3 SIRIM GAS international Sdn Bhd, (410334) No", Persaran Dato Monto. P.OSOX 7036, Secton 2, 'B _ 40700 Shan Alam, Setangor Oar Ersan, Malysi, ie Tel: 03-55445253 / 55448252 Fax o3-s5ee52"2 SIRIME farses conn QAS: TEST REPORT REPORT NO.: 2017EEA0380 PAGE: 1 OF 14 This Test Report refers only tosamples submitted by the applicant o SIRIM GAS international Sdn. Bhd. and tested by SIRIM QAS Internationa Sd. Bhd. This report shall not be reproduced, except in full and shall not be used for adverising purposes by any means or forms (including bu nt limit o acvertsing purposes) without witten approval fram Managing Director, SIRIM QAS Intemational Sdn. Bhd. Please refer tho last page for Conaltions Rotating To The Use of Test Report shal apply. Applicant CUPRA INTERNATIONAL LTD. Level 23-1 Premier Suite, Menara 1 Mont Kiara, No. 1 Jalan Kiara, Mont Kiara, 50480 Kuala Lumpur, Malaysia Manufacturer : CUPRA INTERNATIONAL LTD. P.O BOX 957, OFFSHORE INCORPORATIONS CENTER, ROAD TOWN, TORTOLA, BRITISH VIRGIN ISLANDS. Product : G.I CONDUIT AND FITTINGS Reference Standard) : BS EN61386-1: 2008 Method of test BS EN 61386 -21 : 2004 + A11 : 2010 Description of sample : Brand ‘CUPRA Class 4 Size (mm) 20, 25, and 32 Date received of 07% March 2017 Complete Application Job No, 20171420191 Overall test result. :_ COMPLIED (See page 2 for details) Issued date > —9 MAY 2017 IRI MUSTAFFA) Head Electrical & Electronic 1 Section Testing Services Department (ABDUL BDUL RAZAK} Testing Executive REPORT NO.: 2017EEA0380 PAGE: 2 OF 14 "Tis Test Repor refers ony fo samples submited by the applicant fo SIRI GAS ltemational Sch, Bhd. end tested by SIRIM OAS International Sdn. Bnd. This fepot shal not be reproduced. except intl and shal nol be Used for advertising purposes by any means or ‘orms (melucing but net imied to advertsing purposes) without wntten approval rom Managing Drectr, SIRIMAQAS interatenal Sn, hd, Please refer the last page for Concitions Relating To The Use of Test Repest snall apply. SUMMARY OF TESTS: 1, This is a type test report as requested by the applicant. 2. The samples submitted for testing has been checked in accordance to BS EN 61386 -1: 2008 and BS EN 61386 ~ 21 : 2004 + A11 : 2010. 3. Unless otherwise specified, tests were conducted at ambient temperature of 25 = 5° C. 4, The abbreviation used in this test report denotes as follows; PASS —_ : Complied with the requirement NA : Not Applicable with the requirement FAIL: Did Not Comply with the requirement ‘SUMMARY OF RESULT/S: 1, The submitted test samples as described in this test report complied with the requirements of BS EN 61386 -1:2008 and BS EN 61386 - 21 : 2004+ A11 : 2010. ADDITIONAL INFORMATION: 1. Tested by — : Mr. Ishar Abdul Hamed 2. Checked by : Mr Abdul Aziz Abdul Razak 3. Date of test sample(s) received; a) 1* submission : 17" March 2017 b) 2 submission : WL, REPORT NO.: 2017EEA0380 PAGE: 3 OF 14 "Tis Test Repor refers ony fo samples submited by the applicant fo SIRI GAS ltemational Sch, Bhd. end tested by SIRIM OAS International Sdn. Bnd. This fepot shal not be reproduced. except intl and shal nol be Used for advertising purposes by any means or forms (inclucing but nat limited to advertising purposes) withaut wrtten approval from Managing Director, SIRIM QAS Intemational Sd, hd, Please refer the last page for Concitions Relating To The Use of Test Repest snall apply. Clause [Requirement Remark Result 7 MARKING AND DOCUMENTATION Pass 7.4 [Conduit (conduit fitting) is marked on the product with a trade mark or a name identifying the manufacturer or responsible CUERA Fass vendor... [Conduit (conduit fitting) is marked in addition in such a way that it can be identified in the pee manufacturer's, or responsible vendor's, literature . : . TAA [Conduit is also marked with the classification jcode, in accordance with annex A, and Class 4 Pass includes at least the first four digits (optional) Faz Manufacturer indicates the compatibility of parts within a conduit system 7.1101 [Conduit is marked in accordance with 7.1 along its entire length at regular intervals of Pass preferably 1 m but not longer than 3 m (m) Pass Each length is marked at least once Pass '7.1.102 Minimum inside diameter and the [classification for the system in accordance ‘See appended table =a lwith clause 6 are documented by the 7.4.102 manufacturer 72 [Conduit fitting is marked in accordance with 7.1, on. Pass - the product sae is Pass ~a label attached to the product, or on the box Jor carton containing the fittings (if the marking Pass Jon the product is impractical) 7.3 Flame propagating material is orange in NA [colour Flame propagating material is not coloured lorange by painting or other superficial means Non-flame propagating material is of any [colour except yellow, orange or red, unless is [clearly marked on the product to be of non- flame propagating material 7.4 Earthing facilities are indicated by the symbol © {for protective earth in accordance with IEC Pass |60417, symbol 6041 EO iS REPORT NO.: 2017EEA0380 PAGE: 4 OF 14 forms (incluaing but not hd, Please refer the last "Tis Test Repor refers ony fo samples submited by the applicant fo SIRI GAS ltemational Sch, Bhd. end tested by SIRIM OAS International Sdn. Bnd. This fepot shal not be reproduced. except intl and shal nol be Used for advertising purposes by any means or ited to advertsing purposes) without writen approval from Managng Drectr, SIRIM QAS Intematcnal Sdn, ge for Cenations Relsting To The Use of Test Report shall appy. [clause [Requirement Remark Result [This marking is not placed on easily Pa ss removable parts, for example scrows 75 [Compliance with 7.1 to 7.4 checked by 7 Comell ss inspection 76 Marking is durable and clearly legible Pass [Compliance checked by inspection and by rubbing the marking by hand for 15 s with a piece of cloth soaked with water, and again Pass, for 15 s with a piece of cloth soaked with petroleum spirit 8 DIMENSIONS Pass at [Outside diameters comply with IEC 60423 ..:| See appended table &.1A| Pass Threads comply with IEC 60423 See appended table 8.1B Pass a2 [Threadable conduits and threadable conduit tings comply with table 101 (except See appended table 8.2A | Pass. {terminating conduit fitings) Non-threadable conduit fitings comply with table 102 (except fitings which are part of a NA jconduit system declaring tensile strength) Minimum inside diameter of the conduit [system is as declared by the manufacturer | S°° appended table 8.2C | Pass 9 [CONSTRUCTION Pass ot [There are no sharp edges, burrs or surface Paes projections within the conduit system [The manufacturer provides guidelines to assist the safo installation of tho conduit Pass, [system 92 [Screws, if any, used for attaching [components or covers to conduit fittings, or ee in joints to conduits, do not cause damage to [cable insulation when correctly inserted [Screws have ISO metric threads Pass -Thread-cutting screws are not used Pass Fixing screws and small clips for use with non-metallic or composite conduit fittings, of mpoens NA non-metallic material, are isolated from insulated conductors or cables, REPORT NO.: 2017EEA0380 PAGE: 5 OF 14 "Tis Test Repor refers ony fo samples submited by the applicant fo SIRI GAS ltemational Sch, Bhd. end tested by SIRIM OAS International Sdn. Bnd. This fepot shal not be reproduced. except intl and shal nol be Used for advertising purposes by any means or forms (inclucing but nat limited to advertising purposes) withaut wrtten approval from Managing Director, SIRIM QAS Intemational Sd, hd, Please refer the last page for Concitions Relating To The Use of Test Repest snall apply. Clause [Requirement Remark Result 9.3 Test for screw fixing using preformed threads| See appended table 9.3, NA [After the test: no damage sustained by the [screw or nut, such as breakage of the screw NA. jor damage to the head or thread Test for screw fixing using thread-forming | 5.6 appended table 9.4 NA 9.4 [screws [After the test: no damage, such as breakage NA lof the screw or damage to the head or thread 9.5 [Any material within the joint have at least the /same level of resistance to the external Pass influence as either the conduit or the conduit, fitting 96 Indications whether the conduit system that Jare assembled by means other than threads [can be disassembled and if so, how this can Pass be achieved, are provided by the manufacturer 10 MECHANICAL PROPERTIES Pass 10.1 Mechanical strength NA. 10.4.1 [Conduit systems have adequate mechanical strength 10.1.2 [Conduits do not crack and are not deformed |when bent or compressed, or exposed to impact or extreme temperature, according to their classification 1013 [Conduit systems intended as a mounting for Jother equipment have adequate mechanical strength 101.4 Compliance of 10.1.1 to 10.1.3 checked by the tests specified in 10.2 to 10.8 10.3 Impact test Pass 12 samples of conduit, each (200 ¢ 5) rm in length, or 12 samples of conduit fittings |subjected to an impact test using the Segppemeniabio Os | Pass apparatus shown in figure 2 1033 |At least 9 of the 12 samples passed the test Pass REPORT NO.: 2017EEA0380 PAGE: 6 OF 14 "Tis Test Repor refers ony fo samples submited by the applicant fo SIRI GAS ltemational Sch, Bhd. end tested by SIRIM OAS International Sdn. Bnd. This fepot shal not be reproduced. except intl and shal nol be Used for advertising purposes by any means or forms (inclucing but nat limited to advertising purposes) withaut wrtten approval from Managing Director, SIRIM QAS Intemational Sd, hd, Please refer the last page for Concitions Relating To The Use of Test Repest snall apply. Clause [Requirement Remark Result 11 ELECTRICAL PROPERTIES Pass 14 Electrical requirements Pass W441 [Conduit systems declaring electrical Jcontinuity characteristics are checked by the tests in 11.2 immediately after the tests in 142 W412 [Conduit systems of metal or composite materials are so constructed that accessible metal parts can be bonded to earth 11413 [Accessible conductive parts of the metal or [composite conduit system, which may become live in the event of a fault, are be effectively earthed W414 [Conduit systems of non-metallic or Jcomposite materials, where declared, have Jan adequate electrical insulating strength [and insulating resistance 11.2 Bonding test Pass [Test carried out on an arrangement of Jconduits and conduit fittings prepared in Jaccordance with the manufacturer's See appended table 112] Pass instructions and figure 3: resistance not jexceed 0,1 2 14 EXTERNAL INFLUENCES Pass 144 Degree of protection provided by enclosure NA [Conduit systems, when assembled in Jaccordance with the manufacturer's instructions, have adequate resistance to IP jexternal influences according to the a ‘classification deciared by the manufacturer, with a minimum requirement of 1P30.... 144.41 Degree of protection — Ingress of foreign solid NA lobjects 14.1.2 Degree of protection — Ingress of water NA 142 Resistance against corrosion. Pass 14.2.4 Resistance to corrosion classification for painted and zinc coated steel and steel aaa Pass [composite conduits and conduit (able 10). Kes Matin AN REPORT NO.: 2017EEA0380 PAGE: 7 OF 14 "Tis Test Repor refers ony fo samples submited by the applicant fo SIRI GAS ltemational Sch, Bhd. end tested by SIRIM OAS International Sdn. Bnd. This fepot shal not be reproduced. except intl and shal nol be Used for advertising purposes by any means or ‘orms (melucing but net imied to advertsing purposes) without wntten approval rom Managing Drectr, SIRIMAQAS interatenal Sn, hd, Please refer the last page for Concitions Relating To The Use of Test Repest snall apply. Clause [Requirement Remark Result For non-ferrous metallic and composite [conduit systems, the manufacturer provided Pass information about its protection against jcorrosion 1422 Tests for resistance to corrosion for painted and zinc coated steel and Bas [steel composite conduits systems 142.21 — |Low protection conduit and conduit fittings inspected for completeness of covering by NA the protective coating, both inside and outside 142.22 — [Test for medium protection conduit and [conduit fitings: after completion of the test, the samples showed no more than two blue NA [coloured spots on each square centimetre of the surface, and no blue spot had a }dimension larger than 1,5 mm Test for high protection conduit and conduit {ittings: after the test, the sample showed no precipitation of copper which cannot be Pass |scrubbed off in running water, if necessary after immersion for 15's in a 10% solution of hydrochloric acid in water REPORT NO.: 2017EEA0380 PAGE: 8 OF 14 "Tis Test Repor refers ony fo samples submited by the applicant fo SIRI GAS ltemational Sch, Bhd. end tested by SIRIM OAS International Sdn. Bnd. This fepot shal not be reproduced. except intl and shal nol be Used for advertising purposes by any means or forms (incluaing but not hd, Please refer the last ited to advertsing purposes) without writen approval from Managng Drectr, SIRIM QAS Intematcnal Sdn, ge for Cenations Relsting To The Use of Test Report shall appy. ANNEX 1 7.1102 |TABLE: Minimum inside diameter declared by manufacturer for the | Pass system Minimum inside diameter declared by Size manufacturer for the system (mm) _| Verdict 20 16.48 Pass 25 22.43 Pass 32 28.88 Pass [Supplementary information: 1A __ | TABLE: Checking of dimensions of conduits Pass Maximum outside Minimum outside | Minimum outside Size diameter diameter diameter {alltype of conduits) _| (metallic conduits) _} (non-metallic conduits) Outside Gauge Gauge diameters | Metric | Gaugefia2 | Verdict | fig.3A | Verdict | fig.3b | Verdict threads | d, (mm) (mm) (mm) dy (mm) 20+0-03 | M20 2004 Pass | 19,700 | Pass | 19,70 NA 25+0-0,4 |_M25 25,04 Pass_| 24600 | Pass | 2460 NA 320-04 | _M2 32,04 Pass_| 31,600 | Pass | 31,60 NA [Supplementary information: [8.18 | TABLE: Checking of dimensions of threads Pass > External threads of conduits and Internal threads of fittings ize fitings Outside Go gauge fig. 4 ] Nogo gauge | Go gauge fig. 5 | No go gauge fig. diameters | MOue | threaded) fig. 4 (plain) (threaded) 5 (plain) (mm) Verdict Verdict Verdict Verdict 2040-03 | M20 Pass Pass Pass Pass: 2540-04 | M2 Pass Pass Pass Pass 32+00,4 | _M32 Pass Pass Pass Pass | Supplementary information: REPORT NO.: 2017EEA0380 PAGE: 9 OF 14 "Tis Test Repor refers ony fo samples submited by the applicant fo SIRI GAS ltemational Sch, Bhd. end tested by SIRIM OAS International Sdn. Bnd. This tepot shall not be reproduced. except in fll and shall nol De used fr advertising purposes by any means or forms (inclucing but nat limited to advertising purposes) withaut wrtten approval from Managing Director, SIRIM QAS Intemational Sd, hd, Please refer the last page for Concitions Relating To The Use of Test Repest snall apply. ANNEX 2 82A | TABLE: Checking of thread lengths according to table 101 (threadable | Pass conduits and threadable conduit fittings) External Thread Internal Thread Size Minimum | Length Minimum | Length length | measured | Verdict | length | measured | Verdict allowed (mm)| __ (mm) allowed (mm)| (mm) 20 140 14,05 Pass 15.0 17.52 Pass 25 770 17,10 Pass 18.0 20,13 Pass 32 19.0 19,27 Pass 200 22,92 Pass [Supplementary information 82C | TABLE: Checking of minimum inside diameter of the conduit system | Pass Minimum inside diameter of the | inside diameter of the conduit Size conduit system declared by Retinarelelotaa| verdet manufacturer (mm) ye 20 Not specified 76.48 Pass 25 Not specified 22,43 Pass 32 Not specifed 28,88 Pass ‘Supplementary information: mn =) lz CET REPORT NO.: 2017EEA0380 PAGE: 10 OF 14 "Tis Test Repor refers ony fo samples submited by the applicant fo SIRI GAS ltemational Sch, Bhd. end tested by SIRIM OAS International Sdn. Bnd. This fepot shal not be reproduced. except intl and shal nol be Used for advertising purposes by any means or forms (inclucing but nat limited to advertising purposes) withaut wrtten approval from Managing Director, SIRIM QAS Intemational Sd, hd, Please refer the last page for Concitions Relating To The Use of Test Repest snall apply. ANNEX 3 10.3 |TABLE: Impact test Pass [Classification (second digit) arsais = Test temperature (table 1) (°C) = 25 = Mass of hammer (table 5) (kg) 2.0 a Fall height (table 5) (mm) .... 300 = Cire gauge tae 102, | Nosianot disintegration /to | Tota seo | Nof through the sample samples | rat ‘sample | N° of samples | N° of samples| N° of samples | N° of samples | Which which passed | which failed | which passed | which failed | Passed the test the test the test the test | the test 20 | 1-12 12 : 12 : 12 | Pass 25 | 112 12 : 12 : 12 | Pass 32 | 112 12 : 12 : 12 | Pass ‘Supplementary information: 11.2 __ |TABLE: Bonding test Pass Classification (sixth digit)... 4 = pa | orcas lan emscem cel stentl| memes | (mm) | sample 10 pieces of conduit wo - 20 10 2 way conduit fitting (straight) 1.300 0.052 | Pass 20 10 2 way conduit fitting (box) 1,000 0.040 | Pass 20 10 Sway conduit fitting 1.100 0.044 | Pass 25 10 2 way conduit iting (straight) 1.075 0.043 | Pass 25 10 2 way conduit fitting (box) 1.200 0.048 | Pass 25 10 Sway conduit fitting 1.000 0.040 | Pass 32 10 2.way conduit fitting (straight) 0.975 0.039 | Pass 32 10 2 way conduit fitting (box) 1.050 0.042 | Pass 32 10 ‘Sway conduit fitting 1.000 0.040 | Pass ‘Supplementary information REPORT NO.: 2017EEA0380 PAGE: 11 OF 14 "Tis Test Repor refers ony fo samples submited by the applicant fo SIRI GAS ltemational Sch, Bhd. end tested by SIRIM OAS International Sdn. Bnd. This fepot shal not be reproduced. except intl and shal nol be Used for advertising purposes by any means or ‘orms (melucing but net imied to advertsing purposes) without wntten approval rom Managing Drectr, SIRIMAQAS interatenal Sn, hd, Please refer the last page for Concitions Relating To The Use of Test Repest snall apply. PHOTOGRAPH(S) OF TEST SAMPLE(S) REPORT NO.: 2017EEA0380 PAGE: 12 OF 14 "Tis Test Repor refers ony fo samples submited by the applicant fo SIRI GAS ltemational Sch, Bhd. end tested by SIRIM OAS International Sdn. Bnd. This fepot shal not be reproduced. except intl and shal nol be Used for advertising purposes by any means or ‘orms (melucing but net imied to advertsing purposes) without wntten approval rom Managing Drectr, SIRIMAQAS interatenal Sn, hd, Please refer the last page for Concitions Relating To The Use of Test Repest snall apply. PHOTOGRAPH(S) OF TEST SAMPLE(S) REPORT NO.: 2017EEA0380 PAGE: 13 OF 14 “This Test Repon refers only fo samples submited by me applicant fo SIRIM GAS inemalional Sah. Bhd. end tested by SIRIM GAS International Sdn. Bnd. This fepot shal not be reproduced. except intl and shal nol be Used for advertising purposes by any means or ‘orms (melucing but net imied to advertsing purposes) without wntten approval rom Managing Drectr, SIRIMAQAS interatenal Sn, Bhd. Please refer the last page for Conaitions Relating To The Use of Test Repost shall epply PHOTOGRAPH(S) OF TEST SAMPLE(S) REPORT NO.: 2017EEA0380 PAGE: 14 OF 14 "Tis Test Repor refers ony fo samples submited by the applicant fo SIRI GAS ltemational Sch, Bhd. end tested by SIRIM OAS International Sdn. Bnd. This tepot shall not be reproduced. except in fll and shall nol De used fr advertising purposes by any means or forms (inclucing but nat limited to advertising purposes) withaut wrtten approval from Managing Director, SIRIM QAS Intemational Sd, hd, Please refer the last page for Concitions Relating To The Use of Test Repert sll apply PHOTOGRAPH(S) OF TEST SAMPLE(S) 10. " ‘CONDITIONS RELATING TO THE USE OF SIRIM AS INTERNATIONAL TEST REPORT A Test Report willbe issued in respect of Testing Services conducted and shall relate only to the Sample actually tested SIRIM QAS International makes no warranty whatsoever and the Applicant shall not represent in any manner that any duplication or mass production of the Product is same as the Sample actually tested or that SIRIM QAS International has “ested any of the duplicated or mass produced Product The Test Report shall not be amended, changed, varied or modified in any manner whatsoever by the Applicant or otherwise. Ifthe Test Report is to be furnished to any third party or to the public, each such Test Report shall be furnished in full, egible and in its entirety. The Test Report shall not be reproduced and shall not in any event be used for any advertising purposes or whatsoever ‘without written approval from the Managing Director of SIRIM QAS International of No 1, Persiaran Dato’ Menteri, Building 8, Section 2, P.O. Box 7035, 40700 Shah Alam, Selangor Darul Ehsan. Customer (Applicant/Manufacture/Factory, etc) is not permitted to use any SIRIM QAS International, SIRIM or other SIRIN's subsidiaries logo or words on packaging, sample's manual, technical spectfcation, brochuresfflvers or any other ‘neans without the prior written approval from the Managing Director of SIRIM QAS International If such approval is obtained from the Managing Director of SIRIM GAS Intemational, the Applicant may only include the shrase, 'A sample of this product has been tested by SIRIM QAS Intemational... (Test Report No) .. (dated)... (for ‘what test) .. (to which standard)” or such similar words which stress that only the Sample was actually tested. This ‘hrase shall only be used for the purpose of product advertisement or product promotion (eg: brochures). For avoidance of doubt, the statement shall not be used on the sample and packaging of the sample. In the event there is an investigation from @ Government Regulatory Agency concerning the Applicant's Test Report, SIRIM QAS International may disclose the information pertaining to the Test Report for purposes of such investigation Further or in the alternative, its strictly forbidden unless with prior written approval from the Managing Director of SIRIM ‘AS International, to represent in ary manner whatsoever thet SIRIM QAS International, SIRIM and/or other SIRIM's subsidiaries has endorsed, approved or validated the Product of the Applicant in any manner whatsoever. In the event the Applicant is found in breach of this provision, SIRIM QAS International, SIRIM andlor other SIRIM's subsidiaries without prejudice to any other rights and remedies may take whatever action necessary including but not imited to: 2) _ Informing and placing a notice in the media; 2) Obtaining an injunction from Court (cost on a soliitr-client basis to be bome by the Applicant): 3) Refusing to accept any further Product for Testing Services from the Applicant or whosoever related to the Applicant, ‘whether subsidiary or otherwise; 1) Instructing the Applicant to withdraw and recall the advertisement, statement or document in question and advertise «a clarification and apology to SIRIM GAS Intemational, SIRIM andlor other SIRIM's subsidiaries twice in a national Publication of SIRIM QAS International's choice at the Applicants sole cost; and }) Informing or lodging a report pertaining the Apolicant's Test Report withthe relevant authorites. Certified true copies of the Test Report may be issued upon request by the Applicant upon payment ofthe relevant fee. Sorrections to test report shall only be allowed within 6 months from issuance date ofthe test report and shall be limited ‘0 maximum 3 times, after either case whichever occurs earlier, a new test report shall be issued and replace the previous ane (having errors) oF lack of information). Issuance of Supplementary Report to the original Test Report shall be forthe ‘ollowings; 8) Misprints and typo errors b) Missing technical information ©). Test date not reported 4) Mistake in reporting of test data

You might also like