Air System Sizing Summary for Meeting Room - 02

Project Name: Coca - Cola Plant at Bangaluru Prepared by: ANA Design Consultancy 09-22-2012 04:22PM

Air System Information


Air System Name Equipment Class Air System Type Meeting Room - 02 SPLT AHU SZCAV Number of zones Floor Area Location 1 130.0 ft Bangalore, India

Sizing Calculation Information


Zone and Space Sizing Method: Zone CFM Sum of space airflow rates Space CFM Individual peak space loads Calculation Months Sizing Data Jan to Dec Calculated

Central Cooling Coil Sizing Data


Total coil load Total coil load Sensible coil load Coil CFM at Nov 1600 Max block CFM Sum of peak zone CFM Sensible heat ratio ft/Ton BTU/(hr-ft) Water flow @ 10.0 F rise 1.2 13.9 11.5 559 599 599 0.832 112.4 106.7 N/A Tons MBH MBH CFM CFM CFM Load occurs at OA DB / WB Entering DB / WB Leaving DB / WB Coil ADP Bypass Factor Resulting RH Design supply temp. Zone T-stat Check Max zone temperature deviation Nov 1600 92.8 / 79.9 74.3 / 59.9 53.0 / 50.2 47.3 0.210 43 56.0 1 of 1 0.0 F F F F % F OK F

Supply Fan Sizing Data


Actual max CFM Standard CFM Actual max CFM/ft 599 CFM 537 CFM 4.61 CFM/ft Fan motor BHP Fan motor kW n/a 0.51 kW

Outdoor Ventilation Air Data


Design airflow CFM CFM/ft 28 CFM 0.21 CFM/ft CFM/person 6.95 CFM/person

Hourly Analysis Program v4.51

Page 1 of 4

System Psychrometrics for Meeting Room - 02


Project Name: Coca - Cola Plant at Bangaluru Prepared by: ANA Design Consultancy 09-22-2012 04:22PM

November DESIGN COOLING DAY, 1600

TABLE 1:

SYSTEM DATA
Dry-Bulb Temp (F) 92.8 74.3 53.0 56.0 56.0 73.0 73.5 Specific Humidity (lb/lb) 0.02173 0.00894 0.00796 0.00796 0.00796 0.00832 0.00832 Sensible Heat (BTU/hr) 486 11550 1622 9193 266 Latent Heat (BTU/hr) 1480 2327 845 -

Component Ventilation Air Vent - Return Mixing Central Cooling Coil Supply Fan Cold Supply Duct Zone Air Return Plenum

Location Inlet Outlet Outlet Outlet Outlet Outlet

Airflow (CFM) 26 559 559 559 559 559 559

CO2 Level (ppm) 400 1636 1636 1636 1636 1696 1696

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 0.967 BTU/(hr-CFM-F) Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4250.8 BTU/(hr-CFM) Site Altitude = 3021.0 ft

TABLE 2:

ZONE DATA
Zone Sensible Load (BTU/hr) 8980 Zone T-stat Cond Mode (BTU/hr) Cooling 9193 Zone Temp (F) 73.0 Zone Airflow (CFM) 559 CO2 Level (ppm) 1696 Terminal Heating Coil (BTU/hr) 0 Zone Heating Unit (BTU/hr) 0

Zone Name Zone 1

Hourly Analysis Program v4.51

Page 2 of 4

System Psychrometrics for Meeting Room - 02


Project Name: Coca - Cola Plant at Bangaluru Prepared by: ANA Design Consultancy 09-22-2012 04:22PM

WINTER DESIGN HEATING

TABLE 1:

SYSTEM DATA
Dry-Bulb Temp (F) 59.0 0.0 0.0 0.0 0.0 79.1 Specific Humidity (lb/lb) 0.00588 0.00000 0.00000 0.00000 0.00000 0.00000 Airflow (CFM) 0 0 0 0 0 0 CO2 Level (ppm) 400 0 0 0 0 0 Sensible Heat (BTU/hr) 0 0 0 0 0 Latent Heat (BTU/hr) 0 0 0 -

Component Ventilation Air Vent - Return Mixing Central Cooling Coil Supply Fan Zone Air Return Plenum

Location Inlet Outlet Outlet Outlet Outlet

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 0.967 BTU/(hr-CFM-F) Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4250.8 BTU/(hr-CFM) Site Altitude = 3021.0 ft

TABLE 2:

ZONE DATA
Zone Sensible Load (BTU/hr) -43 Zone T-stat Cond Mode (BTU/hr) Deadband 0 Zone Temp (F) 59.2 Zone Airflow (CFM) 0 CO2 Level (ppm) 0 Terminal Heating Coil (BTU/hr) 0 Zone Heating Unit (BTU/hr) 0

Zone Name Zone 1

Hourly Analysis Program v4.51

Page 3 of 4

Psychrometric Analysis for Meeting Room - 02


Project Name: Coca - Cola Plant at Bangaluru Prepared by: ANA Design Consultancy 09-22-2012 04:22PM

Location: Bangalore, India Altitude: 3021.0 ft. Data for: November DESIGN COOLING DAY, 1600
1. Outdoor Air 2. Mixed Air 3. Central Cooling Coil Outlet 4. Supply Fan Outlet 5. Room Air 6. Return Plenum Outlet

0.024
1

0.022 0.020 0.018 0.016 0.014 0.012

2 6

0.010 0.008 0.006 0.004 0.002 0.000 100

Specific Humidity ( lb/lb )

30

40

50

60

70 80 Temperature ( F )

90

Hourly Analysis Program v4.51

Page 4 of 4