Product Specification

03244C

MFR 11
Multi Function Relay
Protection

APPLICATIONS DESCRIPTION

The MFR 1 Series is a family of industrial Features (all versions)


grade protective relays that offer multiple • True RMS voltage • True RMS sensing
protective features in a single package. • Configurable trip/control set points
• Configurable delays for each alarm • Synch-check
Using a digital processor to measure true • Two-line LC display
RMS values enables a high degree of • Programmable relay
measuring accuracy regardless of MFR 11/MP outputs
harmonics, transients or disturbing pulses. • 24 Vdc power supply
• 3 configurable relays
• Discrete inputs for
The MFR 11 model is a generator or mains • Over-/undervoltage monit. (59/27) enabling or remote
protection unit packaged into one compact • Over-/underfrequency monit. (81O/U) acknowledgment
device. Typical applications are generators • Voltage asymmetry monitoring (47)
and switchgear equipment that require • PC and front panel
independent protection architecture. Different MFR 11/NU configurable
packages offer additional functionality. Same features as MFR 11/MP, plus:
• Wide-range power supply (no 24 Vdc) • Microprocessor
The MFR 11/MP is for mains protection use (90 to 265 Vac/dc) technology for
with over-/undervoltage, -frequency and accurate, repeatable
voltage asymmetry with 24 Vdc power supply MFR 11/VDEW and reliable
while the MFR 11/NU has the same Same features as MFR 11/MP, plus:
operation
functions, but utilizes a wide-range power • Vector/phase shift monitoring (78)
supply. • Programmable
MFR 11/G59
The MFR 11/VDEW adds phase/vector jump Same features as MFR 11/MP, plus: threshold setpoints
monitoring to the MP package. The • 8 configurable relays with individual time
MFR 11/G59 package adds df/dt (ROCOF) • Vector/phase shift monitoring (78) delays
protection. The MFR 11/G59N has the same • df/dt ROCOF monitoring (81RL)
features as the G59 package, but utilizes the • CE marked
wide-range power supply. MFR 11/G59N
Same features as MFR 11/G59, plus:
• UL/cUL Listed
The MFR 11/SC is used for synch-check and • Wide-range power supply (no 24 Vdc) • GL Approval
zero voltage detection to check whether two (90 to 265 Vac/dc)
systems are synchronous or de-energized.
MFR 11/SC
The compact size and multiple functions of Same features as MFR 11/MP, plus:
the MFR 11 help to simplify switchgear • 2 configurable relays
design. The digital display offers a user- • Synch-check (fixed to relay 3) (25)
friendly interface to setup the unit as well as • Zero voltage monitoring: dead bus start
monitor the operation and display any functionality (close CB to dead busbar)
alarms.
MFR 11/SC+N
Same features as MFR 11/SC, but
• Wide-range power supply (no 24 Vdc)
(90 to 265 Vac/dc)
SPECIFICATIONS
Accuracy ..........................................................................................Class 1 Relay outputs ................................................................................ isolated
Power supply.............................................................24 Vdc (18 to 30 Vdc) Contact material ............................................................................... AgCdO
Packages NU / G59N / SC+N: 90 to 265 Vac/dc Load (GP).................................................24 Vdc@2 Adc, 250 Vac@2 Aac
Intrinsic consumption ..................................................................max. 12 W Pilot duty (PD) ......................................................................24 Vdc@1 Adc
Ambient temperature................................................................ -20 to 70 °C Housing......................................................Type APRANORM DIN 43 700
Ambient humidity...................................................... 95 %, non-condensing Dimensions .........................................................................96×72×130 mm
Voltage .........Rated /Δ: [1] 66/115 Vac [4] 230/400 Vac [7] 398/690 Vac Front cutout .................................................................................91×67 mm
Maximum value (Vmax): [1] 150 Vac [4] 300 Vac [7] 600 Vac Connection ................................................ screw/plug terminals depending
Rated voltage Vph-ground: [1] 150 Vac [4] 300 Vac [7] 400 Vac on connector 1.5 mm² or 2.5 mm²
Rated surge voltage: [1] 2.5 kV [4] 4.0 kV [7] 4.0 kV Front.................................................................................insulating surface
Linear measuring range up to .......................................................1.3×Vrated Protection system................................................................................ IP 21
Measuring frequency................................................50/60 Hz (40 to 70 Hz) Weight ............................................... depending on version, approx. 800 g
Input resistance................................[1] 0.21 MΩ, [4] 0.7 MΩ, [7] 1.04 MΩ Disturbance test (CE).................................................. tested according to
Max. power consumption per path ................................................ < 0.15 W applicable EN guidelines
Discrete inputs .............................................................................. isolated Listings ..................................... UL/cUL listed (note: max. voltages apply)
Input range ....................................................................18 to 250 Vac or dc for ordinary loc., file E212970
Input resistance.....................................................................approx. 68 kΩ Approvals........................................................... GL (Germanischer Lloyd)

DIMENSIONS
Front view

Configuration port 35 mm
65 mm
72 mm

27 mm

Back plate mounting


optional (please order
brackets P/N 8923-1023)
Bottom view
130 mm 50 mm
Back view with
connecting terminals
8

Configuration port
1 16
96 mm

90 mm

130 mm

70 75

32 17

Configuration port 2005-09-09 | MFR 11 Dimensions r1ww-3605-ab.skf


WIRING DIAGRAM

Packages G59 / G59N


19 20 21 22 23 24 25 26 27 28 29 30 31 32
Relay 8

Relay 7

Relay 6

Relay 5
3/4

Relay 4
supervised system (variable)

all Packages
4

(Measuring voltage N)
3/4

Measuring voltage Measuring voltage L3


three-wire or
2

four-wire system Measuring voltage L2


all Packages

9 10 11 12 13 14 15 16
1

Measuring voltage L1
Relay 3
(Package SC: Synch-check)
CB

Relay 2
MFR 11 (Multi Function Relay)
Pack. SC
70 71 72

not measured Synchronizing voltage L3


Relay 1
2/3
synchronizing system (fixed)

(Ready for operation)


Synchronizing voltage L2

Synchronizing voltage L1
The synchronizing voltage must be connected three-
phase if the measuring voltage is connected three-
phase (N not connected). If the measuring voltage is
connected four-phase (L1-L2-L3-N), the synchronizing
voltage may be connected two-phase (L1-L2). L3 is
connected only for compensation and is not measured.
24 Vdc
all Packages
8

Packages SC+N/NU/G59N: 90 to 265 Vac/dc


Measuring voltage: 100 V AC or 400 V AC
0 Vdc
7

The socket for the PC parameterization is situated


on the side of the unit. This is where the DPC
6

Blocking of protective functions must be plugged in.


or remote acknowledgement
5

Subject to technical modifications. 2005-09-13 | MFR 11 Wiring Diagram r13ww-3705-ap.skf


FEATURES OVERVIEW
International
Woodward
PO Box 1519 MFR 11
Fort Collins CO, USA

VDEW

SC+N
G59N
80522-1519

G59
MP

NU

SC
1000 East Drake Road
Fort Collins CO 80525
ANSI
Ph: +1 (970) 482-5811 Measuring/Display
Fax: +1 (970) 498-3058 Voltage 9 9 9 9 9 9 9
Voltage (2nd input for synch-check) 9 9
Europe
Woodward Governor Company Accessories
Leonhard-Reglerbau GmbH Configuration via PC #1 9 9 9 9 9 9 9
Handwerkstrasse 29 Protection
70565 Stuttgart, Germany
Ph: +49 (0) 711 789 54-0 Overvoltage 59 9 9 9 9 9 9 9
Fax: +49 (0) 711 789 54-100 Undervoltage 27 9 9 9 9 9 9 9
Overfrequency 81O 9 9 9 9 9 9 9
Distributors & Service Underfrequency 81U 9 9 9 9 9 9 9
Woodward has an international Voltage asymmetry 47 9 9 9 9 9 9 9
network of distributors and
vector/phase shift (dϕ/dt) 78 9 9 9
service facilities. For your
nearest representative, call the df/dt (ROCOF) 81RL 9 9
Fort Collins plant or see the Function
Worldwide Directory on our Synch-check 25 9 9
website.
Zero voltage monitoring: dead bus
9 9
Corporate Headquarters start (close CB to dead busbar)
Rockford IL, USA I/O's
Ph: +1 (815) 877-7441 Output relays (configurable) 74 3 3 3 8 8 3 3
www.woodward.com/power Power Supply
24 Vdc 9 9 9 9
90 to 265 Vac/dc 9 9 9
Listings/Approvals
CE marked 9 9 9 9 9 9 9
UL/cUL listed 9 9 9 9
For more information contact:

GL (Marine) 9 9 9 9
Product Number P/N
Measuring inputs 110 Vac 5448-884 LR20610 8441-1003 5448-885 8441-1004 8441-1005 8441-1110
Measuring inputs 400 Vac 8441-1023 8441-1027 8441-1049 LR20406 8441-1103 8441-1097 8441-1111
Measuring inputs 700 Vac LR21100 8441-1084

#1 Cable incl. software necessary (DPC, Product Number P/N 5417-557)

TYPICAL APPLICATIONS
MFR 11/MP MFR 11/G59 MFR 11/SC

MFR 11/G59 MFR 11/SC


Subject to technical MFR 11/MP
modifications.
27 25
This document is distributed for
informational purposes only. It is not 27 59
to be construed as creating or
59 81O
becoming part of any Woodward
Governor Company contractual or 81U
warranty obligation unless expressly 81O
stated in a written sales contract. 47
52 off 81U
52 off 78