Fire Alarm and Life Safety System

Inspection Certificate
For

Capri at Hunters Creek Bldg 5-


14316 Fredrick.
14316 Fredricksburg Drive
Orlando, Florida 32837

Tested to NFPA 72 Standards

This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages
of this report provide performance measurements, listed ranges of acceptable results, and complete
documentation of the inspection. Whenever discrepancies exist between acceptable performance
standards and actual test results, notes and/or recommended solutions have been proposed or provided
for immediate review and approval.

Inspection Date
Nov 12, 2019

Building: Capri at Hunters Creek Bldg 5-14316 Fredrick. Company: United Fire Protection - Orlando
Contact: Natalyn Rios Contact: Jeff Evans
Title: Contact Title: Tech
Executive Summary
Generated by: BuildingReports.com

Building Information
Building: Capri at Hunters Creek Bldg 5-14316 Contact: Natalyn Rios
Fredrick.
Address: 14316 Fredricksburg Drive Phone: 407-855-1088
Address: Fax:
City/State/Zip: Orlando, Florida 32837 Mobile:
Country: United States of America Email: natalyn.rios@fsresidential.com

Inspection Performed By
Company: United Fire Protection - Orlando Inspector: Jeff Evans
Address: 4602 35th Street Phone: 321-246-0894
Address: Suite 100 Fax:
City/State/Zip: Orlando, Florida 32811 Mobile:
Country: United States Email: jevans@united-fire.com

System Control Unit


Manufacturer: Silent Knight Inspection Date: 11/12/2019 IDC Style:
Model Number: 5198 Install Date: 11/12/2019 SLC Style:
Software Version: Version Date: 11/12/2019 NAC Style:
Location: 1st Breezeway Current Protection:

Monitoring
Company: Phone: Account #:

Central Station Signal Verification


Type: Mfg: Model #:
Test Time/Date: Restore Time:

United Fire Protection - Orlando Page 1 of 7 07/28/2020


Executive Summary
Inspection Summary
Total Items Serviced Passed Failed/Other
Category:
Qty % Qty % Qty % Qty %
Sound Test 1 5.88% 1 100.00% 1 100.00% 0 0%

Control 3 17.65% 3 100.00% 3 100.00% 0 0%

Initiating 12 70.59% 12 100.00% 12 100.00% 0 0%

Supervisory 1 5.88% 1 100.00% 1 100.00% 0 0%

Totals 17 100% 17 100.00% 17 100.00% 0 0%

Certification
Company: United Fire Protection - Orlando Building: Capri at Hunters Creek Bldg 5-14316 Fredrick.
Inspector: Jeff Evans Contact: Natalyn Rios

United Fire Protection - Orlando Page 2 of 7 07/28/2020


Executive Summary
Inspection & Testing
Generated by: BuildingReports.com

Building: Capri at Hunters Creek Bldg 5-


Control Panel: 1 - Silent Knight 5198
14316 Fredrick.
The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or
Failed/Other. Items are listed by Category. Each item includes the services performed, and the time & date at which testing
occurred.
Device Type Location Service Time Date

Passed
Control
Battery 1st Breezeway Tested 11:33:36 AM 11/12/2019
Battery 1st Breezeway Tested 11:35:37 AM 11/12/2019
Control Panel 1st Breezeway Tested 11:32:47 AM 11/12/2019
Initiating
Heat Detector 1st Breezeway Above FACP Tested 11:32:13 AM 11/12/2019
Pull Station 1st Breezeway Outside 503 Tested 11:36:49 AM 11/12/2019
Pull Station 1st Breezeway Outside 516 Tested 11:36:15 AM 11/12/2019
Pull Station 1st Outside 505 Tested 11:44:59 AM 11/12/2019
Pull Station 1st Outside 509 Tested 11:50:21 AM 11/12/2019
Pull Station 1st Outside 511 Tested 11:50:08 AM 11/12/2019
Pull Station 1st Outside 519 Tested 11:47:24 AM 11/12/2019
Pull Station 2nd Breezeway Outside 504 Tested 11:37:08 AM 11/12/2019
Pull Station 2nd Breezeway Outside 517 Tested 11:37:44 AM 11/12/2019
Pull Station 3rd Breezeway Outside 505 Tested 11:39:08 AM 11/12/2019
Pull Station 3rd Breezeway Outside 518 Tested 11:38:25 AM 11/12/2019
Waterflow Switch 1st Front of Building Tested 12:44:33 PM 11/12/2019
Supervisory
Tamper Switch 1st Front of Building Tested 12:45:30 PM 11/12/2019

United Fire Protection - Orlando Page 3 of 7 07/28/2020


Inspection & Testing
Service Summary
Generated by: BuildingReports.com

Building: Capri at Hunters Creek Bldg 5-14316 Fredrick.


The Service Summary section provides an overview of the services performed in this report.
Device Type Service Quantity

Passed
Battery Tested 2
Control Panel Tested 1
Heat Detector Tested 1
Pull Station Tested 10
Tamper Switch Tested 1
Waterflow Switch Tested 1
Total 16
Grand Total 16

United Fire Protection - Orlando Page 4 of 7 07/28/2020


Service Summary
Sound and Visual Testing
Generated by: BuildingReports.com

Building: Capri at Hunters Creek Bldg 5-14316 Fredrick.


The Sound and Visual Testing section lists various points throughout your building where audible and visual alarm
notification devices were tested. Any bar-coded audible and visual devices will appear in the Inspection and Testing
section of this report. Items in this section are grouped by Passed or Failed/Other. Where specific decibel readings were
recorded, they will appear under the ambient and alarm columns. The Voice column indicates whether the Sound Test
Point passed the Voice Intelligibility requirements. The STI or Sound Transmission Index is shown if recorded.
Intelligibility Sound
Location Comment Ambient Alarm Voice STI Test

Passed
Sound Test Points
Passed 0001

United Fire Protection - Orlando Page 5 of 7 07/28/2020


Sound and Visual Testing
Battery & Power Supply Testing
Generated by: BuildingReports.com

Building: Capri at Hunters Creek Bldg 5-


Control Panel: 1 - Silent Knight 5198
14316 Fredrick.
The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used
to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.
Rated Rated Post
Type Location Ah Volts Pre Test Test Min Ah Tested Ah
Battery
Passed
Sealed Lead Acid 1st Breezeway 8 12 13.57 11.30
Sealed Lead Acid 1st Breezeway 8 12 13.57 11.30

United Fire Protection - Orlando Page 6 of 7 07/28/2020


Battery & Power Supply Testing
Inventory & Warranty Report
Generated by: BuildingReports.com

Building: Capri at Hunters Creek Bldg 5- Control Panel: 1 - Silent Knight 5198
14316 Fredrick.
The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A
complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last
year, and devices installed for two years or more are grouped together for easy reference.
Device or Type Category % of Inventory Quantity
Heat Detector Initiating 5.88% 1
Control Panel Control 5.88% 1
Battery Control 11.76% 2
Pull Station Initiating 58.82% 10
Sound Test Sound Test 5.88% 1
Waterflow Switch Initiating 5.88% 1
Tamper Switch Supervisory 5.88% 1
Type Qty Model # Description Install Date

In Service - 90 Days - 1 Year


Heat Detector 1 11/12/2019
Interstate
Battery 2 5198 Sealed Lead Acid 11/12/2019
Milwaukee
Tamper Switch 1 VSC 11/12/2019
Potter Electric
Waterflow Switch 1 VSC 11/12/2019
RSG
Pull Station 7 RMS1-P 11/12/2019
Pull Station 3 RMS1-P Single Action 11/12/2019
Silent Knight
Control Panel 1 5198 11/12/2019

United Fire Protection - Orlando Page 7 of 7 07/28/2020


Inventory & Warranty Report