fan
Motor
Coil
Wall
Drawing 3-1
For ceiling concealed modular air handling unit, please spare access spare
above ceiling for unit inspection. And there shall be enough space between unit
and ceiling to make water seal and condensing water piping.
2 ) Please make sure the basement and support can afford the unit’s
4
operating weight, and the unit is set leveling.
3)For floor mounted unit, please set the unit on basement, which shall has
proper height for free draining, and then leveling, adjusting and fixing. And install
dampers and other accessories at last.
4 ) For ceiling mounted unit, please make sure the lifting bar stable, solid
and correct positioned. The joint of unit and lifting bar shall be tightened by dual
nuts, and make it level and centering, and force uniform on every lifting point.
Unit shall be transported integrally, and it needs only to be installed as per
steps above. While sometimes, it needs to be transported by sections, and then
combined on site. For unit that exceeds limited size of transportation, we will
provide site assemble service.
Please remind the following item when combining.:
A. Stick seal joint strip on joint face of sections.
B. Keep the correct combination sequence. All sections are marked clearly, and
please check the marks carefully when combination, and strictly follow the
general assemble drawing. (as attached)
C. Push and move the jointing sections to make sure there is no apparent gap.
Please make the side and top straight when tight up the bolt.
D. Please make the side and top straight when tight up the bolt.
Drawing 3-2
E. (5) Please tight up the iron bar with bolts when all sections are well installed
(as Drawing 2-2). The sequence is:tight up the mountings(M10x50mm
bolts),tight up fame (side frame first and then top frame).
3.2、Connection and Refrigerant charging:
5
(1)Connection
For small unit, it is of bell mouth connection. Connection pipe, which is expanded
without rip or crack, shall be directed at check valve and then connect together. For
large capacity unit, it is of welting connection. After welting, there shall be no weld
flash or slag patch. Remarks: please discharge and clear nitrogen in outdoor unit and
indoor unit to avoid human injury.
The system shall be installed with oil return bend in according to the height
difference between indoor unit and outdoor unit, adding one bend every 5m. If the
pipe is horizontally quite long, oil return bend is also recommended. To avoid vapor or
energy loss, gas pipe and liquid pipe shall be strictly insulated. And since the
temperature of gas pipe can reach to 100℃ above, insulation shall be hot-resistant
and flame retardant.
(3)Refrigerant charge
A 、 For small unit, refrigerant has been charged, if the connection pipe length is
within 5m, then no need to recharge. When pipe length is beyond 5m, additional
refrigerant need to be charged as per form below.
.B、For large capacity unit, there is no refrigerant when leaving factory. 。After
Leak detection, Evacuation ,at first close the composite pressure gauge, cut off the
vacuum pump , use the middle leather hose of the composite pressure gauge to
connect with the fluoride bottle, put the fluorine bottle upside down on the electronic
scales and open the high-pressure side of the composite pressure gauge, so that the
liquid refrigerant is charged into the system from the high pressure side, When the
refrigerant system pressure rise filling stop, and the charging amount has not reached
the rated value, close the high-pressure valve, open the low pressure valve, started
the unit, Please seek help for professional and technical personnel from the low-
pressure side gap filling gaseous refrigerant, until it reaches the rated charging
quantity. When pipe length is beyond 7m, additional refrigerant need to be charged as
per form below. Remarks: liquid refrigerant is not allowed to be charged into unit
7
on operating.
8
4.10. After normally running for one month, please power off the unit and check
tightness of belt and adjust it, and fill lubricant if there is filler well. Check if the
bolts in key parts are loosing, and tight up.
4.11. For the unit runs all year around, bearings of fan and motor shall be filled with
lubricant oil every half year, while for the unit powered off in transition season, it
shall be filled with lubricant oil every year.
4.12. After two years’ operation, please conduct comprehensive maintenance. To
clear the scale in heat exchanger by chemical methods, and clean the fins with
compressed air or water.
9
reason. Please mind the checking on fan blower and bearing. If there is any
damage on bearing, please replace it immediately.
B. Sound:
If there is any abnormal vibration, please stop the fan instantly to find out the
reason. Please mind the belt creep, loose connection, foreign materials,
bearing/motor failure, especially the bearing.
C. Temperature:
Please mind the temperature on bearing base/motor cover. If you can only keep
your finger 3~4 seconds on the base/cover, then it means the temperature is
about 60℃, or you can use instrument for precision recognizing. Belt creep can
result in belt overheat when the fan is stopped, please test the tension and adjust
it
Drawing 4-1
A. Slight loose the 4 fixing bolts.
B. Move the motor with adjusting bolts.
C. If the adjusting bolts are limited and the motor can not be moved to required
position, then loose jack bolts on bracket, and move to proper position.
D. Fix up all bolts when the belt is adjusted well.
4.15.2. Belt Replacement
Loose bolts on motor bracket, and move the motor toward the fan, take off
old belt and fit on new one. If there are more than one belt, then replace all of
them. The new and old belts shall be replaceable, and completely have the same
length. Belts shall be tested and tensed as above mentioned. Check tension of
the belts after one hour running, and check them again one week later. Abrasion
will appear on V type belts with time increasing. When fan revolving speed is
slowing down, and the supply air volume is reducing, all V type belts shall be
replaced.
When replacing the belts, the new selected belts shall have the same model
no., specification as the old ones. When the specification is unknown, it can be
calculated. The replacing procedures are as following:
A. Stop the fan, and hang a warning board with “in operation, no switching on”, to
avoid and human injury and/or equipment damage.
B. Loose bolts on motor and rail fixing screw
C. Take off old belts and fit on new ones.
11
D. Adjust position of bolts to get a proper belt tension, as above mentioned.
E. Adjust setting-up bolts to make pulley face of motor and fan on the level face.
Seeing the drawing 4-2:
F. Tight up bolts.
G. Start up motor and check until every thing is normal.
4.16. With appropriate water seal when the unit is installed, you need to ensure a
smooth condensate drain shown in drawing 4-3. Operator should always check
whether there is enough water in the trap, or should be full. If there is no
condensate in the season, the condensate system valve should be closed.
12
A. Pre-filters are set in slide bracket. Vertical type, horizontal type are designed
front draw our or side draw out, while ceiling concealed type designed side
draw out or down draw out. The primary filter can be washed repeatedly, long-
term use.
B. Mid-filter and sub-high/High efficiency filter are modular design with different
standard size.
C. Pre-filters are set in slide bracket,designed side draw out or down draw out.。
D. Pre-filters are installed well before installing mid-filter, please check the
sealing strip on frame of every filter elements. After installing every filter
elements one by one, chuck the filter frame and slide bracket with clamping
screw from the leeward side.
E. The sealing face of sub-HEPA / HPEA is the surface of outlet side frame.
There is sealing strip on filter frame, and the side with sealing strip must be
installed on leeward side. After installed all filters one by one,please tight all
filter elements from the windward side with fastener on bracket.
F. When installing sub-high/high efficiency filter, the division plate of every filter
element must be vertically.
Notes:
(1) When the pressure on both side of the mid-filter and sub-high filters are higher
than the initial resistance about 150Pa, The pressure on both side of the HEPA
are higher than the initial resistance is twice, you should Clean or replace the
filters.
(2) The early and medium efficiency bag filter are multi-bag (6 bags or bags),
When installation, it should be marked by the direction of the filter on the border,
and keep the filters vertically.
(3) It must clean the air duct system before the clean room start, after the unit
running for 12 hours, the sub-filter and HEPA can be the installation.
(4) The sub-high filter and HEPA should be unpacking carefully and handle
(5) With the gap between the sealing tape tightly sealed filter bridge to prevent the
airflow bypass.
(6) The installation of filters should be from under to upon, when take down should
be from upon to under.
5. Operation manual
13
Thank you for using our air conditioning unit. Please read the following instructions carefully
before using the unit!
Air conditioning unit uses PLC as the main control system, with text displays as a local operating
human-machine interface (HMI). Customer can operate and monitor the unit with the local HMI.
touch display
Above picture is the HMI used in the control system.
The monitoring and operating part is in middle of the panel. The user can control the whole
unit through touching the panel. There are buttons’ introduction in below content:
Backward page-turning: press once will turn to the backward page of the screen
Forward page-turning: press once will turn to the forward page of the screen.
Return key: No matter in any menu, press the button, the screen will return to
main screen .
When touch the parameters needed revise or button in main menu screen, the touch panel will
show a soft keyboard. Except the numbers and letters , several keys are defined in below
content:
14
key, press it to not save and exit.
5.2.Menu Introduction
5.2.1 Main Menu
A.Parameter Display
A1、Control Parameter:
Ctrl Temp,Ctrl_Humi :The controlled temperature and humidity detected by control system. The
controlled temperature and humidity is the basic of the instruction of control system.Controlled
pressure difference:When the unit is set to the pressure difference control fan frequency, such
as the actual unit without pressure difference control function, it does not need to pay attention
to. Controlled dew point, set dew point : Be converted by temperature & humidity and
temperature set& humidity set. When dew point control is not used, it is only displayed, and
dehumidification control is used when dew point control is enabled.
This screen displays the set-point of temperature / humidity/ differential pressure, and can not
be changed in this screen. You can enter the set menu to change the value.
The upper right corner is the current internal clock of the control system. It is mainly used for
timing operation. Please modify the time through the status menu. System time needs to be set
when "empty" or when the time is inconsistent with the actual time after the week.
A2、Unit State:OFF/ON/ALARM/R_STOP/DELAY.
OFF:Unit is stop;
ALARM:Unit failure occurs;
R_STOP: refers to when the remote control switch is used and it is disconnected, the start-up
15
command is switched to start, the unit can not start;
DELAY: refers to the stop instruction, and the unit is delayed.
A3、Control mode:AUTO/MAN/TIMING
AUTO:The unit will automatically adjust the operation status of the unit according to the logic of
the control system.
MAN : Unit components will be operated manually and are not recommended for use by
customers. You can see the manual menu in detail.
TIMING:The unit will start and stop automatically according to the time set by customers. See
"Timing Menu" in detail.
A4、Run mode:Summer/Winter/ Aeration
Summer/Winte : The unit adjusts the fan,
refrigeration, dehumidification, heating and
humidification operation according to the temperature
and humidity.
Aeration : the unit only start up the supply fan for
ventilation.
B.Menu Select
Select the menu to enter through the footer:《MAIN》、《STATUS》、《ALARM》、《TREND》、
《SET》Note: To enter the settings menu, you need to login to the corresponding permissions. If
there is no login status, you can not enter the settings menu.
C、Unit ON/OFF
"OFF" and "ON" buttons, by clicking on the touch screen buttons to complete the start and stop of
the unit. Click to enter the confirmation screen:
Click "Confirm" to start the unit, and click "Cancel" to maintain the original state.
16
5.2.2.1 Input Status
The input status display screen shows the
current status of each digital input point
of PLC. When the small circle is red, it
means that the input point is closed, and
when the small circle is gray, it means
that the input point is disconnected.
For the meaning of each input point,
please refer to the attached table.
And Others
Mainly introduce the company's situation and contact information, program version, etc., here do
not elaborate.
Picture
Temperature and humidity curve screen
is used to display the change trend of
temperature and humidity parameters in
15 minutes.
The blue curve represents the air
temperature and the red curve
represents the air humidity.
The maximum and minimum values are
the statistical limit values of temperature
and humidity data during this period.
19
5.2.5 Set Menu
Press the "SET" key to enter the settings menu. The settings menu can only be accessed if the
user logs in as USER privilege. If the login is not successful, the settings button will pop up the
login window, and the user needs to enter the user name and login password.
User name of Settings menu: USER; password: 8230.
After pressing the Enter Confirmation, the system returns to the current menu, and when pressing
the "SET" button, you can enter the "SET" menu.
A.Timing function: Set the Start point and Stop point in a week. The unit will run and stop
according to the set time.
B. Timing start-stop function set order:
a) Set time from Sun to Sat.
b) Enable the timing every day. Switch “No” to “Yes”.
c) Enable the mainly timing. Switch Timing function from “Forbit” to “Use”.
d) Return to main screen and touch the ON/OFF button and close the remote switch. The unit
status is “ON”.
When the above work is done, the timing function setting is finished. When the Start time
arrives, the unit will run automatically. When the Stop time arrives, the unit will stop
automatically.
21
The running time is accumulated time of
compressor operating. When the value is
over 5000, the control system will display
the ‘Compressor run overtime’ to prompt
the customer to maintain the
compressor.After the maintaining, you
can press ‘Reset’key to reset the run
time to 0.
CPU124XP
25
6. Trouble analysing and Shooting
Fault Cause Checking and Trouble Shooting
Fan reversing Change sequence
Cut-off valve is not completely open Open the valve bigger
Exhaust System with air and other non- Check forfluid electromagnetic valve circuit
pressure is too condensable gas Removing the gas from the Note fluoride
high The outdoor condenser dust blockage mouth ,re-vacuum if necessary
Refrigerant charge excess Clean the condenser
Drain refrigerant
Exhaust Check the condensation pressure controller
Ambient temperature is too low
pressure is too circuit
Refrigerant leaking or filling not enough
low Leak detection and charge fluoride
Exhaust pressure is too high See the exhaust pressure is too high "
The suction
Refrigerant charge excessive Release the part of the refrigerant
pressure is too
Excessive inhalation of fresh air Reduce the amount of new wind suction
high
Return air temperature is too high Adjust the engine room return air facilities
26
Overcurrent relay tripped burned out
insurance Replace damaged components
The control circuit is not turned Check the control system wiring
No current Check the power supply
Compressor can
Contactor coil burnout Replace damaged parts
not start
Power phase sequence connection error And reconnect exchange two of wiring
Communicator off on time setting error View alarm category, take appropriate measures
The temperature sensor detects that the Check and reset
temperature exceeds the set value
Contactor coil burnout
Replace the coil
Heating failure Heating tube burn
Replace air switch
Heated air switch thermal overload