Professional Documents
Culture Documents
LGC RESU10h SalesInstallationTraining v6
LGC RESU10h SalesInstallationTraining v6
Cathode
Separator
Anode
Manufacturing capabilities
Operating global cell manufacturing with production capacities > 65GWh by 2020
Successfully suppling quality li-ion cells to the world’s leading automotive EV manufacturers
~700k EVs with zero safety infractions
Company with a chemical background (you want this of your battery manufacturer)
Experience in multiple lithium chemistries, battery formats and applications ranging
from handheld devices to EVs
RESU13
Category RESU10H
Total Energy 9.8 kWh Light & Compact Design
Usable Energy1) 9.3 kWh
Charge 400 ~ 450VDC Easy for installation with
Inverter Interface Voltage Range
Discharge 350 ~ 430VDC world best energy density
Electrical Continuous 11.9A@420V / 14.3A@350V
Charge/Discharge Current
Characteristics Peak discharge 18.9A@370V for 10 sec.
Max. Charge/Discharge Power2) 5kW Wall mounting installation
Peak Power (only discharge)3) 7kW for 10 sec.
Communication Interface RS485
DC Disconnect Circuit Breaker, 25A, 600V rating
Mechanical Dimension (W x H x D) 29.3’’ X 35.7’’ X 8.1’’ IP55 (NEMA 3R) supporting
Characteristics Weight 214 lbs outdoor installation
Installation Location Indoor / Outdoor (Wall-Mounted)
Operating Temperature 14 ~ 113°F (-10 ~ 45°C)
Operating
Operating Temperature (Recommended) 59 ~ 86°F (15 ~ 30°C)
Conditions
Storage Temperature4) -22 ~ 131°F (-30 ~ 55°C) Maximum power of 5kW
Cooling Strategy Natural Convection
Cell UL1642
(RESU10H)
Safety
Battery Pack TUV (IEC 62619) / CE / UL1973
Reliability/
Hazardous Materials Classification Class 9
Certification
Transportation UN38.3 (UNDOT) High efficiency
Ingress Rating IP55
in its product’s heat dissipation
※ Test Conditions - Temperature 25°C, at the beginning of life
※ Total Energy is measured under specific condition from LGC(0.3CCCV/0.3CC)
1) Value for Battery Cell Only (Depth of Discharge 95%), 2kW charge/discharge power. Requisite certifications
2) LG Chem recommends 3.3kW for maximum battery lifetime supported
3) Peak Current excludes repeated short duration (less than 10 sec. of current pattern)
4) Commissioning RESU should be within 180 of manufacturing date; RESU will be
shipped with up to 30% SOC
Do
Do Not
Not Publish
Publish
Very Important!!
Do Not Publish
Turn off the circuit breaker and Replace wiring box cover, close
then turn off the auxiliary switch latches and contact customer
support 1-888-375-8044
Do Not Publish
12”
(4) (2)
12” 12”
(4) (2)
24”
* (n) denotes recommended number of fasteners
* min. clearance of 250mm (10”) between fasteners
1) Preparation 2) Unpacking 3) W/M Bracket Installation
Location Check s/n Proper Fixation
- Wall stability - Battery age - Use minimum 12 screws for
- Clearance - Battery type W/M bracket fixation
- Environmental considerations - Keep pkg materials - Check minimum screws
(no direct sunlight & rain/snow) numbers for each zone
- No flammables or explosives nearby Before Mounting
- Battery Pack
Personal Safety - Manual
- Wear protective gear (PPE) - W/M Bracket
- Screws (2ea)
12”
12” 12”
24”
Strongly recommended to exhaust all inverter troubleshooting before resorting to the battery.
RESU Resource Page……………………………...........…… for RESU updates and RESU related materials
https://mailchi.mp/830aaacb3c75/lgchem_ess_northamerica
This is important!
Linh Tran
Director of Sales – Residential ESS
ltran@lgchem.com
415-715-4673 (text/call)