SIPROTEC 5

Configuration
Apr 29, 2021 8:49 AM

Device: 7SA87 Distance Prot. 1-/3-p.

Product code
Short: P1A369198
Long: 7SA87-DAAA-AA0-0AAAA0-AP0111-12111B-AAA000-000AC0-CH1BA1-EB0

Firmware: Current version


Housing width: 1/2 x 19''
Housing type: Flush mounting
Binary inputs: 31
Binary outputs: 38 Relays (30 Standard, 8 Fast, 0 High-Speed, 0 Power)
Current transformers: 4 for protection
Voltage transformers: 4 standard
Measuring-transducer inputs: 0 (20 mA or 10 V, fast)
0 (20 mA, standard)
CPU: CP300
Modules in 19" row 1: IO208 , PS201 , IO231
Modules in 19" row 2:
LEDs/Push-buttons: 16 LEDs
Operation Panel: Integrated
Key switch: Without
Display type: Small display
Front Design: Standard
Power Supply: DC 60 V-250 V, AC 100 V-230 V
Redundant Power Supply: No

Communication/Plug-in modules:
Communications encryption: Normal
Integrated Ethernet port J: for DIGSI 5
Plug-in module position E: ETH-BA-2EL: 2x electric Ethernet 100 Mbit/s, RJ45 Communication Protocols:
applicable for DIGSI 5, IEC 61850-8-1 MMS and GOOSE, IEC 60870-5-104,
DNP3 TCP, Modbus TCP, Synchrophasor (IEEE C37.118 - IP), Profinet IO, SUP,
DHCP, SNTP, SNMP, etc. Redundancy protocols: Line Mode, RSTP, HSR, PRP
Plug-in module position F: Port is available but not assembled

Functions:
SIPROTEC 5
Configuration
Apr 29, 2021 8:49 AM

Function points class: Base + 250 function points

Note on function-points class


The function-points class results from the sum of the function points of the selected functions. You can apply these
functions as selected. The device allows also each other selection of functions as long as the sum of the required
function points is within the selected function-points class. With the maximum function-points class of 1400 it is
possible to activate all the functions in the device. The function-points exceeding 1400 are free of charge. In the
engineering phase DIGSI 5 checks that the selected configuration is suitable (capable of running in the device) before
loading it to the device.

Miscellaneous:
Warranty: 5 years
Firmware: Current version
SIPROTEC 5
Configuration
Apr 29, 2021 8:49 AM

Functional scope 7SA87 Distance Prot. 1-/3-p.:


Always Add selected Result
ANSI Function Abbr. included Qty. x Value = Points Qty.
Protection functions for 3-pole tripping 3-pole

Protection functions for 1-pole tripping 1-pole

Hardware quantity structure expandable I/O

Process Bus Client Protocol (Note: This PB client x 100 =


function requires at least one dedicated
ETH-BD-2FO plug-in module, with
V8.0)
IEC61850-9-2 Merging Unit stream MU x 200 =
(Note: This function requires a
dedicated ETH-BD-2FO per stream,
with V8.0)
IEC61850-9-2 Merging Unit MU x 295 =
stream 7SS85 CU (Note: Only for
communictation with 7SS85 CU, This
function requires a dedicated ETH-
BD-2FO, with V8.40)
21/21N Distance protection Z<, V< / 1x x 95 = 1x
I>/(V,I)
21T Impedance protection for transformers Z< x 25 =
25 Synchrocheck, synchronization function Sync x 60 =
27 Undervoltage protection: "3-phase" V< x 5 =
or "positive-sequence system V1" or
"universal Vx"
27R, Rate-of-voltage-change protection (from dV/dt x 5 =
59R V8.30)
Undervoltage-controlled reactive power Q>/V< x 15 =
protection
32, 37 Power protection active/reactive power P<>, x 10 =
Q<>
37 Undercurrent I< x 10 =
38 Temperature supervision >

46 Negative-sequence overcurrent I2>, x 15 =


protection with direction (V2,I2)
47 Overvoltage protection, negative- V2> x 5 =
sequence system
49 Thermal overload protection , I²t x 10 =
SIPROTEC 5
Configuration
Apr 29, 2021 8:49 AM

Functional scope 7SA87 Distance Prot. 1-/3-p.:


Always Add selected Result
ANSI Function Abbr. included Qty. x Value = Points Qty.
50/51 Overcurrent protection, phases I> 2x x 30 = 2x
TD
Instantaneous tripping at switch onto SOTF
fault
50HS Instantaneous high-current tripping I>>>

50/51 Overcurrent protection with positive- I1>


TD sequence current I1 (from V7.9)
50N/ Overcurrent protection, ground IN>
51N TD
50N/ Overcurrent protection, 1-phase IN>
51N TD
50Ns/ Sensitive ground-current detection INs> x 15 =
51Ns for systems with resonant or isolated
neutral systems incl. a) 3I0>, b)
admittance Y0>, c) 3I0-harm> (from
V7.8)
Ground-fault detection via pulse pattern IN-pulse x 15 =
detection; Note: this stage additionally
requires the function 50Ns/51Ns or
67Ns "Sensitive ground-fault detection
for systems with resonant or isolated
neutral"
Intermittent ground-fault protection Iie> x 20 =
50BF Circuit-breaker failure protection, 1-/3- CBFP x 25 =
pole
50EF End-fault protection (Note: Only useable x 5 =
for distributed busbar protection with
7SS85 CU with V8.40)
50RS Circuit-breaker restrike protection CBRS x 20 =
51V Overcurrent protection, voltage t=f(I,V) x 10 =
dependent
59, 59N Overvoltage protection: "3-phase" V> x 5 =
or "zero-sequence system V0" or
"universal Vx"
60 Voltage-comparison supervision U> x 5 =
67 Directional overcurrent protection, I>, (V,I) x 40 =
phases
SIPROTEC 5
Configuration
Apr 29, 2021 8:49 AM

Functional scope 7SA87 Distance Prot. 1-/3-p.:


Always Add selected Result
ANSI Function Abbr. included Qty. x Value = Points Qty.
67N Directional overcurrent protection for IN>, (V,I) x 30 =
ground faults in grounded systems
67Ns Dir. sensitive ground-fault detection x 30 =
for systems with resonant or isolated
neutral incl. a) 3I0>, b) V0>, c) Cos-/
SinPhi, d) Transient ground-fault fct., e)
Phi(V,I), f) admittance
Directional stage with a harmonic; (V0h,I0h) x 10 =
Note: this stage additionally requires
the function "67Ns Dir. sensitive
ground-fault detection for systems with
resonant or isolated neutral"
Directional intermittent ground-fault Iie dir> x 20 =
protection
68 Power-swing blocking Z/t x 25 =
74TC Trip-circuit supervision TCS

78 Out-of-step protection Z/t x 55 =


79 Automatic reclosing, 1-/3-pole AR x 55 =
SAD Secondary Arc Detection (SAD) during SAD x 15 =
1-pole AR-cycles (from V8.30); Note:
SAD additionally requires the function
points for "Automatic reclosing, 1-/3-
pole"
81 Frequency protection: "f>" or "f<" or "df/ f<>; df/ x 5 =
dt" dt<>
81U Underfrequency load-shedding f<(UFLS) x 15 =
Vector-jump protection > x 20 =
85/21 Teleprotection for distance protection

85/27 Weak or no infeed: echo and tripping WI

85/67N Teleprotection for directional ground


fault protection
86 Lockout

87N T Restricted ground-fault protection IN x 15 =


87 Stub-fault differential protection (for x 35 =
STUB breaker-and-a-half scheme)
SIPROTEC 5
Configuration
Apr 29, 2021 8:49 AM

Functional scope 7SA87 Distance Prot. 1-/3-p.:


Always Add selected Result
ANSI Function Abbr. included Qty. x Value = Points Qty.
90V Automatic voltage controller for two- x 150 =
winding transformer
90V Automatic voltage controller for two- x 180 =
winding transformer with parallel
operation
Number of two-winding transformers 2x x 5 = 2x
with parallel operation (Note: only
together with the function "Automatic
voltage controller for two-winding
transformer with parallel operation")
90V Automatic voltage controller for three- x 200 =
winding transformer
90V Automatic voltage controller for grid x 175 =
coupling transformer
FL Fault locator, single-sided FL-one 1x x 25 = 1x
FL Fault locator plus (from V7.9) FL plus x 45 =
PMU Synchrophasor measurement PMU x 40 =
AFD Arc-protection (only with plug-in module
ARC-CD-3FO)
Measured values - standard

Measured values - extended: Min, Max, x 3 =


Avg
Switching statistic counters

PQ-Basic measured values: THD (Total


Harmonic Distortion) and harmonics
(from V8.01) THD voltage aggregation
values (from V8.40)
PQ-Basic measured values: Voltage x 20 =
unbalance (from V8.40)
PQ-Basic measured values: Voltage x 30 =
variations - voltage dips, swells and
interruptions (from V8.40)
PQ-Basic measured values: TDD - x 10 =
Total Demand Distortion (from V8.40)
CFC (Standard, control)

CFC arithmetic x 40 =
SIPROTEC 5
Configuration
Apr 29, 2021 8:49 AM

Functional scope 7SA87 Distance Prot. 1-/3-p.:


Always Add selected Result
ANSI Function Abbr. included Qty. x Value = Points Qty.
Circuit-breaker wear monitoring Ix, I²t, 2P x 10 =
Switching sequences function x 5 =
Inrush current detection

External trip initiation

Control

PoW Point-on-wave switching (from V7.90) PoW x 425 =


Circuit-breaker 4x x 3 = 4x
Disconnector/Grounding switch 4x x 3 = 4x
Fault recording of analog and binary
signals
Monitoring and supervision

Protection interface, serial

Region France: Overload protection for x 10 =


lines 'PSL-PSC'
Region France: Overcurrent protection x 10 =
'MAXI-L'
Region France: Power-system x 10 =
decoupling protection 'PDA'
Region France: Overload protection for x 10 =
transformers
Frequency-tracking groups (from V7.8)

Cyber Security: Role-Based Access x 25 =


Control (from V7.8)
Temperature acquisition via
communication protocol
Cyber Security: IEEE 802.1x based x 10 =
network authentication (from V8.3)
Sum: 0