You are on page 1of 44

BRITISH STANDARD BS EN 3-10:2009

Portable fire
extinguishers
Part 10: Provisions for evaluating
the conformity of a portable fire
extinguisher to EN 3-7

ICS 13.220.10

NO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAW


BS EN 3-10:2009

National foreword

This British Standard is the UK implementation of EN 3-10:2009. It


supersedes BS EN 3-6:1996 which is withdrawn.
The UK participation in its preparation was entrusted to Technical
Committee FSH/2, Fire extinguishers.
A list of organizations represented on this committee can be obtained on
request to its secretary.
This publication does not purport to include all the necessary provisions
of a contract. Users are responsible for its correct application.
Compliance with a British Standard cannot confer immunity
from legal obligations.

This British Standard Amendments/corrigenda issued since publication


was published under the
authority of the Standards
Policy and Strategy Date Comments
Committee on 31 July 2010

© BSI 2010

ISBN 978 0 580 54044 8


BS EN 3-10:2009

EUROPEAN STANDARD EN 3-10


NORME EUROPÉENNE
EUROPÄISCHE NORM November 2009

ICS 13.220.10 Supersedes EN 3-6:1995

English Version

Portable fire extinguishers - Part 10: Provisions for evaluating


the conformity of a portable fire extinguisher to EN 3-7

Extincteurs d'incendie portatifs - Partie 10: Dispositions Tragbare Feuerlöscher - Teil 10: Festlegungen für die
pour l'évaluation de la conformité d'un extincteur d'incendie Bestätigung der Konformität tragbarer Feuerlöscher nach
portatif à l'EN 3-7 EN 3-7

This European Standard was approved by CEN on 17 October 2009.

CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European
Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national
standards may be obtained on application to the CEN Management Centre or to any CEN member.

This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the respons bility of a CEN member into its own language and notified to the CEN Management Centre has the same status as the
official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland,
France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal,
Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.

EUROPEAN COMMITTEE FOR STANDARDIZATION


COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG

Management Centre: Avenue Marnix 17, B-1000 Brussels

© 2009 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 3-10:2009: E
worldwide for CEN national Members.
BS EN 3-10:2009
EN 3-10:2009 (E)

Contents Page

Foreword ..............................................................................................................................................................3
Scope ......................................................................................................................................................4
2 Normative references ............................................................................................................................4
3 Terms and definitions ...........................................................................................................................5
4 Symbols and abbreviations ..................................................................................................................5
5 Documentation for type testing and audits ........................................................................................6
5.1 Identification of the applicant ...............................................................................................................6
5.2 Identification of the manufacturer........................................................................................................6
5.3 Identification of the extinguisher .........................................................................................................6
5.4 Documents provided with the extinguisher ........................................................................................6
5.5 Pressure Safety ......................................................................................................................................6
5.6 Quality Management System ................................................................................................................6
5.7 Extinguishing media toxicological information ..................................................................................6
6 Initial type testing ..................................................................................................................................6
7 Factory Production Control (FPC) .......................................................................................................7
7.1 Requirements .........................................................................................................................................7
7.2 Additional requirements .......................................................................................................................8
8 Reference numbering and marking .....................................................................................................8
9 Items to be regularly checked and recorded during production ......................................................8
10 Surveillance ......................................................................................................................................... 11
Annex A (informative) Points to be checked by the surveillance body ...................................................... 12
A.1 Minimum audit frequency .................................................................................................................. 12
A.2 Audits content ..................................................................................................................................... 12
A.2.1 Manufacturer and subcontractors .................................................................................................... 12
A.2.2 Applicant .............................................................................................................................................. 13
A.3 Audit report ......................................................................................................................................... 13
Annex B (normative) Technical Data Sheet of an extinguisher .................................................................. 14
Annex C (normative) Model of laboratory report .......................................................................................... 16
PORTABLE FIRE EXTINGUISHER .................................................................................................................. 16
Annex 1 to the test report ............................................................................................................................... 35
Annex 2 to the test report ............................................................................................................................... 38
Annex 3 to the test report ............................................................................................................................... 39
Bibliography ..................................................................................................................................................... 40

2
BS EN 3-10:2009
EN 3-10:2009 (E)

Foreword
This document (EN 3-10:2009) has been prepared by Technical Committee CEN/TC 70 “Manual means of fire
fighting equipment”, the secretariat of which is held by AFNOR.

This European Standard shall be given the status of a national standard, either by publication of an identical
text or by endorsement, at the latest by May 2010, and conflicting national standards shall be withdrawn at the
latest by May 2010.

Attention is drawn to the possibility that some of the elements of this document may be the subject of patent
rights. CEN [and/or CENELEC] shall not be held responsible for identifying any or all such patent rights.

This document supersedes EN 3-6:1995.

EN 3 consists of the following parts, under the general title Portable fire extinguishers:

 Part 7 1): Characteristics, performance requirements and test methods;


)
Part 8 2 : Additional requirements to EN 3-7 for the construction, resistance to pressure and mechanical
tests for extinguishers with a maximum allowable pressure equal to or lower than 30 bar;


2)
Part 9 : Additional requirements to EN 3-7 for pressure resistance of CO2 extinguishers;

 Part 10 3): Provisions for evaluating the conformity of a portable fire extinguisher to EN 3-7.

According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following
countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Cyprus, Czech
Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain,
Sweden, Switzerland and United Kingdom.

1) Superseded EN 3-1, EN 3-2, EN 3-4 and EN 3-5.


2) EN 3-8 and EN 3-9 superseded EN 3-3.
3) EN 3-10 supersedes EN 3-6.

3
BS EN 3-10:2009
EN 3-10:2009 (E)

1 Scope
This European Standard specifies the minimum requirements for attesting the conformity of portable fire
extinguishers to EN 3-7, as well as the requirements for the quality and production control of the fire
extinguishers.

It specifies the documentation to be provided regarding:

 identification of the applicant;

 identification of the manufacturer, if not the applicant;

 identification of subcontractor(s), if applicable;

 identification of the extinguisher;

 documents provided with the extinguisher;

 CE marking;

 quality management system;

 extinguishing media toxicological information.

It specifies methods for:

 type testing;

 factory assessment;

 controls during production.

NOTE 1 A test report and a satisfactory audit supporting documentation could form the basis for an applicant to
request a certification of his product from an EA accredited certification body. Additional requirements can be made by
national regulations and/or quality marks.

NOTE 2 Where appropriate, component family testing could be applied.

2 Normative references
The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.

EN 3-7:2004+A1:2007, Portable fire extinguishers — Part 7: Characteristics, performance requirements and


test methods

CEN/TR 15642, Unified tests procedures for the tests of EN 3-7

EN ISO 9001:2000, Quality management systems — Requirements (ISO 9001:2000)

ISO/TR 8550 (all parts), Guidance on the selection and usage of acceptance sampling systems for inspection
of discrete items in lots

4
BS EN 3-10:2009
EN 3-10:2009 (E)

3 Terms and definitions


For the purposes of this document, the terms and definitions given in EN 3-7:2004+A1:2007 and the following
apply.

3.1
surveillance body
inspection body third party, independent from the manufacturer

3.2
testing laboratory
third party independent from the manufacturer

3.3
manufacturer
legal entity that assembles and normally fills the fire extinguisher

3.4
sub contractor
legal entity that undertakes on behalf of the manufacturer specific operations formally described in a sub-
contract agreement

3.5
applicant
legal entity, which assumes full product responsibility

NOTE The applicant may also be the manufacturer.

3.6
EA
accreditation of laboratories, inspection bodies and certification bodies by the European Co-operation for
Accreditation

NOTE The European Co-operation for Accreditation (EA) is the European network of nationally recognised
accreditation bodies based in the European geographical area and is acknowledged by the European Commission and
EFTA by memorandum of understanding concerning co-operation (see www.european-accreditation.org ).

3.7
certification body
impartial body, governmental or non-governmental, possessing the necessary competence and responsibility
to carry out certification of conformity according to given rules of procedure and management

4 Symbols and abbreviations


For the purposes of this document, the following symbols and abbreviations apply.

EA European Accreditation

PED Pressure Equipment Directive (97/23/EC)

QMS Quality Management System

FPC Factory Production Control

TDS Technical Data Sheet

5
BS EN 3-10:2009
EN 3-10:2009 (E)

5 Documentation for type testing and audits

5.1 Identification of the applicant

The identification of the applicant shall be provided.

5.2 Identification of the manufacturer

All locations directly controlled by the manufacturer and involved in the extinguisher’s manufacture shall be
identified.

5.3 Identification of the extinguisher

Identification of the extinguisher shall contain:

 complete set of drawings in accordance clearly characterising the model; drawing shall enable each piece
of pressure equipment and component to be identified;

 Technical Data Sheet (TDS) (see model in Annex B).

5.4 Documents provided with the extinguisher

Documents on storage, installation, use and maintenance instructions shall be provided.

5.5 Pressure Safety

PED EC approval certificate(s) for fire extinguisher’s assembly covering both, type and production, from a
PED notified body shall be provided.

Clear link shall be made between EC type approval and the model of extinguisher.

5.6 Quality Management System

The Quality Management System documentation, if any, shall be provided

NOTE Users of this document are advised to consider the desirability of accreditation in accordance with
EN ISO 9001 delivered by an EA certification body or other Quality Management System (QMS) documentation giving an
equivalent quality confidence. Equivalency is subjected to certification body’s appreciation.

5.7 Extinguishing media toxicological information

Safety data sheet in accordance with European Directive 1907/2006/EC including its modifications shall be
provided.

6 Initial type testing


The applicant shall make available to a testing laboratory for assessment to EN 3-7:

 a batch of 50 extinguishers from which the number of extinguishers necessary for the verification shall be
taken; the extinguishers selected shall be regarded as prototypes;

 full documentation (drawings, technical file, etc.) of the extinguisher to be tested;

 a documentation relating to the extinguishing media;

6
BS EN 3-10:2009
EN 3-10:2009 (E)

 a technical data sheet of the extinguisher to be tested in accordance with Annex B.

NOTE Applicants are advised to consider the desirability of using a EA accredited laboratory, which is a third party
independent from the manufacturer to perform tests in accordance with EN 3-7 and EA accredited in accordance with
EN ISO/IEC 17025.

The testing laboratory shall issue a laboratory test report in accordance with Annex C. For this, it shall carry
out the complete listed tests and checks programme.

Where unified test procedures exist according to CEN/TR 15642, they shall be used in the testing of the
extinguisher.

The laboratory’s accreditation shall take these procedures into consideration.

7 Factory Production Control (FPC)

7.1 Requirements

The FPC system shall fulfil the requirements described in the following clauses, where applicable, which are
taken from EN ISO 9001:2000.

 4.2 (Documentation requirements), except 4.2.1 a).

 5.1 e) (Ensuring the availability of resources).

 5.5.1 (Responsibility and authority).

 5.5.2 (Management representative).

 6 (Resource management).

 7.1 (Planning of product realisation) except 7.1 a).

 7.2.3 c) (Customer communication, information coming back from customers and customer complaints).

 7.4 (Purchasing).

 7.5 (Production and service provision).

 7.6 (Control of monitoring and measuring devices).

 8.2.3 (Monitoring and measurement of processes).

 8.2.4 (Monitoring and measurement of product).

 8.3 (Control of non conforming product).

 8.5.2 (Corrective action).

The above requirements cover amongst others: calibration, training, records, complaints and requirements of
Clause 9.

NOTE The FPC system can be part of a Quality Management System, e.g. in accordance with EN ISO 9001.

Where a current EN ISO 9001 certified QMS is existing, it may be taken into consideration.

7
BS EN 3-10:2009
EN 3-10:2009 (E)

7.2 Additional requirements

a) Means for manufacturing extinguishers and/or extinguisher’s components shall be available;

b) Means for performing the required controls shall be available and regularly calibrated;

c) Product traceability records shall be available.

8 Reference numbering and marking


Upon successful completion of all tests and controls, a reference number can be issued by an EA accredited
certification body or a national ministry. This reference number shall be marked on the extinguisher as
described in EN 3-7:2004+A1:2007, 16.2.

9 Items to be regularly checked and recorded during production


Items listed in Table 1 and Table 2 shall be regularly checked and recorded as a minimum:

8
BS EN 3-10:2009
EN 3-10:2009 (E)

Table 1 — Controls, tests and frequency

Item nr as
per test EN 3-7 Frequency during
Title
report (see Clause manufacture
Annex C)
1 4.2 Control of discharge N/R
2 4.3 Operation position N/R
3 4.4 Hose assembly Periodically a
4 4.5 Propellants Based on documentation
Means of checking pressure for stored pressure
5 4.6 N/R
extinguishers
6 6.1 Nominal charges N/R
7 6.2 Filling tolerances Periodically a
8 6.3 Design of filling opening N/R
Periodically a
9 7.1.1 Duration of operation, minimum duration Manufacturer shall define
acceptable limits
10 7.1.2 Duration of operation, spread of measurements N/R
11 7.2 Residual charge Periodically a
12 7.3 Commencement of discharge Periodically a
13 7.4 Temperature cycling N/R
14 8.1 Retention of propellant N/R
see 8.3 of
15 8.2 Leakage acceptance level
EN 3-7:2004+A1:2007
16 9.2 Dielectric test, for water based extinguishers N/R
17 10.1 General requirement for use of extinguishers N/R
18a 10.2 Operating force for C02 extinguishers Periodically a
st
18b 10.2 Operating force for other extinguishers – 1 device Periodically a
nd
18c 10.2 Operating force for other extinguishers – 2 device Periodically a
19 10.3 Safety devices Periodically a
20 10.4 Filter for water based extinguishers N/R
21a 10.5 Hose and coupling systems, for C02 extinguishers Periodically a
21 b 10.5 Hose and coupling systems, for other extinguishers Periodically a
22a 10.6 Control valve, for C02 extinguishers N/R
22b 10.6 Control valve, for 1 and 2 kg powder extinguishers N/R
22c 10.6 Control valve, for other extinguishers N/R
23 11.1.1 Pressure gauge N/R
to be continued

9
BS EN 3-10:2009
EN 3-10:2009 (E)

Table 1 (continued)

Item nr as
per test EN 3-7 Frequency during
Title
report (see Clause manufacture
Annex C)
24 11.1.2 Pressure gauge scale N/R
25 11.1.3 Pressure gauge error after cycling N/R
26 11.1.4 Capability of pressure gauge materials N/R
27 11.2 Pressure indicator N/R
28 12.1 Horn / hose for C02 extinguishers N/R
29 12.2 Horn resistance to static load N/R
30 12.3 Security of horn / hose fixing Periodically a
31 12.4 Horn resistance to temperature N/R
32 13 Mounting bracket N/R
33 14.1 Resistance to external corrosion N/R
34 14.2 Resistance to internal corrosion N/R
35 15.2 Class A fire rating N/R
36 15.3 Class B fire rating N/R
37 15.3 Suitability for polar solvents N/R
38 15.4 Class F fire rating N/R
39 16.1 Extinguisher identification, colour Periodically a
40 16.2 Marking Periodically a
N/R: not required (but listed to follow EN 3-7 requirements).
a Frequency shall be established by the manufacturer and shall be relevant with the checked item and quantity produced.
Requirements of ISO/TR 8550 (all parts) shall be taken into consideration.

Table 2

A Conformity to TDS Periodically a


B Conformity to documents for components used including Periodically a
extinguishing media
C Percentage of principal components of powder Periodically a
D Physical and chemical characteristics for additives used in water Periodically a
based extinguishers according to manufacturer’s specification
E Internal volume Periodically a
F External painting: adhesion / thickness (compared to the minimum Periodically a
declared)
G Internal lining (where applicable): controlled according to Periodically a
manufacturer’s specification
H Torque (Body/valve) Periodically a
I Propellant pressure or weight where appropriate Periodically a
a Frequency shall be established by the manufacturer and shall be relevant with the checked item and quantity
produced. Requirements of ISO/TR 8550 (all parts) shall be taken into consideration.

10
BS EN 3-10:2009
EN 3-10:2009 (E)

10 Surveillance
The points to be checked by a surveillance body are given in Annex A.

NOTE The manufacturer, or the sub contractors where they fill or assemble the fire extinguisher, should be subjected
to the surveillance described in Annex A. A surveillance body EA is accredited in accordance with EN ISO/IEC 17020.

11
BS EN 3-10:2009
EN 3-10:2009 (E)

Annex A
(informative)

Points to be checked by the surveillance body

A.1 Minimum audit frequency


The minimum audit frequency is once a year for the applicant, manufacturer and subcontractor(s) if
applicable.

A.2 Audits content

A.2.1 Manufacturer and subcontractors

With regard to manufacturer and subcontractors, the audits cover the products manufactured to EN 3-7.

Where the certified QMS exists conforming to EN ISO 9001 (see 5.6), it shall be taken into consideration.

Where the QMS is not certified, audits shall also cover relevant parts (see Clause 7).

The manufacturer shall make the tests records relating to Clause 9 available to the auditor.

Audits shall include records review. At the auditor’s discretion, selected tests from the list below shall be
assessed. Common component may be tested to reduce the number of samples.

Tests are performed on extinguishers selected at random by the auditor from production or from stock.

A selection of extinguishing media for analysis according to points C and D of Table 2 can be made by the
auditor at the occasion of the audit.

These tests may be performed at manufacturer’s facilities or another suitable facility.

Within a 5 year period, each test listed below shall have been performed on each model of a manufacturer:

 external painting: adhesion / thickness (compared to the minimum declared by the manufacturer);

 internal lining (where applicable): controlled according to manufacturer’s specification;

 filling tolerance;

 torque (Body/valve) CO2; extinguishers only;

 propellant pressure or weight where appropriate;

 hose and coupling system: performance of the hose (minimum pressure resistance);

 safety device removal force;

 marking;

 tightness-leak test;

12
BS EN 3-10:2009
EN 3-10:2009 (E)

 duration of operation / residual charge (at 20 ± 5) °C;

 duration of operation / residual charge (at limit temperature);

 pressure indicating device.

A.2.2 Applicant

The following should be checked:

 that applicant is authorized to represent the manufacturer;

 all required technical files of the extinguisher are available;

 whether applicant has a system for handling complaints;

 whether applicant has available information from the manufacturer on the result of the half-year audits
and whether applicant is informed on major problems with the extinguisher during the production (in other
words, is there a good communication on these relevant points between applicant and manufacturer?).

A.3 Audit report


The auditor shall provide the audited with an audit report that contains the assessments made, including
controls and tests results. A copy of all audit report(s) shall be delivered to the applicant.

13
BS EN 3-10:2009
EN 3-10:2009 (E)

Annex B
(normative)

Technical Data Sheet of an extinguisher


Name and address of the applicant

Name and address of the manufacturer (when not the applicant) and place(s) of manufacture

Name and address of subcontractor and place(s) of subcontractor activity, where applicable
[In this case please also describe subcontracted activity]

Name, title and address of person responsible for this testing

Description of modification

Date when extinguishers could be available for testing

Model number

Existing model or range name

Type of extinguisher
Gas cartridge
Stored pressure
Extinguishing medium Nominal charge:
CO2
Foam
Water
Water plus additive
Powder
Freezing point depressant
Pressure relief device
Bursting disc
Declared min./max. operating temperatures and corresponding pressures:
Tmin: °C Tmax: °C P(Tmin) bar P(Tmax): bar

Class of fire and target ratings

…/…

14
BS EN 3-10:2009
EN 3-10:2009 (E)

Table of parts

Drawing No
Part Supplier Part No Material
issue status
Body/cylinder
Valve
Hose
Horn
Strainer
Bursting disc
Gas cartridge
Dip tube

Table for extinguishing agent

Characteristics Manufacture Specification


Chemical composition (Powder/Halon)
Principle components (Powder)
Particle distribution a (Powder)
3
Density in kg/dm
(Foaming agents)
2
Viscosity 10 mm /s
(Foaming agents)
Refractive index
D
N20
(Foaming agent)
PH (Foaming agent)

Spectrogram b
a Method used to be stated Percentage for at least 3 particle sizes to be given.
b At (20 + 2) °C - Infrared spectrogram to be supplied for foam concentrate and powder.

NB If during testing changes are made this data sheet will be revised.

Please submit in duplicate technical documentation comprising:

1) one set of drawings clearly characterising the model, including at a minimum those listed in the table of parts
above;

2) details of the extinguishing agent giving its physical and chemical characteristics, including at minimum the
information required in the table for extinguishing agent above;

3) an explanatory note on the type of heat treatment and welding and assembly process the cylinder has
undergone.

15
BS EN 3-10:2009
EN 3-10:2009 (E)

Annex C
(normative)

Model of laboratory report

This is a laboratory test report and not a product certification approval.

M O D E L LA B O R A T O R Y R E P O R T

(Information contained on these two pages of the report shall be considered as the minimum list of details
required in the introduction.)

• Identification and address Date of Issue of the report of the laboratory

LABORATORY TEST REPORT


Report nr : …………….

Requested by : …………….

PORTABLE FIRE EXTINGUISHER

Tests for conformity with EN 3-7:2004+A1:2007

• Identification of extinguisher:

ƒ Type: (manufacturer’s designation of the model)………according to general drawing nr: ……………

ƒ Manufacturer (identification, address etc.): …………

ƒ Type and commercial name of extinguishing medium (or media): ……………

ƒ Nominal charge of extinguisher: ……………

ƒ Pressurisation (method, type, gas, mass or pressure): ……………

16
BS EN 3-10:2009
EN 3-10:2009 (E)

• Conclusion of the tests:

Conformity of submitted samples with all applicable clauses of the standard: YES / NO.

(details: see summary (taking model variants into consideration where relevant))

ƒ Operating temperature range : from ….. °C to ….. °C

ƒ Checked working pressure : at Tmin ................bar; at Tmax ..............bar

ƒ Dielectric suitability (applicable only for water based extinguisher): ……………

ƒ Fire class(es) intended for : ……………

ƒ Fire ratings achieved : ……………

• Supplementary information:

• Samples

*Quantity of provided samples : ……………

*Receipt of the samples by the lab – date : ……………

• Conformity to documentation

The extinguishers submitted can be identified from the detailed documentation supplied by the manufacturer
comprising:

* Annex 1: Conformity of the extinguishing media to the technical data provided by the
manufacturer

* Annex 2: List of documents included in this tests report (the minimum documents to identifies the
fire extinguisher)

* Annex 3 (if relevant): List of documents not included in this tests report, but registered by the
laboratory

* PED references: Certificate’s nr….

Notified Body’s nr,…

• Report

* This report comprises …… pages, annexes 1 and …… annexes.

* Only the materials detailed in this report have been subjected to tests.

* The summary and conclusions of checks and tests are given on page …… .

* This report or any part of it may not be reproduced without the written permission of the
laboratory.

Laboratory stamp Signature and position of the person or

persons responsible of the laboratory

This is a laboratory test report and not a product certification approval.

17
BS EN 3-10:2009
EN 3-10:2009 (E)

Table C.1 — Summary of checks and tests

EN 3-7 Applicable Conformity


Item nr Title
Clause Yes / No Yes / No
1 4.2 Control of discharge
2 4.3 Operating position
3 4.4 Hose assembly
4 4.5 Propellants
5 4.6 Means of checking pressure for stored pressure extinguishers
6 6.1 Nominal charges
7 6.2 Filling tolerances
8 6.3 Design of filling opening
9 7.1.1 Duration of operation, minimum duration
10 7.1.2 Duration of operation, spread of measurements
11 7.2 Residual charge
12 7.3 Commencement of discharge
13 7.4 Temperature cycling
14 8.1 Retention of propellant
15 8.2 Leakage acceptance level
16 9.2 Dielectric test, for water based extinguishers
17 10.1 General requirement for use of extinguishers
18a 10.2 Operating force for CO2 extinguishers
st
18b 10.2 Operating force for other extinguishers-1 device
nd
18c 10.2 Operating force for other extinguishers-2 device
19 10.3 Safety devices
20 10.4 Filter for water based extinguishers
21a 10.5 Hose and coupling systems, for CO2 extinguishers
21b 10.5 Hose and coupling systems, for other extinguishers
to be continued

18
BS EN 3-10:2009
EN 3-10:2009 (E)

Table C.1 (continued)

EN 3-7 Applicable Conformity


Item nr Title
Clause Yes / No Yes / No
22a 10.6 Control valve, for CO2 extinguishers
22b 10.6 Control valve, for 1 and 2 kg powder extinguishers
22c 10.6 Control valve, for other extinguishers
23 11.1.1 Pressure gauge
24 11.1.2 Pressure gauge scale
25 11.1.3 Pressure gauge error after cycling
26 11.1.4 Compatibility of pressure gauge materials
27 11.2 Pressure indicator
28 12.1 Horn / hose for CO2 extinguishers
29 12.2 Horn resistance to static load
30 12.3 Security of horn / hose fixing
31 12.4 Horn resistance to temperature
32 13 Mounting bracket
33 14.1 Resistance to external corrosion
34 14.2 Resistance to internal corrosion
35 15.2 Class A fire rating
36 15.3 Class B fire rating
37 15.3 Class B polar solvent
38 15.4 Class F fire rating
39 16.1 Extinguisher identification, colour
40 16.2 Marking

19
BS EN 3-10:2009
EN 3-10:2009 (E)

Model of laboratory test report according to EN 3-7:2004+A1:2007

1) Control of discharge (EN 3-7:2004+A1:2007, 4.2)

Provision of device to interrupt discharge (yes/no)


Self closing device (yes/no)
Conformity to 4.2 (yes/no)

2) Operating position (EN 3-7:2004+A1:2007, 4.3)

Operation without inversion (yes/no)


Operating device location conform to requirements (yes/no)
Conformity to 4.3 (yes/no)

3) Hose assembly (EN 3-7:2004+A1:2007, 4.4)

Nominal charge (kg/l)


Requirement for hose (yes/no)
Length of actual flexible hose fitted (mm)
Required length (mm) ≥ 400 / ≥ 250
Conformity to 4.4 (yes/no)

4) Propellants (EN 3-7:2004+A1:2007, 4.5)

Type of propellant (to be checked by documentation)


Tracer
Conformity to 4.5 (yes/no)

5) Means of checking pressure for stored pressure extinguishers (EN 3-7:2004+A1:2007, 4.6)

Means for pressure check available (yes/no/not applicable)


A – Pressure gauge ❏
B – Pressure indicator ❏
C – Pressure connection ❏
Compliance to 4.6 (yes/no)

6) Nominal charges (EN 3-7:2004+A1:2007, 6.1)

Nominal charge (kg/l)


Conformity to 6.1 (yes/no)

20
BS EN 3-10:2009
EN 3-10:2009 (E)

7) Filling tolerances (EN 3-7:2004+A1:2007, 6.2)

Sample 1 2 3 4
Actual charge (kg/l)
Deviation from nominal (%)
Maximum allowed tolerance (%)
Conformity to 6.2 (yes/no)

8) Design of filling opening (EN 3-7:2004+A1:2007, 6.3)

Provision to vent pressure (yes/no)


Pressure released within 1/3 of disassembly (yes/no)
Diameter of actual filling opening (mm)
Required minimum diameter: ≥ 20 mm if nominal charge ≤ 3 (kg/l) ≥
or ≥ 25 mm if nominal charge > 3 (kg/l)
Conformity to 6.3 (yes/no)

9) Duration of operation, minimum duration (EN 3-7:2004+A1:2007, 7.1.1)

Sample 1 2 3
Measured duration (s)
Required duration (s) ≥
Conformity to 7.1.1 (yes/no)

10) Duration of operation, spread of measurements (EN 3-7:2004+A1:2007, 7.1.2)

Deviation of measured time from average discharge duration:


Average discharge duration (s)
Sample 1 2 3
Actual deviation (%)
Required deviation (%) ≤ ± 15
Conformity to 7.1.2 (yes/no)

11) Residual charge (EN 3-7:2004+A1:2007, 7.2)

Residue as a percentage of the nominal charge:


Sample 1 2 3
Actual (%)
Required (%) ≤ 10
Conformity to 7.2 (yes/no)

21
BS EN 3-10:2009
EN 3-10:2009 (E)

12) Commencement of discharge (EN 3-7:2004+A1:2007, 7.3)

Sample 1 2 3
Measured (s)
Required (s) ≤4
Conformity to 7.3 (yes/no)

13) Temperature cycling (EN 3-7:2004+A1:2007, 7.4)

Temperature cycling Cycle A Cycle B


Sample 1 2 3 4
Temperature at start of cycle (°C) Tmin: Tmin: Tmax: Tmax:
Temperature at end of cycle (°C) Tmax: Tmax: Tmin: Tmin:
Commencement of discharge, actual (s)
Commencement of discharge, required (s) ≤ 10
Duration of operation, actual (s)
Maximum duration of operation, required (s) a

Minimum duration of operation, required (s) ≥6


Duration of operation for CO2, actual (s)
Max. duration of operation for CO2, required (s) b ≤ c ≤
Residual charge, actual (%)

Residual charge, required (%) ≤d


Conformity to 7.4 (yes/no)
a The maximum duration of operation shall be not more than twice the value established at a temperature of 20 °C for
all extinguishers except for CO2.
b For CO2 tested at Tmax, the duration of operation shall be less or equal than the duration measured at 20 °C.
c For CO2 tested at Tmin, the duration of operation shall be less or equal to 2,5 times the duration measured at 20 °C.
d Maximum 15 % for BC powder, maximum 10 % for all other agents.

14) Retention of propellant (EN 3-7:2004+A1:2007, 8.1)

Verification possible (yes/no)


Verification method (by weighing / by pressure)
Verification device (connection / gauge / indicator)
Conformity to 8.1 (yes/no)

22
BS EN 3-10:2009
EN 3-10:2009 (E)

15) Leakage acceptance level (EN 3-7:2004+A1:2007, 8.2)

Sample 1 2
Stored pressure extinguishers:

Actual leakage % a

Required rate of leakage ≤ 6 % / year a

Extinguishers and/or gas cartridges checked by weighing:

Actual leakage % b

Required rate of leakage ≤ 5 % weight / year b

Gas cartridge extinguishers:


3
Actual leakage (cm /min/kg(l))

≤ 5 cm /min/kg(l)
3
Required rate of leakage

Conformity to 8.2 (yes/no)

a For stored pressure extinguishers, % of the expanded free gas volume at 20 °C.
b For propellant cartridges and CO2 extinguishers % of the nominal charge.

16) Dielectric test, for water based extinguishers (EN 3-7:2004+A1:2007, 9.2)

Actual current at 35 kV (mA)


Required current at 35 kV (mA) ≤ 0,5 mA
Conformity to 9.2 (yes/no)

17) General requirement for use of extinguishers (EN 3-7:2004+A1:2007, 10.1)

Capable to use extinguisher without mounting, removal or modifying of any component


except for the safety device (yes/no)
Conformity to 10.1 (yes/no)

23
BS EN 3-10:2009
EN 3-10:2009 (E)

18a) Operating force for CO2 extinguishers (EN 3-7:2004+A1:2007, 10.2)

Activation without repetition of action (yes/no)


at Tmin: at Tmax:
Force to activate the extinguisher °C °C

Sample 1 2 3 4
Actual (N)
Required (N) ≤ 300
Force to activate the extinguisher, if applicable at 40 °C
Sample 1 2

Actual (N)
Required (N) ≤ 200
Conformity to 10.2 (yes/no)

18b) Operating force for other extinguishers (EN 3-7:2004+A1:2007, 10.2)


st
device:

Activation without repetition of action (yes/no)


at Tmin: at Tmax:
Force to activate the extinguisher:
°C °C
Sample 1 2 3 4

Actual force to activate finger trigger (N)


Required force to activate finger trigger (N) ≤ 100

Actual force to squeeze grip lever (N)


Required force to squeeze grip lever (N) ≤ 200
Actual force to screw down hand wheel (N) a
Required force to screw down hand wheel (N) a ≤ 100
Actual energy to strike knob (J)
Required energy to strike knob (J) ≤2
Conformity to 10.2 (yes/no)
a Measured at outside of the wheel. Maximum of 360° rotation to full open position.

24
BS EN 3-10:2009
EN 3-10:2009 (E)

18c) Operating force for other extinguishers (EN 3-7:2004+A1:2007, 10.2)


nd
2 device:

at Tmin: at Tmax:
Force to activate the control valve: °C °C
Sample 1 2 3 4

Actual force to activate finger trigger (N)


Required force to activate finger trigger (N) ≤ 100

Actual force to squeeze grip lever (N)


Required force to squeeze grip lever (N) ≤ 200
Conformity to 10.2 (yes/no)

19) Safety devices (EN 3-7:2004+A1:2007,10.3)

Release of safety device distinct from operating mechanism (yes/no)


Removal of safety device can be seen (yes/no)
Force to release safety device at Tmin at 20 at Tmax
°C °C °C
Sample 1 2 3 4 5
Actual (N)
Required (N) 20 ≤ X ≤ 100
Attempt to initiate discharge without release of safety device:
Sample 1 2
Deformation or damage of operating mechanism in case of double (yes/no)
force
Conformity to 10.3 (yes/no)

20) Filter for water based extinguishers (EN 3-7:2004+A1:2007, 10.4)

Filter position upstream of smallest orifice (yes/no)


Area of each filter orifice smaller than smallest area of the discharge passage (yes/no)
2
Area of smallest orifice in discharge passage (mm )
2
Total area of filter orifices (mm )
Total filter area 8 times larger than smallest orifice area (yes/no)
Filter accessible for maintenance (yes/no)
Conformity to 10.4 (yes/no)

25
BS EN 3-10:2009
EN 3-10:2009 (E)

21a) Hose and coupling systems, for CO2 extinguishers (EN 3-7:2004+A1:2007, 10.5)

Burst pressures (bar) at Tmin , 20 °C and Tmax (°C):

Actual test temperature sample 1


Required test temperature (20 ± 5) °C
Actual burst pressure sample 1
Required burst pressure ≥ 1,5 × P(Tmax )

Actual test temperature sample 2


Required test temperature Tmax
Actual burst pressure sample 2
Required burst pressure ≥ 1,25 × P(Tmax )

Actual test temperature sample 3


Required test temperature Tmax
Actual burst pressure sample 3
Required burst pressure ≥ 1,25 × P(Tmax )

Actual test temperature sample 4


Required test temperature Tmin
Actual burst pressure sample 4
Required burst pressure ≥ 1,25 × P(Tmax )

Actual test temperature sample 5


Required test temperature Tmin
Actual burst pressure sample 5
Required burst pressure ≥ 1,25 × P(Tmax )
Functional throughout operating temperature range (yes/no)
Suitable design to prevent hose damage (yes/no)

Conformity to 10.5 (yes/no)

26
BS EN 3-10:2009
EN 3-10:2009 (E)

21b) Hose and coupling systems, for other extinguishers (EN 3-7:2004+A1:2007, 10.5)

Burst pressures (bar) at Tmin, 20 °C and Tmax (°C):

Actual test temperature sample 1


Required test temperature (20 ± 5) °C
Actual burst pressure sample 1
Required burst pressure ≥ 3 × P(Tmax )

Actual test temperature sample 2


Required test temperature Tmax
Actual burst pressure sample 2
Required burst pressure ≥ 2 × P(Tmax )

Actual test temperature sample 3


Required test temperature Tmax
Actual burst pressure sample 3
Required burst pressure ≥ 2 × P(Tmax )

Actual test temperature sample 4


Required test temperature Tmin
Actual burst pressure sample 4
Required burst pressure ≥ 2 × P(Tmax )

Actual test temperature sample 5


Required test temperature Tmin
Actual burst pressure sample 5
Required burst pressure ≥ 2 × P(Tmax )
Functional throughout operating temperature range (yes/no)
Suitable design to prevent hose damage (yes/no)

Conformity to 10.5 (yes/no)

22a) Control valve, for CO2 extinguishers (EN 3-7:2004+A1:2007, 10.6.1 and 10.6.4)

Equipped with self-closing discharge valve (yes / no)


Sample 1 2
Initial mass before discharge (kg)
Remaining mass A measured within 10 s of completion of partial discharge (kg)
Remaining mass B discharge measured after 5 min of completion of partial
discharge (kg)
Actual ratio remaining mass B / remaining mass A (%)
Required ratio remaining mass B / remaining mass A (%) ≥ 80
Conformity to 10.6 (yes/no)

27
BS EN 3-10:2009
EN 3-10:2009 (E)

22b) Control valve, for 1 and 2 kg powder extinguishers (EN 3-7:2004+A1:2007, 10.6.1 and 10.6.3)

Equipped with self-closing discharge valve (yes/no)


Sample 1 2
Remaining pressure A measured within 10 s of completion of partial discharge
(bar)
Remaining pressure B measured after 2 min of completion of partial discharge
(bar)
Actual ratio remaining pressure B / remaining pressure A (%)
Required ratio remaining pressure B / remaining pressure A (%) ≥ 80
Conformity to 10.6 (yes/no)

22c) Control valve, for other extinguishers (EN 3-7:2004+A1:2007, 10.6.1 and 10.6.2)

Equipped with self-closing discharge valve (yes/no)


Sample 1 2
Initial pressure A before discharge (bar)
Remaining pressure B measured within 10 s of completion of partial discharge
(bar)
Remaining pressure C measured after 5 min of completion of partial discharge
(bar)
Actual ratio pressures C / A (%)
Required ratio pressures C / A (%) ≥ 50
Actual ratio pressures C / B (%)
Required ratio pressures C / B (%) ≥ 80
Conformity to 10.6 (yes/no)

23) Pressure gauge (EN 3-7:2004+A1:2007, 11.1.1)

Pressure gauge present (yes/no)


Capable of being checked on good working order with an external pressure (yes/no/not
applicable)
Conformity to 11.1.1 (yes/no/not applicable)

28
BS EN 3-10:2009
EN 3-10:2009 (E)

24) Pressure gauge scale (EN 3-7:2004+A1:2007, 11.1.2)

Scale calibrated in bars (yes/no)


Zero zone (yes/no)
End stop on zero zone (yes/no)
End stop at negative pressure side of the zero zone (yes/no)
Pointer contact end stop (yes/no)
Green zone between operating pressures (yes/no)
Tolerance of –15 % for pressure at Tmin (yes/no)
Tolerance of +6 % for pressure at Tmax (yes/no)
Pressures rounded off to full or half bar (yes/no)
Side zones of green zone coloured red (yes/no)
Operating pressure at +20° indicated (yes/no)
Scale length ≥ 1,5 × length from zero to the high pressure end of the green zone (yes/no)
Pointer radially into the green zone with length of between 50 % and 80 % of the green zone
height (yes/no)
Position of pointer clearly visible at ends of green zone and at operating pressure at 20 °C
(yes/no)
Conformity to 11.1.2 (yes/no/not applicable)

25) Pressure gauge error after cycling (EN 3-7:2004+A1:2007, 11.1.3)

Initial After 1 000 cycles


Sample 1 2 3 1 2 3
Beginning of green zone (bar)
Error ≤ 1 bar (yes/no)
End of green zone (bar)
Error ≤ ± 6 % (yes/no)
Operating pressure at 20 °C (bar)
Error ≤ ± 0,5 bar (yes/no)
Conformity to 11.1.3 (yes/no/not applicable)

26) Compatibility of pressure gauge materials (EN 3-7:2004+A1:2007, 11.1.4)

Gauge materials compatible with the extinguishing medium and propellant (yes/no)
Conformity to 11.1.4 (yes/no/not applicable)

29
BS EN 3-10:2009
EN 3-10:2009 (E)

27) Pressure indicator (EN 3-7:2004+A1:2007, 11.2)

Pressure indicator present (yes/no)


Indication of operable condition (yes/no)
Minimum operating temperature (°C)
Pressure at minimum operating temperature; P(Tmin) (bar)
Sample 1 2
Measured pressure at P(Tmin) indication (bar)
Indication error < ±1 bar (yes/no)
Conformity to 11.2 (yes/no/not applicable)

28) Horn / hose for CO2 extinguishers (EN 3-7:2004+A1:2007, 12.1)

Horn provided with a handle (yes / no)


Conformity to 12.1 (yes/no)

29) Horn resistance to static load (EN 3-7:2004+A1:2007, 12.2)

Visible damage after static load test (yes / no)


Diameter of the horn before static load test (mm)
Diameter of the horn after static load test (mm)
Actual ratio of horn diameter before/after static load test (%)
Required ratio of horn diameter before/after static load test (%) < 10
Conformity to 12.2 (yes/no)

30) Security of horn / hose fixing (EN 3-7:2004+A1:2007, 12.3)

Method of locking Mechanical Adhesive


Actual torque to loosen hose / horn assembly (Nm)
Required torque to loosen assembly (Nm) ≥ 20 ≥ 10
Conformity to 12.3 (yes/no)

31) Horn resistance to temperature (EN 3-7:2004+A1:2007, 12.4)

Sample 1 2
Diameter of the horn at ambient temperature before discharge (mm)
Diameter of the horn after raising temperature to Tmax and discharge (mm)
Actual ratio of horn diameter before/after the test (%)
Required ratio of horn diameter before/after the test (%) ≤ 10
Visible damage after temperature/ discharge test (yes/no)
Conformity to 12.4 (yes/no)

30
BS EN 3-10:2009
EN 3-10:2009 (E)

32) Mounting bracket (EN 3-7:2004+A1:2007, Clause 13)

Easy removal extinguisher from bracket (yes/no)


Method of removal is obvious (yes/no)
Capable of supporting twice the total mass of extinguisher without permanent
deformation (yes/no)
Conformity to Clause 13 (yes/no)

33) Resistance to external corrosion (EN 3-7:2004+A1:2007, 14.1)

Observations after the salt spray test as per H.1 of Annex H:


Sample 1 2
Operating force for CO2 extinguishers – 10.2 (yes/n.a.)
Actual (N)
Required (N) ≤ 200
Operating force for other extinguishers – 10.2 (yes/n.a.)
Actual force to activate finger trigger (N)
Required force to activate finger trigger (N) ≤ 100
Actual force to squeeze grip lever (N)
Required force to squeeze grip lever (N) ≤ 200
Actual force to screw down hand wheel (N)
Required force to screw down hand wheel (N) ≤ 100
Actual energy to strike knob (J)
Required energy to strike knob (J) ≤2
Force to release safety device – 10.3:
Actual (N)
Required (N) 20 ≤ 100
Duration of operation – 7.1.2:
Measured (s)
Average duration, see item 10 (s)
Actual deviation from the average duration time (%)
Required deviation from the average duration time (%) ≤ 25
Return of pressure gauge/ indicator to indication of no pressure (yes/no/n.a.)
Burst pressure hose – 10.5 for CO2 extinguishers (yes/n.a.)
Actual burst pressure
Required burst pressure ≥ 1,5 × P(Tmax)
Burst pressure hose – 10.5 for other extinguishers (yes/n.a.)
Actual burst pressure
Required burst pressure ≥ 3 x P(Tmax)
Corrosion of metal likely to impair the operation or
safety (yes/no)
Conformity to 14.1 (yes/no)

31
BS EN 3-10:2009
EN 3-10:2009 (E)

34) Resistance to internal corrosion (EN 3-7:2004+A1:2007, 14.2)

Observations after 8 times temperature cycle as per H.2 of Annex H:


Sample 1 2
Evidence of corrosion (yes/no)
Detachment of coating (yes/no)
Cracking of coating (yes/no)
Bubbling of coating (yes/no)

Change of agent colour a (yes/no)


Conformity to 14.2 (yes/no)
a Except for change resulting from the thermal cycling.

35) Class A fire rating (EN 3-7:2004+A1:2007, 15.2)

Test No 1 2 3
Fire size
Moisture of test fire wood: measured average (%)
Required (%) 10 to 15
Actual ambient temperature within test room (°C)
Required temperature within test room (°C) 0 to 30
Minimum oxygen concentration recorded during the test (%)
Required oxygen concentration (%) ≥ 19
Fire extinguished: (yes / no)
Measured time to extinguish fire (min-s)
Required ≤ 5 min for ≤ 21A; ≤ 7 min for ≥ 27A
Achieved test fire rating – Class A

Minimum required test fire rating – Class A a A

Conformity to 15.2 (yes/no)


a As per Table 3 or 4 of 6.4.2.

32
BS EN 3-10:2009
EN 3-10:2009 (E)

36) Class B fire rating (EN 3-7:2004+A1:2007, 15.3)

Test No 1 2 3
Fire size
Actual ambient temperature (°C)
Required ambient temperature (°C) 0 to 30
Actual wind speed, if outdoors (m/s)
Accepted wind speed (m/s) <3
Fire extinguished: (yes/no)
Heptane left after extinction (yes/no)
Measured (mm)
Required (mm) >5
Achieved test fire rating – Class B
Minimum required test fire rating – Class B a B

Conformity to 15.3 (yes/no)


a As per Table 5, 6, 7 or 8 of 6.4.3.

37) Class B – Polar solvent fire test (EN 3-7:2004+A1:2007, 15.3)

Test No 1 2 3
Actual ambient temperature (°C)
Required ambient temperature (°C) 10 to 20
Actual fuel temperature (°C)
Required fuel temperature (°C) 15 to 20
Fire extinguished (yes/no)
Measured time to extinguish fire (min – s)
Required time to extinguish fire (min) ≤3
Test fire achieved (yes/no)
Conformity to 15.3 (yes/no)

33
BS EN 3-10:2009
EN 3-10:2009 (E)

38) Class F fire rating (EN 3-7:2004+A1:2007, 15.4)

Test No 1 2 3
Fire size
Actual ambient temperature (°C)
Required ambient temperature (°C) 0 to 30
Measured time to reach auto-ignition (h – min)
Required time to reach auto-ignition (h – min) < 3 h 30 min
Measured auto-ignition temperature (°C)
Required auto-ignition temperature (°C) 330 to 380
Complete discharge of the extinguisher without
Interruption (yes/no)
Fire extinguished (yes/no)
Burning material ejected (yes/no)
Re-ignition within 20 min (yes/no)
Oil left after extinction (yes/no)
Enlargement of flames observed (yes/no)
Achieved test fire rating – Class F F

Minimum required test fire rating – Class F a F


Conformity to 15.4 (yes/no)
a As per Table L.1 of Annex L.

39) Extinguisher identification, colour (EN 3-7:2004+A1:2007, 16.1)

Colour of extinguisher body red RAL 3000 (yes/no)


Colour coded for extinguishant (yes/no)
Coded area ≤ 10 % of body surface area (yes/no/n.a.)
National regulation for colour code extinguishant applicable (yes/no)
Conformity to 16.1 (yes/no)

40) Marking (EN 3-7:2004+A1:2007, 16.2)

Conformity to 16.2 (yes/no)

34
BS EN 3-10:2009
EN 3-10:2009 (E)

Annex 1 to the test report

Powder characteristics to be tested in accordance with EN 615

Manufacturer Sample Within specification


Characteristics
specification measurement yes/no
Commercial name
Chemical Composition (Clause 7)
Chemical name % Method %
st
1 component
nd
2 component
rd
3 component
th
4 component
……
Particle distribution (Clause 6)
Method
> 125 µm (%) ± 5
> 63 µm (%) ± 8
> 40 µm (%) ± 8
Colour
Conformity to manufacturer’s specification (yes/no)

35
BS EN 3-10:2009
EN 3-10:2009 (E)

Water based extinguishing agents characteristics to be tested.

NOTE 1 Fill one table to each component as defined on the label and/or the filling instructions (excluding water) and
one table for the extinguishing media ready to use.

First component

Characteristics Test temperature Manufacturer Sample Within specification


°C a specification measurement yes/no
Commercial name
3
Density in kg/dm (--- ± 2) °C
2
Viscosity in mm /s (--- ± 2) °C
Refractive index (--- ± 2) °C
N D 20
pH (--- ± 2) °C
Conformity to Manufacturer’s specification (yes/no)

An infrared spectrogram performed by the laboratory shall be included in the documentation for future comparison.
a Temperature given by the manufacturer which shall be in the range of 15 °C to 30 °C.

Second component (if any)

Characteristics Test temperature Manufacturer Sample Within specification


°C a specification measurement yes/no
Commercial name
3
Density in kg/dm (--- ± 2) °C
2
Viscosity in mm /s (--- ± 2) °C
Refractive index (--- ± 2) °C
N D 20
pH (--- ± 2) °C
Conformity to Manufacturer’s specification (yes/no)

An infrared spectrogram performed by the laboratory shall be included in the documentation for future comparison.
a Temperature given by the manufacturer which shall be in the range of 15 °C to 30 °C.

36
BS EN 3-10:2009
EN 3-10:2009 (E)

Third component (if any)

Extinguishing media

Characteristics Test temperature Manufacturer Sample Within specification


°C a specification measurement yes/no
Commercial name
3
Density in kg/dm (--- ± 2) °C
2
Viscosity in mm /s (--- ± 2) °C
Refractive index (--- ± 2) °C
N D 20
pH (--- ± 2) °C
Conformity to Manufacturer’s specification (yes/no)

An infrared spectrogram performed by the laboratory shall be included in the documentation for future comparison.
a Temperature given by the manufacturer which shall be in the range of 15 °C to 30 °C.

NOTE 2 In cases where the manufacturer supplied the specifications of all the components, the laboratory can
compensate the lack of supply of the extinguishing media by performing the measurement using a sample prepared by
himself using the same formula of the manufacturer.

37
BS EN 3-10:2009
EN 3-10:2009 (E)

Annex 2 to the test report

List of documents included in this test report.

38
BS EN 3-10:2009
EN 3-10:2009 (E)

Annex 3 to the test report

List of documents non-included in this report.

39
BS EN 3-10:2009
EN 3-10:2009 (E)

Bibliography

[1] EN 615, Fire protection — Fire extinguishing media — Specifications for powders (other than class D
powders)

[2] EN ISO/IEC 17020, General criteria for the operation of various types of bodies performing inspection
(ISO/IEC 17020:1998)

[3] EN ISO/IEC 17021, Conformity assessment — Requirements for bodies providing audit and
certification of management systems (ISO/IEC 17021:2006)

[4] EN ISO/IEC 17025, General requirements for the competence of testing and calibration laboratories
(ISO/IEC 17025:2005)

[5] Regulation (EC) No 1907/2006 of the European Parliament and of the Council of 18 December 2006
concerning the Registration, Evaluation, Authorisation and Restriction of Chemicals (REACH),
establishing a European Chemicals Agency, amending Directive 1999/45/EC and repealing Council
Regulation (EEC) No 793/93 and Commission Regulation (EC) No 1488/94 as well as Council
Directive 76/769/EEC and Commission Directives 91/155/EEC, 93/67/EEC, 93/105/EC and
2000/21/EC

[6] European Directive 97/23/EC – Directive 97/23/EC of the European Parliament and of the Council of
29 May 1997 on the approximation of the laws of the Member States concerning pressure equipment

40
BS EN 3-10:2009

This page has been intentionally left blank


BS EN 3-10:2009

BSI - British Standards Institution


BSI is the independent national body responsible for preparing British
Standards. It presents the UK view on standards in Europe and at the
international level. It is incorporated by Royal Charter.
Revisions
British Standards are updated by amendment or revision. Users of British
Standards should make sure that they possess the latest amendments or
editions.
It is the constant aim of BSI to improve the quality of our products and services.
We would be grateful if anyone finding an inaccuracy or ambiguity while using
this British Standard would inform the Secretary of the technical committee
responsible, the identity of which can be found on the inside front cover. Tel:
+44 (0)20 8996 9000. Fax: +44 (0)20 8996 7400.
BSI offers members an individual updating service called PLUS which ensures
that subscribers automatically receive the latest editions of standards.
Buying standards
Orders for all BSI, international and foreign standards publications should be
addressed to Customer Services. Tel: +44 (0)20 8996 9001. Fax: +44 (0)20 8996
7001 Email: orders@bsigroup.com You may also buy directly using a debit/credit
card from the BSI Shop on the Website http://www.bsigroup.com/shop
In response to orders for international standards, it is BSI policy to supply the
BSI implementation of those that have been published as British Standards,
unless otherwise requested.
Information on standards
BSI provides a wide range of information on national, European and
international standards through its Library and its Technical Help to Exporters
Service. Various BSI electronic information services are also available which
give details on all its products and services. Contact Information Centre. Tel:
+44 (0)20 8996 7111 Fax: +44 (0)20 8996 7048 Email: info@bsigroup.com
Subscribing members of BSI are kept up to date with standards developments
and receive substantial discounts on the purchase price of standards. For details
of these and other benefits contact Membership Administration. Tel: +44 (0)20
8996 7002 Fax: +44 (0)20 8996 7001 Email: membership@bsigroup.com
Information regarding online access to British Standards via British Standards
Online can be found at http://www.bsigroup.com/BSOL
Further information about BSI is available on the BSI website at http://
www.bsigroup.com.
Copyright
Copyright subsists in all BSI publications. BSI also holds the copyright, in the
UK, of the publications of the international standardization bodies. Except as
permitted under the Copyright, Designs and Patents Act 1988 no extract may
be reproduced, stored in a retrieval system or transmitted in any form or by any
BSI Group means – electronic, photocopying, recording or otherwise – without prior written
Headquarters 389 permission from BSI.
Chiswick High Road,
London, W4 4AL, UK This does not preclude the free use, in the course of implementing the standard,
Tel +44 (0)20 8996 9001 of necessary details such as symbols, and size, type or grade designations. If
Fax +44 (0)20 8996 7001 these details are to be used for any other purpose than implementation then the
www.bsigroup.com/ prior written permission of BSI must be obtained.
standards Details and advice can be obtained from the Copyright and Licensing Manager.
Tel: +44 (0)20 8996 7070 Email: copyright@bsigroup.com

You might also like