ENGINE GOVERNORS

EAM111
GOVERNING AMERICA

SYSTEM
GAC to MTU
Interface Module C ORP.®

INSTALLATION WIRING
See Wiring Diagram.
The EAM111 is an electronic interface module designed to work
with the MTU MDEC electronic engine controls. The module can Note 1:
accept a speed setting voltage range signal as wide as 0-10V When using the load sharing/ sync input with 5.0V DC at Terminal
DC or a narrow trimming voltage centered around 5.0V DC. The C, a jumper must be placed between Terminals E and 2. Terminals
module’s output can be configured to be either a 4-20 or 0-20 mA A, B, and D shall all be left open. This will yield about a 12 mA
signal for the MDEC system. Integral range and zero adjustments output. Adjust the zero adjustment for exactly 12 mA with the load
allow the installer to precisely configure the output vs. the input sharing module connected to the control (5.0V DC at Terminal C).
characteristics.
Note 2:
Power for the module comes from the 24V DC system powering the To change from a 0-20 ma range to a 4-20 ma range, a jumper must
MDEC engine control. be added between Terminals A and B.

Note 3:
The common battery minus connections between the MDEC control,
the EAM111, and the load sharing and synchronizer system should
be as direct as possible electrically (minimum voltage difference).

SPECIFICATIONS

Input Impedance (Terminals D & 4).................................................................1K ohms, min


Input impedance (Terminals C & 4).........................................................................2 M ohms
Output capability (Terminals 3 & 4).....................................................20 mA up to 4.5 vdc
Output transfer function (C vs out)...............................................0 vdc - 10 vdc +/- .5 vdc
Output transfer function (D vs out)............................................17.5 +/- .5 to 6.5 +/- .5 mA
DC supply voltage (Terminals 1 & 4)....................................................................15 to 32 vdc
DC supply current (Terminals 1 & 4).................................................................................30 mA
Temp Range.......................................................................................................-40° to +85°C

Governors America Corp., 720 Silver Street Agawam, MA 01001


phone: 413.786.5600 fax: 413.789.7736
www.governors-america.com
info@governors-america.com
1
DIAGRAM 1 SYSTEM WIRING/OUTLINE

TO MTU CONTROL
0 - 20 mA OR 4 - 20 mA
OUTPUT NOTE 3: TERMINAL 4 (-24V DC) MUST BE AT THE
SAME POTENTIAL AS THE LOAD SHARING UNIT,
24V DC - SYNCHRONIZER, AND MTU CONTROL MINUS
INPUTS. CONNECT ALL (-) TERMINALS TO THE
SUPPLY MTU MINUS INPUT.
+

ADJUSTMENTS
ZERO
DIMENSIONS: 1 2 3 4 USE THIS ADJUSTMENT TO SET A SINGLE
+24V DC OUT GND CALIBRATION POINT.
OVERALL
EAM111 FOR EXAMPLE: 0V DC INPUT = 0mA (OR 4mA)
C

3.45 X 2.91 (87,6 X 73,9) ZERO


OUTPUT TO THE MTU CONTROL
A

MTU INTERFACE MODULE


MOUNTING
G

INPUTS
2.75 X 2.03 (69,8 X 51,6) mA RANGE
LSM\SYC 0-10V +10V
RANGE
RANGE
.20 (5,1) DIAMETER HOLES A B C D E USE THIS ADJUSTMENT TO CALIBRATE THE RELATIONSHIP
BETWEEN THE VOLTAGE INPUT AT TERMINAL D AND THE
OUTPUT CURRENT TO THE MTU CONTROL. THE RATIO OF
ADJUSTMENT IS 5:1, CW INCREASES THE SENSITIVITY.
NOTE 2:
SELECT
OUTPUT RANGE
OPEN = 0 - 20 mA 5K
CLOSED = 4 - 20 mA
MANUAL SPEED ADJUST
(OPTIONAL 0 - 10V DC INPUT
FOR 0 - 20 mA OUTPUT)
USE THIS DIAGRAM FOR VARIABLE SPEED
OPERATION WITH THE MTU CONTROL

TO MTU CONTROL
12 mA NOMINAL
OUTPUT NOTE 3: TERMINAL 4 (-24V DC) MUST BE AT THE
SAME POTENTIAL AS THE LOAD SHARING UNIT,
SYNCHRONIZER, AND MTU CONTROL MINUS
24V DC - INPUTS. CONNECT ALL (-) TERMINALS TO THE
SUPPLY MTU MINUS INPUT.
+
NOTE 1

ADJUSTMENTS
1 2 3 4
+24V DC OUT GND ZERO
USE THIS ADJUSTMENT TO SET A SINGLE
EAM111
C

DIMENSIONS: ZERO CALIBRATION POINT.


A

MTU INTERFACE MODULE


FOR EXAMPLE: 12mA OUTPUT TO THE MTU CONTROL
G

OVERALL mA RANGE
INPUTS
RANGE CORRESPONDS TO A 5V DC SIGNAL
3.45 X 2.91 (87,6 X 73,9) A B
LSM\SYC 0-10V +10V
C D E AT TERMINAL C.
MOUNTING RANGE
THIS ADJUSTMENT IS NOT USED WHEN THE EAM111
2.75 X 2.03 (69,8 X 51,6) IS IN THE LOAD SHARING / SYNC MODE.
.20 (5,1) DIAMETER HOLES

USE THIS DIAGRAM TO INTERFACE THE MTU


FROM LSM & CONTROL WITH GAC LOAD SHARING AND
SYC OUTPUT SYNCHRONIZING MODULES.

12 mA NOMINAL OUTPUT

This document is subject to change without notice.