Professional Documents
Culture Documents
GE Internal
These instructions do not purport to cover all details or variations in equipment, nor to provide for every possible
contingency to be met during installation, operation, and maintenance. The information is supplied for informational
purposes only, and GE makes no warranty as to the accuracy of the information included herein. Changes, modifications,
and/or improvements to equipment and specifications are made periodically and these changes may or may not be reflected
herein. It is understood that GE may make changes, modifications, or improvements to the equipment referenced herein or to
the document itself at any time. This document is intended for trained personnel familiar with the GE products referenced
herein.
GE may have patents or pending patent applications covering subject matter in this document. The furnishing of this
document does not provide any license whatsoever to any of these patents.
GE Internal – This document is proprietary. It contains information that belongs to the General Electric Company and is
furnished to its customer solely to assist that customer in the installation, testing, operation, and/or maintenance of the
equipment described. This document or the information it contains shall not be reproduced in whole or in part or disclosed to
any third party without the express written consent of GE.
GE provides the following document and the information included therein as is and without warranty of any kind,
expressed or implied, including but not limited to any implied statutory warranty of merchantability or fitness for
particular purpose.
For further assistance or technical information, contact the nearest GE Sales or Service Office, or an authorized GE Sales
Representative.
GE Internal
Document Updates
Revision Update Description
Acronyms and Abbreviations Added UCSC
Indicates a procedure or condition that, if not strictly observed, could result in damage
to or destruction of equipment.
Caution
Attention
This equipment contains a potential hazard of electric shock, burn, or death. Only
personnel who are adequately trained and thoroughly familiar with the equipment
and the instructions should install, operate, or maintain this equipment.
Warning
Isolation of test equipment from the equipment under test presents potential electrical
hazards. If the test equipment cannot be grounded to the equipment under test, the
test equipment’s case must be shielded to prevent contact by personnel.
Always ensure that applicable standards and regulations are followed and only
properly certified equipment is used as a critical component of a safety system. Never
assume that the Human-machine Interface (HMI) or the operator will close a safety
critical control loop.
Warning
• General Troubleshooting describes general issues that may be found during operation, but does not provide specific
alarm numbers.
• Specific Alarm Troubleshooting describes specific alarm messages as they are displayed on the ToolboxST* application.
With power applied, this equipment contains a potential hazard of electric shock or
burn. Only adequately trained persons who are thoroughly familiar with the
equipment and the instructions should maintain this equipment.
Warning
To prevent electric shock while servicing the equipment, personnel must understand
and follow all safety requirements for working around dangerous voltages. Make sure
that all power sources to the equipment are turned off, then ground and discharge the
equipment before performing any adjustments, servicing, or other acts requiring
Warning physical contact with the electrical components or wiring.
Any reference in this document to the UCSB controller infers the applicable form of
the Universal Stand-alone Controller (UCSB or UCSC) in the user’s system. For more
information, refer to the Mark VIe and Mark VIeS Control Systems Volume II:
General-purpose Applications System Guide (GEH-6721_Vol_II), the chapter
Attention Controllers and Unmanaged Switches.
This equipment contains a potential hazard of electric shock or burn. Only personnel
who are adequately trained and thoroughly familiar with the equipment and the
instructions should install, operate, or maintain this equipment, or have access to the
location where it is installed.
Warning
To prevent electric shock or burn while servicing the equipment, personnel must
understand and follow all safety requirements for working around dangerous voltages.
Obey local site lockout/tagout (LOTO) procedures, wear appropriate personal
protective equipment (PPE), and follow GE instructions when performing any
adjustments, services, or other tasks requiring physical proximity or contact with the
Warning circuit boards, electrical components, or wiring of the exciter.
Due to the large amount of energy passing through the exciter power converter, failure
to properly reinstall shields or to completely latch doors and covers compromises these
safeguards and places personnel at higher risk when within the environs of the exciter.
Understand and follow the safety procedures and warning labels.
Shock and burn hazard boundaries for the Excitation Control Equipment are
dependent upon the specific site application conditions, including Power Potential
Transformer (PPT) voltage, the mega volt-ampere (MVA) and impedance ratings, and
fault overcurrent clearing time of the power sources feeding the exciter. It is the
Warning responsibility of the customer to perform an arc flash analysis of the system,
understand the hazard boundaries that exist, and employ adequate safeguards to
protect personnel who may be in the proximity of the exciter, whether working on it or
not. These safeguards include restricted access for unqualified personnel, prohibition
of unsafe online maintenance practices, and use of appropriate LOTO procedures and
PPE for qualified personnel who must access the exciter.
To prevent personal injury or death, personnel must be aware of arc flash hazards,
and must maintain safe distances at all times as determined by released energy
calculations. The extent of arc flash hazards is not known until the site-specific
installation is evaluated; therefore GE recommends that an arc flash assessment be
Warning conducted for each installation.
The following table illustrates the Arc Flash Protection Boundary (AFPB) and Hazard Risk Category Number (HRC#) based
on assumed installation conditions that might exist in a typical exciter application. These calculations are based on equations
published in NFPA™-70E, Electrical Safety in the Workplace (2012). These numbers are illustrative only, and must not be
interpreted as applicable to any customer site installation. It is the responsibility of the customer to perform an arc flash
analysis of his installation and implement appropriate safeguards as mentioned above. Consider modifications to the
installation to reduce the hazard levels during periods when maintenance personnel must be present to perform online repair
procedures. These modifications might include the use of reduced energy let-through (RELT) circuit breakers, arc flash
detection technology, or faster fault clearing time settings used during maintenance periods.
Note This content provides general and example electrical safety information. For TSR system applicable information, refer
to the section Digital Front-end, Kits, and Separated Controls Cabinet Applications.
Upstream Fault
Exciter Source MVA AFPB HRC #
Clearing Time
0.1 sec 2480 mm (98 in) 4
100 mm Multi-bridge 15
0.3 sec 4300 mm (169 in) Extreme Hazard
100 mm Warm Backup 0.1 sec 1570 mm (62 in) 3
6
(WBU) 0.3 sec 2720 mm (107 in) Extreme Hazard
0.1 sec 1160 mm (45 in) 2
77 mm 3.25
0.3 sec 2000 mm (79 in) 3
0.1 sec 810 mm (32 in) 1
53 mm 1.6
0.3 sec 1400 mm (55 in) 3
0.1 sec 480 mm (19 in) 1
42 mm 0.45
0.3 sec 830 mm (33 in) 1
0.3 sec 340 mm (13 in) 0
120 A Regulator 0.075
2.0 sec 1240 mm (49 in) 3
35 A Regulator 0.01 0.3 sec 120 mm (5 in) 0
To safely use the grounding balls within this equipment, site personnel must be properly qualified and aware of site specific
installation parameters as follows:
• Before using the grounding balls, verify the available short circuit current and clearing time of the overcurrent protective
equipment does not exceed their rating. These parameters are site specific, and not necessarily determined by equipment
within GE scope of supply.
• Use grounding clamps and cables that are compatible with the grounding balls and properly rated for the site parameters.
• Comply with site safety procedures and relevant standards such as those provided in the following list.
Refer to relevant standards, including:
Catastrophic component failures, sometimes due to □ Monitor and mitigate external conditions that can lead to
premature failures.
external causes such as inadequate cooling,
□ Be careful not to damage new or reused parts during installation
excessive vibration, damage to insulating mica
procedures.
sheets or sleeves, transient overvoltage, or
□ Do not reuse questionable parts.
application beyond ratings
□ Know the equipment ratings and do not exceed them.
• Wear appropriate PPE for the equipment. For a separated EX2100e control cabinet, this is typically PPE-0.
• Field installation of harnesses for separated control cabinets or field mounted kits can introduce hazards and failure
modes if proper procedures are not followed. Failures at wire and cable connections are one of the leading causes of
electrical equipment misoperation, including unnecessary trips and failure of protective functions such as the 86 lockout
circuit to operate when needed. Watch out for:
− Open circuits or loose connections
− Short circuits
− Inadvertent contact and energizing cables with unintended voltages
− Insulation damage from installation or abrasion over time
− Conductor damage such as kinks, stretching, and stray strands at terminations
− Voltages present on harnesses during maintenance due to remote equipment not locked out. Establishing an
electrically safe state for work on the controls in some situations may also require lock-out to be performed on the
power converter, and vice versa.
− Poor terminations and stress on connectors. If harnesses are supplied pre-terminated, ensure the terminations and
connectors are not damaged during harness installation.
− Poor routing and protection of harnesses. Where harnesses pass through building or cabinet walls, provide adequate
protection against damage and sealing to prevent propagation of contaminants during normal operation and arc blast
gases during fault events. Refer to the applicable Installation and Startup manual, the section Cable Damage
Prevention for the equipment.
− Failure to separate harnesses by voltage and electromagnetic compatibility (EMC) levels. For the equipment, refer to
applicable Installation and Startup manual, the section General Cable Specification and Routing Guidelines.
• Be sure protective and functional grounding is provided for the detached equipment, per instructions provided in the
system elementary diagram. A minimum #2 AWG grounding wire must be provided from the detached control equipment
to the building system ground point. The power conversion cabinets must also be bonded to this point. For grounding
details, refer to the equipment elementary diagram.
• Look for hazards such as those in the above subsections during inspections following installation and maintenance.
• Control Troubleshooting provides possible solutions for problems that may occur during operation, such as the following:
− Touchscreen problems
− Board/module, power supplies, and fan failures
− Serial link functionality, erratic operation, and stability issues
− Noise and nuisance faults, wiring, and power supply failures
− Temperature alarms, events, and faults
• Control Cabinet Troubleshooting provides some possible solutions for problems that may occur in the control cabinet,
including the following:
− Diagnostic LED indications on boards/modules and/or Universal Controller Stand-alone board (UCSB)
− Communication issues
− Power supply issues
• Auxiliary Module Troubleshooting provides some possible solutions for problems that may occur with the auxiliary,
including the following:
− Breakers not closed
− Feedback and bridge voltage/current issues
− Exciter overload trips
− Harmonic noise
− AC line filter resistor problems
• Power Conversion Module Troubleshooting provides some possible solutions for problems that may occur in the PCM,
such as:
− 41A breaker trips
− High temperature alarms
− Fan failures
• Runtime Warnings describes errors that may occur during the download and expansion of the application code.
Underexcitation limit □ If the UEL LIMIT is ACTIVE, raise the excitation until clear, then reset the alarm.
(UEL) event □ Check the settings of UEL limits.
□ Check EX2100e control calculations of watts and volt-ampere reactives (VARs) versus other
plant instrumentation.
□ Check the Ethernet cables to the remote control operator interface (COI).
Link presence loss fault □ If communication to the COI is lost, use the optional touchscreen to operate the EX2100e
control.
□ Check for alarms in inactive control.
Control/bridge transfers □ Check for alarms in C control.
(redundant systems only) □ Check the settings of protective functions in C control.
C control is not included in dual Regulator systems.
□ Clear the alarm using the Reset Faults command.
□ If the alarm does not reset, review the ToolboxST application diagram, FGD_In , for the fault
location and calculated resistance. Consult station operation standing instructions for
operation with field ground. If the problem persists, contact the nearest GE sales or service
office, or an authorized GE sales representative.
Ground detector faults □ For Brushless Regulator applications, check the external third-party ground detector and the
connections at the Exciter Regulator Third-party Ground Detector Terminal (ERGT) board.
□ For field ground detector (FGD) oscillator problems, review the diagram, FGD_Seq , and
perform a FGD test. If this clears the condition, reset faults and continue operation. If not,
replace the EX2100e Auxiliary Interface (ERAX) board, Exciter Attenuation Module (EXAM),
or cable.
Note The excitation control can broadcast codes through an Ethernet Global Data (EGD) link.
Alarm icon:
Green = No event
Yellow = Alarm present
Red = Trip present
Main Touchscreen
2400
Description Fault Reset
2401
Description AtoD Gain(s) Flt
Possible Cause One of the ESYS analog channels failed during a calibration test.
Solution Check the ESYS and replace if other reasons for the failure are not found.
2402
Description Bridge Heat Sensor
Possible Cause The bridge temperature sensor for the bridge is faulty and gives an open indication due to:
Solution
• Check the thermistor to the ERAX and replace the ERAX if necessary.
• Check the ERAX and replace if necessary.
• Check the bridge temperature sensor.
• Check wiring and connections.
• Check the temperature reading.
2403
Description Bridge Warm Alarm
Possible Cause Temperature feedback exceeded the alarm level as set by P.WarmCelsius due to:
Solution
Possible Cause This extra alarm input is driven by a pointer and is specific to the application.
2405
Description High Field Current
Possible Cause Field current has exceeded P.FldCurHiSet(Adc) for P.FldCurHiSec (sec). An unusual call for high field
current to meet power system demands has occurred due to:
Solution
2406
Description AlrmFldInvT
Possible Cause The field overcurrent inverse time device caused a alarm due toin correct operation or system conditions.
Solution Check for incorrect operation or system conditions that could have caused excessive field current for an extended
duration.
2407
Description FldMode: Current Reg
Possible Cause Field current regulation has been active after the delayed run time due to:
Solution
Possible Cause Field temperature (based on resistance calculation) exceeded P.HiFieldTemp due to:
Solution
2409
Description AlrmPTUV
Solution
• Check PT fuses.
• Check PT switches and close if they are open.
• Check PT feedback (wiring).
• Check voltage phase to phase balance.
• Check the ESYS and replace if necessary.
2410
Description Alrm VHz Limit
Possible Cause The VHz limiter has became active while in auto mode due to:
Solution
Solution
2412
Description VPTs Failed (DualPT)
Possible Cause The main set of PTs have failed in dual PT mode due to:
Solution
• Check the voltage reaching the ESYS screws (44, 46, 48).
• Check the PT wiring to switches.
• Check the wiring to the ESYS.
• Check the ESYS and replace if necessary.
2413
Description AlrmXPTs_Rev
Possible Cause The extra PT input frequency was sensed reversed due to:
Solution
Possible Cause The extra set of PTs have failed in dual PT mode due to:
Solution
• Check the voltage reaching the ESYS screws (43, 45, 47).
• Check the PT wiring to switches.
• Check the wiring to the ESYS.
• Check the ESYS and replace if necessary.
2415
Description Aux52G Diag Flt
Possible Cause
Solution
2416
Description Aux86 Diag Flt
Possible Cause
• Lockout device (86) input does not match the other controller
• P.AuxForce86 mismatch between M1 and M2
• Wiring issue from the ERAX of one controller to another
• ERAX failure
Solution
Possible Cause The capture summation only works with floats. It is not correct for any type other than floats.
2418
Description Cmd K3 Diag Flt
Possible Cause The state of the K3 driver command and the feedback from the relay driver on the ERAX disagree due
to:
Solution
2419
Description Cmd 41 Diag Flt
Possible Cause The state of the 41 driver command and the feedback from the relay driver on the ERAX disagree due to
failure of the ERAX.
2420
Description DC Overcurrent Trip
Solution
• Check for an external short circuit or low impedance on the bridge output.
• Verify the shunt size is correct for the load.
• Check and replace bad wiring.
• Retune regulator current regulator.
• Check for a rotating diode failure.
Possible Cause The measured DC link voltage is low by comparison to P.DCLinkLev due to:
Solution
2422
Description Dyn Dis Cmd Fbk
Possible Cause
Solution
2423
Description Dyn Discharge Watts
Possible Cause The power dissipation limit of the dynamic discharge (DD) resistor has been exceeded due to:
Solution
Possible Cause There is no heart beat from the block area to the inner loop due to a missing application block or false
execution.
Solution Add the inverter block using application heart beat signals.
2425
Description ACL/Inner Loop Watchdog Alarm
Possible Cause There is a timing issue between the inner loop and block area.
Solution No action is required if this appears during startup, otherwise perform the following:
• Check for low idle time and reduce excessive blockware loading, if possible.
• Check for unusual system events that can cause excessive processor burden.
2426
Description ERAX Board Identifier
Note This alarm should not occur without a board failure or an HSSL programming problem.
Solution
Possible Cause
Note ERAX PSOK monitors ±50 V input for the FGD power amplifier and 85G, ±8 V for the FGD and thermistor analog
signals, and 5V for the gate drive interfaces and other logic. The signal helps ensure that relays and gate drives fail to a benign
state.
A failure of one of these supplies will generate another alarm, such as out-of-range FGD or other feedback signals. Presence
of a PSOK alarm without other alarms may signal an out-of-range power supply and perhaps a pending failure.
Solution
2428
Description ESYS Board Identifer
Note This should not occur without a board failure or HSSL programming problem.
2429
Description ESYS Instance
Possible Cause
Note The ESYS power suppply monitor includes 55 V dc contact-in wetting voltage, 5 V dc logic supply, and a reset from
the HSLA, and helps ensure the DACs and relays fail to a benign state.
Presence of this alarm may explain other issues such as non-functional contact inputs, or a pending power supply failure.
Solution
• Check 28 V at the JS# connector for the offending section (M1, M2).
• Check for high surface contamination on the board and follow cleaning procedures.
• Check for excessive cabinet temperature and improve the thermal environment if not within specifications.
• Verify that the PSOK LED on the HSLA is lit. If P28 is good at ESYS-JS#, but the HSLA PSOK is not lit, replace the
HSLA.
• Check the open circuit voltage at the TB2 high side contact inputs (odd numbered terminals 27 - 39) and verify it is 50-55
V. Check for excessive loading on these contact inputs.
• Check the ESYS relays for possible coil shorts drawing excess current, including the following:
− Relay LEDs are lit
− No relays are excessively hot
− If the relay is removed, the PSGOOD alarm is clear
− Status feedback alarms are not occurring
• Check the ESYS and replace if necessary.
2431
Description ESYS External Power Supply #1
Possible Cause
• P.ESYS_PS1_En is incorrect
• Problem with the cabling from the ESYS to the 28 V power supplies
• Problem with the wiring and overcurrent protection to the 28 V power supplies
• Problem with the incoming supply voltages
• PSOK LEDs on the supplies are not lit
• Failed 28 V output from the supplies
• ESYS failure
Solution
Possible Cause
• P.ESYS_PS1_En is incorrect
• Problem with the cabling from the ESYS to the 28 V power supplies
• Problem with the wiring and overcurrent protection to the 28 V power supplies
• Problem with the incoming supply voltages
• PSOK LEDs on the supplies are not lit
• Failed 28 V output from the supplies
• ESYS failure
Solution
2433
Description ESYS External Power Supply #3
Possible Cause
• P.ESYS_PS1_En is incorrect
• Problem with the cabling from the ESYS to the 28 V power supplies
• Problem with the wiring and overcurrent protection to the 28 V power supplies
• Problem with the incoming supply voltages
• PSOK LEDs on the supplies are not lit
• Failed 28 V output from the supplies
• ESYS failure
Solution
Possible Cause
• P.ESYS_PS1_En is incorrect
• Problem with the cabling from the ESYS to the 28 V power supplies
• Problem with the wiring and overcurrent protection to the 28 V power supplies
• Problem with the incoming supply voltages
• PSOK LEDs on the supplies are not lit
• Failed 28 V output from the supplies
• ESYS failure
Solution
2435
Description ESYS Section (M1,M2) Incorrect
Possible Cause The cables from the ESYS sections to the corresponding master are incorrect.
Solution
2436
Description Customer Analog 1
Possible Cause Customer analog input #1 to the ESYS does not match the other controller due to:
Solution
Possible Cause Customer analog input #2 to ESYS does not match the other controller due to:
Solution
2438
Description Gen AC Gnd Flt Alm
Possible Cause
Solution
Possible Cause The cable to the EXAM of the field ground detector is open due to:
2440
Description Gen DC Gnd Flt Alm
Possible Cause
Possible Cause
Solution
2442
Description Gen Gnd Flt Alm
Possible Cause
Possible Cause
2444
Description Gen Neg Bus Ground
Possible Cause
Solution
2445
Description FGD Osc Neg V Low
2446
Description FGD Osc Pos V Low
Possible Cause
Solution
2448
Description FGD Test Failed
Possible Cause The field ground detector oscillator and SVS test has failed due to:
Solution
2449
Description 41M Fail to Open
Possible Cause
• Problem with the auxiliary feedback connection from the 41M device, causing the auxiliary contact to close
• Mechanical failure of the 41M device
• Incorrect software settings
Solution
Possible Cause
• Problem with the auxiliary feedback connection from the 41M device, causing the auxiliary contact to open
• Mechanical failure of the 41M device
• Incorrect software configuration of the 41M auxiliary and command
Solution
2451
Description Current Check Failed
Possible Cause During start/stop state 1, the field current was in excess of 5% AFNL (should be near zero, based on
modelled current in a brushless system) due to:
• Brushless system:
− Badly offset regulator current feedback
− Modeled field current and regulator current have in compatible settings
− Problem with the shunt wiring
− Bad ERAX circuitry
• DC Rotating system:
− Badly offset generator field current
− Problem with the fiber-optic cable from the EDFF to the ERAX
− Problem with the shunt wiring
− EDFF failure
− ERAX failure
Solution
• Brushless system:
− Run the offset removal test.
− Check the settings in the application software.
− Check shunt wiring.
− Check and Check the ERAX circuity and replace if necessary.
• DC Rotating system:
− Run the offset removal test.
− Check the fiber-optic cable connections from the EDFF to the ERAX.
− Check shunt wiring.
− Check the EDFF and replace if necessary.
− Check the ERAX and replace if necessary.
Possible Cause During a start, the field current was unable to build current to exceed P.IfldBuild in the allowed test time
P.BuildSec due to:
Note Multiple system errors, including improper configuration, internal or external failures, could be responsible.
General system:
Solution
General system:
2453
Description Start Stop Logic
Solution Contact the nearest GE sales or service office, or an authorized GE sales representative.
Possible Cause During the Running state, the 41M device auxiliary contact was sensed open due to:
• Problem with the auxiliary feedback connection from the 41M device
• Mechanical failure of the 41M
• External device has commanded the 41M to open
• Incorrect software settings
Solution
2455
Description AbortStop Trip
Possible Cause Other failures caused a shutdown through an abnormal sequence, including a stop given prior to reaching
the Running state.
2456
Description Problem FieldCurrent
Possible Cause Field current measurement disagrees with the other controller due to:
Solution
Possible Cause Field voltage measurement disagrees with the other controller due to:
Solution
2458
Description Problem Gating
Possible Cause The master gating control is suspected to have failed (based on modeling regulator voltage as firing
command times dc link voltage) due to:
Solution
2459
Description Problem Hi Current
Possible Cause
• Generator high level current measurement disagrees with the other controller
• High negative sequence or dc component was present
Solution
• From the ToolboxST application, review the signals and make adjustments as needed.
• Check the ESYS and replace if necessary.
• Generator high level current measurement disagrees with the other controller
• High negative sequence or dc component was present
Solution
• From the ToolboxST application, review the signals and make adjustments as needed.
• Check the ESYS and replace if necessary.
Possible Cause Regulator current measurement disagrees with the other controller.
Solution
2462
Description Problem with Regulator Voltage
Possible Cause Regulator voltage measurement disagrees with the other controller.
Solution
2463
Description Problem Gen Voltage
• Generator high level current measurement disagrees with the other controller
• High negative sequence or dc component was present
Solution
• From the ToolboxST application, review the signals and make adjustments as needed.
• Check the ESYS and replace if necessary.
2464
Description Problem ExtraVoltage
Possible Cause
Solution
Possible Cause
Solution
• From the ToolboxST application, review signals and determine which master section is in error and compare them to the
actual hardware input state.
• Check the force parameter for each controller.
• Check the HSLA to the ESYS connection seating.
• Check the HSLA and replace if necessary.
• Check the ESYS and replace if necessary.
2466
Description GP In 2 Diag Flt
Possible Cause
Solution
• From the ToolboxST application, review signals and determine which master section is in error and compare them to the
actual hardware input state.
• Check the force parameter for each controller.
• Check the HSLA to the ESYS connection seating.
• Check the HSLA and replace if necessary.
• Check the ESYS and replace if necessary.
Possible Cause
Solution
• From the ToolboxST application, review signals and determine which master section is in error and compare them to the
actual hardware input state.
• Check the force parameter for each controller.
• Check the HSLA to the ESYS connection seating.
• Check the HSLA and replace if necessary.
• Check the ESYS and replace if necessary.
2468
Description GP In 4 Diag Flt
Possible Cause
Solution
• From the ToolboxST application, review signals and determine which master section is in error and compare them to the
actual hardware input state.
• Check the force parameter for each controller.
• Check the HSLA to the ESYS connection seating.
• Check the HSLA and replace if necessary.
• Check the ESYS and replace if necessary.
Possible Cause
Solution
• From the ToolboxST application, review signals and determine which master section is in error and compare them to the
actual hardware input state.
• Check the force parameter for each controller.
• Check the HSLA to the ESYS connection seating.
• Check the HSLA and replace if necessary.
• Check the ESYS and replace if necessary.
2470
Description GP In 6 Diag Flt
Possible Cause
Solution
• From the ToolboxST application, review signals and determine which master section is in error and compare them to the
actual hardware input state.
• Check the force parameter for each controller.
• Check the HSLA to the ESYS connection seating.
• Check the HSLA and replace if necessary.
• Check the ESYS and replace if necessary.
Possible Cause
Solution
• From the ToolboxST application, review signals and determine which master section is in error and compare them to the
actual hardware input state.
• Check the force parameter for each controller.
• Check the HSLA to the ESYS connection seating.
• Check the HSLA and replace if necessary.
• Check the ESYS and replace if necessary.
2472
Description GP Out 1 Diag Flt
Possible Cause The state of GP relay #1 on ESYS does not match the commanded state due to:
• Relay #1 is bad
• ESYS relay drive is bad
Solution
• Check if V.GpOut1_Rfb does not match V.GP_Output_1. If not, replace the relay.
• Check if V.GpOut1_Dfb does not match V.GP_Output_1. If not, check the ESYS and replace if necessary.
2473
Description GP Out 2 Diag Flt
Possible Cause The state of GP relay #2 on ESYS does not match the commanded state due to:
• Relay #2 is bad
• ESYS relay drive is bad
Solution
• Check if V.GpOut2_Rfb does not match V.GP_Output_2. If not, replace the relay.
• Check if V.GpOut2_Dfb does not match V.GP_Output_2. If not, check the ESYS and replace if necessary.
Possible Cause The state of GP relay #3 on ESYS does not match the commanded state due to:
• Relay #3 is bad
• ESYS relay drive is bad
Solution
• Check if V.GpOut3_Rfb does not match V.GP_Output_3. If not, replace the relay.
• Check if V.GpOut3_Dfb does not match V.GP_Output_3. If not, check the ESYS and replace if necessary.
2475
Description GP Out 4 Diag Flt
Possible Cause The state of GP relay #4 on ESYS does not match the commanded state due to:
• Relay #4 is bad
• ESYS relay drive is bad
Solution
• Check if V.GpOut4_Rfb does not match V.GP_Output_4. If not, replace the relay.
• Check if V.GpOut4_Dfb does not match V.GP_Output_4. If not, check the ESYS and replace if necessary.
2476
Description Hw DC OverCurrent
Possible Cause A hardware detected overcurrent through the ERAX, which is the result of regulator current exceeding
2.5 times the regulator shunt value due to:
Solution
• Check for an external short circuit and replace any bad circuitry.
• Check the high capacitance loading on output.
• Check the shunt size and replace with the correct size if necessary.
• Check the shunt wiring and fix any wiring issues.
• Check the ERAX and replace if necessary.
Possible Cause
• De-saturation
• Failed driver
Solution
2478
Description HW IGBT U Fault
Possible Cause
• De-saturation
• Failed driver
Solution
2479
Description HW IGBT V Fault
Possible Cause
• De-saturation
• Failed driver
Solution
Possible Cause
Solution
2481
Description RDFD Alarm 1
Solution
2482
Description RDFD Alarm 2
Solution
2483
Description RDFD Trip 1
Solution
Solution
2485
Description Start Dynamic Discharge Test Failure
Possible Cause
Solution
2486
Description Status 41 Bad
Possible Cause
• Problem with the wiring from the 41 device and the ERAX
• ERAX failure
Solution
2487
Description ACL Not Ready
Note This alarm may occur during the startup sequence but should clear following a touchscreen reset.
Possible Cause
Possible Cause Temperature feedback from the power converter has exceeded the trip level as set by P.Hot_Celsius due
to:
Solution
2489
Description Bridge Trip
Possible Cause A trip occurred in the bridge through the ERAX feedback signal due to:
• Hardware overcurrent
• Gate drive faults
Solution
2490
Description Trip from ERAX
Possible Cause The controller has lost communications from its ERAX board in the power conversion module due to:
Note This trip may appear at startup or during unexpected power supply events.
Solution
Possible Cause The controller has lost communications from its ESYS due to:
Note This trip may appear at startup or during unexpected power supply events.
Solution
2492
Description Trip External FGD
Possible Cause The application generated a trip from the external ground detector.
2493
Description ACL GP Trip
2494
Description Trip via Lockout(86)
Possible Cause
Solution
• Check the generator protection relay initiating the 86 lockout relay and troubleshoot accordingly.
• Check for open wiring to the 86 input to the ERAX and the lockout relays.
• Check the ERAX and replace if necessary.
Possible Cause The impedance based 40 (LOE inner) device #1 caused a trip due to:
Solution
2496
Description TripLOE2 (40 outer)
Possible Cause The impedance based 40 (LOE outer) device #2 caused a trip due to:
Solution
2497
Description NotRunning 52Closed
Possible Cause
• Closed 52G
• High noise level on 52G wiring
• Failure of ESYS sensing
Solution
Possible Cause The online (52G closed) field overcurrent inverse time device caused a trip due to:
• Software parameter settings prevented overexcitation limiters to hold current below the trip level
• OEL trip function is not coordinated with limiters
• Failure of the current regulator due to untuned settings
Solution
• Check for software parameter settings that prevented overexcitation limiters to hold current below the trip level.
• Coordinate the OEL trip function with limiters.
• Check the settings and tune as necessary.
2499
Description Trip Offline OEL
Possible Cause The off-line (52G open) field overcurrent inverse time device caused a trip from failure to regulate
terminal voltage or field current due to:
• Software parameter settings prevented overexcitation limiters to hold current below the trip level
• OEL trip function is not coordinated with limiters
• Failure of the current regulator due to untuned settings
Solution
• Check for software parameter settings that prevented overexcitation limiters to hold current below the trip level.
• Coordinate the OEL trip function with limiters.
• Check the settings and tune as necessary.
2500
Description Running at 0 speed
Possible Cause The exciter was in the Running state with 52G open and was not commanded to stop prior to generator
speed run down.
Possible Cause Straight time high voltage device 59T caused a trip due to:
Solution
2502
Description TripVHz1
Possible Cause Straight time V/Hz 24T device #1 caused a trip due to:
2503
Description Trip VHz 2
Possible Cause Inverse time V/Hz 24T device #2 caused a trip due to:
Possible Cause The state of the trip #1 driver relay on the ESYS does not match the command due to:
Solution
• Check for proper seating of the HSLA on the ESYS and make adjustments as needed.
• Check the HSLA and replace if necessary.
• Check the ESYS and replace if necessary.
2505
Description Trip Out 2 Diag Flt
Possible Cause The state of the trip #2 driver relay on ESYS does not match the command due to:
Solution
• Check for proper seating of the HSLA on the ESYS and make adjustments as needed.
• Check the HSLA and replace if necessary.
• Check the ESYS and replace if necessary.
Possible Cause Task 1 (fastest) execution task exceeded the time available for completion.
2507
Description Task 2 exec overrun
Possible Cause Task 2 (1 msec) execution task exceeded the time available for completion.
2508
Description Task 3 exec overrun
Possible Cause Task 3 (slowest) execution task exceeded the time available for completion.
Possible Cause An excessive offset has been detected during a push-button dc offset removal test (regulator and
generator field voltage and currents) due to:
• Regulator voltage:
− Regulator voltage incorrect external measurement
− Problem with the module wiring
− ERAX failure
Solution
• Regulator voltage:
− Confirm that regulator voltage is zero by external measurement
− Check the module wiring and make corrections as needed.
− Check the ERAX and replace if necessary.
Possible Cause
Solution
• Check for system failures that may have allowed for lack of regulation.
• Check for incorrect protection versus limiter behavior, such as the UEL.
2511
Description Transfer LOE4
Solution
• Check for system failures that may have allowed for lack of regulation.
• Check for incorrect protection versus limiter behavior, such as the UEL.
2512
Description Transfer OEL
Possible Cause The backup master has detected an over excitation event and requested a master transfer due to:
• Overexcitation event
• Incorrect protection versus limiter behavior
Solution
• Check for system failures that may have allowed for lack of regulation.
• Check for incorrect protection versus limiter behavior, such as the UEL.
2513
Description Transfer VHz3 (str)
Possible Cause The C controller has made a master transfer request high V/Hz condition using its straight time V/Hz
device #3 due to incorrect protection versus limiter behavior such a incorrect V/Hz limit setting.
Solution
• Check for system failures that may have allowed for lack of regulation.
• Correct any incorrect V/Hz limit settings.
Possible Cause The C controller has made a master transfer request to a high V/Hz condition using its inverse time V/Hz
device #4. due to incorrect protection versus limiter behavior.
Solution
• Check for system failures that may have allowed for lack of regulation.
• Correct any incorrect V/Hz limit settings.
2515
Description ACL GP Alarm
2516
Description Reverse Field Current
Note This trip may occur during some cross compound unit conditions when both the EX2100e control and other excitation
units are in parallel.
2517
Description Problem on Low DC Link
Possible Cause Low dc link voltage caused a transfer to the backup controller due to:
Solution
Possible Cause The dc link voltage is below the parameter setting of DCLinkTrpLev due to:
Solution
2519
Description CT Failure A phase
Possible Cause The AB and AC CT pairs show a high standard deviation on the current waveforms due to:
Solution
Possible Cause The AB and BC CT pairs show a high standard deviation on the current waveforms due to:
Solution
2521
Description CT Failure C phase
Possible Cause The BC and AC CT pairs show a high standard deviation on the current waveforms due to:
Solution
2522
Description CT Failure X phase
Possible Cause A single CT pair, or all three, show a high standard deviation due to:
Solution
• Using the ToolboxST application tools, check all phases of the CT for failure.
• Check for an unusual CT wiring error, such as an ESYS/EXCT input wired to the same phase.
• Check the ESYS and replace if necessary.
Possible Cause The dc link voltage has exceeded the setpoint due to:
Solution
2524
Description ERAX HSLA Temperature Trip
Possible Cause The temperature of the HSLA on ERAX has exceeded the temperature trip setpoint.
2525
Description ERAX HSLA Temperature Alarm
Possible Cause The temperature of the HSLA on ERAX has exceeded the temperature alarm setpoint.
2526
Description ERAX Group Trip
Possible Cause The ERAX group does not match the requirements.
• Check the attribute, BridgeType, and verify that the ERAX board group is correct:
− 35 A requires ERAXH1
− 120 A requires ERAXH2
• Check P.ERAXGroup for any overrides.
• If the board group is incorrect, replace the ERAX.
Possible Cause The temperature of the HSLA on the ERAX is below the diagnostic setpoint.
2528
Description Transfer Command Diagnostic
Note This diagnostic is produced by the backup controller and passed to the master as a Transfer Command alarm.
Possible Cause A command to transfer masters was attempted by the backup controller but the transfer did not occur
due to:
• Problem with the wire harness from EDSL (J5T) to K5T coil
• Problem with the wire harnesses from EDSL (J11M1, J11M2) to each PCM and the ERAX
• EDSL failure
• ERAX failure
Solution
• Check the wire harness from the EDSL (J5T) to the K5T coil as follows:
− If the K5 coil cannot energize, M1 will remain as master.
− Verify that the K5T coil resistance is less than 100 Ω.
− If the coil resistance is high, replace the K5T coil.
• Check the wire harnesses from the EDSL (J11M1, J11M2) to each PCM and to the ERAX located inside the PCM.
• Check the EDSL and replace if necessary.
• Check the ERAX (the backup master is the one that commands a transfer) and replace if necessary.
Note This alarm is produced by the active master as a result of receiving a Transfer Command diagnostic from the backup
controller.
Possible Cause A command to transfer masters was attempted by the backup controller but the transfer did not occur
due to:
• Problem with the wire harness from EDSL (J5T) to K5T coil
• Problem with the wire harnesses from EDSL (J11M1, J11M2) to each PCM and the ERAX
• EDSL failure
• ERAX failure
Solution
• Check the wire harness from the EDSL (J5T) to the K5T coil as follows:
− If the K5 coil cannot energize, M1 will remain as master.
− Verify that the K5T coil resistance is less than 100 Ω.
− If the coil resistance is high, replace the K5T coil.
• Check the wire harnesses from the EDSL (J11M1, J11M2) to each PCM and to the ERAX located inside the PCM.
• Check the EDSL and replace if necessary.
• Check the ERAX (the backup master is the one that commands a transfer) and replace if necessary.
2530
Description Transfer Without Command
Possible Cause A master transfer occurred without a command being issued due to:
• Problem with the wire harness from EDSL (J5T) to K5T coil
• Problem with the wire harnesses from EDSL (J11M1, J11M2) to each PCM and the ERAX
• EDSL failure
• ERAX failure
Solution
• Check the wire harness from the EDSL (J5T) to the K5T coil as follows:
− If the K5 coil cannot energize, M1 will remain as master.
− Verify that the K5T coil resistance is less than 100 Ω.
− If the coil resistance is high, replace the K5T coil.
• Check the wire harnesses from the EDSL (J11M1, J11M2) to each PCM and to the ERAX located inside the PCM.
• Check the EDSL and replace if necessary.
• Check the ERAX (the backup master is the one that commands a transfer) and replace if necessary.
2531
Description Peer Controller is Not OK
Possible Cause A controller was informed by the other controller that it is not OK. due to a trip or a problem.
Solution Using the ToolboxST application, investigate the peer controller for alarms to determine what is causing the
condition.
Possible Cause During the start sequence, K3 failed to close due to:
Solution
• Check K3 coil.
• Check the K3 coil to ERAX-J7 harness.
• Check the ERAX and replace if necessary.
0
Description Diagnostic Alarm Reset
20
Description ToolboxST application detects unhealthy link or loss of communication between [ ] and controller.
Possible Cause
Solution
• Verify that the Ethernet cables and network switch are operating correctly.
• Verify that the I/O pack configuration (such as Type, HW Form, Bar Code, position) matches the actual hardware.
• Manually restart the I/O pack or module.
• If ToolboxST communication is working correctly, any additional diagnostics should indicate the cause of the problem.
• Build and download parameters to the I/O pack or module.
• Download firmware and parameters to the I/O pack or module.
• Build and download the configuration to the controller, wait for I/O pack communication status to change, then scan and
download to the I/O pack.
Note This alarm is not reported to the WorkstationST Alarm Viewer. This alarm is generated by the ToolboxST application,
not by the firmware.
Possible Cause
Solution
• Verify that the I/O pack or module configuration (such as Type, HW Form, Bar Code, position) matches the actual
hardware.
• Perform a build and download the configuration to the controller, wait for pack communication status to change, then
scan and download to the I/O pack or module.
• Manually restart the I/O pack or module.
22
Description ToolboxST application detects a diagnostic status signal (...L3DIAG, ATTN, and/or LINK_OK...) is [ ];
therefore, the status signal is inaccurate, unknown, or indeterminate
Possible Cause
Solution
Note This alarm is not reported to the WorkstationST Alarm Viewer. This alarm is generated by the ToolboxST application,
not by the firmware.
Possible Cause
Note This alarm is not reported to the WorkstationST Alarm Viewer. This alarm is generated by the ToolboxST application,
not by the firmware.
Possible Cause
Solution
• Verify that the I/O pack configuration (such as Type, HW Form, Bar Code, position) matches the actual hardware.
• Build and download the configuration to the controller, wait for pack communication status to change, then scan and
download to the I/O pack or module.
• Manually restart the I/O pack or module.
• Check network cables for proper connection.
• Verify that the switch is functioning correctly.
Note This alarm is not reported to the WorkstationST Alarm Viewer. This alarm is generated by the ToolboxST application,
not by the firmware.
Possible Cause
Solution
259
Description Application Runtime Error - [ ] Frame overruns occurred
Possible Cause Overloaded processor sequencer malfunction (one or more frame overruns occurred)
Solution
For a controller, perform the following to increase the frame idle time:
• From the ToolboxST application, rebuild the system, then download the application and configuration to the I/O module.
• Replace the I/O module.
Possible Cause There is an overloaded processor or a processor malfunction. Frame number skips were detected. The
frame number should incrementally increase during Controlling state.
Solution
For a controller, do the following:
• Reduce the application or increase the EGD period to reduce the processor load.
• Upgrade the controller to one with a faster processor.
• Replace the controller.
For an I/O module, do the following:
• From the ToolboxST application, rebuild the system, then download the application and configuration to the I/O module.
• Replace the I/O module.
279
Description Could not determine platform type from hardware
Possible Cause
• During commissioning/maintenance: Incorrect firmware version or hardware malfunction (firmware could not recognize
host hardware type)
• During normal operation: Hardware failure
Solution
• Verify that all connectors are aligned properly and fully seated.
• Check the firmware version for compatibility with platform. If correct, replace the controller.
Possible Cause
• During commissioning/maintenance: Platform type identified in the application configuration does not match actual
hardware
• During normal operation: Hardware failure
Solution
• Fix the platform type in the ToolboxST application. From the General tab, select General Properties and Platform.
• Rebuild and download the application.
• If problem persists, replace the controller.
282
Description Firmware Load Error - application independent processes failed to initialize
Possible Cause Runtime malfunction. An application-independent firmware process could not be started successfully.
Solution
283
Description Firmware error - Internal process crashed
Solution
Solution Check application loading and reduce the amount of application code or frequency of execution. Build
application and download to all controllers.
294
Description Controller CPU overtemperature, Temp [ ] °C, Threshold [ ] °C
Possible Cause
Solution
• Check the fan (if applicable), the ambient temperature, and for the presence of dust.
• Replace the controller.
300
Description Application Code Load Failure
Possible Cause
During commissioning/maintenance:
Solution
Possible Cause
• Multiple alarm variables changing state too quickly to transmit all transitions
• Excessive alarms in queue (Plant-wide system failures)
Solution
During commissioning/maintenance:
• Reduce the number of alarms that can change state at the same time (filter alarm variables in the application code).
During normal operation:
321
Description Internal Runtime error - Process Alarms not being scanned
Possible Cause Runtime malfunction: alarms not being scanned. Controller may restart on software watchdog timeout
due to processor overload.
Solution
322
Description Configuration Load error - Too many consumed EGD variables for Fault Tolerant EGD
Possible Cause Number of relevant, consumed UDH EGD variables exceeds fault tolerant EGD limitation of 1400 bytes
of data.
Normal UDH EGD operation not affected; however, in the event of UDH EGD failure, some consumed variables may not be
transmitted to redundant controllers over the IONet (if applicable).
• Reduce the amount of relevant, consumed UDH EGD data by removing the appropriate number of variables from EGD
pages.
323
Description EGD Error - Fault Tolerant EGD activated
Possible Cause EGD exchange timeout occurred on requesting controller. Redundant processor (if applicable) is unable
to receive UDH EGD inputs and requested that EGD data be transferred over the IONet.
Solution
• Verify that all controllers on the UDH network are receiving all expected EGD exchanges.
• Verify that all relevant devices are powered on and producing data on the network.
Possible Cause An EGD exchange timeout occurred on the requesting controller. Redundant processor (if applicable)
unable to receive UDH EGD inputs and has requested that EGD data be transferred over the IONet.
Solution
• Check UDH network and verify that all redundant controllers are receiving all expected EGD exchanges.
• Verify that all relevant devices are powered on and producing data on the network.
326
Description Communication lost from R processor
Possible Cause
Solution
• Go online with the R processor. Verify that the processor is in the Controlling state. If not communicating or in
Controlling state, restart the processor.
• Check for disconnected IONet cables or malfunctioning switches.
• Rebuild and download the application.
• Check for a defective Ethernet cable to network switch.
• Check for a defective network switch:
− Place the Ethernet cable into empty port.
− If the problem persists, replace the network switch.
Possible Cause
Solution
• Go online with the S processor. Verify that the processor is in the Controlling state. If not communicating or in
Controlling state, restart the processor.
• Check for disconnected IONet cables or malfunctioning switches.
• Rebuild and download the application.
• Check for a defective Ethernet cable to network switch.
• Check for a defective network switch:
− Place the Ethernet cable into empty port.
− If the problem persists, replace the network switch.
328
Description Communication lost from T processor
Possible Cause
Solution
• Go online with the T processor. Verify that the processor is in the Controlling state. If not communicating or in
Controlling state, restart the processor.
• Check for disconnected IONet cables or malfunctioning switches.
• Rebuild and download the application.
• Check for a bad Ethernet cable to network switch.
• Check for a bad network switch:
− Place the Ethernet cable into empty port.
− If the problem persists, replace the network switch.
• IONet malfunction
• Controllers have different application revisions
• One or more controllers powered down
• Controller overloaded by external command messages
Solution
330
Description Startup sequence failed - Data initialization timeout S processor
• IONet malfunction
• Controllers have different application revisions
• One or more controllers are powered down
• Controller is overloaded by external command messages.
Solution
• IONet malfunction
• Controllers have different application revisions
• One or more controllers are powered down
• Controller is overloaded by external command messages
Solution
332
Description Overtemperature - Controller rebooted and throttled
Possible Cause
Solution
334
Description Application Error – [ ] Frame Skips Detected
Possible Cause
Solution
Possible Cause A modification has occurred in the code segment for one of the processes. This indicates that a hardware
memory failure has occurred.
336
Description Controller is Unlocked
Possible Cause
Solution From ToolboxST application, lock the controllers before running safety functions.
337
Description Output exchange disagreement detected
Possible Cause IONet malfunction or hardware problem. For at least one output, a difference was detected between the
controller outputs. This alarm remains active until the controllers agree on all outputs. A difference for non-Boolean data
generally indicates a deviation of more than 10% from the median value or no IONet EGD configuration is present. For
median values near zero, the variation exceeds integer 2 or real value 0.2.
Solution
• For the Mark VIe runtime, use the ToolboxST disagreement display (View | Disagreements) to determine which variables
are in disagreement.
• In the application, avoid use of global variable 'ControllerID' and avoid the use of sequencing block 'USB_HB'.
• Check IONet (switches, cables); rebuild and download application to all processors. If the problem persists, replace the
processor module.
347
Description Running Application does not match the Branded Application
Note The purpose of branding is to label a verified safety application, and to ensure that it is running.
Solution
Possible Cause
Solution
• Check for evidence of I/O pack restart (diagnostic alarms, error logs).
• Replace Ethernet cable(s).
• Replace the I/O pack.
• Move the I/O pack’s Ethernet cable into an empty IONet switch port. If problem persists, replace the IONet switch.
349
Description Intermittent Communications on IONet2 – Packet Loss Exceeded [ ]%
Possible Cause
Solution
• Check for evidence of I/O pack restart (diagnostic alarms, error logs).
• Replace Ethernet cable(s).
• Replace the I/O pack.
• Move the I/O pack’s Ethernet cable into an empty IONet switch port. If problem persists, replace the IONet switch.
350
Description Intermittent Communications on IONet3 – Packet Loss Exceeded [ ]%
Possible Cause
Solution
• Check for evidence of I/O pack restart (diagnostic alarms, error logs).
• Replace Ethernet cable(s).
• Replace the I/O pack.
• Move the I/O pack’s Ethernet cable into an empty IONet switch port. If problem persists, replace the IONet switch.
Possible Cause A hardware memory failure because application process data was modified (data should not change after
controller goes online)
353
Description Memory Validation Failed – Configuration Shared Memory
Possible Cause A hardware memory failure because system process data was modified (data should not change after
controller goes online)
354
Description Memory Validation Failed – IONet Data Structures
Possible Cause There is a hardware memory failure because IONet process data was modified (data should not change
after the controller goes online)
355
Description State Exchange Voter disagreement detected
Possible Cause
Solution
• Use the ToolboxST disagreement display (View | Disagreements) to determine which variables are in disagreement.
• In the application, avoid use of global variable 'ControllerID' and avoid the use of 'USB_HB' block.
• Check IONet (switches, cables). If problem persists, replace the processor module.
356
Description NANs detected in CALC or NAN_BREAKER block
Possible Cause
Solution
• Check for external devices that may be sending NaNs to the controller.
• If conditions persists, replace the controller.
Possible Cause There is a possible hardware malfunction. Sequencer critical clients were scheduled out of order or were
overrun. This alarm occurs following three successive frames of sequencer critical client out-of-order detections. After five,
the controller is put into the FAILURE control state.
358
Description Internal Runtime error - Sequencer client execution underrun
Possible Cause Possible hardware malfunction. Sequencer critical client underrun detected. Alarm occurs after a
sequencer critical client has been run slower than its nominal rate three times in a row; after five, controller put in FAILURE
control state.
Solution
359
Description Internal Runtime error - Sequencer client execution overrun
Possible Cause Possible hardware malfunction. Sequencer critical client overrun detected. Alarm occurs after a
sequencer critical client has been run faster than its nominal rate three times in a row; after five, controller put in FAILURE
control state.
Solution
360
Description Internal Runtime error - Sequencer frame period out-of-bounds (±15%)
Possible Cause Possible hardware malfunction. Frame period greater than ±15% of nominal. Alarm occurs following
frame period out-of-bounds condition occurring three frames in a row; after five, controller put in FAILURE control state.
Solution
Possible Cause Possible hardware malfunction. Sequencer frame state timeout greater than ±15% of nominal. Alarm
occurs following a sequencer frame state timeout being out-of-bounds three frames in row; after five, controller put in
FAILURE control state.
Solution
362
Description Internal Runtime error - Sequencer frame number skip detected
Possible Cause Possible hardware or IONet malfunction. Frame number skips detected. Frame number should
monotonically increase until rollover; alarm occurs following three skips in a row, after five, controller put in FAILURE
control state.
Solution
363
Description Memory Validation failed - Sequencer data structures
Possible Cause Hardware memory failure. Sequencer process data was modified (data should not change after the
controller is online).
364
Description Too many state voter disagreements detected
Possible Cause
• State exchange voter disagreement overflow. System exceeded the limit of 128 simultaneous disagreements at once.
• Application error
• Hardware problem or IONet malfunction
Solution
• Use the ToolboxST disagreement display (View | Disagreements) to determine which variables are in disagreement.
• In the application, avoid use of global variable 'ControllerID' and avoid the use of 'USB_HB' block.
• Check IONet (switches, cables).
• If problem persists, replace the controller.
Possible Cause
375
Description Controller has entered Quality Control (QC) Mode
Possible Cause The device has received a command to enter factory QC mode.
462
Description Hardware Reconfigured: Reboot by removing and reapplying power
Solution
• After reapplying power, Rebuild and download baseload, firmware and application.
• If the problem persists, replace the controller.
463
Description Internal runtime error - Could not create the Command and Event Log (CEL) file
Possible Cause Internal runtime error. Could not create the CEL file.
Solution
464
Description Ethernet Interface [ ] disabled due to excessive traffic
Possible Cause Network interface has been disabled to protect itself from excessive activity on the network.
Solution
Possible Cause Network interface has been disabled to protect itself from excessive activity on the network
Solution
466
Description Ethernet Interface [ ] disabled due to excessive traffic
Possible Cause Network interface has been disabled to protect itself from excessive activity on the network
Solution
467
Description Ethernet Interface [ ] disabled due to excessive traffic
Possible Cause Network interface has been disabled to protect itself from excessive activity on the network.
Solution
468
Description Ethernet Interface [ ] disabled due to excessive traffic
Possible Cause Network interface has been disabled to protect itself from excessive activity on the network.
Solution
Possible Cause
Solution
470
Description UDH EGD fault detected by the S processor
Possible Cause
Solution
471
Description UDH EGD fault detected by the T processor
Possible Cause
Solution
Possible Cause
• A download from the ToolboxST application to an I/O pack and/or the Auto-Reconfiguration server has failed
• Not all of the I/O packs were selected for download
487
Description Auto-Reconfiguration server failed scanning or downloading an I/O pack
Possible Cause At least one I/O pack is in an unexpected state that the Auto-Reconfiguration server is unable to handle
Solution
488
Description EGD Error - Could not configure consumed exchanges from one or more Producers
Possible Cause
Solution
• Rectify configuration error. Compress all pages and download application to Producer.
• Ensure each Producer is powered on and in the Controlling state.
• Refer to the Network Troubleshooting guide for possible solutions.
• Replace the Consumer and/or Producer hardware.
Possible Cause
Solution
• Add the offending variable to the Producer's EGD configuration, compress the Page and download the application to the
Producer.
• Remove the reference to the offending variable from the Consumer's application code; build and download application to
the Consumer.
• Compress the EGD Page in the Producer where the variable has been added; build and download the application to the
Producer.
490
Description Software watchdog has been disabled
Possible Cause
Solution
491
Description Hardware watchdog has been disabled
Possible Cause
Solution
Possible Cause
Solution
494
Description CDH EGD fault detected by the S processor
Possible Cause
Solution
Possible Cause
Solution
496
Description Failed to incorporate the user-configured frame state timeouts
Possible Cause
Solution
497-498
Description Fan loss detected for controller fan [ ]
Possible Cause
• Hardware malfunction
• Fan power not applied
Solution
• The online download procedure temporarily stores the previous and new application configuration in memory.
• The footprint of the application configuration/code has been enlarged.
• Memory usage can grow over time if there is a memory leak.
Solution
502
Description Syspage inconsistency detected
503
Description Communications timeout with Remote System Log Server
Possible Cause
Solution
Possible Cause When in Secure mode, the controller only permits authorized executables. An unauthorized executable
has been detected and dismissed.
Solution
505
Description R network shared I/O module inputs unhealthy
Possible Cause
Note When using the Shared IONet feature, this alarm is generated if there is a problem with receiving inputs from any
shared I/O module on the R IONet. Refer to Mark Controllers Shared IONet User Guide (GEH-6812).
Solution
Possible Cause
Note When using the Shared IONet feature, this alarm is generated if there is a problem with receiving inputs from any
shared I/O module on the S IONet. Refer to Mark Controllers Shared IONet User Guide (GEH-6812).
Solution
507
Description T network shared I/O module inputs unhealthy
Possible Cause
Note When using the Shared IONet feature, this alarm is generated if there is a problem with receiving inputs from any
shared I/O module on the T IONet. Refer to Mark Controllers Shared IONet User Guide (GEH-6812).
Solution
100 GEH-6788H EX2100e Excitation Control Diagnostic Alarms for Regulator Systems
GE Internal
508
Description Application mismatch between redundant controllers
Possible Cause
• One processor installed new application code while the other processor(s) did not
• Processor was replaced and application code was built with a different version of the ToolboxST application
Solution
509
Description Controller certificate has been revoked
Possible Cause
Solution
• Transition the controller from Secure to Open state then back to Secure to generate a new certificate and private key.
• Contact the Certificate Authority (CA) Administrator.
510
Description Controller certificate will expire within 30 days
Solution
• Transition the controller from Secure to Open state then back to Secure to generate a new certificate and private key.
• Contact the Certificate Authority (CA) Administrator.
Solution
• Transition the controller from Secure to Open state then back to Secure to generate a new certificate and private key.
• Contact the Certificate Authority (CA) Administrator.
512
Description Controller certificate will expire in one day
Solution
• Transition the controller from Secure to Open state then back to Secure to generate a new certificate and private key.
• Contact the Certificate Authority (CA) Administrator.
513
Description Controller certificate has expired; controller is no longer in Secure state
Possible Cause
Solution
102 GEH-6788H EX2100e Excitation Control Diagnostic Alarms for Regulator Systems
GE Internal
514-537
Description Controller To Controller (C2C) Inputs Unhealthy on IONet [ ] from ControlSet [ ]
Possible Cause
Note A control set is a controller in a shared IONet group. There are 24 Controller to Controller (C2C) diagnostic alarms
assigned for eight control sets. Each control set contains three diagnostics for its IONets.
Solution
538
Description Certificate Authority (CA) certificate will expire within 30 days
539
Description Certificate Authority (CA) certificate will expire within seven days
540
Description Certificate Authority (CA) certificate will expire within one day
542
Description Certificate Revocation List (CRL) has expired
Solution
1. Contact the CA Administrator and request/confirm the renewal of the CRL.
2. After the CRL is renewed, from the Mark VIe Device menu select View | Diagnostics | Controller Advanced Diagnostics.
3. Expand the Commands tree, expand the Diagnostics tree, and double-click Get CRL for controller from CA
Server.
4. Confirm the reply, CRL received successfully, which indicates that the Mark VIe to CA Server connection is healthy.
5. Close the Advanced Diagnostics Commands window.
543
Description Total memory consumption has exceeded [ ] percent
Possible Cause
• Memory leak
• Application code is too large
Solution
544
Description Communications error with Certificate Authority Server
Possible Cause
• Certificate Authority (CA) server not in network or not in operation (server is down)
• Incorrect CA server IP address in system configuration
• Network issue (cables/switch) connecting controller to CA server
Solution
104 GEH-6788H EX2100e Excitation Control Diagnostic Alarms for Regulator Systems
GE Internal
545
Description Active PFFA diagnostics detected
Possible Cause At least one configured PFFA module contains an active diagnostic. Since each controller within a
control set monitors the diagnostic conditions of PFFA modules and connected Fieldbus devices, PFFA diagnostics may differ
between the individual controllers.
Solution
• If there are active PFFA diagnostics in the WorkstationST Alarm Viewer, correct those issues.
• If there are no active PFFA diagnostics in the Alarm Viewer, go online specifically to the controller with this 545
diagnostic using the ToolboxST application. From the Component Editor Hardware tab, select the PFFA with active
diagnostics, and correct the identified issues.
546
Description This component is or has been in factory test mode.
Possible Cause The controller or I/O pack has received the command to enter factory test mode.
547
Description Default user password detected
Note It is the user’s responsibility to change the default password to a unique password. If you do not know the default
password, contact the nearest GE Sales or Service Office, or an authorized GE Sales Representative.
To change the controller password, refer to the ToolboxST User Guide for Mark Controls Platform (GEH-6703), the section
Controller Password Change.
Possible Cause
Solution
106 GEH-6788H EX2100e Excitation Control Diagnostic Alarms for Regulator Systems
GE Internal
1000-2024
Description Inputs unhealthy on IO Module [ ], S pack IONet [ ] - Message Timeout
Possible Cause
Solution
1000-2024
Description Inputs unhealthy on IO Module [ ], T pack IONet [ ] - Message Timeout
Possible Cause
Solution
Possible Cause
Solution
1000-2024
Description Inputs unhealthy on IO Module [ ], R pack IONet [ ] - Message Length not valid
Possible Cause Application/configuration does not match in the I/O pack and controller.
Solution
1000-2024
Description Inputs unhealthy on IO Module [ ], S pack IONet [ ] - Message Length not valid
Possible Cause Application/configuration does not match in the I/O pack and controller.
Solution
108 GEH-6788H EX2100e Excitation Control Diagnostic Alarms for Regulator Systems
GE Internal
1000-2024
Description Inputs unhealthy on IO Module [ ], T pack IONet [ ] - Message Length not valid
Possible Cause Application/configuration does not match in the I/O pack and controller.
Solution
1000-2024
Description Inputs unhealthy on IO Module [ ], IONet [ ] - Message Length not valid
Possible Cause Application/configuration does not match in the I/O pack and controller.
Solution
1000-2024
Description Inputs unhealthy on IO Module [ ], R Pack IONet [ ] - Major Signature Mismatch
Possible Cause Application/configuration does not match in the I/O pack and controller.
Solution
Possible Cause Application/configuration does not match in the I/O pack and controller.
Solution
1000-2024
Description Inputs unhealthy on IO Module [ ], T Pack IONet [ ] - Major Signature Mismatch
Possible Cause Application/configuration does not match in the I/O pack and controller.
Solution
1000-2024
Description Inputs unhealthy on IO Module [ ] IONet [ ] - Major Signature Mismatch
Possible Cause Application/configuration does not match in the I/O pack and controller.
Solution
110 GEH-6788H EX2100e Excitation Control Diagnostic Alarms for Regulator Systems
GE Internal
1000-2024
Description Inputs unhealthy on IO Module [ ], R Pack IONet [ ] - Minor Signature Mismatch
Possible Cause Application/configuration does not match in the I/O pack and controller.
Solution
1000-2024
Description Inputs unhealthy on IO Module [ ], S Pack IONet [ ] - Minor Signature Mismatch
Possible Cause Application/configuration does not match in the I/O pack and controller.
Solution
1000-2024
Description Inputs unhealthy on IO Module [ ], T Pack IONet [ ] - Minor Signature Mismatch
Possible Cause Application/configuration does not match in the I/O pack and controller.
Solution
Possible Cause Application/configuration does not match in the I/O pack and controller.
Solution
1000-2024
Description Inputs unhealthy on IO Module [ ], R Pack IONet [ ] - Timestamp Mismatch
Possible Cause Application/configuration does not match in the I/O pack and controller.
Solution
1000-2024
Description Inputs unhealthy on IO Module [ ], S Pack IONet [ ] - Timestamp Mismatch
Possible Cause Application/configuration does not match in the I/O pack and controller.
Solution
112 GEH-6788H EX2100e Excitation Control Diagnostic Alarms for Regulator Systems
GE Internal
1000-2024
Description Inputs unhealthy on IO Module [ ], T Pack IONet [ ] - Timestamp Mismatch
Possible Cause Application/configuration does not match in the I/O pack and controller.
Solution
1000-2024
Description Inputs unhealthy on IO Module [ ] IONet [ ] - Timestamp Mismatch
Possible Cause Application/configuration does not match in the I/O pack and controller.
Solution
1000-2024
Description Inputs unhealthy on IO Module [ ] IONet [ ] - Message Timeout
Possible Cause Application/configuration does not match in the I/O pack and controller.
Solution
Possible Cause Note: If this diagnostic is active, the module needs to be replaced immediately. If it is simplex, the
devices under this PFFA have lost communication. If it is redundant and not replaced, and a controller on the remaining
module's IONet goes down, then control is lost for all devices under the PFFA modules.
Solution
• If the Control/Status communication is working correctly, any additional diagnostics should indicate the cause of the
problem.
• Build and download parameters to the PFFA module and controller.
• Verify Serial cable is attached correctly.
• Verify that the Ethernet cables and network switch are operating correctly.
• Manually restart the PFFA module.
114 GEH-6788H EX2100e Excitation Control Diagnostic Alarms for Regulator Systems
GE Internal
Glossary of Terms
Application code Software that controls the machine or process, specific to the application.
Automatic Voltage Regulator (AVR) AVR is controller software that maintains the generator terminal voltage through
the Field Voltage Regulator.
Auxiliary source A source of 3-phase ac power for the exciter, but not from the generator being controlled.
Bus Upper bar for power transfer, also an electrical path for transmitting and receiving data.
Configure To select specific options, either by setting the location of hardware jumpers or loading software parameters
into memory.
De-excitation The de-excitation circuit produces a conduction path through a discharge resistor or inductor to dissipate the
field current after a unit trip.
Dual Redundancy An operation that uses two sets of control, I/O, and power channels in a redundant configuration for
higher reliability.
EDIS Exciter Power Distribution Module distributes 125 V dc to the power supplies.
EGD Ethernet Global Data, a control network and protocol for the controller. Devices share data through EGD exchanges
(pages).
Ethernet LAN with a 10/100 Mbit collision avoidance/collision detection system used to link one or more computers
together. Basis for TCP/IP and I/O services layers that conform to the IEEE 802.3 standard.
EX2100e Exciter GE static exciter; regulates the generator field current to control the generator output voltage.
Field flashing The supply of initial exciter current during startup, usually from station batteries.
Field ground detector The field ground detector is an active circuit that detects a ground in either the ac or dc sections of
the exciter and field wiring.
Firmware The set of executable software that is stored in memory chips that hold their content without electrical power,
such as EEPROM or Flash.
Gating Controlling the conduction of the power IGBTs or SCRs with an input pulse train (or a voltage).
HMI Human-machine Interface, usually a computer running Windows and CIMPLICITY HMI software.
I/O Input/output interfaces that allow the flow of data into and out of a device.
Line filter Filter networks across the 3-phase input lines to the exciter to minimize the voltage spikes that result from the
abrupt decay of current during SCR commutations.
Power Conversion Module (PCM) The PCM or Bridge consists of six thyristors connected in a 3-phase bridge, with
associated protection and control devices, to generate the dc field voltage.
Power Distribution Module (EDIS) The PDM distributes 125 V dc to the power supplies for the controllers and I/O
termination boards.
Permanent Magnet Generator (PMG) source An application in which the exciter receives ac power for the field from
a PMG mounted on the shaft of the generator. The PMG output frequency is typically 420 Hz or higher.
Power Potential Transformer (PPT) A PPT is attached to the generator terminals or an auxiliary bus to provide 3-phase
power for the exciter; referred to as a potential source.
Power System Stabilizer (PSS) PSS software produces a damping torque on the generator to reduce generator
oscillations.
Product code (runtime) Software stored in the controller's memory that converts application code (pcode) to executable
code.
PRV resistors These resistors reduce stress on the SCRs by balancing voltages on the SCRs during pole slip events.
Redundant A system containing of duplicated components (boards or modules), which can transfer functionality from a
failed component to one of the duplicate components without loss of the entire system's functionality.
Runtime errors Controller problems indicated on the front panel by coded flashing LEDs, and also in the Log View of the
ToolboxST application.
Simplex System with only one set of control and I/O modules. Contrast with redundant control systems.
TCP/IP Communications protocols developed to inter-network dissimilar systems. It is a de facto UNIX standard, but is
supported on almost all systems. TCP controls data transfer and IP provides the routing for functions.
TMR Triple Modular Redundancy. An operation that uses three sets of control and I/O (channels M1, M2, and C) and votes
the results.
ToolboxST application A Windows-based software package used to configure the EX2100e and Mark VIe turbine
controller.
Touchscreen Diagnostic Display Interface also referred as keypad provides exciter status icons and displays fault
information. It can also be used to run the exciter, reset the exciter, display data, and provide other control functions.
Warm backup (WBU) Two bridges are connected to the field but only one is actively producing power. The other bridge
does not receive gating pulses until it is required to take over from the active bridge.