REFRIGERATION AND
AIR CONDITIONING Technical leaflet
Technical leaflet Capacity regulators, type CPCE and LG
Introduction CPCE capacity regulator are used to adapt and is designed for hot gas injection into the
compressor capacity to actual evaporator load. evaporator just after the expansion valve.
It is installed in a bypass line between the high Liquid-gas mixer type LG can be used at the point
and low pressure sides of the refrigeration system of injection to assure a proper mixture.
Metric conversions
1 psi = 0.07 bar
5/ (t °F – 32) = t °C
9 1 2
Metric conversions
1 psi = 0.07 bar
5/ (t °F – 32) = t °C
9 1 2
1 ton = 3.5 kW
Selection (continued) Determine the corrections factor for the From the correction factors table (see below) a
expansion valve superheat setting. superheat setting of 9°F, R404A corresponds to a
Step 2 factor of 1.3.
Correction factors
Suction temp. ts
Superheat of expansion valve ∆ts °F
after reduction Refrigerant
°F
R134a 0.1 0.5 0.9 1.0 1.0 1.0 1.0
+50
R22, R404A, R507, R407C 0.3 0.9 1.0 1.0 1.0 1.0 1.0
R134a 0.1 0.3 0.7 1.0 1.0 1.0 1.0
+30
R22, R404A, R507, R407C 0.2 0.9 1.0 1.0 1.0 1.0 1.0
R134a 0.1 0.3 0.6 1.0 1.3 1.4 1.4
+15
R22, R404A, R507, R407C 0.1 0.5 1.0 1.0 1.0 1.0 1.0
R134a 0.1 0.3 0.6 1.0 1.5 2.2 2.4
−5
R22, R404A, R507, R407C 0.1 0.3 0.7 1.0 1.0 1.0 1.0
R134a 0.1 0.3 0.6 1.0 1.5 2.2 2.9
−20
R22, R404A, R507, R407C 0.1 0.3 0.6 1.0 1.3 1.4 1.4
−40 R22, R404A, R507, R407C 0.1 0.3 0.6 1.0 1.5 2.0 2.2
Step 4 Now select the appropriate capacity table A CPCE 22 delivers a replacement capacity of 8.0
and choose the column for minimum suction ton at a minimum suction temperature of –20°F
temperature ts and the column for condensing and a condensing temperature of 90°F.
temperature tc.
Using the corrected replacement capacity, select
a valve that provides an equivalent or greater
capacity.
Metric conversions
1 psi = 0.07 bar
5/ (t °F – 32) = t °C
9 1 2
1 ton = 3.5 kW
Capacity Minumum suction temperature ts after Regulator capacity Q tons at condensing temperature tc °F
Type pressure/temperature reduction
°F 70 90 100 120 140
R22
+50 2.2 4.6 6.1 7.6
+30 3.7 4.9 6.2 7.7
+15 3.9 4.9 6.2 7.8
CPCE 12 9.5
–5 3.9 5.0 6.3 7.9
–20 2.3 3.1 4.2 5.3
–40 1.2 1.6 2.2
+50 3.3 6.8 9.0 11.2
+30 5.3 7.2 9.1 11.3
+15 5.7 7.3 9.2 11.4
CPCE 15 13.9
–5 5.7 7.3 9.3 11.6
–20 3.3 4.5 6.0 7.7
–40 1.7 2.2 3.0
+50 4.3 9.0 11.9 14.9
+30 7.1 9.5 12.0 15.0
+15 7.5 9.7 12.2 15.2
CPCE 22 18.4
–5 7.6 9.7 12.2 15.3
–20 4.4 6.0 8.0 10.2
–40 2.3 3.0 4.1
R134a
+50 0.9 4.2 5.8 7.2 9.1
+30 3.1 4.5 5.8 7.3 9.1
CPCE 12 +15 2.3 3.2 4.3 5.8 7.3
–5 1.4 1.8 2.5 3.3 4.2
–20 0.9 1.1 1.5 2.0 2.5
+50 0.9 6.1 8.5 10.7 13.4
+30 4.6 6.7 8.5 10.7 13.4
CPCE 15 +15 3.3 4.7 6.3 8.5 10.7
–5 1.9 2.7 3.5 4.8 6.1
–20 1.1 1.4 2.0 2.6 3.2
+50 1.3 8.2 11.2 14.1 17.7
+30 6.1 8.9 11.3 14.1 17.7
CPCE 22 +15 4.4 6.1 8.4 11.2 14.1
–5 2.6 3.5 4.7 6.3 8.2
–20 1.5 2.0 2.8 3.6 4.5
R404A/R507
+50 2.2 4.6 6.2 7.7
+30 3.6 5.0 6.2 7.7
+15 3.9 5.0 6.3 7.7
CPCE 12 9.6
–5 4.0 5.0 6.3
–20 3.1 4.2 5.4
–40 1.7 2.2 2.9
+50 3.3 6.8 9.1 11.3
+30 5.4 7.3 9.1 11.3
+15 5.7 7.3 9.1 11.3
CPCE 15 14.1
–5 5.7 7.3 9.1
–20 4.5 6.1 7.9
–40 2.4 3.2 4.1
+50 4.4 9.0 12.1 15.0
+30 7.2 9.6 12.1 15.0
+15 7.6 9.6 12.1 15.1
CPCE 22 18.7
–5 7.6 9.8 12.1
–20 5.9 8.0 10.5
–40 3.2 4.3 5.4
Metric conversions
1 psi = 0.07 bar
5/ (t °F – 32) = t °C
9 1 2
1 ton = 3.5 kW
Capacity (continued) Minimum suction temperature ts after Regulator capacity Q tons at condensing temperature tc °F
Type pressure/temperature reduction
°F 70 90 100 120 140
R407C
+50 2.4 5.0 6.6 8.2
+30 4.0 5.3 6.7 8.3
+15 4.2 5.3 6.7 8.4
CPCE 12 10.3
–5 4.2 5.4 6.8 8.5
–20 2.5 3.3 4.5 5.7
–40 1.3 1.7 2.4
+50 3.6 7.3 9.7 12.1
+30 5.7 7.8 9.8 12.2
+15 6.2 7.9 9.9 12.3
CPCE 15 15.0
–5 6.2 7.9 10.0 12.5
–20 3.6 4.9 6.5 8.3
–40 1.8 2.4 3.2
+50 4.6 9.7 12.9 16.1
+30 7.7 10.3 13.0 16.2
+15 8.1 10.5 13.2 16.4
CPCE 22 19.9
–5 8.2 10.5 13.2 16.5
–20 4.8 6.5 8.6 11.0
–40 2.5 3.2 4.4
The capacities are based on:
Liquid temperature ahead of expansion valve tl = 100°F
1. Liquid inlet
2. Hot gas inlet LG
3. Outlet
Metric conversions
1 psi = 0.07 bar
5/ (t °F – 32) = t °C
9 1 2
1 ton = 3.5 kW
CPCE LG
L1 Weight H H1 L1 NV Weight
Type Type
in. lbs in. in. in. in. lbs
Metric conversions
1 in. = 25.4 mm
1 lb = 0.454 kg