SIPROTEC 5

Configuration
May 4, 2021 8:56 AM

Device: 7VK87 Breaker Management Dev.

Product code
Short: P1D17471
Long: 7VK87-DAAA-AA0-0AAAA0-AA0111-12111B-BAA000-000AC0-CB1BA1

Firmware: Current version


Housing width: 1/3 x 19''
Housing type: Flush mounting
Binary inputs: 11
Binary outputs: 9 Relays (3 Standard, 6 Fast, 0 High-Speed, 0 Power)
Current transformers: 4 for protection
Voltage transformers: 4 standard
Measuring-transducer inputs: 0 (20 mA or 10 V, fast)
0 (20 mA, standard)
CPU: CP300
Modules in 19" row 1: IO202 , PS201
Modules in 19" row 2:
LEDs/Push-buttons: 16 LEDs
Operation Panel: Integrated
Key switch: Without
Display type: Small display
Front Design: Standard
Power Supply: DC 60 V-250 V, AC 100 V-230 V
Redundant Power Supply: No

Communication/Plug-in modules:
Communications encryption: Normal
Integrated Ethernet port J: for DIGSI 5
Plug-in module position E: ETH-BB-2FO: 2x optical Ethernet 100 Mbit/s, 1300 nm, duplex LC connector,
2 km over 50/125 um or 62.5/125 um multimode optical fiber Communication
Protocols: applicable for DIGSI 5, IEC 61850-8-1 MMS and GOOSE, IEC
60870-5-104, DNP3 TCP, Modbus TCP, Synchrophasor (IEEE C37.118 - IP),
Profinet IO, SUP, DHCP, SNTP, SNMP, etc. Redundancy protocols: Line Mode,
RSTP, HSR, PRP
Plug-in module position F: Port is available but not assembled
SIPROTEC 5
Configuration
May 4, 2021 8:56 AM

Functions:
Function points class: Base

Note on function-points class


The function-points class results from the sum of the function points of the selected functions. You can apply these
functions as selected. The device allows also each other selection of functions as long as the sum of the required
function points is within the selected function-points class. With the maximum function-points class of 1400 it is
possible to activate all the functions in the device. The function-points exceeding 1400 are free of charge. In the
engineering phase DIGSI 5 checks that the selected configuration is suitable (capable of running in the device) before
loading it to the device.

Miscellaneous:
Warranty: 5 years
Firmware: Current version
SIPROTEC 5
Configuration
May 4, 2021 8:56 AM

Functional scope 7VK87 Breaker Management Dev.:


Always Add selected Result
ANSI Function Abbr. included Qty. x Value = Points Qty.
Protection functions for 3-pole tripping 3-pole

Protection functions for 1-pole tripping 1-pole

Hardware quantity structure expandable I/O

Process Bus Client Protocol (Note: This PB client x 100 =


function requires at least one dedicated
ETH-BD-2FO plug-in module, with
V8.0)
IEC61850-9-2 Merging Unit stream MU x 200 =
(Note: This function requires a
dedicated ETH-BD-2FO per stream,
with V8.0)
IEC61850-9-2 Merging Unit MU x 295 =
stream 7SS85 CU (Note: Only for
communictation with 7SS85 CU, This
function requires a dedicated ETH-
BD-2FO, with V8.40)
25 Synchrocheck, synchronization function Sync 1x x 60 = 1x
27 Undervoltage protection: "3-phase" V< x 5 =
or "positive-sequence system V1" or
"universal Vx"
27R, Rate-of-voltage-change protection (from dV/dt x 5 =
59R V8.30)
32, 37 Power protection active/reactive power P<>, x 10 =
Q<>
37 Undercurrent I< x 10 =
38 Temperature supervision >

46 Negative-sequence overcurrent I2> x 10 =


protection
46 Negative-sequence overcurrent I2>, x 15 =
protection with direction (V2,I2)
47 Overvoltage protection, negative- V2> x 5 =
sequence system
50/51 Overcurrent protection, phases I> x 20 =
TD
Instantaneous tripping at switch onto SOTF
fault
SIPROTEC 5
Configuration
May 4, 2021 8:56 AM

Functional scope 7VK87 Breaker Management Dev.:


Always Add selected Result
ANSI Function Abbr. included Qty. x Value = Points Qty.
50HS Instantaneous high-current tripping I>>>

50/51 Overcurrent protection with positive- I1>


TD sequence current I1 (from V7.9)
50N/ Overcurrent protection, ground IN> x 10 =
51N TD
50N/ Overcurrent protection, 1-phase IN>
51N TD
50BF Circuit-breaker failure protection, 1-/3- CBFP 1x x 25 = 1x
pole
50EF End-fault protection (Note: Only useable x 5 =
for distributed busbar protection with
7SS85 CU with V8.40)
50RS Circuit-breaker restrike protection CBRS x 20 =
59, 59N Overvoltage protection: "3-phase" V> x 5 =
or "zero-sequence system V0" or
"universal Vx"
60 Voltage-comparison supervision U> x 5 =
67 Directional overcurrent protection, I>, (V,I) x 40 =
phases
67N Directional overcurrent protection for IN>, (V,I) x 30 =
ground faults in grounded systems
74TC Trip-circuit supervision TCS

79 Automatic reclosing, 1-/3-pole AR 1x x 55 = 1x


SAD Secondary Arc Detection (SAD) during SAD x 15 =
1-pole AR-cycles (from V8.30); Note:
SAD additionally requires the function
points for "Automatic reclosing, 1-/3-
pole"
81 Frequency protection: "f>" or "f<" or "df/ f<>; df/ x 5 =
dt" dt<>
81U Underfrequency load-shedding f<(UFLS) x 15 =
Vector-jump protection > x 20 =
86 Lockout

87N T Restricted ground-fault protection IN x 15 =


SIPROTEC 5
Configuration
May 4, 2021 8:56 AM

Functional scope 7VK87 Breaker Management Dev.:


Always Add selected Result
ANSI Function Abbr. included Qty. x Value = Points Qty.
90V Automatic voltage controller for two- x 150 =
winding transformer
90V Automatic voltage controller for two- x 180 =
winding transformer with parallel
operation
Number of two-winding transformers 2x x 5 = 2x
with parallel operation (Note: only
together with the function "Automatic
voltage controller for two-winding
transformer with parallel operation")
90V Automatic voltage controller for three- x 200 =
winding transformer
90V Automatic voltage controller for grid x 175 =
coupling transformer
FL Fault locator, single-sided FL-one x 25 =
PMU Synchrophasor measurement PMU x 40 =
AFD Arc-protection (only with plug-in module
ARC-CD-3FO)
Measured values - standard

Measured values - extended: Min, Max, x 3 =


Avg
Switching statistic counters

PQ-Basic measured values: THD (Total


Harmonic Distortion) and harmonics
(from V8.01) THD voltage aggregation
values (from V8.40)
PQ-Basic measured values: Voltage x 20 =
unbalance (from V8.40)
PQ-Basic measured values: Voltage x 30 =
variations - voltage dips, swells and
interruptions (from V8.40)
PQ-Basic measured values: TDD - x 10 =
Total Demand Distortion (from V8.40)
CFC (Standard, control)

CFC arithmetic x 40 =
Circuit-breaker wear monitoring Ix, I²t, 2P x 10 =
SIPROTEC 5
Configuration
May 4, 2021 8:56 AM

Functional scope 7VK87 Breaker Management Dev.:


Always Add selected Result
ANSI Function Abbr. included Qty. x Value = Points Qty.
Switching sequences function x 5 =
Inrush current detection

External trip initiation

Control

PoW Point-on-wave switching (from V7.90) PoW x 425 =


Circuit-breaker 4x x 3 = 4x
Disconnector/Grounding switch 4x x 3 = 4x
Fault recording of analog and binary
signals
Monitoring and supervision

Protection interface, serial

Region France: Overload protection for x 10 =


lines 'PSL-PSC'
Region France: Overcurrent protection x 10 =
'MAXI-L'
Region France: Power-system x 10 =
decoupling protection 'PDA'
Region France: Overload protection for x 10 =
transformers
Frequency-tracking groups (from V7.8)

Cyber Security: Role-Based Access x 25 =


Control (from V7.8)
Temperature acquisition via
communication protocol
Cyber Security: IEEE 802.1x based x 10 =
network authentication (from V8.3)
Sum: 0