You are on page 1of 48

Manufacturing Forward

Compressed Air Dryers

MKP 18 - MKP 10000


Instruction Manual
EC DECLARATION OF CONFORMITY
In accordance with EC Machinery directives
2006/95/EEC (LVD), 2004/108/EEC (EMC)
Inspection certificate No:46,57 2006/42/EC.
Inspection Certificate No:47,58
Inspection Body :Bureau Vertias (2287)
We,
MIKROPOR
Org.San. Bol. Buyuk Selcuklu Blv.
No:4 06935 Ankara/ TURKEY
declare that, under our sole responsibility for manufacture
and supply, the products;

The Product: Refrigerant Air Dryer

Type: MKP 18 to MKP 10000

Trade Mark: Mikropor Refrigerant Air Dryer

Serial No: 0113MA00001 to 5214MA99999

Which this declaration relates, are in conformity with the


provisions of the above directives using the following
principal standards,

EN12100-1:2011, EN12100-2:2011, EN1050, EN13857:2010,


EN378-1+A2:2012, EN60204-1:2010, EN60529:2003,
NEN-EN-IEC61000-6-1:2008,
NEN-EN-IEC61000-6-2:2008,
NEN-EN-IEC61000-6-3:2008/A1:2011,
NEN-EN-IEC61000-6-4:2008,
EN61000-3-2, issued at Ankara,
on 02/01/2013
BS EN 13445-1:2009, for Mikropor by
BS EN 13445-3:2009,
ISO 15609-2:2005, Volkan AYHAN
V.P. of Sales and Operations
ISO 15613-2006,
ISO 15614-6:2008
TABLE OF CONTENTS

1. Important safety notes - Please read ....................... 1

1.1. Transportation ............................................................ 1

1.2 Positioning .................................................................. 1

1.3 Installation ................................................................... 1

1.4 Before operating ......................................................... 1

1.5 Maintenance by an engineer ...................................... 1

1.6 Maintenance by the user ............................................ 1

2. Introduction to the MKP dryer .................................. 2

3. Operation ..................................................................... 4

4. Technical specifications ............................................ 10

5. Diagrams .............................................................................11

6. General Arrangements .............................................. 28

7. Main Settings .............................................................. 28

8. Drawings...................................................................... 29

9. Components location............................................... 41

10.Troubleshooting ........................................................ 42

11. Warranty .................................................................................... 45


I. IMPORTANT SAFETY NOTES – Please READ

A) When operating the air dryer the operator must apply safe working methods and observe all local safety
instructions and relevant regulations.
B) Prior to installation, the dryer and the compressed air system are to be depressurized and disconnected
from the electrical main supply.
C) The user is responsible for safe operating conditions. Parts and accessories must be replaced if inspection
shows that safe operation cannot be assured.
D) Installation, operation, maintenance and repair are only to be authorized, trained and skilled engineers.
E) The minimum and maximum values stated must be observed, as well as all of the safety precautions described
in this manual.
F) If any statement in this manual does not comply with the local legislation, the strongest standard is to be applied.

1.1. Transportation

A) Use care and caution when transporting the dryer. Avoid dropping and other physical abuse.
B) A forklift can be used to transport the dryers provided the forks are long enough to support its full width or
length and caution is used throughout the move.

1.2. Positioning

A) The dryer must be installed horizontally. A minimum of 50 cm clearance around the dryer is necessary to
allow a good ventilation and easy access for servicing.
B) The ambient temperature in the room should not exceed 50°C and should not be below 4°C, taking the heat
radiated by the dryer into account.
C) (40 watt for each liter/sec under ISO 7183-A condition or 18 watts for each SCFM under ISO 7183-B condition).

1.3. Installation

A) In addition to the general mechanical construction procedures and local regulations, the following instructions
need to be emphasized:
1) Only authorized, trained and skilled engineers should install the compressed air dryer.
2) Safety devices, protecting covers or insulation in the dryers never to be dismantled or modified.
Each pressure vessel or accessory installed outside the dryer with air above atmospheric pressure must be fitted
with the required pressure relief safety valves.

1.4. Before Operating

A) Review all safety precautions.


B) The piping must have the correct diameter and be adapted to the operating pressure (see technical specification).
C) Never operate the dryer at pressure above the maximum specified on the dryer label (check the technical specs too).
D) The drains should be opened to atmosphere. If the drains are connected to a pipe / hose, the diameter of the hose
/ pipe should be large enough to create no back pressure during drain. It is not recommended to reduce the diameter of
the hose / pipe less than port that is given at the drain outlet of the unit.
The hose / pipe should be at atmospheric pressure at all time. Back pressure in relevant pipe will result in permanent
damage on drain system and the affect function of the filters and / or dryers.

1.5. Maintenance by an Engineer

A) Maintenance and repairs should only be performed when the air dryer is shut down and depressurized and when
the main power switch is turned off.
B) Use only the appropriate tools for maintenance and repair.
C) Before dismantling a part under pressure, disconnect the pressure sources and depressurize the system.
D) Proceed carefully during maintenance and repair. Prevent dirt from entering by covering parts and orifices with
a clean cloth, paper or tape. A receiver should never be welded or modified in any way.
E) Never leave tools, loose parts or cleaning rags in or on the air dryer.
F) Before returning the dryer into service, check the setting of the control and safety devices as well as the pressure
and the temperature of the compressed air circuit.

1
1.6. Maintenance by the user

A) Keep the dryer clean.


B) Regularly check the correct operation of the condensate drain trap.
C) Every six months, check and clean the drain strainer by undoing the access screw and rinsing the filter with tap
water to remove the trapped dirt from the inside
D) For aircooled dryers, clean the air condenser as soon as it’s dirty or clogged.
E) For optional water-cooled condensers, use only clean water andinstall a water filter if needed.
Use water counter flow to clean condenser if need.
F) Check the trouble-shooting list in case of maintenance troubles.
G) Check operating pressures, temperatures and time settings after maintenance. If operating and safety devices
function properly, the air dryer may be used.

2. INTRODUCTION TO THE DRYER

A) Manufacturer: MiKROPOR / www.mikropor.com

B) Purpose of this dryer

1) This refrigerated compressed air dryer has been designed to remove water vapor from industrial compressed air.
2) This dryer has been designed for indoor operation.
3) The minimum and maximum values stated must be observed, as well as the safety precautions described
in this manual.

C) Dryer label

The following label is affixed on the cabinet


of the refrigerant compressed air dryer.
D) Working details

1) Refrigerant circuit:

The refrigerant circuit can be divided in 3 parts:

a) Low pressure section with an evaporator (heat exchanger)


b) High-pressure section including: Condenser, liquid receiver, (if installed) and the filter dryer.
c) Control circuit including: Compressor, Expansion valve, by-pass valve (if installed),
Fan pressure switch (if installed)

2) For water - cooled dryers:

a) Water valve
b) Safety high pressure switch (if installed)

3) The Refrigerant circuit operates as follows:

a) The compressor compresses gaseous refrigerant to a high temperature.


b) The hot refrigerant condenses in the condenser. Being liquefied it is stored in the liquid receiver (if installed).
c) The liquid is taken out the storage vessel and injected in the evaporator (heat exchanger) by an expansion valve.
This expansion valve is protected by a filter, which removes particles and humidity that could be in the circuit.
d) The injected liquid fills in the refrigerant section of the air / refrigerant heat exchanger and evaporates by taking
out the calories from the compressed air. The gaseous refrigerant is sucked in the compressor and the cycle
carries on.
e) In order to keep the evaporation pressure steady, and thus the refrigerant temperature in the heat exchanger,
a by-pass valve is injecting hot gaseous refrigerant in the circuit. On certain dryers, an automatic expansion valve
regulates this.

4) Compressed air circuit

a) The saturated hot compressed air flows into the Economiserwhere it is pre-cooled by the out flowing dry
chilled air. In the cold zone of the air refrigerant section it continues to cool

2
down to dew point and enters the separator where condensates are collected. The outgoing chilled air is then
warmed up in the economizer by the hot incoming air.
b) The condensates are collected after centrifugal separation and drained out through the automatic trap.
c) As long as the compressed air temperature does not drop below dew point, there will be no condensation
in the air circuit.

5) Refrigerant compressor

Being of the hermetic type, it requires no servicing.

6) Condenser

a) The air condensers are equipped with a helecoidal at the condenser refrigerant level.
On certain type of dryers, a water-cooled condenser can be fitted.
b) In this case, a water valve being driven by the refrigerant circuit is taking care of its regulation.

7) Refrigerant circuit protection

a) Klixon: The single phase compressors are equipped with a klixon which is a thermal sensitive switch
controlling the temperature of the compressor and possible overintensity.
In case of malfunction, the klixon trips but switches on again automatically as soon as the compressor has
cooled down.
b) High Pressure Security Switch: Refrigerant line is considered as a pressure vessel. That is why it is
protected against bursts by the help of manually reset switch. It is set to 25 bars for dryers working with R134a
c) Filter dryer: A refrigerant circuit is a closed circuit and total water removal in the refrigerant circuit is
paramount in order to obtain a correct functioning.
d) To avoid problems, the refrigerant circuit must be vacuumed before loading the refrigerant.
It is equipped with a filter dryer, which also traps any solid particles, which may have migrated into the circuit
during assembly.
e) Water-cooled dryers have a safety high-pressure switch.
In case of cooling water failure, the safety switch stops the dryer. When the safety switch has tripped out,
it has to be manually resettled before switching on the dryer.

8) Refrigerant circuit controls

a) Liquid refrigerant injection: The liquid refrigerant is into the evaporator by a control valve. This valve is a
thermostatic or pressostatic one maintaining a constant overheats of the refrigerant in the evaporator(s).
b) Constant evaporating pressure: In the dryers equipped with a by-pass valve, the evaporating pressure is kept
constant by a controlled injection of hot gas from the high-pressure side into the low-pressure section
of the circuit.

9) Condensate drain - trap assembly

Dismantling the drain is easy because it can be isolated from the air circuit under pressure with a ball valve.
The drain has to be depressurized before being dismantled.

10) Heat Exchanger Modular design

a)The dryers are equipped with a compact Mono Bloc Heat Exchanger module.
This assembly has been specially designed to dry compressed air and is made of:
1) An Economiser which pre-cools the entering hot air with the out flowing cold air.
2) An air/refrigerant exchanger cooling down the compressed air.
3) A centrifugal separator concentrating all condensates and requiring no maintenance.

11) Accessories

a) Dew point indicator: Located on the control panel, it displays the value of the pressure dew point.
b) Temperature switch: Located inside the dryer, this temperature switch is adjustable from 0 up to 35 °C.
c) Energy Saving Device: (ESD) This device helps dryer save energy when there is not any compressed air flow
in the dryer. (Please see the models have standart and optional in next page)
d) Filter change alarm on the front panel

3
3. OPERATION

3.1. Operation

A) Control panels: The control panel of the dryer includes the following elements:

Monophase ESD1 Monophase ESD1

MKP 18 - MKP 498 MKP 660 - MKP 870

2 3

1 4
1 2 3

1) ESD1 (Standard)
2) Filter change Alarm**
5
3) Start / Stop Button
1) ESD1 (Standard)
2) Start Light
3) N/A
4) Filter change Alarm**
5) Main Switch

Triphase ESD3

MKP 1110 - MKP 10000

1) ESD3 (Standard)
5) EMERGENCY STOP

** IMPORTANT NOTE: The Dryer has two Compressed Air Filter inside.
It is better to change filter element for the best efficiency when the alarm light is active.
It is recommended to keep replacement filter elements in your stock
in order to replace them when needed.

ATTENTION : MKP range dryers have low pressure drop according its competitors.
Do not use MKP range dryers together with other dryers which have higher pressure drop
without getting the confirmation from our technical team.

4
3.2. During Operation
Regularly check the digital temperature controller ESD1 or ESD3 on dryer.

B) Start up and shut-down


Warning: Avoid leaving the dryer off when compressed air is still flowing through it.

C) Starting for the first time or after a long stop


1) Set the rotary switch to “I” This preheats the dryer and turns the drain system on.
It is recommended to leave the dryer power on permanently so the crankcase heater runs continuously.

2) IMPORTANT NOTE!

After a long stop of the dryer it is MANDATORY to allow a preheating period of minimum 4 hours
before starting again, to avoid any compressed air flow during preheating.

3) Follow the daily starting and shut down preocedure.

D) Daily starting and shut-down


1) Push on the green button to start the dryer.
2) The start light will indicate that the dryer is running.
3) To stop the dryer, first stop the airflow (either shut-down the air compressor or close the inlet/outlet or
by-pass valve) When the air flow is stopped set the rotary switch on “ 0 “ Set it again on “ I “ in order to keep the
preheating on.
4) IMPORTANT NOTE!
Avoid leaving the dryer stopped when compressed air is still flowing through it.
5) To switch the already preheated dryer on again, simply push the green start button.

E) Digital Temperature Control technical features (ESD1)

ESD1
!
-The terminals 01 to 05 and 11-12 are
electrically live. While the instrument
is powered, never touch to these
terminals.

Before operating the controller,


ensure that the controller is correctly
configured. Incorrect configuration
could result in damage to the process
(Pic.1) being controlled.

The labels on the sides of the controller identify the ordering code (Type) serial number and wiring connections.

ESD1: Standard for monophase dryers


ESD3: PLC clear text multilingual indication of alarms, maintenance and running hours
+ Energy Saving Device automatic switching OFF at no load and ON
when warm compressed air is entering. (NOTE: Please see the ESD3 manual which is given with Dryer)

5
1) Operating principle

The display visualizes the temperature when the temperature is reduced to 20C and stable for 10 min.
than the controller switches off the dryer. It switches on the dryer again when the temperature reaches to 90C
If the temperature detected is higher or lower than the temperaure set by the trimmer R1 and R2, the relay is
powered and related
Alarm led is lightened on display;
When the temperature detected by the temperature probe is within the normal working range than the alarm is
resetted and both alarm light and the relay is swithhed off.

-
-

Explanation Parameters for ESD1

6
F) Bekomat Drain Technical Features (Optional)

7
8
MKP
Technical Specifications
& Diagrams
4. TECHNICAL SPECIFICATIONS

Maximum Maximum Maximum


Absorbed Max. Fuse Refrigerant Pressure drop working ambient inlet
Model Capacity Connection Voltage Power Amperaje Amperaje gas (mbar) pressure temperature temperature
(m3/h) Size (kw) (Amp) (Amp) (bars) o
( C) (oC)

MKP 18 18 1/2’’ 230/1/50 0,32 3 4 R134a 100 16 50 60


MKP 30 30 1/2’’ 230/1/50 0,32 3 4 R134a 140 16 50 60
MKP 42 42 1/2’’ 230/1/50 0,37 3,5 4 R134a 220 16 50 60
MKP 66 66 3/4’’ 230/1/50 0,37 3,5 4 R134a 50 16 50 60
MKP 96 96 3/4’’ 230/1/50 0,60 6 8 R134a 100 16 50 60
MKP 130 130 3/4’’ 230/1/50 0,68 7 8 R134a 150 16 50 60
MKP168 168 1 1/2’’ 230/1/50 0,82 8,5 10 R134a 100 16 50 60
MKP240 240 1 1/2’’ 230/1/50 1,08 11,5 16 R134a 150 16 50 60
MKP300 300 1 1/2’’ 230/1/50 1,27 12,5 16 R134a 80 16 50 60
MKP396 396 2’’ 230/1/50 1,30 15 16 R134a 120 16 50 60
MKP498 498 2’’ 230/1/50 1,30 15,5 16 R134a 100 16 50 60
MKP660 660 2” 230/1/50 1,43 20 25 R134a 100 16 50 60
MKP870 870 2” 230/1/50 1,81 24 25 R134a 120 16 50 60
MKP1110 1110 3” 400/3/50 2,77 14,5 16 R134a 220 16 50 60
MKP1380 1380 3” 400/3/50 3,14 16 20 R134a 180 16 50 60
MKP1710 1710 3” 400/3/50 4,03 21 25 R134a 120 16 50 60
MKP2220 2220 3” 400/3/50 4,62 22,5 25 R134a 220 16 50 60
MKP2664 2664 DN100 400/3/50 5,51 27 30 R134a 170 16 50 60
MKP3132 3132 DN100 400/3/50 6,16 29,5 30 R134a 250 16 50 60
MKP4068 4068 DN100 400/3/50 7,76 41,5 50 R134a 200 16 50 60
MKP4680 4680 DN100 400/3/50 9,92 49 50 R134a 220 16 50 60
MKP5580 5580 DN150 400/3/50 11,13 57,5 63 R134a 200 16 50 60
MKP6300 6300 DN150 400/3/50 11,91 60,5 63 R134a 230 16 50 60
MKP7200 7200 DN150 400/3/50 15 81,5 100 R134a 220 16 50 60
MKP8400 8400 DN200 400/3/50 15 81,5 100 R134a 220 16 50 60
MKP10000 10000 DN200 400/3/50 18,43 102 125 R134a 220 16 50 60

FOR ALL MODELS


Nominal Pressure 7 bar
Maximum pressure 16 bar
Maximum ambient temperature 50°C
Minimum ambient temperature 4°C
Maximum inlet temperature 60°C

10
1

AIR OUTLET AIR CIRCUIT:

-A: Air/Refrigerant exchanger


9 D -B: Manual valve
MKP 18 - MKP 300

AIR INLET
-C: Solenoid valve and timer
2 8 -D: Air filter
5.1 AIR FLOW DIAGRAMS

M
A
REFRIGERANT CIRCUIT:
S

11
4 -1. Compressor
3
B C -2. Fan
5. DIAGRAMS

-3. Condenser
-4. Fan switch**
-5. High pressure switch*
5 6 7
-6. Filter dryer
-7. Expansion valve
-8. Air/Refrigerant exchanger
IMPORTANT NOTICE: -9. Hot gas by-pass valve**
REFRIGERANT GAS FLOW
5 : Only from MKP66 to MKP300 *
9 : Only from MKP168 to MKP300 ** COMPRESSED AIR FLOW

DRAIN FLOW
MKP 396 - MKP 10000
1

11

AIR OUTLET AIR CIRCUIT:

-A: Air/Refrigerant exchanger


12 F -B: Manual valve
AIR INLET
-C: Membrane valve
2 9 -D: Solenoid valve
10 -E: Timer*
-F: Air filter**

M
A E
S
REFRIGERANT CIRCUIT:

12
D
4 -1. Compressor
3
B C -2. Fan
-3. Condenser
-4. Fan switch
-5. High pressure switch
5 7 8
-6. Liquit recevier
6 -7. Filter dryer
-8. Expansion valve
IMPORTANT NOTICE: -9. Air/Refrigerant exchanger
E : Timer is not used from MKP1110 to MKP10000 * REFRIGERANT GAS FLOW
-10. Low pressure switch
F : Only from MKP498 to MKP2220 **
COMPRESSED AIR FLOW -11. Suction acumulator****
12 : Hot gas by-pass valve with solenoid
control only used from MKP4068 to MKP10000 *** DRAIN FLOW -12. Hot gas by-pass valve***
11 : Suction acumulator is not used MKP396 and MKP498 ****
5.2 ELECTRICAL DIAGRAMS

13
A14: Filter change buzzer
A20: Drain supply
A40-1: Start capacitor
K01: Compressor start relay
FIELD INSTALLED K02: Compressor motor contactor
K30: Economizer relay (ESD1)
S01: On/off button
S10: Fan pressure switch
S16: Filter service contact
M01: Compressor motor
M10: Fan motor
P: Compressor motor overload protector
HP: indicates high pressure
PT: Temperature sensor (PT100)
Electrical Circuit
MKP 18 - MKP 42
14
A14: Filter change buzzer
A20: Drain supply
A40-1: Start capacitor
FIELD INSTALLED K01: Compressor start relay
K02: Compressor motor contactor
K30: Economizer relay (ESD1)
S01: On/off button
S10: Fan pressure switch
S16: Filter service contact
S12: High pressure safety switch
M01: Compressor motor
M10: Fan motor
P: Compressor motor overload protector
HP: indicates high pressure
Electrical Circuit

PT: Temperature sensor (PT100)


MKP 66 - MKP 240
15
A14: Filter change buzzer
A20: Drain supply
A31: Bleeder resistor
FIELD INSTALLED A40-1: Start capacitor
A40-2: Run capacitor
K01: Compressor start relay
K02: Compressor motor contactor
K30: Economizer relay (ESD1)
S01: On/off button
S10: Fan pressure switch
S12: High pressure safety switch
S16: Filter service contact
M01: Compressor motor
M10: Fan motor
P: Compressor motor overload protector
HP: indicates high pressure
PT: Temperature sensor (PT100)
MKP 300
Electrical Circuit
16
A14: Filter change buzzer
A15: Running lamp (Green)
FIELD INSTALLED A20: Drain supply
A31: Bleeder resistor
A40-1: Start capacitor
A40-2: Run capacitor
A50: Fan motor capacitor
K01: Compressor start relay
K02: Compressor motor contactor
K30: Economizer relay (ESD1)
S01: On/off button
S10: Fan pressure switch
S12: High pressure safety switch
S16: Filter service contact
NOTE 1: COMPRESSOR MOTOR DRAWING CAN BE M01: Compressor motor
TYPE 1 or TYPE 2 DEPENDING ON ASSEMBLED M10: Fan motor
COMPRESSOR MODEL HP: indicates high pressure
NOTE 2: A15 DOES NOT EXIST IN MKP 396 PT: Temperature sensor (PT100)
Electrical Circuit
MKP 396 - MKP 870
A11 : Remote control running lamp (Green)
A13: Remote control stand-by lamp (Red)
A20: Electronic timer
A21: Drain Test
A41: Remote control alarm contact
B16: Computer / Communication connection (RS485)
B17: Dewpoint analog output (4-20mA/0-100C)
EMR4: Phase protection relay
F10 : Control circuit protection
F11 : Control circuit protection
K20 : Drain supply test relay
P1 : Overload protector of compressor
P10 : Overload protector of fan motor
PT1 : Inlet air temperature sensor (PT100)
PT2 : Heat exchanger temperature sensor (PT100)
PT3 : Low pressure line sensor (PT100)
PT4 : High pressure line sensor (PT100)
PT5 : Ambient temperature sensor (PT100)
PT6 : Condenser outlet temperature sensor (PT100)
S2 : Limit switch
S3 : Emergency button

17
S5 : Remote control start button
S7 : Remote control stop button
S8 : Remote control contact
S9 : Obstruction for manual on/off
S10 : Fan pressure switch
S12 : High pressure safety switch
S13 : Low pressure switch
S15 : Service contact
S16 : Filter service contact
S31 : Fan heat termal 1
S32 : Fan heat termal 2
Q1 : Compressor motor contactor
Q10: Fan motor contactor
HP : Indicates high pressure
LP : Indicates low pressure
TH : Indicates thermal

FIELD INSTALLED

Broken line cables are dependent on customer wish.


Electrical Control Circuit

NOTE 1: S16 DOES NOT EXIST IN MKP 2664 and MKP 3132
MKP 1110 - MKP 3132

NOTE 2: DRAIN SYSTEM CAN BE TYPE 1 or TYPE 2


18
A01 : Control circuit transformer
MAIN PROTECTION AND DISCONNECTING MEANS SHALL BE PROVIDED BY A30 : Compressor chankaser heater
THE INSTALLER OF RESIDUAL CURRENT AUTOMATIC CIRCUIT BREAKER B15 : Control circuit supply
EMR4 : Phase protection relay
ELECTRICAL SPECIFICATIONS SIZE IS AMPS-600 VAC
F1,F2 : A01 Primary protection
F3, F4: A30 overload protection
COMPRESSOR FAN MOTOR E L EC T R I C A L S U P P LY L I N E M1 : Compressor motor
UN 400V/3/50 UN 400V/3/50 3 PHASE + PROTECTION EARTH M10 : Fan motor 1
CABLE SIZE M11 : Fan motor 2
MKP 1110 FLA 10 A 1.82 Kw MKP 1110 FLA 0.50 A 0.18 Kw MKP 1110 4G2.5mm P1 : Overload protector of compressor
MKP 1380 FLA 11 A 2.19 Kw MKP 1380 FLA 0.50 A 0.18 Kw MKP 1380 4G2.5mm P10 : Overload protector of fan
MKP 1710 FLA 15 A 2.9 Kw MKP 1710 FLA 0.72 A 0.270 Kw MKP 1710 4G4mm Q1 : Compressor contactor
MKP 2220 FLA 10 A 3.49 Kw MKP 2220 FLA 0.72 A 0.270 Kw MKP 2220 4G4mm Q10 : Fan contactor
MKP 2664 FLA 10 A 3.9 Kw MKP 2664 FLA 1.8 A 0.510 Kw MKP 2664 4G4mm X1 : Main supply connection
MKP 3132 FLA 10 A 4.57 Kw MKP 3132 FLA 1.82 A 0.510 Kw MKP 3132 4G4mm terminal block

MAXIMUM SET : 15%


Electrical Power Circuit
MKP 1110 - MKP 3132

FIELD INSTALLED
A11 : Remote control running lamp (Green)
A13: Remote control stand-by lamp (Red)
A20: Electronic timer
A21: Drain Test
A41: Remote control alarm contact
B16: Computer / Communication connection (RS485)
B17: Dewpoint analog output (4-20mA/0-100C)
EMR4: Phase protection relay
F10 : Control circuit protection
F11 : Control circuit protection
K20 : Drain supply test relay
P1 : Overload protector of compressor
P2 : Compressor thermal protection
P10 : Overload protector of fan motor
PT1 : Inlet air temperature sensor (PT100)
PT2 : Heat exchanger temperature sensor (PT100)
PT3 : Low pressure line sensor (PT100)
PT4 : High pressure line sensor (PT100)
PT5 : Ambient temperature sensor (PT100)
PT6 : Condenser outlet temperature sensor (PT100)
S2 : Limit switch
S3 : Emergency button
S5 : Remote control start button
S7 : Remote control stop button
S8 : Remote control contact

19
S9 : Obstruction for manual on/off
S10 : Fan pressure switch
S12 : High pressure safety switch
S13 : Low pressure switch
S15 : Service contact
S16 : Filter service contact
S31 : Fan heat termal 1
S32 : Fan heat termal 2
Q1 : Compressor motor contactor
Q10: Fan motor contactor
V1 : By-pass valve
HP : Indicates high pressure
LP : Indicates low pressure
TH : Indicates thermal

FIELD INSTALLED

Broken line cables are dependent on customer wish.


Electrical Control Circuit

NOTE 1: A25 AND P2 JUST EXIST IN MKP 5580


MKP 4068 - MKP 5580

NOTE 2: DRAIN SYSTEM CAN BE TYPE 1 or TYPE 2


20
A01 : Control circuit transformer
A30 : Compressor chankaser heater
MAIN PROTECTION AND DISCONNECTING MEANS SHALL BE PROVIDED BY B15 : Control circuit supply
THE INSTALLER OF RESIDUAL CURRENT AUTOMATIC CIRCUIT BREAKER EMR4 : Phase protection relay
F1,F2 : A01 Primary protection
ELECTRICAL SPECIFICATIONS SIZE IS AMPS-600 VAC F3, F4: A30 overload protection
M1 : Compressor motor
M10 : Fan motor 1
COMPRESSOR FAN MOTOR E L EC T R I C A L S U P P LY L I N E M11 : Fan motor 2
UN 400V/3/50 UN 400V/3/50 3 PHASE + PROTECTION EARTH P1 : Overload protector of compressor
CABLE SIZE P10 : Overload protector of fan motor
MKP 4068 FLA 28 A 5.63 Kw MKP 4068 FLA 2.63 A 0.780 Kw MKP 4068 4G10mm Q1 : Compressor contactor
MKP 4680 FLA 34 A 6.79 Kw MKP 4680 FLA 2.63 A 0.780 Kw MKP 4680 4G16mm Q10 : Fan contactor
MKP 5580 FLA 41 A 9 Kw MKP 5580 FLA 2.63 A 0.780 Kw MKP 5580 4G16mm X1 : Main supply connection
terminal block
MAXIMUM SET : 15%
Electrical Power Circuit
MKP 4068 - MKP 5580

FIELD INSTALLED
A11 : Remote control running lamp (Green)
A13: Remote control stand-by lamp (Red)
A20: Electronic timer
A21: Drain Test
A41: Remote control alarm contact
B16: Computer / Communication connection (RS485)
B17: Dewpoint analog output (4-20mA/0-100C)
EMR4: Phase protection relay
F10 : Control circuit protection
F11 : Control circuit protection
K20 : Drain supply test relay
P1 : Overload protector of compressor
P2 : Compressor thermal protection
P10 : Overload protector of fan motor 1
P11 : Overload protector of fan motor 2
P12 : Overload protector of fan motor 3
PT1 : Inlet air temperature sensor (PT100)
PT2 : Heat exchanger temperature sensor (PT100)
PT3 : Low pressure line sensor (PT100)
PT4 : High pressure line sensor (PT100)
PT5 : Ambient temperature sensor (PT100)
PT6 : Condenser outlet temperature sensor (PT100)
S2 : Limit switch
S3 : Emergency button

21
S5 : Remote control start button
S7 : Remote control stop button
S8 : Remote control contact
S9 : Obstruction for manual on/off
S10 : Fan pressure switch
S12 : High pressure safety switch
S13 : Low pressure switch
S15 : Service contact
S16 : Filter service contact
S31 : Fan heat termal 1
S32 : Fan heat termal 2
S33 : Fan heat termal 3
Q1 : Compressor motor contactor
Q10: Fan motor contactor 1
Q11 : Fan motor contactor 2
Q12 : Fan motor contactor 3
V1 : By-pass valve
HP : Indicates high pressure
LP : Indicates low pressure
TH : Indicates thermal
FIELD INSTALLED
MKP 6300

Broken line cables are dependent on customer wish.


NOTE 1: DRAIN SYSTEM CAN BE TYPE 1 or TYPE 2
Electrical Control Circuit
22
A01 : Control circuit transformer
A30 : Compressor chankaser heater
B15 : Control circuit supply
EMR4 : Phase protection relay
F1,F2 : A01 Primary protection
MAIN PROTECTION AND DISCONNECTING MEANS SHALL BE PROVIDED BY F3, F4: A30 overload protection
THE INSTALLER OF RESIDUAL CURRENT AUTOMATIC CIRCUIT BREAKER M1 : Compressor motor
M10 : Fan motor 1
ELECTRICAL SPECIFICATIONS SIZE IS AMPS-600 VAC M11 : Fan motor 2
M12 : Fan motor 3
E L EC T R I C A L S U P P LY L I N E P1 : Overload protector of compressor
COMPRESSOR FAN MOTOR
3 PHASE + PROTECTION EARTH P10 : Overload protector of fan motor 1
UN 400V/3/50 UN 400V/3/50
P11 : Overload protector of fan motor 2
CABLE SIZE P11 : Overload protector of fan motor 3
MKP 6300 FLA 41 A 9 Kw MKP 6300 FLA 2.63 A 0.780 Kw MKP 6300 4G16mm Q1 : Compressor contactor
Q10 : Fan contactor 1
MAXIMUM SET : 15% Q11 : Fan contactor 2
Q12 : Fan contactor 3
MKP 6300

X1 : Main supply connection


FIELD INSTALLED terminal block
Electrical Power Circuit
A11 : Remote control running lamp (Green)
A13: Remote control stand-by lamp (Red)
A20: Electronic timer
A21: Drain Test
A41: Remote control alarm contact
B16: Computer / Communication connection (RS485)
B17: Dewpoint analog output (4-20mA/0-100C)
EMR4: Phase protection relay
F10 : Control circuit protection
F11 : Control circuit protection
K20 : Drain supply test relay
P1 : Overload protector of compressor
P2 : Compressor thermal protection
P10 : Overload protector of fan motor 1
P11 : Overload protector of fan motor 2
PT1 : Inlet air temperature sensor (PT100)
PT2 : Heat exchanger temperature sensor (PT100)
PT3 : Low pressure line sensor (PT100)
PT4 : High pressure line sensor (PT100)
PT5 : Ambient temperature sensor (PT100)
PT6 : Condenser outlet temperature sensor (PT100)
S2 : Limit switch
S3 : Emergency button

23
S5 : Remote control start button
S7 : Remote control stop button
S8 : Remote control contact
S9 : Obstruction for manual on/off
S10 : Fan pressure switch
S12 : High pressure safety switch
S13 : Low pressure switch
S15 : Service contact
S16 : Filter service contact
S31 : Fan heat termal 1
S32 : Fan heat termal 2
S33 : Fan heat termal 3
S34 : Fan heat termal 4
Q1 : Compressor motor contactor
Q10: Fan motor contactor 1
Q11 : Fan motor contactor 2
V1 : By-pass valve
HP : Indicates high pressure
LP : Indicates low pressure
TH : Indicates thermal
FIELD INSTALLED
Electrical Control Circuit

Broken line cables are dependent on customer wish.


MKP 7200 - MKP 8400

NOTE 1: DRAIN SYSTEM CAN BE TYPE 1 or TYPE 2


24
A01 : Control circuit transformer
A30 : Compressor chankaser heater
B15 : Control circuit supply
EMR4 : Phase protection relay
F1,F2 : A01 Primary protection
F3, F4: A30 overload protection
M1 : Compressor motor 1
M2 : Compressor motor 2
MAIN PROTECTION AND DISCONNECTING MEANS SHALL BE PROVIDED BY M10 : Fan motor 1
THE INSTALLER OF RESIDUAL CURRENT AUTOMATIC CIRCUIT BREAKER M11 : Fan motor 2
M12 : Fan motor 3
ELECTRICAL SPECIFICATIONS SIZE IS AMPS-600 VAC M13 : Fan motor 4
P1 : Overload protector of compressor 1
COMPRESSOR FAN MOTOR E L EC T R I C A L S U P P LY L I N E P2 : Overload protector of compressor 2
UN 400V/3/50 UN 400V/3/50 3 PHASE + PROTECTION EARTH P10 : Overload protector of fan motor 1
CABLE SIZE
P11 : Overload protector of fan motor 2
Q1 : Compressor contactor 1
MKP 7200 FLA 28 A 5.63 Kw MKP 7200 FLA 2.63 A 0.780 Kw MKP 7200 4G25mm Q2 : Compressor contactor 2
MKP 8400 FLA 28 A 5.63 Kw MKP 8400 FLA 2.63 A 0.780 Kw MKP 8400 4G25mm Q10 : Fan contactor 1
Q11 : Fan contactor 2
MAXIMUM SET : 15% X1 : Main supply connection
Electrical Power Circuit

terminal block
MKP 7200 - MKP 8400

FIELD INSTALLED
A11 : Remote control running lamp (Green)
A13: Remote control stand-by lamp (Red)
A20: Electronic timer
A21: Drain Test
A41: Remote control alarm contact
B16: Computer / Communication connection (RS485)
B17: Dewpoint analog output (4-20mA/0-100C)
EMR4: Phase protection relay
F10 : Control circuit protection
F11 : Control circuit protection
K20 : Drain supply test relay
P1 : Overload protector of compressor
P2 : Compressor thermal protection
P10 : Overload protector of fan motor 1
P11 : Overload protector of fan motor 2
P12 : Overload protector of fan motor 3
PT1 : Inlet air temperature sensor (PT100)
PT2 : Heat exchanger temperature sensor (PT100)
PT3 : Low pressure line sensor (PT100)
PT4 : High pressure line sensor (PT100)
PT5 : Ambient temperature sensor (PT100)
PT6 : Condenser outlet temperature sensor (PT100)
S2 : Limit switch

25
S3 : Emergency button
S5 : Remote control start button
S7 : Remote control stop button
S8 : Remote control contact
S9 : Obstruction for manual on/off
S10 : Fan pressure switch
S12 : High pressure safety switch
S13 : Low pressure switch
S15 : Service contact
S16 : Filter service contact
S31 : Fan heat termal 1
S32 : Fan heat termal 2
S33 : Fan heat termal 3
S34 : Fan heat termal 4
S35 : Fan heat termal 5
S36 : Fan heat termal 6
Q1 : Compressor motor contactor
Q10: Fan motor contactor 1
Q11 : Fan motor contactor 2
Q12 : Fan motor contactor 3
V1 : By-pass valve
FIELD INSTALLED HP : Indicates high pressure
LP : Indicates low pressure
MKP 10000

TH : Indicates thermal
Broken line cables are dependent on customer wish.
Electrical Control Circuit

NOTE 1: DRAIN SYSTEM CAN BE TYPE 1 or TYPE 2


26
A01 : Control circuit transformer
A30 : Compressor chankaser heater
B15 : Control circuit supply
EMR4 : Phase protection relay
F1,F2 : A01 Primary protection
F3, F4 : A30 overload protection
M1 : Compressor motor 1
M2 : Compressor motor 2
M10 : Fan motor 1
M11 : Fan motor 2
MAIN PROTECTION AND DISCONNECTING MEANS SHALL BE PROVIDED BY M12 : Fan motor 3
THE INSTALLER OF RESIDUAL CURRENT AUTOMATIC CIRCUIT BREAKER M13 : Fan motor 4
M14 : Fan motor 5
ELECTRICAL SPECIFICATIONS SIZE IS AMPS-600 VAC M15 : Fan motor 6
P1 : Overload protector of compressor 1
COMPRESSOR FAN MOTOR E L EC T R I C A L S U P P LY L I N E P2 : Overload protector of compressor 2
UN 400V/3/50 UN 400V/3/50 3 PHASE + PROTECTION EARTH P10 : Overload protector of fan motor 1
P11 : Overload protector of fan motor 2
CABLE SIZE
P12 : Overload protector of fan motor 3
MKP 10000 FLA 28 A 5.63 Kw MKP 10000 FLA 2.63 A 0.780 Kw MKP 10000 4G35mm Q1 : Compressor contactor 1
Q2 : Compressor contactor 2
MAXIMUM SET : 15% Q10 : Fan contactor 1
Q11 : Fan contactor 2
MKP 10000

Q12 : Fan contactor 3


FIELD INSTALLED
Electrical Power Circuit

X1 : Main supply connection


terminal block
MKP
General Arrengements
Main Settings
Spare Parts
Drawings
6. GENERAL ARRANGEMENTS

Model Filter Quantity Element Type Length Width Height Weight


and Type (mm) (mm) (mm) (Kg)

MKP 18 1 * GKO50X + 1 * GKO50Y MKO50 KIT 413 363 557 32


MKP 30 1 * GKO50X + 1 * GKO50Y MKO50 KIT 413 363 557 32
MKP 42 1 * GKO50X + 1 * GKO50Y MKO50 KIT 413 363 557 32
MKP 66 1 * GKO150X + 1 * GKO150Y MKO150 KIT 473 453 832 51
MKP 96 1 * GKO150X + 1 * GKO150Y MKO150 KIT 473 453 832 53
MKP 130 1 * GKO150X + 1 * GKO150Y MKO150 KIT 473 453 832 55
MKP168 1 * GKO500X + 1 * GKO500Y MKO500 KIT 553 503 874 78
MKP240 1 * GKO500X + 1 * GKO500Y MKO500 KIT 553 503 874 83
MKP300 1 * GKO500X + 1 * GKO500Y MKO500 KIT 553 503 874 86
MKP396 1 * GKO851X + 1 * GKO851Y MKO851 KIT 678 648 1157 160
MKP498 1 * GKO1210X + 1 * GKO1210Y MKO1210 KIT 678 648 1157 165
MKP660 1 * GKO1210X + 1 * GKO1210Y MKO1210 KIT 948 728 1370 220
MKP870 1 * GKO1210X + 1 * GKO1210Y MKO1210 KIT 948 728 1370 230
MKP1110 1 * GKO1820X + 1 * GKO1820Y MKO1820 KIT 948 798 1460 270
MKP1380 1 * GKO1820X + 1 * GKO1820Y MKO1820 KIT 948 798 1460 285
MKP1710 1 * GKO2700X + 1 * GKO2700Y MKO2700 KIT 1163 778 1725 392
MKP2220 1 * GKO2700X + 1 * GKO2700Y MKO2700 KIT 1163 778 1725 410
MKP2664 Not Included Not Included 1397 847 1770 492
MKP3132 Not Included Not Included 1397 847 1770 520
MKP4068 Not Included Not Included 1467 1077 1930 696
MKP4680 Not Included Not Included 1467 1077 1930 718
MKP5580 Not Included Not Included 2188 1062 1925 900
MKP6300 Not Included Not Included 2188 1062 1925 -
MKP7200 Not Included Not Included 2697 897 1975 -
MKP8400 Not Included Not Included 2697 897 1975 -
MKP10000 Not Included Not Included 2550 1550 2100 1600

7. MAIN SETTINGS

Superheat of Evaporating Fan Security Security Drain Refrigerant Water flow


thermostatic pressure pressure high low timer temperature valve
expansion switch pressure pressure switch (if water
valve switch switch condenser)

ALL MODELS 5OC - 10OC 2.05 bar 9 - 12 bar 25 bar 1.6 bar 5 min. - 5 sec. 45OC 11 bar

28
TOP VIEW

413
CONTROL
PANEL 363 AIR OUTLET
129,5 117 71,7
G 1/2" AIR INLET
G 1/2"

29,4
CONNECTION
CABLE

29
556,8
COOLING AIR OUTLET
477,9
480,2
8. DRAWINGS

COOLING AIR INLET

100
FRONT VIEW BACK VIEW
LEFT VIEW 130
DRAIN
RIGHT VIEW
M8x4

51,5
260
51,5
13 387 13
MKP 18 - MKP 42

BOTTOM VIEW
AIR OUTLET
TOP VIEW G 3/4"
473
AIR INLET
CONTROL
PANEL 453 G 3/4" 80,5129,6 82
CABLE
CONNECTION

77,5
29,3

30
831,8
725

694,1

COOLING AIR OUTLET


DRAIN
COOLING AIR INLET
100

FRONT VIEW BACK VIEW


LEFT VIEW RIGHT VIEW 100
M8x4

51,5
350
51,5
13 447 13
MKP 66 - MKP 130

BOTTOM VIEW
553

503
TOP VIEW

AIR INLET AIR OUTLET


CONTROL
G 1 1/2"
PANEL G 1 1/2" 112,4 167,6
100,5
121,8

95
CONNECTION
29,5 CABLE

31
873,8
701

COOLING AIR OUTLET

COOLING AIR INLET


100

FRONT VIEW 150 BACK VIEW


LEFT VIEW DRAIN
RIGHT VIEW
12,3 528,5 12,3
14x4

51,5
400
51,5
TOP VIEW
MKP 168 - MKP 300
678

TOP VIEW

648
198,6 152,7 AIR OUTLET CONTROL
G 2" PANEL

103,4
AIR INLET
G 2" SUPPLY CABLE
GLAND

246,2
29,45

1157,3

32
83,8 COOLING AIR OUTLET

807,7
COOLING AIR INLET

171
FRONT VIEW BACK VIEW
DRAIN
RIGHT VIEW
LEFT VIEW 564,8
56,6
5x 4
Ø
11,

124
400 BOTTOM VIEW
MKP 396 - MKP498
948 TOP VIEW

198,9 152,7 AIR OUTLET 728


AIR INLET
G 2"
G 2" CONTROL
PANEL

350,2
1369,3

33
932
83 COOLING AIR OUTLET
SUPPLY CABLE
GLAND COOLING AIR INLET

177,3
DRAIN FRONT VIEW RIGHT VIEW BACK VIEW
LEFT VIEW

269
Ø14x4

410
269
39 650 39
MKP 660 - MKP 870

BOTTOM VIEW
948 TOP VIEW
198,9 305,6 AIR OUTLET 798
AIR INLET G 3"
G 3" ESD3
ELECTRICAL
CABINET

262,5

34
1459
COOLING AIR OUTLET

1018,1
83
COOLING AIR INLET

177,3
DRAIN FRONT VIEW RIGHT VIEW BACK VIEW
LEFT VIEW
Ø14x4

269
410
269
MKP 1110 - MKP 1380

39 720 39

BOTTOM VIEW
615 81,5
COOLING AIR OUTLET

81,5 500 500 81,5

81,5
TOP VIEW
778 1163 243,8 275,2

AIR INLET AIR OUTLET


ESD3 G 3"
G 3"

35
1722,3
100

1292,3
1198,5
COOLING AIR INLET
CABLE
CONNECTION 83

452
382
312
177,5
FRONT VIEW LEFT VIEW DRAIN RIGHT VIEW
BACK VIEW

39
700
39

311,5 540 311,5


M8x4
MKP 1710 - MKP 2220

BOTTOM VIEW
54,3 644,2 644,2 54,3

83,5
680
COOLING AIR OUTLET

83,5
TOP VIEW

262 316 1397 847

AIR

478
OUTLET

ESD3

273
DN100
FLANGE
AIR 102,5

36
INLET 109,2
CABLE
CONNECTION COOLING AIR INLET
DRAIN

1018
521,9
451,9
381,9
311,9

177,2
LEFT VIEW CABLE FRONT VIEW RIGHT VIEW
BACK VIEW
117,2 CONNECTION

540 153,5
153,5
M8

323,5 750 323,5


x8

BOTTOM VIEW
MKP 2664 - MKP 3132
101.0 632.5 632.5
101.1
101.2

874.7
COOLING AIR OUTLET

101.1
TOP VIEW
1467.0 1077.0
465.4 315.5

AIR OUTLET
500.2
ESD3
272.5 DN100
FLANGE
AIR INLET 103.8
CABLE

37
CONNECTION COOLING AIR INLET 105.9
1153.5 127.2
DRAIN

657.2
587.2
517.2
447.2

288.4
LEFT VIEW RIGHT VIEW FRONT VIEW RIGHT VIEW

55.5

966.0

55.5
17
55.5 1356.0 55.5 x4
BOTTOM VIEW
MKP 4068 - MKP 4680
101.8 900.0 184.1 900.0 101.8

93.7

874.7
COOLING AIR OUTLET COOLING AIR OUTLET

93.6
TOP VIEW

454.4 316.0 2188 1062.0

AIR OUTLET
498.4

272.5 DN150 ESD3


FLANGE
102.8
AIR INLET

1924.0
COOLING AIR INLET 108.8
1153.1 130.0
DRAIN

38
312.5

657.1
587.1
517.1
447.1
BACK VIEW RIGHT VIEW FRONT VIEW LEFT VIEW

55.5

951.0

55.5
17x4
55.5 2076.6 55.5
BOTTOM VIEW
MKP 5580 - MKP 6300
COOLING AIR OUTLET COOLING AIR OUTLET

TOP VIEW
605,5
897 2697
289,5

AIR OUTLET
ESD3
FLANGE

39
104,3
AIR INLET

1974
COOLING AIR INLET

1425,7
128,75
DRAIN

1153,2

657
587
517
447
201,3
RIGHT VIEW LEFT VIEW
FRONT VIEW BACK VIEW
DN150 FLANGE (MKP 7200)
DN200 FLANGE (MKP 8400)
786

2586 Ø
17
BOTTOM VIEW
MKP 7200 - MKP 8400
COOLING AIR OUTLET

TOP VIEW 1203,6


1550 2550 832

ESD3 AIR OUTLET

DN200 FLANGE

104,3

40
2100
COOLING AIR INLET
1481,4

1153,3
719,71

657
587
517
447
201,8

FRONT VIEW RIGHT VIEW


DRAIN LEFT VIEW
BACK VIEW

1436

Ø1
2436 7
BOTTOM VIEW
MKP 10000
9. COMPONENTS LOCATION

All main components locatad into dryer identified with labels as listed here under.
CAUTION: Due to manufacture design, some components out of the list are not installed into the dryer.

41
10. TROUBLESHOOTING

Problem Possible Cause Repair Comments


Dryer is The connection has Invert two phases 3-phase dryers are equipped with a phase controller
switched on, inverted phases to avoid the fans from turning in the opposite
indicator light direction.
is lit but the
refrigerant Several factors can cause compressor failure.
compressor Refrigeration unit is not functioning Check refrigeration compressor A qualified refrigeration technician needs to check
does not turn on. all the electrical and refrigerant circuit and controls.

The refrigerant high pressure protection The refrigerant safety high The dryer is protected against excessively high
has tripped pressure switch has tripped. refrigerant pressure. If the condenser efficiency has
reduced, the switch will trip. Manually reset the
switch.

In case of water cooled con-


densers, check the water
control valve

Excessive ambient temperature Be sure that dryer is working A high ambient temperature may cause the
in temperatures lower than the refrigerant system to operate at higher than normal
design conditions. pressures. Results will be higher than normal
Designed conditions and evaporator temperature.
correction factors are described lmportant: adequate air circulation around the dryer,
in this manual. and proper ventilation in the equipment room should
guarantee a low enough ambient temperature.

Excessive temperature on Allow time to compressor to Compressor is protected against overly high
Dryer is crankcase of compressor. cool down. Reason may be a temperatures of the crankcase by a thermal switch.
switched on, possible incorrect adjustment
but the refrigerant of hot gas bypass valve or
compressor shortage of refrigerant
does not turn on.
Excessive compressed Be sure that dryer is working The dryer is designed for working in calculated
air inlet temperature. in temperatures lower than conditions (see description in this manual).
design conditions. If conditions are exceeded, the dryer will be
overflowed, dew point will go up and protecting
devices can switch off.

Clogged condenser fins or clogged Clear fins or water condenser The clogged fins in the condenser will restrict the
water condenser. of all obstructions. air passage and reduce the refrigeration capacity,
causing high temperature in the evaporator.
Possible high crankcase temperature Same will occur if water condenser is clogged with
mud or dirt. Air condenser and water condenser
Possible loss of phase should be periodically checked and cleaned.
Protect water circuit by an adapted filter.
Possible low voltage causing overload
trip Possible failed compressor

Too much compressed air flow. Check actual flow This dryer is designed for a maximum air flow at
through the dryer. design conditions. If too much air is pumped
into the dryer, water removal capacity may not be
sufficient, resulting in liquid carryover down stream.
Check the rated output the air compressor.

Faulty electrical wiring Inspect the circuit The compressor-on light should be wired into the
refrigerant compressor circuit. See wiring diagrams
in this manual.

One electrical protection Reset the protection or The dryer is protected against high amp draw by
has tripped. replace the blown fuse. fuse and/or overload relay that can trip in case of
need. Reset or replace fuse once, but do not persist
if it trips again, request assistance from a qualified
refrigeration contractor.

Dryer is switched Fan has to run if refrigerant high Check that compressed air Fan operates automatically to keep refrigerant
on but fan is not pressure reaches upper set point. flows through the dryer. Check pressure below the maximum value. The fan can
running. that fan blades are free to move. stop if pressure is under the recommended setting.
Check the fan pressure switch.

When compressor Compressor is slugging liquid refrigerant Be sure the pre-heating period Refrigerant may move between receivers when
starts, it vibrates at start up. of at least 2 hours is refrigerant compressor is stopped and not heated,
a lot and makes respected especially if stopped for a long time.
mechanical noise. This migration may cause liquid shock (slugging) in
valves specially on large dryers containing more
refrigerant

42
Problem Possible Cause Repair Comments
Water in Compressed Air Inlet and Check inlet and outlet This dryer is designed for air flow in one direction
system outlet connections are reversed. connections. only. Inlet and outlet directions are identified on
the dryer.
Drain system is timed solenoid valve,
Drain system is clogged Restore a free flow of water pneumatically assisted which has to be adjusted
or inoperative. condensate. Check water in accordance with values listed in this manual.
evacuation. The Solenoid valve includes a strainer that has to be
periodically checked and cleaned.
Membranes of pneumatically assisted drain have to
be checked or replaced every 6 months.

Bypass system is open Check the valves Important: Bypass piping should be installed
around the dryer so the dryer can be isolated for
service without shutting down the air supply.
During dryer operation, valves must be set so all air
goes into the system. Check tightness
of the bypass system.

Free moisture remains in pipe lines. Blow out the system Before the dryer is first started all free moisture
should be blown out of the system.

Excessive air flow Check actual flow through the This dryer is designed for a maximum air flow.
dryer. If too much air is pumped into the dryer, water removal
capacity may not be sufficient, resultingin liquid
Carry over downstream. Check the rated flow of the
air compressor .
Excessive free moisture Check the separator and drain In some system there may be an accumulation of free
system and compressor after moisture in the line ahead of the dryer. If this moisture
cooler ahead of the dryer. is pumped into the dryer intermittently, the water
removal capacity may not be sufficient.
A water separator should be installed in the line
before the dryer.

Excessive compressed Be sure that dryer is working The dryer is designed to work for calculated design
air inlet temperature. lower than design conditions conditions. Should the conditions be exceeded,
the dryer will be overflowed, dew point will go up
and protecting devices can switch off.

Clogged condenser fins Clear fins of all obstructions The clogged fins in the condenser will restrict air
passage and reduce refrigerant capacity causing
water downstream. Fins should be periodically
checked and cleaned.

Shortage of refrigerant Fix the leak and add a Loss of refrigerant will cause improper functioning.
charge of refrigerant. A qualified, refrigeration specialist should perform
the necessary repairs, or factory should be
contacted if the unit is in warranty.

Check to be certain refrigerant To check if the compressor is running, check


Refrigeration system is not functioning compressor is running compressor-on light. lt is possible for the fan to be
operating but not the compressor.
Compressor not running can be caused by several
taeters. A qualified refrigeration technician should
check all refrigerant and electrical controls

Excessive pressure dew point Readjust refrigerant The refrigerant pressure adjustment should be
evaporating pressure done by a qualified refrigeration engineer. This is
a very sensitiye device and incorrect settings may
create other failures.

High pressure Excessive compressed Check actual pressure and This dryer is designed for a maximum air flow.
drop air flow or too law air inlet pressure. flow through the dryer. If too much air is pumped into the dryer,
water removal capacity may not be sufficient,
resulting in liquid carry-over downstream.
Check the rated flow of the air compressor.

Freeze up Check that compressor room Frosting of the Iines is an indication that controls
ambient, are set too low. The following should be done by
an experienced refrigeration technician.

Fan switch could have failed Controls may be adjusted in the fields by means of
in closed position keeping fan the hot gas bypass valve. This is to be done
on. by a qualified refrigerant technician.

Clean heat exchanger Dryer are supposed to be used with compressed


Clogged heat exchanger with areverse air flow. air free of any aggressive contaminants. Some
The unit will contamination may require extra maintenance of
not run or the heat exchanger.
cycles off
and on. Line disconnect switch is Close the start or disconnect If the dryer is not operating, check the disconnect
open. switch. switch or circuit breaker to be certain it is on.
The fuse to the power line should be checked and
Fuse or breaker is open Replace fuse or reset breaker. replaced if needed. Never replace a burnt fuse
with an oversized fuse.

Faulty refrigerant Determine the cause and make Failure of compressor to run may be caused by
compressor or controls. correction several factors. A qualified refrigeration specialist
should check all electrical and refrigeration controls,
or factory should be contacted if unit is in warranty.
Excessive compressed air Design conditions and correction The dryer is designed for working into calculated design
inlet temperature. factors are described in this manual. conditions. Should the conditions be exceeded,
Be sure that dryer is working the dryer will be overflowed, dew point will go up and
in ambient temperatures protecting devices may trip.
below design conditions.

43
Problem Possible Cause Repair Comments
The unit will not run Excessive ambient Designed conditions and cor- A high ambient temperature may cause the refrigerant
or cycles off and on. temperature rection factors are described system to operate at higher than normal pressures.
in dryer . Be sure that dryer is Results will be a higher than normal evaporator
working lower than design temperature.
conditions. Important: there should be adequate air circulation
around the dryer, and proper ventilation in the
equipment room should guarantee a low enough
ambient temperature.

Clear fins of all obstructions. The clogged fins in the condenser will restrict the air
Clogged condenser fins passage and reduce the refrigeration capacity,
causing high temperature in the evaporator.
Fins should be periodically checked and cleaned.

Fix the leak and add a charge Loss of refrigerant will cause improper functioning.
Shortage of refrigerant of refrigerant. Dryers are equipped with a temperature switch which
maintains the amount of refrigerant to maintain
proper cooling of the compressor.
A shortage of refrigerant may cause suction line to
become very hot, causing the temperature switch
to trip. A qualified refrigeration specialist should
perform the necessary repairs.

Error sign occurs on Check refrigerant gas and If there is not enough refrigerant gas or if the working
digital temperature The dew point is too low make sure that the working temperature and inlet temperatures are very high,
control device or too high. conditions are within the cor- the dew point will increase.
rect range.
Drain Failure Back pressure or Back First of all replace the Max drain hose length after the dryer
reduction of drain port. drain / drains. Open drain to must not exceed 10 meters.
atmosphere (no back pressure)
-  if hose / pipe is used to carry Max drain hose height from the dryer
the drain somewhere else; must not exceed 3 meters.
keep or enlarge the diameter.
The drain port size should not be reduced.
There should not be any fitting that may cause
pressure drop such as valves, elbow, tees, etc.
on the drain connection.

Drain should be at atmospheric pressure at all times.


Any back pressure will result in failure
and malfunction.

44
11.WARRANTY

Refrigerated Dryer (MKP)


WARRANTY POLICY

When used under the conditions recommended by the manufacturer Mikropor, MKP Dryer is warranted to be
free from defects in material and workmanship for a period of twenty-four (24) months from date of receipt, not to
exceed thirty (30) months from the factory ship date, provided Mikropor is furnished the customer’s name, address,
and date of shipment information.

The heat exchanger will be warranted for two (2) years. This warranty is limited to the replacement of the heat exchangers,
F.O.B. Factory, and subject to the same restrictions as outlined below concerning misuse, abuse or accident.
The standard equipment external float drain and optional automatic drain carry a 90-day warranty.
This warranty will apply to equipment installed, operated and maintained in accordance with the procedures
and recommendations as outlined in the owner’s manual published by Mikropor during the life of this warranty,
Mikropor will repair or replace (at Mikropor option) any defective part or assembly free of charge F.O.B. its warehouse
if such defect occurred in normal service and was not due to apparent misuse, abuse or accident.
This Warranty is not transferable.
Any warranty service performed in the field must be authorized by Mikropor Unauthorized service voids the
warranty and any resulting charges will not be paid by Mikropor.
Mikropor makes no other warranties or guarantees, expressed or implied. The merchantability of the
components is expressly excluded. The manufacturer assumes no liability for indirect or consequential damages.

45

You might also like