Professional Documents
Culture Documents
QICC – a Nexans Company is committed to deliver the highest standard wires and power cables to
the local market, GCC and for export.
In order to fit for the customer demand in the Middle East and for export, QICC – a Nexans Company
produces a versatile product range covers most of our customer needs:
BUILDING SECTION:
• Flexible wires and cables up to 16 mm2 to IEC 60227, EN 50525, BS 6004 & BS 6500.
• Building wires (NYA) to IEC 60227, EN 50525 and BS 6004, from 1.5 mm2 and above.
• Halogen Free Flame Retardant wire (HFFR/LSZH) to BS 7211 and EN 50525, with thermo
setting insulation which is alternative to wire type (NYA), where the application requires higher
standards of safety against the emission of smoke, fumes and toxic gases.
The wires coming mainly single core.
1. CONDUCTOR:
Is an object or type of material that permits the flow of electrical current in one or more directions.
Conductor materials are:
- Plain annealed or tin coated copper conductor (to BS EN 1977, ASTM B3, ASTM B49 &ASTM B 33)
- Aluminum (to ASTM B233)
The conductor structure is complying with the requirements of IEC 60228 class 2 stranded, non
compacted, compacted or compacted sector shaped conductors.
2. INSULATION:
The insulating materials used include:
2.1 Polyvinylchloride (PVC): (PVC/A 70 oC) complying with IEC 60502-1 requirements or Types (TI1
70 oC) & Heat Resistant PVC type TI-3 (90 oC to 105 oC) complying with BS EN 50363-3.
2.2 Halogen-Free, Flame Retardant compound (HFFR).
2.3 Cross-linked polyethylene (XLPE): complying with IEC 60502 and GP8 as per BS 7655-1.3
The insulation of building wires is covered by Ultra-violet (UV) resistant Masterbatch.
Number of
cores Colors to IEC 60502-1 Colors to BS 5467
1 Red or Black Brown or Blue
2 Red & Black Brown & Blue
3 Red, Yellow and Blue Brown, Black and Grey
4 Red, Yellow, Blue and Black Blue, Brown, Black and Grey
The standard range of QICC Medium Voltage XLPE cables rated up to and including 33 kV
incorporates copper wire screens based on fault levels of either 3 kA or 10 kA for 1 second. If either
of the standard screen designs does not suit a particular installation, the screen constructions can be
tailored in size to meet the specific fault requirements of any operating system.
6. CABLE ASSEMBLY:
The Insulated cores are assembled together to form the laid up cable cores in case of multi core
cables.
Extruded suitable polymer compound or non-hygroscopic polypropylene filler is applied (when
required) between laid up cores to provide a circular shape to the cable.
7. JACKETINGS:
There are 3 different types of extruded sheaths:
7.1 Outer sheath
It provides protection of the cable from outside.
7.2 Inner sheath
It applies under a metallic protection and - optional - under a lead sheath.
7.3 Bedding
It separate the sheath applied between a lead sheath and a metallic protection (may also
consists of plastic tapes).
8. ARMOUR:
There are 3 different types of armouring are listed below:
Galvanized round steel wire armour “SWA”:
(The wire diameter depends on the cable diameter under armour, min. diameter 0.9 mm).
Single or double layer of steel “STA” :
(The minimum thickness of a tape shall be 0.2 mm).
Aluminum or copper wire armour “AWA / CWA”:
(The wire diameter depends on the cable diameter under armour, min. diameter 0.9 mm).
9. JACKETING MARKETING:
10. INSTALLATION
Low voltage cables with both PVC and XLPE insulation are suitable for indoor and outdoor
applications. The methods are based on IEC 60364-5-52 or BS 7671 IEE wiring regulation
seventeenth edition.
Below are the recommendations to be followed in order to get the optimal cable service:
1. Unarmoured cables are not recommended for direct buried applications, except if the
quoted cables are designed and produced to pass direct burial test requirements (example, direct
burial tests described in UL 1277 and UL 1581).
2. Armoured cables are not recommended for tray applications, as they are heavy in weight
and extra loads are exerted on the tray.
3. A PVC jacket is a very stable material against a wide range of chemicals, while HDPE
jacketed cables can serve better in wet locations.
4. A recommended minimum bending radius as per the technical data sheet of each group.
5. HFFR cables are not recommended for direct buried applications, as the material is soft and
it’s mainly for building proposes.
IEC 60840 Power cables with extruded insulation and their accessories for rated voltages
above 30 kV (Um = 36 kV) up to 150 kV (Um = 170 kV) Test methods and
requirements - Third Edition
IEC 60853-3 Calculation of the Cyclic and Emergency Current Rating of Cables Part 3:
Cyclic Rating Factor for Cables of all Voltages, with Partial Drying of the Soil -
First Edition
IEC 60865-1 Short-circuit currents - Calculation of effects - Part 1: Definitions and
calculation methods - Second Edition; Corrigendum 1: 03/1995
IEC 60885-1 Electrical test methods for electric cables Part 1: Electrical tests for cables,
cords and wires for voltages up to and including 450/750 V - First Edition
IEC 60885-3 Electrical Test Methods for Electric Cables Part 3: Test Methods for Partial
Discharge Measurements on Lengths of Extruded Power Cable First Edition -
First Edition
IEC 60889 Hard-Drawn Aluminum Wire for Overhead Line Conductors - First Edition
IEC 60949 AMD 1 AMENDMENT 1 Calculation of thermally permissible short-circuit currents,
taking into account non-adiabatic heating effects - Edition 1.0
IEC 60986 Short-circuit temperature limits of electric cables with rated voltages from 6
kV (Um = 7,2 kV) up to 30 kV (Um = 36 kV) - Edition 2.1; Consolidated
Reprint
IEC 61089 Round Wire Concentric Lay Overhead Electrical Stranded Conductors - First
Edition; Amendment 1-1997; Replaces 60207 thru 60210: 1966
IEC 62067 Power cables with extruded insulation and their accessories for rated voltages
above 150 kV (Um = 170 kV) up to 500 kV (Um = 550 kV) – Test
methods and requirements - Edition 1.1 * Consolidated Reprint
IEC GUIDE 104 Preparation of Safety Publications and the Use of Basic Safety Publications
and Group Safety Publications - Third Edition
IEC TR 61597 Overhead Electrical Conductors - Calculation Methods for Stranded Bare
Conductors - Edition 1
IEC TS 61394 Overhead Lines - Characteristics of Greases for Aluminium, Aluminium Alloy
and Steel Bare Conductors - Edition 1.0; Includes Access to Additional
Content
2. THE BRITISH STANDARD (BS)
BS 7655: Section 6.1 Specification for Insulating and sheathing materials for cables
SELECTION OF CABLES:
It is essential to consider the specific system and installation conditions to be able to select the right
cable.
The following criteria should be taken into account to choose the suitable cable.
1. Cable Laying:
Depending on the nature of the cable system (fixed or mobile) a rigid or flexible cable should be
selected. The appropriate protection of a cable will be determined taking into account the
mechanical stress and presence of chemical, oils or hydrocarbons.
The VOLTAGE Is the electric potential difference between two points, or the difference in electric
potential energy of a unit charge transported between two points, The standard rate voltage are
defined by three values Uo / U (Um), where :
Uo = rated rms power frequency voltage, core to screen or sheath.
U = rated rms power frequency voltage, core to core.
Um = max. rms power frequency voltage, core to core.
Uo / U 0.6/1 1.8/3 3.6/6 6/10 8.7/15 12/20 18/30 38/66 76/132 127/220
(kV)
Um 1.2 3.6 7.2 12 17.5 24 36 72.5 145 245
(kV)
Cable design for 6/10, 12/20 and 18/30 kV is applicable for 6.35/11, 12.7/22 and 19/33 kV respectively.
Electrical Properties:
Physical Properties:
yp : proximity effect
Generally AC resistance is based on IEC 60287 7. INSULATION RESISTANCE
1000 * LN (D/d)
3. CAPACITANCE R=
2*π
μF/km
R : Insulation resistance at 20° C MΩ.km
C : Operating capacitance μF/km D : Insulated conductor diameter mm
d : Conductor diameter mm
D : Diameter over insulation mm
d : Conductor diameter mm
Єr :Relative permittivity of insulation material
Єr = 4.8 for PVC
Єr = 2.3 for XLPE
8.CHARGING CURRENT 11. VOLTAGE DROP
THE ELECTRIC CURRENT: is a flow of electric charge. In electric circuits this charge is often carried
by moving electrons in a wire. It can also be carried by ions in an electrolyte, or by both ions and
electrons such as in a plasma.
The calculation of the current ratings, Current rating equations(100% load factor) and
calculation of losses are based on IEC 60287 series , and the values of Current ratings for
underground applications (In Duct or Direct Buried) are derived from the latest issue of ERA
Report ‘Current Rating Standards 69.30 Part V’. and the values of current ratings are verified with
the tabulated value in IEC 60364-5-52.
The Current Carry Capacity calculated based on one circuit installed thermally isolated from other
circuits or any other heat source.
Ambient Air Temperature : 30 °C
Ambient Ground Temperature : 20°C Depth
of laying in ground : 0.70 m
Soil Thermal Resistivity :2.5 °K.m/W
For other installation conditions or any value of different air/ ground temperature, depth of laying,
different soil thermal resistivity the customer is divided to multiply the tabulated current rating by the
de-rating factor values as in tables 1 to 8.
DERATING FACTORS
1. INSTALLATION CONDITIONS FOR CABLES IN AIR
Table 1: Rating factors for ambient air temperatures other than 30 °C to be applied to the
current-carrying capacities for cables in the air:
Ambient Insulation
temperature
a °C PVC XLPE Mineral a
and
EPR PVC covered Bare not
or bare and exposed to
exposed to touch 105
touch 70 °C °C
10 1,22 1,15 1,26 1,14
15 1,17 1,12 1,20 1,11
20 1,12 1,08 1,14 1,07
25 1,06 1,04 1,07 1,04
30 1,00 1,00 1,00 1,00
35 0,94 0,96 0,93 0,96
40 0,87 0,91 0,85 0,92
45 0,79 0,87 0,78 0,88
50 0,71 0,82 0,67 0,84
55 0,61 0,76 0,57 0,80
60 0,50 0,71 0,45 0,75
65 – 0,65 – 0,70
70 – 0,58 – 0,65
75 – 0,50 – 0,60
80 – 0,41 – 0,54
85 – – – 0,47
90 – – – 0,40
95 – – – 0,32
a For higher ambient temperatures, consult the manufacturer.
2. INSTALLATION CONDITIONS FOR DIRECT BURIAL CABLES
For a cable installed direct buried, the following tables will be used to calculate the current rates
based on the actual soil thermal resistivity, Ground ambient temperature and the Depth of Laying.
Table 2: Rating factors for ambient ground temperatures other than 20 °C to be applied to the
current-carrying capacities for cables in ducts in the ground:
Ground Insulation
temperature
°C
PVC XLPE and EPR
10 1,10 1,07
15 1,05 1,04
20 1,00 1,00
25 0,95 0,96
30 0,89 0,93
35 0,84 0,89
40 0,77 0,85
45 0,71 0,80
50 0,63 0,76
55 0,55 0,71
60 0,45 0,65
65 – 0,60
70 – 0,53
75 – 0,46
80 – 0,38
Table 3: Rating factors for cables buried direct in the ground or in buried ducts for soil thermal
resistivities other than 2,5 K·m/W to be applied to the current-carrying capacities for reference
method D:
Table 4: Rating factors for one circuit or one multi-core cable or for a group of more than one
circuit:
To be
used with
current-
Arrangement Number of circuits or multi-core cables carrying
capacities,
(cables 1 2 3 4 5 6 7 8 9 12 16 20
Item
reference
touching)
1 Bunched in air, 1,00 0,80 0,70 0,65 0,60 0,57 0,54 0,52 0,50 0,45 0,41 0,38 B.52.2
on a surface, to B.52.13
embedded or
enclosed Methods A
to F
2 Single layer on 1,00 0,85 0,79 0,75 0,73 0,72 0,72 0,71 0,70
wall, floor or
unperforated
cable tray B.52.2 to
systems B.52.7
3 Single layer 0,95 0,81 0,72 0,68 0,66 0,64 0,63 0,62 0,61 No further Method C
fixed directly reduction factor for
under a more than nine
wooden ceiling circuits or multicore
4 Single layer on 1,00 0,88 0,82 0,77 0,75 0,73 0,73 0,72 0,72 cables
a perforated
horizontal or
vertical cable B.52.8
tray systems to B.52.13
5 Single layer on 1,00 0,87 0,82 0,80 0,80 0,79 0,79 0,78 0,78 Methods E
cable ladder and F
systems or
cleats etc.,
NOTE 1 These factors are applicable to uniform groups of cables, equally loaded.
NOTE 2 W here horizontal clearances between adjacent cables exceeds twice their overall diameter, no reduction factor need be applied.
NOTE 3 The same factors are applied to:
– groups of two or three single-core cables;
– multi-core cables.
NOTE 4 If a system consists of both two- and three-core cables, the total number of cables is taken as the number of circuits, and the
corresponding f actor is applied to the tables for two loaded conductors for the two-core cables, and to the tables f or three loaded
conductors for the three-core cables.
NOTE 5 If a group consists of n single-core cables it m ay either be considered as n/2 circuits of two loaded conductors or n/ 3 circuits of
three loaded conductors.
Table 5: Rating factors for more than one circuit, cables laid directly in the ground – Single-core or
multi-core cables:
Number of
circuits
Nil One
cable
(cables 0,125 m 0,25 m 0,5 m
diameter
touching)
2 0,75 0,80 0,85 0,90 0,90
3 0,65 0,70 0,75 0,80 0,85
4 0,60 0,60 0,70 0,75 0,80
5 0,55 0,55 0,65 0,70 0,80
6 0,50 0,55 0,60 0,70 0,80
7 0,45 0,51 0,59 0,67 0,76
8 0,43 0,48 0,57 0,65 0,75
9 0,41 0,46 0,55 0,63 0,74
12 0,36 0,42 0,51 0,59 0,71
16 0,32 0,38 0,47 0,56 0,38
20 0,29 0,35 0,44 0,53 0,66
a a
a Multi-core cables
a Single-core cables
NOTE 1 Values given apply to an installation depth of 0,7 m and a soil thermal
resistivity of 2,5 K·m /W . They are average values for the range of cable sizes and
types quoted for Tables B.52.2 to B.52.5. The process of averaging, together with
rounding off, can result in some cases in errors up to ± 10 %. (W here m ore precise
values are required they may be calculated by methods given in IEC 60287 -2-1.)
NOTE 2 In case of a thermal resistivity lower than 2, 5 K·m /W the corrections factors
can, in general, be increased and can be calculated by the methods given in IEC
60287-2-1.
NOTE 3 If a circuit consists of m parallel conductors per phase, then for
determining the reduction factor, this circuit should be considered as m circuits.
Table 6: Rating factors for more than one circuit, cables laid in ducts in the ground:
b Single-core cables
NOTE 1 Values given apply t o an installation depth of 0,7 m and a soil t herm al
resistivity of 2,5 K·m/W . They are average values for the range of cable sizes and
types quoted for Tables B.52.2 to B.52.5. The process of averaging, together
with rounding off, can result in some cases in errors up to ±10 %. W here m
ore precise values are required they may be calculated by methods given in the IEC
60287series.
NOTE 2 In case of a thermal resistivity lower than 2, 5 K·m/W the corrections factors
can, in general, be increased and can be calculated by the methods given in IEC
60287-2-1.
NOTE 3 If a circuit consists of n parallel conductors per phase, then for determining
the reduction factor this circuit shall be considered as n circuits
Table 7: Rating factors for group of more than one multi-core cable to be applied to reference
current-carrying capacities for multi-core cables in free air:
Vertical
perforated
cable tray 31
systems 1 1,00 0,91 0,89 0,88 0,87 –
(not e 2 1,00 0,91 0,88 0,87 0,85 –
4)
Spaced
Touching
Touching
1 1,00 0,87 0,82 0,80 0,79 0,78
Cable 32
ladder 2 1,00 0,86 0,80 0,78 0,76 0,73
systems, 33
3 1,00 0,85 0,79 0,76 0,73 0,70
cleats, etc. 34
6 1,00 0,84 0,77 0,73 0,68 0,64
(not e
3)
Spaced
1 1,00 1,00 1,00 1,00 1,00 –
2 1,00 0,99 0,98 0,97 0,96 –
3 1,00 0,98 0,97 0,96 0,93 –
NOTE 1 Values given are averages for the cable types and range of conductor sizes considered in Tables A.52.8 to
A.52.13. The spread of values is generally less than 5 %.
NOTE 2 Factors apply to single layer groups of cables as shown above and do not apply when cables are installed in
more than one layer touching each other. Values for such installations may be significantly lower and has to be
determined by an appropriate method.
NOTE 3 Values are given for vertical spacing between cable t rays of 300 mm and at least 20 mm between cable
trays and wall. For closer spacing the factors should be reduced.
NOTE 4 Values are given for horizontal spacing between cable t rays of 225 mm with cable trays mounted back t o
back. For closer spacing the factors should be reduced.
Table 8: Rating factors for groups of one or more circuits of single-core cables to be applied to
reference current-carrying capacity for one circuit of single- core cables in free air
Touching
Perforat
ed cable 1 0,98 0,91 0,87 Three cables
tray 31 2 0,96 0,87 0,81 in
systems
horizontal
3 0,95 0,85 0,78
(not e 3) formation
Vertical
perforat Touching 1 0,96 0,86 – Three cables
31 in vertical
ed cable formation
2 0,95 0,84 –
tray
systems
(not e
Cable4) Touching
ladder
systems, 32 1 1,00 0,97 0,96 Three cables
cleats, etc. 33 2 0,98 0,93 0,89 in
horizontal
(not e 3) 34 3 0,97 0,90 0,86
Touching
Perforat
ed cable
tray 1 1,00 0,98 0,96
systems 31 2 0,97 0,93 0,89
(not e 3)
3 0,96 0,92 0,86
Spaced
Vertical
perforat 1 1,00 0,91 0,89 Three cables
ed cable 31 in trefoil
2 1,00 0,90 0,86 formation
tray
systems
(not e
Cable
4)
ladder
systems, 32 1 1,00 1,00 1,00
cleats, etc.
33 2 0,97 0,95 0,93
(not e 3)
34 3 0,96 0,94 0,90
NOTE 1 Values given are averages f or t he c able types and range of conductor sizes considered in Table B. 52.8
to B.52.13. The spread of values is generally less than 5 %.
NOTE 2 Factors are given for single layers of cables (or trefoil groups) as shown in the table and do not apply
when cables are installed in more than one layer touching each other. Values f or such installations may be
significantly lower and should be determined by an appropriate method.
NOTE 3 Values are given for vertical spacing between cable trays of 300 mm and at least 20 mm between cable
trays and wall. For closer spacing the factors should be reduced.
NOTE 4 Values are given for horizontal spacing between cable trays of 225 mm with cable trays mounted back
to back. For closer spacing the factors should be reduced.
NOTE 5 For circuits having more than one cable in parallel per phase, each three phase set of conductors
should be considered as a circuit for the purpose of this table.
NOTE 6 If a circuit consists of m parallel conductors per phase, then for determining the reduction factor this circuit
should be considered as m circuits.
SHORT CIRCUIT RATING – CONDUCTORS
The permissible short-circuit currents as presented in figures 1 to 6 are calculated in accordance with
IEC 60724:2008.
The calculation method neglects heat loss and is accurate enough for the majority of practical
cases. Any error is on the safe side. However, caution should be exercised when using large size
conductors and an installation radius less than 8 x cable diameter where high deforming forces
may occur. Where such conditions cannot be avoided, it is recommended to reduce the short
circuit rating by 15% or contact SCC technical department.
Figure 1
Ik (0.155/ t) * S
Figure 2 Ik (0.1038/ t) * S
Figure 3 Ik (0.075/ t) * S
Figure 4 Ik (0.068/ t) * S
Figure 5 Ik (0.143/ t) * S
Figure 6
Ik (0.0937/ t) * S
I : Short-circuit current (kA)
k : Duration of short-circuit current t (sec.)
S : Cross-sectional area of conductor (mm2)
Instructions for transport, handling, storage of drums and laying of the cables.
The cables, whether they are armoured or unarmoured, are manufactured with high quality materials
allowing long storage, handling, transport and unreeling subject to the following recommendations.
Before acceptance of a shipment, all reels must be inspected. Any sign of damage should be noticed
to the carrier (broken flanges, damaged wrapping or or lagging, interlocked flanges, broken reels…)
Correct Incorrect
The unloading and the different handling will be done carefully with lifting
equipments.
In case of handling with a crane, an axle is used in crossing the drum centre, lifted from both ends by
two slings. It must have length equal, at least, to the width of the drum. It prevents the lifting cable or
chain from pressing against the reel flanges.
Correct Incorrect
In case of handling with a forklift truck, the drum is laid vertically with care on the forks.
Correct Incorrect
II. Rolling directions
When a reel is rolled from one point to another, it must be rolled “only” in the direction shown by
arrows as printed on the reel.
Correct Incorrect
III. Storage
Cables can be stored, with site temperature limits: -15 + 60 degrees celcius. For Outdoor location the
maximum relative humidity is 90% at all temperatures. The cables drums must be appropriately
wedged, transported and stored in a vertical position (never laid on flange) on a flat, dry and solid
ground that is not liable to settlement.
They must be protected to avoid any mechanical risk and exterior shocks.
The original wooden lags have to be kept until the cable unreeling to ensure a good protection of the
cable. The both ends of the cable (inner & outer ends) have to be watertight in order to avoid
penetration of water or humidity inside the cable. Thermo retractable polyethylene caps must be fixed
on both ends.
V. Ultraviolet Protection
Cable drums with cable that is not “UV” resistant shall at times be covered to protect the cable from
“UV” damage.
Laying temperature:
Installation shall be postponed if the temperature is lower than- 5 degrees celcius. Below this temp.
cables shall be stored in a room where temp. is higher than 10 degrees celcius at least 24hours
before unreeling. Cables shall be unreeled as soon as they are removed from the room and the usual
bending radius should be increased as possible.
Pulling strength:
The pulling strengths applied directly to the copper or aluminum cores of the cables should not
exceed:
- 5daN/mm2 of cross section for copper conductors
-3daN/mm2 of cross section for aluminum conductors.
The pulling must be regular without shock and continuously checked by a dynamometer (esp. in case
of using a winch).
Bending radius:
During the unreeling, the bending radius shall be, at least, “twice the static bending radius (as
specified in our technical data sheets)”.
Cables Unreeling:
The drum shall be settled on jacks by using a spindle through the central hole of the drum.
The unreeling speed shall be monitored at any moment.
The cables must be reeled “only in the opposite direction indicated by the arrow” printed on the
flange of the drum (“do not unreel the cable in the same direction of the arrow”).
Correct Incorrect
Cable Wind direction and end mark shall be indicated on both the flanges. While unreeling, the
cables shall not be twisted, waved or buckled.