admittance of the branch between the node i and the node power flow calculation results of PV power plant are
j. shown in Fig. 4.
¾ Paramters of PV inverter 1Ö<con=18S×
1 ¾ Paramters of PV inverter 2Ö<con=50S×
Yij yij (8)
zij As shown in Fig. 4, when more inverter 2 parameters
are used in the system, the frequency and voltage
Therefore, the admittance matrix can be established amplification of the high frequency resonance point are
based on PV power plant network topology. significantly increased. When the power generation units
in the system all with the same type, there is the only one
resonance peak in the range of 0-1000 Hz, and the
3.3 Harmonic power flow method voltage amplification factor is relatively large.
Harmonic power flow calculation is to solve the Z t2 Zt1 Zd1 Zd2 Zdn ZT Zs

harmonic voltage of each node, according to the network Z t3


equation composed of the harmonic current injected by ZN Yd1 Y d1 Y d2 Y d2 Ydn Ydn YT

each harmonic source node and the harmonic admittance ZN

matrix of the network, as following: Zt2 Z t1 Zt2 Z t1

Z t3 Zt3
U h Z h I h (9) ZN ZN
ZN ZN

Where, 8(h) is the node harmonic voltage vector, =(h) is


the node impedance matrix, =(h)=<-1(h), and <(h) is the
node admittance matrix; ,(h) is the node injection Fig. 3. Network equivalent impedance diagram.
harmonic current vector.
,(h) is the h-th harmonic injection current vector of 0.08
each node. The non-zero element is the h-th harmonic Parameter 1
Parameter 2
injection current Ii(h) of each harmonic source, and the 0.06
Voltage amplification

element without the harmonic source is zero, and the


components to which they are connected are incorporated
into the admittance matrix in the form of their equivalent 0.04

admittance. As the harmonic current injection mode be


known, the harmonic bus voltage can be obtained, and 0.02
the corresponding harmonic line current can also be
obtained.
0.00
It is noticed that harmonic network parameters used in 0 100 200 300 400 500 600 700 800 900 1000
the calculation are related to the harmonic order. Frequency in Hz
Therefore, it is necessary to form the node admittance
matrix of the network multiple times according to the Fig. 4. Influence of converter parameters on harmonic voltage
harmonic order. Due to the particularity of the harmonics, distribution.
it is necessary to form according to the phase sequence of
the subharmonic. The corresponding sequence network. 4.3 Scenario 2: The influence of the number of
PV inverters on the resonant frequency
4 Research cases While the number of inverters running PV power plant is
10, 30, and 50 units, the variation of the harmonic voltage
4.1 Analysis of harmonic resonance mechanism amplification coefficient of the selected node is observed,
of PV power plant based on harmonic power and the analysis results are shown in Fig. 5.
flow method 0.08

10 converters
Researching on harmonic overvoltage mechanism of 30 converters
0.06
multi-power electronic grid-connected system by
Voltage amplification

50 converters
harmonic current flow method, the equivalent impedance
of the harmonic network of a PV power plant in Qinghai 0.04
Province is shown in Fig. 3.
0.02
4.2 Scenario 1: The influence of the impedance
of PV inverter on the resonant frequency 0.00
0 500 1000 1500
Two sets of PV inverters’ impedance parameters are set Frequency in Hz
to analysis the influence of inverter parameters on the
harmonic voltage distribution of the node. The harmonic Fig. 5. Influence of the quantity of converters on harmonic
voltage distribution.

3
E3S Web of Conferences 107, 02002 (2019) https://doi.org/10.1051/e3sconf/201910702002
ICSREE 2019

As shown in Fig. 5, it is obvious that influence of the Based on the impedance characteristics of PV inverter,
input quantity of inverter on the harmonic characteristics the Norton equivalent model of the PV inverter was
of photovoltaic power station. As the number of inverters derived, which is suitable for harmonic analysis. The
invested by the PV power plant increases, the resonant harmonic resonance impedance model of PV power plant
frequency of the resonant point with higher frequency was established by means of the traditional power system
gradually increases, the resonant frequency of the lower admittance analysis method. Using the harmonic current
frequency resonant point gradually decreases. method, the mechanism of harmonic overvoltage in PV
power plants was analysed, and various factors affecting
the harmonic resonance point were analyzed, including
4.4 Scenario 3: The influence of grid strengh on
the converter impedance, the number of converters and
the resonant frequency
the grid strength. The result is used to guide PV power
The short circuit ratio (SCR) of the system is defined as plant to avoid harmonic resonance and cause system
the ratio between the power system short circuit capacity failure.
and the rated capacity of the plant:

SSCR References
KSCR (10)
SN 1. X. YUAN, S. CHENG, J. HU. Multi-time Scale
Voltage and Power Angle Dynamics in Power
The SCR of PV power plant connected to the grid are Electronics Dominated Large Power Systems
set as 3 and 10 respectively, representing the weak grid [J] Ê Proceedings of CSEE È 2016,36(19): 5145-
and the strong grid. The simulation results are shown in 5154+5395 (in Chinese)Ê
Fig. 6.
0.10 2. P. A. Dahono, A control method to damp oscillation
in the input LC filter of AC-DC PWM converters [C].
SCR=3
SCR=10
Proc. PESC'02, pp.1630 - 1635, 2002.
0.08
Voltage amplification

3. E. Twining and D. Holmes. Grid current regulation


of a three-phase voltage source inverter with an LCL
0.06
input filter[J]. IEEE Transactions on Power
Electronics, vol. 18, no. 3, pp. 888-895, May 2003.
0.04
4. W. TONG, S. CHENG, H. XU Ê Investigation of
solution to the non-linear equation setup of
0.02 SHEPWM in converters [J]. Proceedings of the
CSEE, 1998, 18(5) : 357-360(in Chinese).
0.00 5. J. GAO, P. LI, J. SUN. Analysis of Resonance
0 200 400 600 800 1000
Frequency in Hz Distribution Range and Influence Factors of
Clustered Distributed Photovoltaic [J]. Power System
Fig. 6. Influence of power network intensity on harmonic and Clean Energy, 2016,32(07): 125-131+148.
voltage distribution. 6. L. WANG, Z. WANG, B. LU, C. ZHANG. Design
of the Controller of the Single Phase PV Grid-
As shown in Fig. 6, as SCR increasing, the resonant Connected Inverter with LCL Filter [J]. Power
frequency and the voltage amplification of the higher System and Clean Energy, 2014,30(12):114-118.
frequency resonant point increase significantly. For a 7. X. WANG, G. YAO, L. ZHOU, F. WANG, L. GU, J.
resonant point with a lower resonant frequency, the WANG. Analysis of Causes of Oscillation in the
resonant frequency increases and voltage amplification Wind Farm System Based on DFIG [J]. Power
factor decreases. System and Clean Energy, 2017, 33(07): 97-104+109.

5 Conclusion