ELECTRIC POWER
- REGULATORY
AUTHORTY
2018-19
Performance
Evaluation Report
NTDC & K-Electric
Contents
0 EXECUTIVE SUMMARY ................................................................................................................... ES-1
1 INTRODUCTION ....................................................................................................................................... 1
1.1 REPORTING REQUIREMENT .................................................................................................................... 1
1.2 COMPLIANCE ......................................................................................................................................... 1
1.2.1 Rule 7 of PSTR 2005 (System Voltage) ....................................................................................... 1
1.2.2 Rule 8 of PSTR 2005 (System Frequency) .................................................................................. 1
2 BRIEF ABOUT NTDC ................................................................................................................................ 2
2.1 LICENCE................................................................................................................................................ 2
2.2 TRANSMISSION NETWORK .................................................................................................................... 2
2.3 PERFORMANCE AT A GLANCE ................................................................................................................ 3
3 ANALYSIS OF NTDC’S ANNUAL PERFORMANCE REPORT (APR) .............................................. 4
3.1 SYSTEM RELIABILITY ............................................................................................................................ 4
3.1.1 System Duration of Interruption ................................................................................................... 4
3.1.2 System Frequency of Interruption ................................................................................................ 4
3.2 SYSTEM SECURITY ................................................................................................................................. 5
3.2.1 System Collapse/Power Plants Outages ....................................................................................... 6
3.3 QUALITY OF SUPPLY .............................................................................................................................. 7
3.3.1 System Voltage............................................................................................................................. 7
3.3.2 System Frequency ...................................................................................................................... 12
4 BRIEF ABOUT K-ELECTRIC ................................................................................................................ 14
4.1 LICENCE.............................................................................................................................................. 14
4.2 TRANSMISSION NETWORK .................................................................................................................. 14
4.3 PERFORMANCE AT A GLANCE .............................................................................................................. 15
5 ANALYSIS OF KE’S ANNUAL PERFORMANCE REPORT (APR) ................................................. 16
5.1 SYSTEM RELIABILITY .......................................................................................................................... 16
5.1.1 System Duration of Interruption ................................................................................................. 16
5.1.2 System Frequency of Interruption .............................................................................................. 16
5.2 SYSTEM SECURITY ............................................................................................................................... 17
5.3 QUALITY OF SUPPLY ............................................................................................................................ 17
5.3.1 System Voltage........................................................................................................................... 17
5.3.2 System Frequency ...................................................................................................................... 18
APPENDICES..................................................................................................................................................... 19
i
List of Figures
NTDC
Figure 2.1: NTDC transmission system .................................................................................................................. 2
Figure 3.1: Outages hours & No. of interconnection points ................................................................................... 4
Figure 3.2: System duration of Interruption (Hrs/Point)......................................................................................... 4
Figure 3.3: Number of outages & No. of 132kV outgoing circuits ........................................................................ 4
Figure 3.4: System frequency of Interruption (Nos./circuit) .................................................................................. 4
Figure 3.5: Reported ENS...................................................................................................................................... 5
Figure 3.6: Loss of supply incidents & duration per incident ................................................................................. 5
Figure 3.7: Total number of loss of supply incidents with average ........................................................................ 5
Figure 3.8: Region wise loss of supply incidents ................................................................................................... 5
Figure 3.9: Seasonal trend of loss of supply incidents ............................................................................................ 6
Figure 3.10: Number of voltage violations (NTDC) .............................................................................................. 7
Figure 3.11: Number of voltage violations (NTDC Region wise) .......................................................................... 8
Figure 3.12: Number of voltage violations (NTDC Islamabd Region)................................................................... 8
Figure 3.13: Number of voltage violations (NTDC Lahore Region) ...................................................................... 9
Figure 3.14: Number of voltage violations (NTDC Multan Region).................................................................... 10
Figure 3.15: Number of voltage violations (NTDC Hyderabad Region) .............................................................. 11
Figure 3.16: Highest voltage recorded at 500 kV grid stations under Normal condition ..................................... 11
Figure 3.17: Highest voltage recorded at 220 kV grid stations under Normal condition ..................................... 11
Figure 3.18: Lowest voltage recorded at 220 kV grid stations under Normal condition ...................................... 12
Figure 3.19: Highest frequency recorded (Hz) ..................................................................................................... 13
Figure 3.20: Lowest frequency recorded (Hz) ...................................................................................................... 13
K-Electric
Figure 4.1: KE transmission system ..................................................................................................................... 14
Figure 5.1: Outages hours & No. of interconnection points ................................................................................. 16
Figure 5.2: System duration of Interruption (Hrs/Point)....................................................................................... 16
Figure 5.3: Number of outages & No. of 132kV outgoing circuits ...................................................................... 16
Figure 5.4: System frequency of Interruption (Nos./circuit) ................................................................................ 16
Figure 5.5: Reported ENS.................................................................................................................................... 17
Figure 5.6: Loss of supply incidents & duration per incident ............................................................................... 17
Figure 5.7: Total number of loss of supply incidents with average ...................................................................... 17
Figure 5.8: Number of voltage violations (NTDC) .............................................................................................. 17
Figure 5.9: Highest frequency recorded (Hz) ....................................................................................................... 18
ii
List of Tables
NTDC
Table 3.1: Loss of supply incidents, average ENS, duration & financial impact per incident................................ 5
Table 3.2: System collapses/major disturbances .................................................................................................... 6
Table 3.3: Number of voltage violations (NTDC Region wise) ............................................................................. 7
Table 3.4: Number of voltage violations (NTDC Islamabd Region) ...................................................................... 8
Table 3.5: Number of voltage violations (NTDC Lahore Region) ......................................................................... 9
Table 3.6: Number of voltage violations (NTDC Multan Region) ....................................................................... 10
Table 3.7: Number of voltage violations (NTDC Hyderabad Region) ................................................................. 10
Table 3.8: System frequency stats (2018-19) ....................................................................................................... 12
Table 3.9: System frequency details with comparison ......................................................................................... 13
K-Electric
Table 5.1: Loss of supply incidents, average ENS, duration & financial impact per incident .............................. 17
Table 5.2: System frequency stats (2018-19) ....................................................................................................... 18
iii
EXECUTIVE
SUMMARY
0 EXECUTIVE SUMMARY
National Electric Power Regulatory Authority (NEPRA) is the sole regulator of power sector
in Pakistan. Provision of safe, reliable, efficient and affordable electric power to the
electricity consumers is an integral part of NEPRA’s regulatory regime.
In order to encourage safe, efficient and reliable transmission service, NEPRA has framed the
Performance Standards (Transmission) Rules 2005 (PSTR)1. Under PSTR, each transmission
licensee is required to submit to NEPRA an Annual Performance Report (APR) in a manner
as prescribed in PSTR. These performance reports are analyzed by NEPRA in light of the
performance parameters such as System Duration of Interruption, System Frequency of
Interruption, Energy Not Served (ENS), Loss of Supply Incidents and its financial impact,
System Disturbances (if any), Voltage and Frequency Violation Limits prescribed under the
PSTR, and Highest and Lowest Voltage Recorded at National Transmission & Despatch
Company (NTDC) 500 kV and 220 kV grid stations under Normal system conditions.
The APRs for the year 2018-19, submitted by NTDC and K-Electric were reviewed on the
basis of aforementioned parameters. Highlights of the analysis/findings are given below:-
PERFORMANCE OF NTDC
System Duration of Interruption: System duration of interruption is a reliability indicator
that measures the average outage duration that an interconnection point observes in a year.
The interruption was witnessed around 0.32 hours (19 minutes) on average that indicates a
decrease of 47% as compared to preceding year’s average of 0.6 hours (36 minutes).
Energy Not Served (ENS): In order to gauge system security, the estimates of total ENS
during the year as reported by the licensee has been analyzed. The total ENS as reported by
NTDC in 2018-19 is 114 million kWh that is 76% lower over the previous year i.e. 469
million kWh. Based on the average energy sale rate of DISCOs 2 , the financial impact
amounts to around Rs. 638 million.
Loss of Supply Incidents: NTDC reported 66 loss of supply incidents during the year 2018-
19 which translates into total duration of 160 hours. The average ENS per incident along with
duration and subsequent financial impact has been assessed in the following table.
1
Under section 46 of the Regulation of Generation, Transmission and Distribution of Electric Power Act 1997 (XL of 1997), read with
section 7 (2) (c) and section 34 thereof, the National Electric Power Regulatory Authority, with the approval of Federal Government, has
made the Performance Standards (Transmission) Rules (PSTR) notified vide S.R.O 1138(I)/2005 dated 15 th November, 2005.
2
Monthly adjustment in DISCOs approved tariff on account of variation in fuel charges 2018-19:- Average energy sale rate = Rs. 5.6/kWh.
ES-1
Description / Unit / Year Unit 2014-15 2015-16 2016-17 2017-18 2018-19
Loss of Supply Incidents Nos. 125 87 165 142 66
Average ENS per Incident Million kWh 4.264 1.644 0.454 3.3 1.7
Average Duration per Incident Hrs : Min 01 : 12 02 : 24 03 : 07 02 : 06 02 : 24
Financial Impact per Incident Rs. (Million) 42.6 8.322 2.5 17.5 9.7
ES-2
Voltage Variations Violating Prescribed Limits: NEPRA has prescribed limits for voltage
variations in the Rules. During year 2018-19, number of voltage violations for NTDC
remained 144,782 that indicate 3.3% decrease as compared to 149,754 violations in
preceding year.
Highest and Lowest Voltage Recorded Under Normal System Condition: The highest
voltage recorded due to voltage variations at 500 kV voltage class was 565 kV for time
duration of 30 minutes, recorded at Rahim Yar Khan. The voltage of 565 kV shows
approximately 7.6% variation with respect to allowed limit (±5% = 525/475 kV). Detail is
given in section 3.3.1 (figure 3.16).
Similarly, at 220 kV level, highest voltage was 280 kV recorded at Quetta for time duration
of 60 minutes. Voltage of 280 kV indicates approximately 21.2% variation with respect to
allowed limit (±5% = 231/209 kV). Detail of highest voltage incidents is given in section
3.3.1 (figure 3.17). Some of the grid stations with highest voltage incidents are given below;
Highest Voltage Duration of Variation
S. No. Name of Grid Station Recorded Variation w.r.t Allowed Limit
(kV) (min) (%)
1 220 kV Quetta 280 60 21.2%
2 220 kV Khuzdar 250 35 8.2%
3 220 kV Kassowal 250 60 8.2%
4 220 kV Jhimpir 247 60 6.9%
5 220 kV T. M. Khan Road 247 60 6.9%
6 220 kV Sibbi 246 60 6.5%
7 220 kV D. I. Khan 246 60 6.5%
8 220 kV Daud Khel 244 60 5.6%
On the lower side, the voltage remained as low as 135 kV that indicates 35.4% variation with
respect to allowed limit (±5% = 231/209 kV) which is quite alarming and may affect the
consumer end voltages and consequently equipment damage. Some of the grid stations with
lowest voltage incidents are given hereunder:-
Highest Voltage Duration of Variation
S. No. Name of Grid Station Recorded Variation w.r.t Allowed Limit
(kV) (min) (%)
1 220 kV Vehari 135 90 35.4%
2 220 kV Loralai 143 180 31.6%
3 220 kV Shahibagh 170 60 14.8%
4 220 kV Ghazi Road 170 60 13.9%
5 220 kV Quetta 178 60 12.4%
6 220 kV Khuzdar 180 30 13.9%
7 220 kV Kala Shah Kaku 180 120 13.9%
8 220 kV Ravi 180 90 13.9%
9 220 kV WAPDA Town 180 90 13.9%
10 220 kV Gakkhar 181 60 13.4%
11 220 kV Shalamar 183 90 12.4%
12 220 kV Bund Road 184 90 12%
13 220 kV New Kot Lakhpat 185 150 11.5%
14 220 kV Jhimpir 190 60 9.1%
ES-3
In order to diagnose the root cause of low voltage, monitoring activities are being initiated by
NEPRA on periodic basis to avoid any undesirable condition on the system and ensure
continuity and stability of supply to the electricity consumers of Pakistan.
Frequency Variations Violating Prescribed Limits: NEPRA has prescribed limits for
frequency variations under the Rules. During the reported period, NTDC system frequency
varied from 49.44 Hertz to 50.79 Hertz and has violated the prescribed limits 25 times. Detail
is given below:-
ES-4
PERFORMANCE OF K-ELECTRIC
System Duration of Interruption: System duration of interruption was witnessed on
average around 0.61 Hours (37 minutes) which shows an increase of 27% as compared to
preceding year’s average of 0.48 Hours (29 minutes)
Energy Not Served (ENS): In order to gauge system security, the estimates of total ENS
during the year as reported by the licensee has been analyzed. The total ENS as reported by
KE is 2.678 million kWh that is 3.6% greater than the previous year i.e. 2.585 million kWh.
Based on the average energy sale rate3 of KE, the financial impact amounts to around Rs.
34.3 million.
Loss of Supply Incidents: KE has reported 13 incidents of loss of supply during the year
2018-19 which translates into total duration of 4.27 hours. The average ENS per incident
along with duration and subsequent financial impact has been assessed. The detail is given
below:-
Voltage Variations Violating Prescribed Limits: KE’s voltage violations have decreased
by 25% in 2018-19 as compared to preceding year. Further, no violation has occurred at 220
kV level both under normal and N-1 conditions and at 132 kV level, limits were violated
under N-1 condition only.
Conclusion: KE’s performance has been declined with respect to preceding year as the
reliability and security indicators have shown a downturn that needs to be improved to ensure
the continuity and stability of supply to the electricity consumers of Karachi. Voltage and
frequency violations data needs verification as very few violations were reported by KE.
3
KE’s Average energy sale rate = Rs. 12.8172/kWh, subject to adjustment & indexation by NEPRA.
ES-5
INTRODUCTION
Performance Evaluation Report for the year 2018-19
1 Introduction
This Performance Evaluation Report (PER) provides information on the performance of the
transmission licensees i.e. National Transmission & Despatch Company (NTDC) and K-
Electric (KE) as per National Electric Power Regulatory Authority (NEPRA) Performance
Standards (Transmission) Rules (PSTR) 2005 4 , based on their reported data for the year
2018-19.
The document, moreover, takes account of system reliability, security of supply and quality
of supply of the transmission network of the licensees during the reported period.
Comparison over the last five years has also been provided in this regard.
1.2 Compliance
In pursuance of Rule 6 of PSTR 2005, the quality of supply shall be measured with reference
to system voltage and system frequency.
4
In exercise of the powers conferred by section 46 of the Regulation of Generation, Transmission and Distribution of Electric Power Act,
1997 (XL of 1997), read with clause (c) of sub section (2) of section 7 and section 34 thereof, the National Electric Power Regulatory
Authority, with the approval of Federal Government, has made the Performance Standards (Transmission) Rules (PSTR) notified vide
S.R.O. 1138(I)/ 2005 dated 15th November, 2005.
Available at: http://www.nepra.org.pk/Legislation/Rules/Performance%20Standards%20(Transmission)%20Rules%202005.pdf
Page 1|18
NTDC & K-Electric
NTDC
Performance Evaluation Report for the year 2018-19
NTDC commenced its commercial operation on 1st of March 1999 and was organized to take
over the properties, assets, rights, obligations and liabilities of transmission network all over
Pakistan previously owned by Pakistan Water and Power Development Authority (WAPDA),
except the area served by K-Electric.
2.1 Licence
NTDC was granted Transmission Licence No. TL/01/2002 on 31st December 2002 by
NEPRA to engage exclusively in the transmission business for a term of thirty (30) years,
pursuant to Section 17 of the Regulation of Generation, Transmission and Distribution of
Electric Power Act, 1997.
Page 2|18
NTDC & K-Electric
Performance Evaluation Report for the year 2018-19
An overview of the performance of NTDC is given hereunder in light of the reported data;
System Reliability
Frequency
1. Number of times frequency remained 4. Highest frequency recorded = 50.66 Hz
outside the limits in a year = 25 5. Lowest frequency recorded = 49.44 Hz
2. Time duration the frequency remained
outside the limits in a year = 2 Hrs & 59 Allowable limits: 49.5 Hz – 50.5 Hz
min.
3. %age time of the year the frequency
remained outside the limits = 0.034%
time of the year.
Page 3|18
NTDC & K-Electric
Performance Evaluation Report for the year 2018-19
Page 4|18
NTDC & K-Electric
Performance Evaluation Report for the year 2018-19
Table 3.1: Loss of supply incidents, average ENS, duration & financial impact per incident
55 58
50 51
38 38 40
33 36 35
30 29 26 28
26 25 24
19 20
13
7 10 4 7
5
Monthly adjustment in DISCOs approved tariff on account of variation in fuel charges 2018-19:- Average energy sale rate = Rs. 5.6/kWh
Page 5|18
NTDC & K-Electric
Performance Evaluation Report for the year 2018-19
20
9 16
3
18
13 4
6 31 4
14 18 4 2 14
6 3 4 11
30 6
9 10 19 8 7
19 1 15 12
7 13 4 15
9 7 10
9 9 4 4
23 4 3 4
15 3 7 9 12 17 3 12 13
5 5 10 7
0 6
July Aug Sep Oct Nov Dec Jan Feb Mar Apr May June
S. Loading at Duration of
Date Interruption time Interruption Remarks
No.
9 Hrs & 36
1 01-Aug-2018 750 MW 220 kV Bund Road grid station affected.
min
220 kV Kala Shah Kaku, Ghazi Road, Sialkot,
2 04-Aug-2018 2000 MW 1 Hr Gakkhar, Gujrat & Mangla grid stations
affected.
2 Hrs & 30 500 kV Jamshoro & NKI and 220 kV Hala
3 17-Aug-2018 1080 MW
min Road & T. M. Khan grid stations affected.
220 kV Kala Shah Kaku, Ghazi Road,
4 05-Sep-2018 1862 MW 42 min Shalamar, Ravi, Gujrat, Gakkhar & Sialkot
grid stations affected.
5 04-Oct-2018 440 MW 1 Hr K-Electric isolated from NTDC network
6 20-Oct-2018 1100 MW 40 min Partial collapse in south from Dadu-HUBCO
1 Hr & 30
7 12-Nov-2018 916 MW K-Electric isolated from NTDC network
min
All 220 kV transmission lines emanating from
1 Hr & 18
8 22-Nov-2018 500 MW 220 kV Quetta, Khuzdar & Sibbi grid stations
min
tripped due to heavy rain.
Balloki & Guddu 747 power plants and 220
9 02-Jan-2019 1800 MW 16 Hrs kV Ghazi Road & Shalimar grid stations
affected
500 kV Circuits affected;
Balloki – New Lahore circuit # 1 & 2, Guddu
– Guddu 747 – Rahim Yar Khan circuit.
10 03-Jan-2019 1927 MW 24 Hrs
220 kV Circuits affected;
Ghazi Road – Shalimar, Ghazi Road – KSK,
Muzaffargarh – Bahawalpur circuit # 1 & 2,
Page 6|18
NTDC & K-Electric
Performance Evaluation Report for the year 2018-19
S. Loading at Duration of
Date Interruption time Interruption Remarks
No.
Multan circuit # 1 & 2, Okara – Sarfaraznagar
10 03-Jan-2019 1927 MW 24 Hrs circuit # 1 & 2, Sarfaraznagar – NKLP,
Sarfaraznagar – New Lahore.
11 23-Jan-2019 360 MW 5 Hrs System splitting at 500 kV Shikarpur
14 Hrs &
12 25-Jan-2019 2590 MW Shikarpur – HUBCO – K-Electric Collapse
20 min
13 26-Feb-2018 650 MW 20 min Tripping of Chashnupp Complex
It has been observed that system disturbances have occurred 13 times including a partial
system collapse and isolation of K-Electric from NTDC in the year 2018-19 which I
undesirable. NTDC shall follow the day-to-day and long term principles, standards,
procedures and guidelines for Planning, Operation, Dispatch and Connection purposes for
normal and abnormal transmission system conditions to avoid loss of supply to the
consumers and hence financial loss to the national exchequer.
Page 7|18
NTDC & K-Electric
Performance Evaluation Report for the year 2018-19
150,000
100,000
50,000
0
Islamabad
Lahore
Multan
Hyderabad
Total (Normal)
Islamabad
Lahore
Multan
Hyderabad
Total (N-1)
The grid station wise breakup for each region is given hereunder:
Table 3.4: Number of voltage violations NTDC Islamabad Region
S. No. Grid Station 2014-15 2015-16 2016-17 2017-18 2018-19
1 500 kV Rawat 9,376 5,190 6,611 6,202 5,165
2 500 kV Peshawar 2,538 3,613 4,239 2,212 772
3 220 kV Bannu 3,413 2,733 3,394 1,256 1,195
4 220 kV Burhan 422 1,754 1,184 219 265
5 220 kV Daudkhel 8,714 9,456 5,631 1,421 906
6 220 kV ISPR 9 36 269 773 470
7 220 kV Mardan 4,653 2,220 4,008 11,359 13,513
8 220 kV Shahibagh 1,991 943 806 2,703 2,816
9 220 kV University 963 1,210 1,634 2,832 2,812
10 220 kV Mansehra 04-Apr-2018* 1 124
11 220 kV Nowshera * NA
12 220 kV Chakdara * 317
13 220 kV D. I. Khan * 1,830
14 Total 32,079 27,155 27,776 28,978 30,185
* Date commissioned/energized
Figure 3.12: Number of voltage violations (NTDC Islamabad Region)
Page 8|18
NTDC & K-Electric
Performance Evaluation Report for the year 2018-19
49,500
33,000
16,500
Page 9|18
NTDC & K-Electric
Performance Evaluation Report for the year 2018-19
18,000
15,000
12,000
9,000
6,000
3,000
0
P a g e 10 | 1 8
NTDC & K-Electric
Performance Evaluation Report for the year 2018-19
48,000
36,000
24,000
12,000
The detailed circuit wise analysis for each region is given at appendix 1 through appendix 4.
Figure 3.16: Highest voltage recorded at 500 kV grid stations under Normal condition
2018-19 Limit
565 561
545 544 543 542
542 542
538 535 535 535 533
525
Figure 3.17: Highest voltage recorded at 220 kV grid stations under Normal condition
231
P a g e 11 | 1 8
NTDC & K-Electric
Performance Evaluation Report for the year 2018-19
Figure 3.18: Lowest voltage recorded at 220 kV grid stations under Normal condition
209
206 207
198 198 199 200 204
189 190 190 193 195 196 197
183 184 185 185
178 180 180 180 180 181
170 170 170 170
143
135
2018-19 Limit
Other details assessed pertaining to system frequency with a comparison to the preceding
years is given in the following table;
P a g e 12 | 1 8
NTDC & K-Electric
Performance Evaluation Report for the year 2018-19
The following figures show the NTDC’s month wise highest & lowest frequency for the year
2018-19. The dotted red line shows the prescribed limits (upper 50.5 Hz & lower 49.5 Hz) as
per PSTR 2005. Historical data as reported by NTDC is given at appendix 6.
Figure 3.19: Highest frequency recorded (Hz) Figure 3.20: Lowest frequency recorded (Hz)
50.79
50.67 50.51 50.51 50.51 50.51 50.51 50.51 50.52 50.51
50.66 50.68
50.64
50.6 50.58
50.59
50.54
50.5 49.5 49.44
P a g e 13 | 1 8
NTDC & K-Electric
K-Electric
Performance Evaluation Report for the year 2018-19
4.1 Licence
KE was granted Transmission Licence No. TL/01/2002 on 31st December 2002 by NEPRA to
engage exclusively in the transmission business for a term of thirty (30) years, pursuant to
Section 17 of the Regulation of Generation, Transmission and Distribution of Electric Power
Act, 1997.
P a g e 14 | 1 8
NTDC & K-Electric
Performance Evaluation Report for the year 2018-19
System Reliability
Frequency
1. Number of times frequency remained 4. Maximum continuous period of deviation =
outside the limits in a year = 2 7 min
2. Time duration the frequency remained 5. Highest frequency recorded = 51.5 Hz
outside the limits in a year = 13 min
6. No violation at lower end.
3. %age time of the year the frequency
remained outside the limits = 0.003% Allowable limits: 49.5 Hz – 50.5 Hz
time of the year.
P a g e 15 | 1 8
NTDC & K-Electric
Performance Evaluation Report for the year 2018-19
The average number of interruptions Figure 5.4: System frequency of interruption (Nos./Circuit)
per circuit during the reported period
remained 0.39 indicating 62.5% System Frequency of Interruption (Nos./Circuit)
increase in comparison to the preceding
year’s 0.24 as shown in figure 5.4. 0.39
0.32 0.32 0.3
0.24
P a g e 16 | 1 8
NTDC & K-Electric
Performance Evaluation Report for the year 2018-19
0 0
2014-15 2015-16 2016-17 2017-18 2018-19 2014-15 2015-16 2016-17 2017-18 2018-19
Table 5.1: Loss of supply incidents, average ENS, duration & financial impact per incident
13
10 10 10 10
8
6
KE’s Average energy sale rate = Rs. 12.8172/kWh, subject to adjustment & indexation by NEPRA.
P a g e 17 | 1 8
NTDC & K-Electric
Performance Evaluation Report for the year 2018-19
Figure 5.8 shows historical trend over the five years period. Detailed circuit wise analysis is
given at appendix 5.
The upper and lower limits as prescribed in PSTR are 50.5 Hz & 49.5 Hz respectively. The
figure below shows KE’s month wise highest frequency for the year 2018-19. The dotted red
line shows the prescribed limit (upper 50.5 Hz). The lower limit has not been violated as
reported by KE. Historical data as reported by KE is given at appendix 6.
Figure 5.9: Highest frequency recorded (Hz)
KE Limit
51.6 51.5
51.4
51.2
51 50.8
50.8
50.5
50.6
50.4
50.2
P a g e 18 | 1 8
NTDC & K-Electric
Performance Evaluation Report for the year 2018-19
APPENDIX 1
Page 19
NTDC & K-Electric
Islamabad Region
1 of 13
Total No. of Variations (Normal) 9,376 5,190 6,611 6,202 5,165 Highest Voltage Under Normal Condition @500kV level
Total No. of Variations (N-1) ‒ ‒ ‒ ‒ −
Total of Normal & N-1 9,376 5,190 6,611 6,202 5,165 Highest Voltage Under Normal Condition @220kV level
Performance Evaluation Report for the year 2018-19 500 kV Grid Station Rawat
Islamabad Region
2 of 13
Total No. of Variations (Normal) 2,346 3,613 4,239 2,212 772 Highest Voltage Under Normal Condition @500kV level Lowest Voltage Under Normal Condition @220kV level
Total No. of Variations (N-1) 192 ‒ ‒ − −
Total of Normal & N-1 2,538 3,613 4,239 2,212 772 Highest Voltage Under Normal Condition @220kV level
Performance Evaluation Report for the year 2018-19 500 kV Grid Station Sheikh Muhammadi Peshawar
Islamabad Region
3 of 13
Total No. of Variations (Normal) 2,424 2,652 3,394 1,256 1,195 Highest Voltage Under Normal Condition Lowest Voltage Under Normal Condition
Total No. of Variations (N-1) 989 81 − − −
Total of Normal & N-1 3,413 2,733 3,394 1,256 1,195
Performance Evaluation Report for the year 2018-19 220 kV Grid Station Bannu
Islamabad Region
4 of 13
Normal 220 kV 211 877 594 168 135 237 60 238 60 241 240 232 60 241 60 − − − − 203 60 200 120 206 60
Burhan - Tarbela
N-1 Ckt I, II & III − − − − − − − − − − − − − − − − − − − − − − − − −
Total No. of Variations (Normal) 422 1,754 1,184 219 265 Highest Voltage Under Normal Condition Lowest Voltage Under Normal Condition
Total No. of Variations (N-1) – − − − −
Total of Normal & N-1 422 1,754 1,184 219 265
Performance Evaluation Report for the year 2018-19 220 kV Grid Station Burhan
Islamabad Region
5 of 13
Total No. of Variations (Normal) 8,549 9,297 5,631 1,421 906 Highest Voltage Under Normal Condition Lowest Voltage Under Normal Condition
Total No. of Variations (N-1) 165 159 − − −
Total of Normal & N-1 8,714 9,456 5,631 1,421 906
Performance Evaluation Report for the year 2018-19 220 kV Grid Station Daudkhel
Islamabad Region
6 of 13
Total No. of Variations (Normal) 9 36 269 773 470 Highest Voltage Under Normal Condition Lowest Voltage Under Normal Condition
Total No. of Variations (N-1) – – − − −
Total of Normal & N-1 9 36 269 773 470
Performance Evaluation Report for the year 2018-19 220 kV Grid Station ISPR (Sangjani)
Islamabad Region
7 of 13
Total No. of Variations (Normal) 4,234 2,220 4,008 11,359 13,513 Lowest Voltage Under Normal Condition
Total No. of Variations (N-1) 419 − − − −
Total of Normal & N-1 4,653 2,220 4,008 11,359 13,513
Performance Evaluation Report for the year 2018-19 220 kV Grid Station Mardan
Islamabad Region
8 of 13
Normal 220 kV
Energized on 19-Apr-2019 Nil Energized on 19-Apr-2019 Nil Energized on 19-Apr-2019 Nil
N-1 Nowshera - Shahibagh
Normal 220 kV
Nowshera - Barotha Energized on 19-Apr-2019 Nil Energized on 19-Apr-2019 Nil Energized on 19-Apr-2019 Nil
N-1 1&2
Normal 220 kV
Energized on 19-Apr-2019 Nil Energized on 19-Apr-2019 Nil Energized on 19-Apr-2019 Nil
N-1 Nowshera - S. M Peshawar
Performance Evaluation Report for the year 2018-19 220 kV Grid Station Nowshera
Islamabad Region
9 of 13
Total No. of Variations (Normal) 1,843 943 806 2,703 2,816 Lowest Voltage Under Normal Condition
Total No. of Variations (N-1) 148 ‒ − − −
Total of Normal & N-1 1,991 943 806 2,703 2,816
Performance Evaluation Report for the year 2018-19 220 kV Grid Station Shahibagh Peshawar
Islamabad Region
10 of 13
Total No. of Variations (Normal) 962 1,210 1,634 2,832 2,812 Highest Voltage Under Normal Condition
Total No. of Variations (N-1) 1 − − − −
Total of Normal & N-1 963 1,210 1,634 2,832 2,812
Performance Evaluation Report for the year 2018-19 220 kV Grid Station University
Islamabad Region
11 of 13
Total No. of Variations (Normal) 2 124 Highest Voltage Under Normal Condition
Total No. of Variations (N-1) Energized May 2018 − −
Total of Normal & N-1 2 124
Performance Evaluation Report for the year 2018-19 220 kV Grid Station Mansehra
Islamabad Region
12 of 13
Total No. of Variations (Normal) 317 Lowest Voltage Under Normal Condition
Total No. of Variations (N-1) Energized 16-Sep-2018 −
Total of Normal & N-1 317
Performance Evaluation Report for the year 2018-19 220 kV Grid Station Chakdara
Islamabad Region
13 of 13
Total No. of Variations (Normal) 1,830 Highest Voltage Under Normal Condition
Total No. of Variations (N-1) Energized 18-Feb-2019 −
Total of Normal & N-1 1,830
Performance Evaluation Report for the year 2018-19 220 kV Grid Station D. I. Khan
Performance Evaluation Report for the year 2018-19
APPENDIX 2
Normal 220 kV
NP NA NP NA NP NA
N-1 Gatti - Yousafwala 2
Normal 220 kV
NP NA NP NA NP NA
N-1 Gatti - Ludewala 1
Normal 220 kV
NP NA NP NA NP NA
N-1 Gatti - Ludewala 2
Total No. of Variations (Normal) 1,189 1,285 3,223 3,155 796 Highest Voltage Under Normal Condition @500kV level
Total No. of Variations (N-1) – – ‒ ‒ ‒
Total of Normal & N-1 1,189 1,285 3,223 3,155 796 Highest Voltage Under Normal Condition @220kV level
Performance Evaluation Report for the year 2018-19 500 kV Grid Station Gatti
Lahore Region
2 of 21
Total No. of Variations (Normal) 318 710 738 Highest Voltage Under Normal Condition @500kV level Lowest Voltage Under Normal Condition @500kV level
Total No. of Variations (N-1) Not applicable ‒ ‒ ‒
Total of Normal & N-1 318 710 738 Highest Voltage Under Normal Condition @220kV level Lowest Voltage Under Normal Condition @220kV level
Performance Evaluation Report for the year 2017-18 500 kV Grid Station Nokhar
Lahore Region
3 of 21
Name of Highest Voltage Recorded (kV) / Time (Min) Lowest Voltage Recorded (kV) / Time (Min)
Condition Transmission Circuit(s)
violating the voltage criteria 2014-15 2015-16 2016-17 2017-18 2018-19 2014-15 2015-16 2016-17 2017-18 2018-19
2014-15 2015-16 2016-17 2017-18 2018-19
Voltage Time Voltage Time Voltage Time Voltage Time Voltage Time Voltage Time Voltage Time Voltage Time Voltage Time Voltage Time
Normal 500 kV 129 24 536 60 534 30 ‒ ‒ ‒ ‒
NP NP NP
N-1 Sheikhupura - Yousafwala ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒
Normal 500 kV 129 24 536 60 534 30 ‒ ‒ ‒ ‒
NP NP NP
N-1 Sheikhupura - Gatti ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒
Normal 500 kV 129 24 900 476 30 536 60 534 30 547 30 539 30 532 90 ‒ ‒ ‒ ‒ 462 60 ‒ ‒ ‒ ‒
Sheikhupura - Nokhar
N-1 Ckt I & II ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒
Normal 500 kV Added in 900 547 30 ‒ ‒
NP Added in 2016-17 NP Added in 2016-17 NP
N-1 Sheikhupura - CCPP Sahiwal 2016-17 ‒ ‒ ‒ ‒ ‒
Normal 500 kV Added in 900 156 26 547 30 538 30 535 60 ‒ ‒ ‒ ‒ ‒ ‒
Added in 2016-17 Added in 2016-17
N-1 Sheikhupura - CCPP Bhikhi 2016-17 ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒
Normal 500 kV 476 52 541 60 535 60 ‒ ‒ ‒ ‒
Energized November, 2017 Energized November, 2017 Energized November, 2017
N-1 Sheikhupura - New Lahore ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒
Normal 220 kV 887 813 2833 3846 986 ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ 198 30 193 30 192 30 198 30 198 60
N-1 Sheikhupura - WTN 3 ‒ 60 392 30 ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ 195 60 ‒ ‒ 190 30 189 30 192 60
Normal 220 kV 887 813 2833 2983 780 ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ 198 30 193 30 192 30 198 30 198 60
Sheikhupura - NKLP
N-1 Ckt I & II 3 ‒ 60 1175 2 ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ 195 60 ‒ ‒ 190 30 190 30 196 60
Normal 220 kV 887 813 2833 12587 4509 ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ 198 30 193 30 192 30 194 30 198 60
Sheikhupura - Bund Road
N-1 Ckt I, II, III & IV 3 ‒ 60 4165 89 ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ 195 60 ‒ ‒ 190 30 190 60 192 60
Normal 220 kV 887 813 2833 2845 472 _ _ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ 198 30 193 30 192 30 198 30 198 60
Sheikhupura - Ravi
N-1 Ckt I & II 3 ‒ 60 596 2 ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ 195 60 ‒ ‒ 190 30 189 30 197 90
Normal 220 kV 887 813 2833 3252 1662 ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ 198 30 192 30 198 30 198 60
N-1 Sheikhupura - ATLAS P/H 3 ‒ 60 655 66 ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ 195 60 190 30 190 30 192 120
NP: Not Provided
Total No. of Variations (Normal) 4,822 4,137 15,065 26,621 8,517 Highest Voltage Under Normal Condition @500kV level Lowest Voltage Under Normal Condition @220kV level
Total No. of Variations (N-1) 15 – 300 6,983 189
Total of Normal & N-1 4,837 4,137 15,365 33,604 8,706 Lowest Voltage Under N-1 Condition @220kV level
Performance Evaluation Report for the year 2017-18 500 kV Grid Station Sheikhupura
Lahore Region
4 of 21
Total No. of Variations (Normal) 1,474 1,966 Highest Voltage Under Normal Condition @ 500kV level Lowest Voltage Under Normal Condition @ 220kV level
Total No. of Variations (N-1) Energized 01-Nov-2017 ‒ ‒
Total of Normal & N-1 1,474 1,966 Highest Voltage Under Normal Condition @ 220kV level
Performance Evaluation Report for the year 2018-19 500 kV Grid Station New Lahore
Lahore Region
5 of 21
Performance Evaluation Report for the year 2018-19 220 kV Grid Station Bandala
Lahore Region
6 of 21
Total No. of Variations (Normal) 3,844 3,598 1,916 5,027 4,581 Lowest Voltage Under Normal Condition
Total No. of Variations (N-1) 187 9 129 475 83
Total of Normal & N-1 4,031 3,607 2,045 5,502 4,664 Lowest Voltage Under N-1 Condition
Performance Review Report for the year 2018-19 220 kV Grid Station Bund Road
Lahore Region
7 of 21
Total No. of Variations (Normal) 938 1,582 4,989 6,529 10,240 Lowest Voltage Under Normal Condition
Total No. of Variations (N-1) 59 ‒ ‒ 15 117
Total of Normal & N-1 997 1,582 6,569 6,544 10,357 Lowest Voltage Under N-1 Condition
Performance Evaluation Report for the year 2017-18 220 kV Grid Station Gakkhar
Lahore Region
8 of 21
Total No. of Variations (Normal) 61 2,539 4,734 Lowest Voltage Under Normal Condition
NA
Total No. of Variations (N-1) – 39 2,156
Total of Normal & N-1 61 NA 2,578 6,940 Lowest Voltage Under N-1 Condition
Performance Evaluation Report for the year 2018-19 220 kV Grid Station Ghazi Road
Lahore Region
9 of 21
Total No. of Variations (Normal) 51 3,611 5,401 Highest Voltage Under Normal Condition Lowest Voltage Under Normal Condition
Energized
Total No. of Variations (N-1) ‒ ‒ ‒
Apr, 2017
Total of Normal & N-1 51 3,611 5,401
Performance Evaluation Report for the year 2018-19 220 kV Grid Station Gujrat
Lahore Region
10 of 21
Total No. of Variations (Normal) 278 208 372 836 340 Highest Voltage Under Normal Condition
Total No. of Variations (N-1) – – – ‒ ‒
Total of Normal & N-1 278 208 372 836 340
Performance Evaluation Report for the year 2018-19 220 kV Grid Station Jaranwala
Lahore Region
11 of 21
Total No. of Variations - Normal 9,413 20,418 4,652 4,308 4,271 Lowest Voltage Under Normal Condition
Total No. of Variations - N-1 997 286 38 321 483
Total of Normal & N-1 10,410 20,704 4,690 4,629 4,754 Lowest Voltage Under N-1 Condition
Performance Evaluation Report for the year 2017-18 220 kV Grid Station Kala Shah Kaku
Lahore Region
12 of 21
Total No. of Variations (Normal) 442 303 486 589 376 Highest Voltage Under Normal Condition Lowest Voltage Under Normal Condition
Total No. of Variations (N-1) – – – 1 –
Total of Normal & N-1 442 303 486 590 376
Performance Evaluation Report for the year 2018-19 220 kV Grid Station Ludewala
Lahore Region
13 of 21
Total No. of Variations (Normal) 20 96 88 48 Highest Voltage Under Normal Condition Lowest Voltage Under N-1 Condition
NA
Total No. of Variations (N-1) – – 40 ‒
Total of Normal & N-1 20 96 NA 128 48
Performance Evaluation Report for the year 2018-19 220 kV Grid Station Nishatabad
Lahore Region
14 of 21
Total No. of Variations (Normal) 16,577 5,237 3,115 4,094 3,542 Highest Voltage Under Normal Condition Lowest Voltage Under Normal Condition
Total No. of Variations (N-1) 6,130 ‒ 25 191 104
Total of Normal & N-1 22,707 5,327 3,140 4,285 3,646 Lowest Voltage Under N-1 Condition
Performance Evaluation Report for the year 2018-19 220 kV Grid Station New Kot Lakhpat
Lahore Region
15 of 21
Total No. of Variations (Normal) 4,650 4,242 1,086 1,618 1,347 Lowest Voltage Under Normal Condition
Total No. of Variations (N-1) 515 2,067 150 159 175
Total of Normal & N-1 5,165 6,309 1,236 1,777 1,522 Lowest Voltage Under N-1 Condition
Performance Evaluation Report for the year 2018-19 220 kV Grid Station New Shalamar
Lahore Region
16 of 21
Total No. of Variations (Normal) 16,165 7,568 6,831 3,471 4,450 Lowest Voltage Under Normal Condition
Total No. of Variations (N-1) 3,044 36 26 222 12
Total of Normal & N-1 19,209 7,604 6,857 3,693 4,462 Lowest Voltage Under N-1 Condition
Performance Evaluation Report for the year 2018-19 220 kV Grid Station Ravi
Lahore Region
17 of 21
Total No. of Variations (Normal) 1156 2532 192 144 28 Highest Voltage Under Normal Condition Lowest Voltage Under N-1 Condition
Total No. of Variations (N-1) 4 4 132 12 24
Total of Normal & N-1 1160 2536 324 156 52
Performance Evaluation Report for the year 2018-19 220 kV Grid Station Samundri Road
Lahore Region
18 of 21
Total No. of Variations (Normal) 3,362 5,350 3,321 2,948 2,546 Lowest Voltage Under Normal Condition
Total No. of Variations (N-1) 169 548 227 20 ‒
Total of Normal & N-1 3,531 5,898 3,548 2,968 2,546
Performance Evaluation Report for the year 2018-19 220 kV Grid Station Sarfaraznagar
Lahore Region
19 of 21
Total No. of Variations (Normal) 831 1,362 2,250 2,346 2,421 Lowest Voltage Under Normal Condition
Total No. of Variations (N-1) 151 1 2 6 4
Total of Normal & N-1 982 1,363 2,252 2,352 2,425 Lowest Voltage Under N-1 Condition
Performance Evaluation Report for the year 2018-19 220 kV Grid Station Sialkot
Lahore Region
20 of 21
Total No. of Variations (Normal) 240 896 850 910 1414 Highest Voltage Under Normal Condition Lowest Voltage Under Normal Condition
Total No. of Variations (N-1) 1 ‒ ‒ ‒ 4
Total of Normal & N-1 241 896 850 910 1418 Lowest Voltage Under N-1 Condition
Performance Evaluation Report for the year 2018-19 220 kV Grid Station Toba Tek Singh
Lahore Region
21 of 21
Total No. of Variations - Normal 4,564 1,381 1,267 2,017 1,388 Lowest Voltage Under Normal Condition
Total No. of Variations - N-1 412 ‒ ‒ 22 4
Total of Normal & N-1 4,976 1,381 1,267 2,039 1,392 Lowest Voltage Under N-1 Condition
Performance Evaluation Report for the year 2018-19 220 kV Grid Station WAPDA Town
Performance Evaluation Report for the year 2018-19
APPENDIX 3
Total No. of Variations (Normal) 14 315 27 194 Highest Voltage Under Normal Condition @500kV level
NIL
Total No. of Variations (N-1) – – – –
Total of Normal & N-1 14 NIL 315 27 194 Highest Voltage Under Normal Condition @220kV level
Performance Evaluation Report for the year 2017-18 500 kV Grid Station D.G. Khan
NTDC Multan Region
Multan Region
2. 500kV Grid Station MULTAN 2 of 11
Total No. of Variations (Normal) 20 8 3 20 Highest Voltage Under Normal Condition @500kV level
NIL
Total No. of Variations (N-1) – − − −
Total of Normal & N-1 20 8 3 NIL 20
Performance Evaluation Report for the year 2018-19 500 kV Grid Station Multan
Multan Region
3 of 11
Normal 500 kV
NIL NIL NIL
N-1 Muzaffargarh - Guddu
Normal 500 kV
NIL NP NIL NP NIL NP
N-1 Muzaffargarh - Multan
Normal 220 kV
NIL NP NIL NP NIL NP
N-1 500kV Grid Station TPS Phase-I - Muzaffargarh
Normal 220 kV
NIL NP NIL NP NIL NP
N-1 500kV Grid Station TPS Phase-II - Muzaffargarh
NP: Not Provided
Performance Evaluation Report for the year 2017-18 500 kV Grid Station Muzaffargarh
Multan Region
4 of 11
Total No. of Variations (Normal) 351 NA 126 543 1,601 Highest Voltage Under Normal Condition @500kV level Lowest Voltage Under N-1 Condition @500kV level
Total No. of Variations (N-1) – NA – – –
Total of Normal & N-1 351 NA 126 543 1,601 Highest Voltage Under Normal Condition @220kV level
Performance Evaluation Report for the year 2018-19 500 kV Grid Station Yousafwala
Multan Region
5 of 11
Total No. of Variations (Normal) 6 Highest Voltage Under Normal Condition @500kV level
Total No. of Variations (N-1) Energized Feb, 2018 NIL ‒
Total of Normal & N-1 6
Performance Evaluation Report for the year 2018-19 500 kV Grid Station Rahim Yar Khan
Multan Region
6 of 11
Total No. of Variations (Normal) 305 506 15 21 657 Highest Voltage Under Normal Condition
Total No. of Variations (N-1) – – 5 ‒ 179
Total of Normal & N-1 305 506 20 21 836 Highest Voltage Under N-1 Condition
Performance Evaluation Report for the year 2018-19 220 kV Grid Station Bahawalpur
Multan Region
7 of 11
Total No. of Variations (Normal) 2,008 3,822 998 1,234 Highest Voltage Under Normal Condition Lowest Voltage Under Normal Condition
NIL
Total No. of Variations (N-1) − − − 40
Total of Normal & N-1 NIL 2,008 3,822 998 1,274 Lowest Voltage Under N-1 Condition
Performance Evaluation Report for the year 2018-19 220 kV Grid Station Kassowal
Multan Region
8 of 11
Total No. of Variations (Normal) 4 650 406 Highest Voltage Under Normal Condition
NIL
Total No. of Variations (N-1) – ‒ 57
Total of Normal & N-1 4 NIL 650 463 Highest Voltage Under N-1 Condition
Performance Evaluation Report for the year 2018-19 220 kV Grid Station Muzaffargarh
Multan Region
9 of 11
Total No. of Variations (Normal) 75 338 526 364 884 Lowest Voltage Under Normal Condition
Total No. of Variations (N-1) – – − 1 −
Total of Normal & N-1 75 338 526 365 884
Performance Evaluation Report for the year 2018-19 220 kV Grid Station Okara
Multan Region
10 of 11
Total No. of Variations - Normal 764 593 2,513 4,915 5,975 Lowest Voltage Under Normal Condition
Total No. of Variations - N-1 ‒ ‒ 6 420 684
Total of Normal & N-1 764 593 2,519 5,335 6,659 Lowest Voltage Under N-1 Condition
Performance Evaluation Report for the year 2018-19 220 kV Grid Station Vehari
Multan Region
11 of 11
Total No. of Variations (Normal) 722 3,282 3,944 Lowest Voltage Under Normal Condition
Energized
Total No. of Variations (N-1) 70 505 817
24-Oct-2016
Total of Normal & N-1 792 3,787 4,761 Lowest Voltage Under N-1 Condition
Performance Evaluation Report for the year 2018-19 220 kV Grid Station Chistian
Performance Evaluation Report for the year 2018-19
APPENDIX 4
Total No. of Variations (Normal) 2,525 835 733 265 152 Highest Voltage Under Normal Condition @500kV level
Total No. of Variations (N-1) – – ‒ ‒ ‒
Total of Normal & N-1 2,525 835 733 265 152 Highest Voltage Under Normal Condition @220kV level
Performance Evaluation Report for the year 2018-19 500 kV Grid Station Dadu
Hyderabad Region
2 of 15
Normal 500 kV 1449 1268 1183 521* 540 180 540 90 540 420 540 420 ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒
* * *
N-1 Guddu - Dadu II ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒
Normal 500 kV ‒ 1382 504 10 ‒ ‒ 638 60 540 300 535 300 ‒ ‒ ‒ ‒ ‒ ‒
Guddu - D.G. Khan NP NP NP
N-1 (Old Multan) ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒
Normal 500 kV 1089 1378 642 540 120 541 90 541 90 ‒ ‒ ‒ ‒ ‒ ‒
NA NA NA
N-1 Guddu - 747 MW CCPP Guddu ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒
Normal 500 kV ‒ 1405 456 13 ‒ ‒ 638 60 540 300 535 120 ‒ ‒ ‒ ‒ ‒ ‒
NP NP NP
N-1 Guddu - Muzaffargarh ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒ ‒
Normal 500 kV
does not exist NA does not exist NA does not exist NA
N-1 Guddu - Shikarpur I
Total No. of Variations (Normal) 2,538 5,433 1,825 1,494 46 Highest Voltage Under Normal Condition @500kV level
Total No. of Variations (N-1) – – – – –
Total of Normal & N-1 2,538 5,433 1,825 1,494 46
Performance Evaluation Report for the year 2018-19 500 kV Grid Station Guddu
Hyderabad Region
3 of 15
Total No. of Variations (Normal) 2,112 1,456 1,688 4,874 5,755 Highest Voltage Under Normal Condition @500kV level
Total No. of Variations (N-1) – – – – –
Total of Normal & N-1 2,112 1,456 1,688 4,874 5,755 Highest Voltage Under Normal Condition @220kV level
Performance Evaluation Report for the year 2018-19 500 kV Grid Station Jamshoro
Hyderabad Region
4 of 15
Total No. of Variations (Normal) 5,389 3,188 1,106 1,118 29 Lowest Voltage Under Normal Condition @500kV level
Total No. of Variations (N-1) – – − ‒ ‒
Total of Normal & N-1 5,389 3,188 1,106 1,118 29 Highest Voltage Under Normal Condition @220kV level
Performance Evaluation Report for the year 2018-19 500 kV Grid Station NKI Karachi
Hyderabad Region
5 of 15
Total No. of Variations (Normal) 567 45 2,242 4,142 7,258 Highest Voltage Under Normal Condition @500kV level
Total No. of Variations (N-1) 5 ‒ − − −
Total of Normal & N-1 572 45 2,242 4,142 7,258 Highest Voltage Under Normal Condition @220kV level
Performance Evaluation Report for the year 2018-19 500 kV Grid Station Shikarpur
Hyderabad Region
6 of 15
Performance Evaluation Report for the year 2018-19 220 kV Grid Station Dharki
Hyderabad Region
7 of 15
Total No. of Variations (Normal) 162 6 10 56 20 Highest Voltage Under Normal Condition
Total No. of Variations (N-1) – – ‒ ‒ −
Total of Normal & N-1 162 6 10 56 20
Performance Evaluation Report for the year 2018-19 220 kV Grid Station Hala Road
Hyderabad Region
8 of 15
Total No. of Variations (Normal) 1,134 796 458 282 246 Highest Voltage Under Normal Condition Lowest Voltage Under Normal Condition
Total No. of Variations (N-1) 6 − − − −
Total of Normal & N-1 1,140 796 458 282 246
Performance Evaluation Report for the year 2018-19 220 kV Grid Station Khuzdar
Hyderabad Region
9 of 15
Total No. of Variations (Normal) 1,168 1,246 1,010 3,140 1,982 Highest Voltage Under Normal Condition Lowest Voltage Under Normal Condition
Total No. of Variations (N-1) 154 − − − 308
Total of Normal & N-1 1,322 1,246 1,010 3,140 2,290 Highest Voltage Under N-1 Normal Condition Lowest Voltage Under N-1 Normal Condition
Performance Evaluation Report for the year 2018-19 220 kV Grid Station Loralai
Hyderabad Region
10 of 15
Total No. of Variations (Normal) 5,730 12,106 888 6,044 8,758 Highest Voltage Under Normal Condition Lowest Voltage Under Normal Condition
Total No. of Variations (N-1) 6,290 − 2 − −
Total of Normal & N-1 12,020 12,106 890 6,044 8,758
Performance Evaluation Report for the year 2018-19 220 kV Grid Station Quetta Industrial-II
Hyderabad Region
11 of 15
Total No. of Variations (Normal) 1,060 1,642 Nil 70 200 Highest Voltage Under Normal Condition
Total No. of Variations (N-1) – – − −
Total of Normal & N-1 1,060 1,642 Nil 70 200
Performance Evaluation Report for the year 2018-19 220 kV Grid Station Rohri
Hyderabad Region
12 of 15
Total No. of Variations (Normal) 5,627 3,921 1,768 2,239 4,579 Highest Voltage Under Normal Condition Lowest Voltage Under Normal Condition
Total No. of Variations (N-1) 214 3 − − −
5,841 3,924 1,768 2,239 4,579
Performance Evaluation Report for the year 2018-19 220 kV Grid Station Sibbi
Hyderabad Region
13 of 15
Total No. of Variations (Normal) 946 374 244 1,054 2,818 Highest Voltage Under Normal Condition
Total No. of Variations (N-1) ‒ ‒ − − −
Total of Normal & N-1 946 374 244 1,054 2,818
Performance Evaluation Report for the year 2018-19 220 kV Grid Station T.M. Khan Road
Hyderabad Region
14 of 15
Total No. of Variations (Normal) 348 888 Highest Voltage Under Normal Condition Lowest Voltage Under Normal Condition
Total No. of Variations (N-1) Energized in Aug 2017 − −
Total of Normal & N-1 348 888
Performance Evaluation Report for the year 2018-19 220 kV Grid Station Jhimpir
Hyderabad Region
15 of 15
Total No. of Variations (Normal) 1,119 Highest Voltage Under Normal Condition
Total No. of Variations (N-1) Added in 2018-19 −
Total of Normal & N-1 1,119
Performance Evaluation Report for the year 2018-19 220 kV Grid Station Dera Murad Jamali
Performance Evaluation Report for the year 2018-19
APPENDIX 5
K-Electric System
Circuit Wise Number of Voltage Variations Violating Criteria
Name of Total Number / Times
Highest Voltage Recorded (kV) / Time (Min) Lowest Voltage Recorded (kV) / Time (Min)
Transmission Circuit(s) violating the limit
Condition
violating the voltage
2014-15 2015-16 2016-17 2017-18 2018-19 2014-15 2015-16 2016-17 2017-18 2018-19
criteria 2014-15 2015-16 2016-17 2017-18 2018-19
Voltage Time Voltage Time Voltage Time Voltage Time Voltage Time Voltage Time Voltage Time Voltage Time Voltage Time Voltage Time
Normal 220 kV − − − − − − − − − −
Nil Nil Nil
N-1 Baldia - Mauripur − − − − − − − − − −
Normal 132 kV − − − − − − − − − − − − − − − − − − − − − − − − −
N-1 Surjani - Maymar − − − − − − − − − − − − − − − − − − − − − − − − −
Normal 132 kV − − − − − − − − − − − − − − − − − − − − − − − − −
N-1 Surjani - Valika − − − − − − − − − − − − − − − − − − − − − − − − −
Normal 132 kV − − − − − − − − − − − − − − − − − − − − − − − − −
N-1 SITE - SGT 1 − − − − − − − − − − − − − − − − − − − − − − − − −
Normal 132 kV − − − − − − − − − − − − − − − − − − − − − − − − −
N-1 SITE - SGT 2 − − − − − − − − − − − − − − − − − − − − − − − − −
Normal 132 kV 1 − − − − − − − − − − − − − − 115 − − − − − − − −
NP
N-1 KDA - Federal B 1 1 − 1 − − − − − − − − − − − 114 117.4 147 − − 118.6 33 − −
Normal 132 kV − − − − − − − − − − − − − − − − − − − − − − − − −
N-1 Valika - N. Karachi − − − − − − − − − − − − − − − − − − − − − − − − −
Normal 132 kV − − − − − − − − − − − − − − − − − − − − − − − − −
N-1 Gulshan - Civic − − − − − − − − − − − − − − − − − − − − − − − − −
Normal 132 kV − − − − − − − − − − − − − − − − − − − − − − − − −
N-1 West Wharf - Lyari − − − − − − − − − − − − − − − − − − − − − − − − −
Normal 132 kV 1 − − − − − − − − − − − − − − 112 − − − − − − − −
NP
N-1 Qayyumabad - K. East 1 1 1 1 1 − − − − − − − − − − 116 117.1 280 114 48 117.3 47 118.3 54
Normal 132 kV − − − − − − − − − − − − − − − − − − − − − − − − −
N-1 Memon Goth - Malir − − − − − − − − − − − − − − − − − − − − − − − − −
Normal 132 kV − − − − − − − − − − − − − − − − − − − − − − − − −
N-1 Malir - CAA − − − − − − − − − − − − − − − − − − − − − − − − −
Normal 132 kV − − − − − − − − − − − − − − − − − − − − − − − − −
N-1 Gulshan - Hospital − − − − − − − − − − − − − − − − − − − − − − − − −
Normal 132 kV 1 − − − − − − − − − − − − − − 121 NP − − − − − − − −
N-1 Gharo - RECP − − − − − − − − − − − − − − − − − − − − − − − − −
Normal 132 kV 1 − − − − − − − − − − − − − − 121 NP − − − − − − − −
N-1 BOC - Dhabeji − − − − − − − − − − − − − − − − − − − − − − − − −
NP: Not Provided
K-Electric System
Circuit Wise Number of Voltage Variations Violating Criteria
Name of Total Number / Times
Highest Voltage Recorded (kV) / Time (Min) Lowest Voltage Recorded (kV) / Time (Min)
Transmission Circuit(s) violating the limit
Condition
violating the voltage
2014-15 2015-16 2016-17 2017-18 2018-19 2014-15 2015-16 2016-17 2017-18 2018-19
criteria 2014-15 2015-16 2016-17 2017-18 2018-19
Voltage Time Voltage Time Voltage Time Voltage Time Voltage Time Voltage Time Voltage Time Voltage Time Voltage Time Voltage Time
Normal 132 kV − 1 − − − − − − − − − − − − − − − 116.9 78 − − − − − −
N-1 Pipri West - KEPZ − − − − − − − − − − − − − − − − − − − − − − − − −
Normal 132 kV − − − − − − − − − − − − − − − − − − − − − − − − −
N-1 KEPZ - Landhi − − − − − − − − − − − − − − − − − − − − − − − − −
Normal 132 kV − − − − − − − − − − − − − − − − − − − − − − − − −
N-1 Gul Ahmed - Airport 1 & 2 − − − − − − − − − − − − − − − − − − − − − − − − −
Normal 132 kV − − − − − − − − − − − − − − − − − − − − − − − − −
N-1 KTPS - PRL − − − − − − − − − − − − − − − − − − − − − − − − −
Normal 132 kV − − − − − − − − − − − − − − − − − − − − − − − − −
N-1 K. East - K. South − − − − − − − − − − − − − − − − − − − − − − − − −
Normal 132 kV − − − − − − − − − − − − − − − − − − − − − − − − −
N-1 Valika - North Nazimabad − − − − − − − − − − − − − − − − − − − − − − − − −
Normal 132 kV − − − − − − − − − − − − − − − − − − − − − − − − −
N-1 Orangi - Valika − − − − − − − − − − − − − − − − − − − − − − − − −
Normal 132 kV − − − − − − − − − − − − − − − − − − − − − − − − −
N-1 Liaquatabad - Azizabad − − − − − − − − − − − − − − − − − − − − − − − − −
Normal 132 kV − − − − − − − − − − − − − − − − − − − − − − − − −
N-1 Port Qasim - Landhi − − − − − − − − − − − − − − − − − − − − − − − − −
Normal 132 kV 1 − − − − − − − − − − − − − − 124 NP − − − − − − − −
N-1 Baldia - Orangi 1 − − − − − − − − − − − − − − 118 − − − − − − − −
Normal 132 kV 1 − − − − − − − − − − − − − − 124 NP − − − − − − − −
N-1 Baldia - Valika − − − − − − − − − − − − − − − − − − − − − − − − −
Normal 132 kV 1 − − − − − − − − − − − − − − 124 NP − − − − − − − −
N-1 Baldia - Hub 1 − − − − − − − − − − − − − − 118 − − − − − − − −
Normal 132 kV 1 − − − − − − − − − − − − − − 124 NP − − − − − − − −
N-1 Baldia - SGT - SITE 1 − − − − − − − − − − − − − − 118 − − − − − − − −
Normal 132 kV 1 1 − − − − − − − − − − − − − 121 NP 116.9 78 − − − − − −
N-1 Pipri - Korangi Town − − − − − − − − − − − − − − − − − − − − − − − − −
NP: Not Provided
K-Electric System
Circuit Wise Number of Voltage Variations Violating Criteria
Total Number / Times
Name of Highest Voltage Recorded (kV) / Time (Min) Lowest Voltage Recorded (kV) / Time (Min)
violating the limit
Condition Transmission Circuit(s)
violating the voltage criteria 2014-15 2015-16 2016-17 2017-18 2018-19 2014-15 2015-16 2016-17 2017-18 2018-19
2014-15 2015-16 2016-17 2017-18 2018-19
Voltage Time Voltage Time Voltage Time Voltage Time Voltage Time Voltage Time Voltage Time Voltage Time Voltage Time Voltage Time
Normal 132 kV 1 1 − − − − − − − − − − − − − 121 NP 116.9 78 − − − − − −
N-1 Pipri - Landhi − − − − − − − − − − − − − − − − − − − − − − − −
Normal 132 kV 1 − − − − − − − − − − − − − − 112 NP − − − − − − − −
N-1 Qayyumabad - DHA 1 1 − − − − − − − − − − − − − − 116 − − − − − − − −
Normal 132 kV 1 − − − − − − − − − − − − − − 116 NP − − − − − − − −
N-1 Queen's Road - Clifton 1 1 1 1 1 − − − − − − − − − − 116 117.1 280 114 48 117.3 47 118.3 54
Normal 132 kV 1 − − − − − − − − − − − − − − 116 NP − − − − − − − −
N-1 Queen's Road - Gizri 1 1 1 1 1 − − − − − − − − − − 116 117.1 280 114 48 117.3 47 118.3 54
Normal 132 kV 1 − − − − − − − − − − − − − − 116 NP − − − − − − − −
N-1 Queen's Road - Elander Road 1 − − − − − − − − − − − − − − 116 − − − − − − − −
Normal 132 kV 1 − − − − − − − − − − − − − − 116 NP − − − − − − − −
N-1 Queen's Road - Old Town 1 1 1 1 1 − − − − − − − − − − 116 117.1 280 114 48 117.3 47 118.3 54
Normal 132 kV 1 − − − − − − − − − − − 116.9 78 − − − − − −
Nil Nil Nil
N-1 Pipri / RECP / Gharo − − − − − − − − − − − − − − − − − − − −
Normal 132 kV 1 − − − − − − − − − − − 116.9 78 − − − − − −
Nil Nil Nil
N-1 Pipri / BOC / Dhabeji − − − − − − − − − − − − − − − − − − − −
Normal 132 kV − − − − − − − − − − − − − − − − − − − −
Nil Nil Nil
N-1 KDA / Memon Goth /Malir 1 − 1 − − − − − − − − − 117.4 280 − − 118.6 33 − −
Normal 132 kV − − − − − − − − − − − − − − − − − − − −
Nil Nil Nil
N-1 Korangi West / Baloch / Gizri 1 − 1 1 − − − − − − − − 117.1 280 − − 117.3 47 118.3 54
Normal 132 kV − − − − −
− − −
N-1 Mauripur - Old Golimar 1 − − 118.2 250
Normal 132 kV − − − − −
− − −
N-1 Mauripur - Lyari 1 − − 118.2 250
NP: Not Provided
Total No. of Variations (Normal) 22 6 Nil Nil Nil Lowest Voltage Under N-1 Condition
Total No. of Variations (N-1) 16 12 7 12 9
Total of Normal & N-1 38 18 7 12 9
APPENDIX 6
NTDC
Highest System Frequency Recorded Violating the Prescribed Upper Limit1 (Hz)
Month
2014-15 2015-16 2016-17 2017-18 2018-19
July 50.71 50.75 NIL 50.5 50.66
Aug 50.68 50.69 50.72 50.56 50.54
Sep 50.55 50.69 50.6 50.56 50.6
Oct 50.69 50.53 NIL NIL 50.58
Nov 50.62 50.62 NIL NIL NIL
Dec 58.63 50.71 50.63 NIL 50.64
Jan 54.69 51.47 50.68 50.64 50.67
Feb 49.49 NIL 50.65 NIL NIL
Mar 50.65 50.64 50.61 50.54 50.59
Apr 50.66 NIL 50.63 50.56 50.68
May 50.69 NIL 50.65 50.62 NIL
June 50.68 49.49 50.64 50.6 50.79
57
Frequency (Hz)
55
53
51
49
July Aug
Sep Oct
Nov Dec
Jan Feb
Mar Apr
May June
1
Upper Limit: 50.50 Hz, Rule 8(1) of PSTR 2005
P a g e A6-1
Performance Evaluation Report for the year 2018-19
Lowest System Frequency Recorded Violating the prescribed Lower Limit2 (Hz)
Month
2014-15 2015-16 2016-17 2017-18 2018-19
July 48.74 49.07 NIL 50.51 50.51
Aug 48.91 49.15 49.36 50.51 50.51
Sep 48.93 49.19 50.51 50.51 50.51
Oct 48.99 49.21 NIL NIL 50.51
Nov 48.83 49.22 NIL NIL NIL
Dec 45 49.32 49.44 NIL 50.51
Jan 45 45 49.37 NIL 49.44
Feb 49.06 NIL 50.53* NIL NIL
Mar 49.11 50.52 50.51* NIL 50.51
Apr 49.02 NIL 49.32 NIL 50.52
May 49.2 NIL 50.52* NIL NIL
June 50.51 49.35 50.51* NIL 50.51
* Cannot be validated
50.8
Frequency (Hz)
48.8
46.8
44.8
July Aug
Sep Oct
Nov Dec
Jan Feb
Mar Apr
May June
2
Lower Limit: 49.50 Hz, Rule 8(1) of PSTR 2005
P a g e A6-2
Performance Evaluation Report for the year 2018-19
K-Electric
Highest System Frequency Recorded Violating the Prescribed Upper Limit3 (Hz)
Month
2014-15 2015-16 2016-17 2017-18 2018-19
July 50.58 50.6 Nil NA ‒
Aug 50.64 Nil Nil NA ‒
Sep 50.51 Nil Nil NA 51.5
Oct 50.53 Nil Nil NA ‒
Nov 50.55 0 Nil NA ‒
Dec 50.82 50.6 Nil NA ‒
Jan 50.54 50.7 50.6 50.9 50.8
Feb 50.51 Nil Nil NA ‒
Mar 50.58 Nil Nil NA ‒
Apr 50.51 Nil Nil 50.6 ‒
May 50.57 50.6 50.6 50.6 ‒
June 50.52 Nil Nil NA ‒
51.5
Frequency (Hz)
51
50.5
50
July Aug
Sep Oct
Nov Dec
Jan Feb
Mar Apr
May June
3
Upper Limit: 50.50 Hz, Rule 8(1) of PSTR 2005
P a g e A6-3
Performance Evaluation Report for the year 2018-19
Lowest System Frequency Recorded Violating the prescribed Lower Limit 4 (Hz)
Month
2014-15 2015-16 2016-17 2017-18 2018-19
July 48.97 49.4 Nil NA ‒
Aug 49.1 49.4 Nil NA ‒
Sep 49.13 49.4 Nil NA ‒
Oct 49.18 49.4 Nil NA ‒
Nov 48.94 Nil Nil NA ‒
Dec 49.15 Nil Nil NA ‒
Jan 49.07 49.4 Nil NA ‒
Feb 49.39 Nil Nil NA ‒
Mar 49.26 Nil Nil NA ‒
Apr 49.26 Nil 49.3 NA ‒
May 49.29 Nil Nil NA ‒
June 49.32 49.4 Nil NA ‒
50
Frequency (Hz)
49
48
47
July Aug
Sep Oct
Nov Dec
Jan Feb
Mar Apr
May June
4
Lower Limit: 49.50 Hz, Rule 8(1) of PSTR 2005
P a g e A6-4
50