Settings
{Schools}
Yemen Office
11
1 3
2
1
Parameters
(1) System Frequency: 50Hz
(2) Maximum input current from AC input 1: 50A
(3) Check to give remote order to change the Maximum input current from AC1
(4) Maximum limit of input current from AC input 2: 16A
(5) Check to enable battery monitor from Color control
(6) Specify the installed battery capacity : 1000, 1500, 2000 or 2500 Ah
1
1
1
1
2
1
3
1 1
1 1
1
Parameters
(1) Keep this without change (None)
(2) AC input Low voltage disconnection set it 195 V
(3) AC input high voltage disconnection set it 253 V
11
1
1
2
1 4
1 1
1 51
1
11
1
13
1
1
Parameters
(1) Inverter output voltage :230 VAC
(2) DC input low voltage shutdown :48VDC
(3) DC input Low Voltage Pre-alarm: 50VDC
(4) State of Charge low shut down: 50%
(5) State of Charge low restart: 100%
1
1 5
1
1
1 1
1
2
1
1
3
1 1 4
1
1
1 1
1
Parameters
(1) Checked to enable charger
(2) Checked to enable storage mode
(3) Select charge curve: Adaptive + battery safe
(4) Keep all these parameters as shown after selection of battery type
(5) Select the battery type: Gel/ AGM, Victron, Gel exide A200
1
1
1
1
Parameters
(1) Keep all Parameters as default
1
1
1
1
12
1
1 3
1
1
1
Parameters
(1) Keep all Parameters as default
(2) Check to stop charger after 10Hrs Bulk
(3) Keep all parameters as defaults
1
1
1
1
Parameters
(1) Keep all Parameters as default