You are on page 1of 1

Specification Sheet for TCV & Desuper-

Heater
Project FANAVARAN Sheet No. 1 OF 1
Service HP STEAM Desuper-Heater Tag No. For TCV-001
DOC No. FNP-01-ED-ME-DSH-0067 REV: 02 MFG. No.
Desuper-Heater Type Spray Nozzle Type Q'ty (Set) 1
Steam Line Size 6" Schedule No. 80
Water Line Size 1/2" Schedule No. 80
1 Medium State Steam / Water Vapor / Liquid
2 Max. Q Nor. Q Min. Q Etc. Design Condition
3 Steam Inlet
4 Flow Rate (Q1) kg/hr 21571 19610 4903
5 Inlet Pressure barG 41.2 41.2 41.2 44
6 Inlet Temperature ℃ 350 350 350 375
7 Enthalpy kj/kg 3091 3091 3091
8 Density kg/㎥ 15.96 15.96 15.96
SERVICE CONDITIONS

9 K -
10 Steam Outlet
11 Flow Rate (Q2) kg/hr 22,000 20,000 5000
12 Outlet Pressure barG 40 40 40 44
13 Temperature ℃ 330 330 330 375
14 Enthalpy Kj/kg 3039 3039 3039
15 Density kg/㎥ 16.18 16.18 16.18
16 Water
17 Flow Rate (QW) kg/hr 428.6 389.7 97.4
18 Outlet Pressure barG 43 43 43
19 Temperature ℃ 109 109 109
20 Enthalpy kj/kg 460.2 460.2 460.2
21 Density kg/㎥ 955.6 955.6 955.6
22 Flow Rate kg/hr 428.6 389.7 97.4
23 Inlet Pressure barG 43 43 43
TCV CALCULATED DATA

24 Outlet Pressure barG 40 40 40


25 Inlet Temperature ℃ 109 109 109
26 Specific Gravity G 0.956 0.956 0.956
27 Molecular Weight M.W 18 18 18
28 Predicted SPL dBA <85 <85 <85
29 Calculated Cv 0.27 0.25 0.032
30 Opening Lift % 80 70 10
31

32 Model No. Later 54 Model No. VTA


DESUPER-HEATER

33 Type Integrated spring loaded nozzle 55 Body Size (B) Port Size (B)
34 Rating & End Connection ½” 600# WATER SIDE 56 Trim Design Trim Type
35 6” 600# STEAM SIDE 57 Rating & End Connection 1/2” 600# Water side , 6” 600# Steam

36 Holder Material Carbon Steel 58 Material Body


TCV
37 Nozzle Material 316SS (VTA) 59 Trim (Plug / Seat) 316 SS (VTA)
38 Flange RF WN 60 Packing Graphite
39 Actuator Type Diaphragm 61 Trim Form VTA
ACTUATOR

40 Model Later 62 Required Seat Tightness ANSI CLASS V


41 Close At (kgf/cm²G) Open At (kfg/cm²G) VTA VTA 63 Rated Cv 0.32 (VTA)
42 Air Supply Pressure 3 to 15 PSIG 64 Painting Color (RAL No.)
43 Fail Position Close 65 Option
AIR SET

44 Hand-Wheel (Location) No 66 Model


R

45 Painting Color (RAL No.) 67 MFG.


Input Signal (mA DC) 4 ~ 20mA (HART) Volume Booster
I / P POSITIONE

46 68

47 Output Pressure (kgf/㎠G) 69 Limit Switch Type / Enclosure


MISCELLANEOUS

48 Type 70 Model No. / Maker


49 Enclosure 71 Solenoid Valve Power / Enclosure
50 Model No. / MFG 72 Model No. / Maker
51 Output (mA DC) Yes 4 ~ 20mA (HART) 73 Air Supply
PTM

Conduit Connection
52 Type 74 Electrical
53 Model No. / MFG. 75 Tubing Material

No. Date Revision Prepared By Checked By Approved By