You are on page 1of 15

ext2.

qxd 13/02/01 17:01 Page 14

tyco Fire & Tyco Electronic


Security Product Group
FM200 Equipment & Components - Standard
FM200 (HFC 227ea) is known chemically as FM200 contains no bromine or chlorine and Typically FM200 requires a design concentration
Heptafluoropropane. FM200 is a colourless gas therefore has zero Ozone Depleting Potential of 7.5%, which is well below the 9% No
which is liquified under pressure for storage. Like (ODP). The atmospheric lifetime of FM200 is Observable Adverse Effect Level (NOAEL). The
Halon 1301 it has a low toxicity level and is super- between 31 and 42 years which along with its’ NOAEL for Halon 1301 is only 5% (the same as
pressurised with Nitrogen to 24.8bar (360psi). It ODP presents a long term solution to fire the design concentration).
rapidly extinguishes most commonly found fires protection requirements.
through a combination of chemical and physical FM200 has been found to be less toxic than Halon
mechanisms. 1301, which makes it safe for use in the fully
automatic mode in occupied areas.

Agent
Product Code
300.205.001
FM200

FM200 Containers - LPCB Approved


Container Size Diameter BS5045 Pt.2* EEC/84/525 EEC/84/527 DOT
6.5 Litre 222 mm 303.205.001 n/a 303.205.009 n/a
8 Litre 254 mm n/a n/a n/a 303.205.015
13 Litre 222 mm 303.205.002 n/a 303.205.010 n/a
16 Litre 254 mm n/a n/a n/a 303.205.016
25.5 Litre 222 mm 303.205.003 n/a 303.205.011 n/a
32 Litre 254 mm n/a n/a n/a 303.205.017
40 Litre 267 mm n/a 303.205.025 n/a n/a
52 Litre 406 mm 303.205.004 n/a 303.205.012 303.205.018
80 Litre 267 mm n/a 303.205.024 n/a n/a
106 Litre 406 mm 303.205.005 n/a 303.205.013 303.205.019
147 Litre 406 mm 303.205.006 n/a 303.205.014 303.205.020
180 Litre 406 mm 303.205.007 n/a n/a 303.205.021
FM200 systems are configured around a range of * Containers manufactured to BS5045 Part 2 will
containers specifically charged with the be supplied if available. Where these are not
appropriate quantity of FM200. Containers are available an alternative (EEC or DOT) will be
manufactured to meet the requirements of British, supplied as appropriate.
European or US D.O.T. standards as follows:
Applicable Standards
BS5045 Part 2 - Welded
EEC/84/525 - Seamless
EEC/84/527 - Welded
DOT 4BW 500/DOT 4BW (HSE) 34.5 - Welded
FM200 Container Label

FM200 Container Assembly Container Dia (mm) Ht to Valve Outlet Tare Weight Max FM200
Size (l) (A) (mm) (B) (Kg) Weight (Kg)
6.5 (BS) 222 300 9 6.5
6.5 (EC) 222 335 9 6.5
8 254 304 15 8
13 (BS) 222 495 12 13
13 (EC) 222 520 12 13
16 254 502 19 16
25.5 (BS/EC) 222 830 17 25.5
32 254 833 26 32
40 267 975 65 40
52 (BS) 406 580 49 52
52 (EC) 406 605 49 52
52 (DOT) 406 595 49 52
80 267 1785 108 80
106 (BS) 406 1021 72 106
106 (EC) 406 1040 72 106
106 (DOT) 406 1020 72 106
147 (BS) 406 1354 90 147
147 (EC) 406 1370 90 147
147 (DOT) 406 1360 90 147
180 (BS) 406 1634 106 180
180 (DOT) 406 1640 106 180

All dimensions/tare weights are approximate due to manufacturing tolerances

Page 14
ext2.qxd 13/02/01 17:02 Page 15

tyco Fire & Tyco Electronic


Security Product Group
Solenoid Actuator - Standard
The solenoid actuator is used to electrically downwards opening the schrader valve in the
operate the container valve and is operated at container valve.
24Vd.c. (Power Consumption - 4.8 Watts). The central pin must be in the retracted position
It is fitted directly onto the top of the container before the solenoid actuator is fitted, otherwise
valve by means of a knurled swivel coupling the container valve will be operated and the
which enables the unit to be positioned as contents discharged.
preferred for electrical connection. The power lead fitted with a DIN plug for
When fitting it is only necessary for the unit to be connecting to the solenoid is to be ordered
hand tight. separately (P/C 304.001.001).
The solenoid actuator is normally fitted to the
container designated as the ‘Master’. The Product Code
actuator is an electro-mechanical device which 304.205.001
when energised causes the central pin to move 24V Solenoid actuator

FM200 Solenoid Lead


Product Code
304.001.001
Solenoid lead

Solenoid Actuator - Flameproof


The Flameproof solenoid actuator is BASEEFA is not dislodged or removed as this will cause an
approved to Ex d IIB requirements and is immediate and potentially hazardous discharge of
operated at 24Vd.c. (Power Consumption - 11.2 FM200. It is recommended that at the time of
Watts). removal all slave containers are disconnected
The CENELEC/BASEEFA Approved Explosion from the ‘Master’.
proof version is available to order to meet EEx d NOTE: Earlier versions of this actuator were not
IIC requirements. designed to be removable from the container
The solenoid actuator is fitted to a schrader valve and no attempt must be made to do so
assembly on the side of the valve body by means whilst the container is pressurised, otherwise this
of a brass swivel nut. It is designed to be will result in immediate and potentially hazardous
removable from the schrader assembly. As there discharge of FM200.
will be pressure in the brass swivel nut, upon
removal of the solenoid the pressure will be Product Code
released. A ‘pop’ will be heard at the time of 304.205.002
removal. It is essential that the schrader assembly 24V Solenoid actuator (BASEEFA)

Local Manual Actuator


The local manual actuator is used to mechanically The unit is designed so that it may be fitted
operate the system at the container position. directly onto the top of the container
When fitting it is only necessary for the unit to be
hand-tight. Product Code
Accidental manual release is prevented by means 304.205.003
of a steel safety pin. The steel safety pin must be Local manual actuator
removed to allow the use of the local manual
actuator.
After removing the safety pin, manual operation is
caused by depressing the strike knob.

Pneumatic Actuator
The pneumatic actuator is used where container A minimum pressure of 4 bar is required to
operation is required by means of gas pressure ensure satisfactory operation.
from the system master container, remote manual Connection to the actuator is 1/4” B.S.P.
release unit or from a pilot container. When fitting
it is only necessary for the unit to be hand tight. Product Code
The unit is designed so that it may be fitted 304.205.004
directly onto the top of the container valve or be Pneumatic actuator
used in conjunction with a solenoid actuator, in
which case it fits directly on top of the solenoid
actuator.

Union Adaptor
The union adaptor is used to enable pipework to containers from the pipework straightforward.
be easily connected to and disconnected from It is recommended that the joint to the container
the FM200 container valve outlet adaptor. It is valve adaptor is made using PTFE tape.
available in two sizes, 25mm and 50mm.
One end is provided with a parallel female thread Product Codes
to provide a compatible joint to the container 309.002.011
outlet adaptor. The other end is provided with a 25mm (1”) Union adaptor
female NPT thread to enable pipework to be 309.002.012
connected. A swivel joint makes disconnecting 50mm (2”) Union adaptor

Page 15
ext2.qxd 13/02/01 17:02 Page 16

tyco Fire & Tyco Electronic


Security Product Group
Remote Manual Actuator (Mechanical)
The Remote Manual Actuator may be used to A pneumatic actuation port is provided to allow
operate the FM200 container from a remote the unit to double as a manual and pneumatic
position using the T528 mechanical manual actuator.
release unit which is connected to the remote The unit is designed so that it may be fitted
manual actuator by wire rope run in conduit. directly onto the top of the container valve or be
A shear strap is fitted to help guard against used in conjunction with a solenoid actuator, in
accidental release. Operation is caused by which case it fits directly on top of the solenoid
moving the lever through 90o, which will break the actuator. When fitting it is only necessary for the
shear strap. The steel safety pin will prevent swivel nut to be hand tightened.
operation and is to be removed upon Product Code
commissioning of the system. 304.205.005
Remote manual actuator (mechanical)
T528 Manual Release Unit
The T528 Manual Release Unit is used where Technical Specification
remote mechanical manual release of the FM200 Net Weight: 0.9Kg
system is required.
The unit comprises of a box with a hinged yellow Product Code
lid which is held in the closed position by two 526.001.018
frangible washers. Inside the unit is a red bar T528 Mechanical manual release unit
which is to be connected to a wire rope run
through a system of conduit and corner pulleys to
the Remote Manual Actuator.
Operation of the FM200 system using the T528 is
a two stage action. Firstly the hinged lid is pulled
downwards towards the operator. This action will
break the frangible washers and expose the red
operating bar. System operation is caused by
pulling hard on the red bar. System discharge will
occur immediately.

Pressure Switch - Standard


The Pressure Switch is normally mounted on a Product Code
connection in the pneumatic actuation tubing and 305.205.002
may be used to provide an electrical indication of Gas released pressure switch
release of FM200 or to perform ventilation shut-
downs or other interlock functions.
The pressure switch requires to be manually reset
following operation.
A minimum pressure of 3 bar is required to
ensure satisfactory operation. Connection to the
pressure switch may be either 1/2” NPT (male) or
1/8” NPT (female).

Pressure Switch - Flameproof


The Flameproof Pressure Switch is BASEEFA Product Code
Approved to meet Ex d IIB requirements. 305.205.003
The Pressure Switch requires to be manually Gas released pressure switch (BASEEFA)
reset following operation.
A minimum pressure of 2 bar is required to
ensure satisfactory operation. Connection to the
pressure switch is 1/4” NPT (female).
A CENELEC/BASEEFA approved explosion proof
version is available to order to meet EEx d IIC
requirements.

Supervisory Pressure Switch


The Supervisory Pressure Switch is an optional
item that is factory fitted at the time of order and
is used to continuously monitor the container
pressure.
In the event of the container pressure falling
below 18 bar the switch will operate to provide an
electrical signal.
The operating pressure is factory set and no
adjustments may be carries out on site.

Product Code
305.205.001
Supervisory pressure switch

Page 16
ext2.qxd 13/02/01 17:04 Page 17

tyco Fire & Tyco Electronic


Security Product Group
Supervisory Pressure Switch - BASEEFA/CENELEC
A BASEEFA Approved Supervisory Pressure To fit the Flameproof or Explosion proof switch
Switch (P/C 305.205.004) is available to meet the requires connecting pneumatic actuation tubing
Ex d IIB requirements. between the supervisory pressure switch port on
A CENELEC/BASEEFA Approved explosion proof the valve and the supervisory pressure switch.
version is available to order to meet EEx d IIC This process involves removing the plug from the
requirements. supervisory pressure switch port in the valve and
Both the Flameproof and Explosion proof quickly connecting the actuation tubing. Upon
versions are variations on the Flameproof and removal of the plug it is normal for a small
Explosion proof ‘gas discharged’ pressure quantity of gas to leak. It is critical that all
switches. connections are gas tight otherwise the container
It is recommended that the Flameproof and will gradually lose its charge.
Explosion proof switches are wall mounted Product Code
adjacent to the container. 305.205.004
Connection to the switch is 1/4” NPT (female). Supervisory pressure switch (BASEEFA)

FM200 Nozzles - Engineered: Aluminium


The Discharge Nozzles are available in a 180o and Where the size of any hazard enclosure
360o pattern and are designed to uniformly determines that one nozzle does not provide
distribute FM200 throughout the hazard area. sufficient coverage the hazard should be
The 180o type has seven ports and the 360o type theoretically sub divided into appropriately sized
has eight ports. modules.
For Pre-Engineered systems the nozzles are Nozzles are provided in aluminium as standard,
available pre-drilled in three sizes. but are available in brass or stainless steel to
Engineered nozzles are available in seven sizes order.
and are drilled with the specific design
requirement.

NOZZLE TYPE PRODUCT CODE Nozzle Coverage


Pre-Engineered Engineered Discharge Nozzles
10mm (180o) Not Available 310.205.022
15mm (180o) Not Available 310.205.011 9 metres
20mm (180o) Not Available 310.205.024
180 Nozzle o

25mm (180o) 310.205.001 310.205.012


32mm (180o) Not Available 310.205.026
40mm (180o) 310.205.003 310.205.013
9 metres
50mm (180o) 310.205.005 310.205.014
10mm (360 )
o
Not Available 310.205.023 360 Nozzle o

15mm (360o) Not Available 310.205.015


20mm (360o) Not Available 310.205.025
25mm (360o) 310.205.002 310.205.016
32mm (360 )
o
Not Available 310.205.027
40mm (360o) 310.205.004 310.205.017
50mm (360o) 310.205.006 310.205.018
Thread Size 10mm NPT 15mm NPT 20mm NPT 25mm NPT 32mm NPT 40mm NPT 50mm NPT
A 25.0mm 29.0mm 35.0mm 41.0mm 50.0mm 60.0mm 76.0mm
B 33.5mm 41.0mm 47.0mm 52.0mm 62.0mm 68.0mm 89.0mm

FM200 Container Brackets (Welded Containers) - 6.5/13/25.5 Litre


The Container Brackets are designed to securely Product Codes
fix a single container to a wall or supporting 311.205.001
structure. 6.5 litre container bracket assembly
The brackets are of a design that allows them to 311.205.002
be wall mounted. They comprise of a steel 13 litre container bracket assembly
cruciform section which is fixed to the wall or 311.205.003
supporting structure and a steel strap used to 25.5 litre container bracket assembly
firmly secure the container to the bracket. A lug at
the bottom of the vertical back section is used to
support the weight of the container. The strap is
fixed around the container to the horizontal back
section using nuts and bolts.

PRESENT ONLY
ON BRACKET
ASSEMBLY
311.205.003 HOLE DIA 11.5 (TYP)

PRODUCT CODE DIM A


311.205.001 172
311.205.002 375
311.205.003 715

SEE DETAIL A

DETAIL A
6.5/13/25.5 LITRE CONTAINER BRACKET

Page 17
ext2.qxd 13/02/01 17:04 Page 18

tyco Fire & Tyco Electronic


Security Product Group
FM200 Container Brackets (Welded Containers) - 8/16/32 Litre
The container brackets are designed to securely
fix a single container to a wall or supporting
structure. The containers are to be floor mounted
only.
The bracket assembly comprises two steel straps,
steel channel section (400mm long) and nut and
bolt.

Product Code
311.205.013
Container brackets 8/16/32 litre containers

FM200 Container Brackets (Seamless Containers)


The bracket is designed to securely fix containers Product Codes
to a wall or supporting structure. It comprises of a SL 93841
section of steel channel and a universal clamp. Container strap - 267mm
The steel channel sections are fixed securely to SL 93852
the wall or supporting structure. The universal Single container wall rack
clamp has a special slotted section which allows
each half to be fitted into the steel channel. The
two halves are clamped together in position
around the container using a nut and bolt.

FM200 Container Brackets (Welded Containers) - 52/106/147/180 Litre


The Container Brackets are designed to securely
fix a single container to a wall or supporting
structure. The containers are to be floor mounted
only.
The bracket assembly comprises a steel strap,
steel channel section and two spring nuts and
bolts.
Product Code
311.205.004
52-180 litre container bracket assembly

210

52/106/147/180 LITRE CONTAINER BRACKET

Manifolds
Manifolds are designed to enable all the Type Product Code
Manifold
containers in a row to be connected to the 65mm x 2 port 307.205.012
supply pipe and may be used in multi container 65mm x 3 port 307.205.013
applications or in main and reserve systems. 65mm x 4 port 307.205.014
All manifolds are pressure tested at the works to 80mm x 2 port 307.205.001
90 bar. 80mm x 3 port 307.205.002
All Product Code Numbers include the manifold 80mm x 4 port 307.205.003
and Check Valves. 80mm x 5 port 307.205.011
65/80/100mm NPT (both ends) 100mm x 2 port 307.205.004
100mm x 3 port 307.205.005
50mm Check Valve 100mm x 4 port 307.205.006
100mm x 5 port 307.205.007
100mm x 6 port 307.205.008
150mm x 3 port 307.205.009
150mm x 4 port 307.205.010
150mm x 5 port 307.205.015
150mm x 6 port 307.205.016
150mm x 7 port 307.205.017
150mm x 8 port 307.205.018
150mm x 9 port 307.205.019
150mm x 10 port 307.205.020
Page 18
ext2.qxd 13/02/01 17:05 Page 19

tyco Fire & Tyco Electronic


Security Product Group
FM200 Manifold Support Brackets
Manifold support brackets are designed to 311.205.011
provide a firm fixing of the manifold to a wall or 100mm Manifold support bracket
supporting structure. Two brackets are required 311.205.012
for each manifold used. 150mm Manifold support bracket

Product Codes
311.205.015
65mm Manifold support bracket
311.205.010
80mm Manifold support bracket

Discharge Hoses
The flexible Discharge Hose connects the Product Codes
container to the check valve on the manifold. 306.205.001
A swivel fitting at the end of the hose allows ease 32mm flexible discharge hose
of installation. 306.205.002
NOTE: The purpose of the 32mm hose is to 50mm flexible discharge hose
prevent excessive pressure loss experienced
when using a 25mm hose from the 25mm FM200
container valve. Connection to the 25mm
container valve is by means of a 32mm x 25mm
adaptor included as part of the 32mm hose
assembly.

Manual Release Caution Plate


The Manual Release Caution Plate provides
instructions to personnel on the use of manual
controls.
One plate is to be fixed adjacent to all positions
from where FM200 can be released manually.
Four 4mm fixing holes are provided.
Technical Specification
Dimensions: 210 x 75 mm

Product Code
314.205.003
Manual release plate

Door Caution Plate - Lock Off


The Door Caution Plate (lock-off) provides Technical Specification
instructions to personnel who may enter an area Dimensions: 210 x 210 mm
protected with FM200.
This version of the caution plate is used when it is Product Code
necessary to instruct personnel to place the 314.205.001
system on manual control before entering the Door caution plate (lock off)
protected area.
One plate is to be fixed to all entrance doors into
an FM200 protected area.
Four 4mm fixing holes are provided.

Door Caution Plate - No Lock-Off


The Door Caution Plate (no lock-off) provides Technical Specification
instructions to personnel who may enter an area Dimensions: 210 x 210 mm
protected with FM200.
This version of the caution plate is used when it is Product Code
permitted to leave the system on automatic 314.205.002
control even while the area is occupied. Door caution plate (no lock off)
One plate is to be fixed to all entrance doors into
an FM200 protected area.
Four 4mm fixing holes are provided.

FM200 Actuation Ancillaries


Product Codes
308.002.001
309.013.001 6mm Kunifer tube
308.002.002
6mm Half hard copper tube
309.010.002
309.010.002 6mm x 1/8” NPT stud coupling
309.010.003
309.010.003 6mm x 1/4” NPT stud coupling
309.011.001
309.011.001 6mm Straight coupling
309.013.001
308.002.001 6mm Equal tee

Page 19
ext2.qxd 13/02/01 17:05 Page 20

tyco Fire & Tyco Electronic


Security Product Group
Typical Container Arrangement

Reference Description
1 FM200 Container Assembly
2 Container Bracket
3 Container Nameplate
4 Pressure Gauge
5 Solenoid Actuator
6 Local Manual Actuator
6a Safety Pin
7 Supervisory Pressure Switch*
8 Pneumatic Actuator
9 Pressure Switch
10 Discharge Nozzle
11 Manual Release Caution Plate
12 Container Design Details
13 Discharge Pipework
14 Pneumatic Actuation Tubing
15 Junction Box

* Optional or variable equipment - not included in


the standard kits.

KITS - Master Containers (Solenoid Operated)


In order to assist in the ordering of correct solenoid, solenoid lead, manual actuator, pressure switches, door caution plates, nozzles,
components to form the FM200 system a number pressure switch, actuation tubing/fittings and pipework, fittings, fixings and any special items
of kits are available to cover the most popular manual caution plate. such as distribution valves.
range of containers. The kit excludes items which are specific to a
Each kit comprises the FM200 container, bracket, individual enclosure such as FM200, supervisory

KITS - Master Containers (Solenoid Operated)


Description Kit No. Weight
6.5 Litre Solenoid operated container assy 901.505.048 13 Kgs
13 Litre Solenoid operated container assy 901.505.049 16 Kgs
25.5 Litre Solenoid operated container assy 901.505.050 22 Kgs
52 Litre Solenoid operated container assy 901.505.051 48 Kgs
106 Litre Solenoid operated container assy 901.505.052 69 Kgs
147 Litre Solenoid operated container assy 901.505.053 84 Kgs
180 Litre Solenoid operated container assy 901.505.054 98 Kgs

KITS - Slave Containers (Pneumatically Operated)


Each kit comprises the FM200 container, bracket, pressure switches, door caution plates, nozzles,
pneumatic actuator and actuation tubing/fittings pipework, fittings, fixings and any special items
and manual caution plate. such as distribution valves.
The kit excludes items which are specific to an
individual enclosure such as FM200, supervisory

KITS - Master Containers (Solenoid Operated)


Description Kit No. Weight
6.5 Litre Pneumatically operated container assy 901.505.041 10 Kgs
13 Litre Pneumatically operated container assy 901.505.042 14 Kgs
25.5 Litre Pneumatically operated container assy 901.505.043 19 Kgs
52 Litre Pneumatically operated container assy 901.505.044 46 Kgs
106 Litre Pneumatically operated container assy 901.505.045 67 Kgs
147 Litre Pneumatically operated container assy 901.505.046 82 Kgs
180 Litre Pneumatically operated container assy 901.505.047 96 Kgs

Page 20
ext2.qxd 13/02/01 17:06 Page 21

tyco Fire & Tyco Electronic


Security Product Group
FM200 Equipment & Components - UL Listed
Agent
Product Code
300.205.001
FM200

FM200 Containers - Dot (UL)


Systems are configured around a range of 303.205.020
containers specifically charged with the 147 Litre container assembly
appropriate quantity of FM200. Containers are 303.205.021
manufactured to meet the requirements of 180 Litre container assembly
DOT4BW500 / DOT4BW(HSE)34.5.

Product Codes
303.205.015
8 Litre container assembly
303.205.016
16 Litre container assembly
303.205.017
32 Litre container assembly
303.205.018
52 Litre container assembly
303.205.019
106 Litre container assembly Label fitted to containers on UL listed systems

Solenoid Actuator - Stackable (UL)


The solenoid actuator is used to electrically when energised causes the central pin to move
operate the container valve. The solenoid is downwards opening the schrader valve in the
operated at 24Vd.c. (Power Consumption - 4.8 container valve.
Watts). The central pin must be in the retracted position
It is fitted directly onto the top of the container before the solenoid actuator is fitted, otherwise
valve by means of a knurled swivel coupling the container valve will be operated and the
which enables the unit to be positioned as contents discharged.
preferred for electrical connection. The power lead fitted with a DIN plug for
When fitting it is only necessary for the unit to be connecting to the solenoid is to be ordered
hand tight. separately (P/C 304.001.001).
The solenoid actuator is normally fitted to the Product Code
container designated as the ‘Master’. The 304.205.008
actuator is an electro-mechanical device which 24V Solenoid actuator

Solenoid Actuator - Side Mounted (UL)


The solenoid actuator is fitted to a schrader Product Code
assembly on the side of the valve body by means 304.205.008
of a brass swivel nut. It is designed to be 24V Solenoid actuator (side mounted)
removable from the schrader assembly. As there
will be pressure in the brass swivel nut, upon
removal of the solenoid the pressure will be
released. A ‘pop’ will be heard at the time of
removal. It is essential that the schrader assembly
is not dislodged or removed as this will cause an
immediate and potentially hazardous discharge of
FM200.

Local Manual Actuator


The local manual actuator is used to mechanically Product Code
operate the system at the container position. 304.205.003
When fitting it is only necessary for the unit to be Local manual actuator
hand-tight.
Accidental manual release is prevented by means
of a steel safety pin. The steel safety pin must be
removed to allow the use of the local manual
actuator.
After removing the safety pin, manual operation is
caused by depressing the strike knob.
The unit is designed so that it may be fitted
directly onto the top of the container

Page 21
ext2.qxd 13/02/01 17:07 Page 22

tyco Fire & Tyco Electronic


Security Product Group
Solenoid Actuator - Pneumatic Actuator (UL)
The pneumatic actuator is used where container Product Code
operation is required by means of gas pressure 304.205.004
from the system master container, remote manual Pneumatic actuator
release unit or from a pilot container. When fitting
it is only necessary for the unit to be hand tight.
The unit is designed so that it may be fitted
directly onto the top of the container valve or be
used in conjunction with a solenoid actuator, in
which case it fits directly on top of the solenoid
actuator.
A minimum pressure of 4 bar is required to
ensure satisfactory operation.
Connection to the actuator is 1/4” B.S.P.

FM200 Container Brackets (UL)


The container brackets are designed to securely
fix a single container to a wall or supporting
structure. The containers are to be floor mounted
only.
The bracket assembly comprises two steel straps,
steel channel section (400mm long) and nut and
bolt.

Product Codes
311.205.013
8-32 litre Container bracket assembly
311.205.014
52-180 litre Container bracket assembly

FM200 Actuation Ancillary (UL)


Product Codes
306.205.003
309.013.005
Flexible pilot hose 1/4” BSP swivel female
309.013.003
Male tee 1/4” BSPP x 1/4” BSPT
309.013.004
306.205.003 Male elbow 1/4” BSPT x 1/4” BSPP
309.013.005
309.013.004 309.013.003 1/4” BSPT x 1/4” BSPP adaptor

Supervisory Pressure Switch (UL)


The Supervisory Pressure Switch is an optional Product Code
item that is Factory fitted at the time of order and 305.205.006
is used to continuously monitor the container Supervisory pressure switch
pressure.
In the event of the container pressure falling
below 18 bar the switch will operate to provide an
electrical signal.
The operating pressure is factory set and no
adjustments may be carries out on site.

Gas Released Pressure Switch (UL)


The Pressure Switch is normally mounted on a Product Code
connection in the pneumatic actuation tubing and 305.205.007
may be used to provide an electrical indication of Gas released pressure switch
release of FM200 or to perform ventilation shut-
downs or other interlock functions.
The pressure switch requires to be manually reset
following operation.
A minimum pressure of 3 bar is required to
ensure satisfactory operation. Connection to the
pressure switch may be either 1/2” NPT (male) or
1/8” NPT (female).

Page 22
ext2.qxd 13/02/01 17:07 Page 23

tyco Fire & Tyco Electronic


Security Product Group
FM200 Manifolds (UL)
Manifolds are designed to enable all the Type Product Code
Manifold
containers in a row to be connected to the 65mm x 2 port 307.205.012
supply pipe and may be used in multi container 65mm x 3 port 307.205.013
applications or in main and reserve systems. 65mm x 4 port 307.205.014
All manifolds are pressure tested at the works to 80mm x 2 port 307.205.001
90 bar. 80mm x 3 port 307.205.002
All Product Code Numbers include the manifold 80mm x 4 port 307.205.003
and Check Valves. 80mm x 5 port 307.205.011
65/80/100mm NPT (both ends) 100mm x 2 port 307.205.004
100mm x 3 port 307.205.005
50mm Check Valve 100mm x 4 port 307.205.006
100mm x 5 port 307.205.007
100mm x 6 port 307.205.008
150mm x 3 port 307.205.009
150mm x 4 port 307.205.010
150mm x 5 port 307.205.015
150mm x 6 port 307.205.016
150mm x 7 port 307.205.017
150mm x 8 port 307.205.018
150mm x 9 port 307.205.019
150mm x 10 port 307.205.020

FM200 Manifold Support Brackets


Manifold support brackets are designed to 311.205.011
provide a firm fixing of the manifold to a wall or 100mm Manifold support bracket
supporting structure. Two brackets are required 311.205.012
for each manifold used. 150mm Manifold support bracket

Product Codes
311.205.015
65mm Manifold support bracket
311.205.010
80mm Manifold support bracket

Discharge Hoses
The flexible Discharge Hose connects the Product Codes
container to the check valve on the manifold. 306.205.001
A swivel fitting at the end of the hose allows ease 32mm Flexible discharge hose
of installation. 306.205.002
NOTE: The purpose of the 32mm hose is to 50mm Flexible discharge hose
prevent excessive pressure loss experienced
when using a 25mm hose from the 25mm FM200
container valve. Connection to the 25mm
container valve is by means of a 32mm x 25mm
adaptor included as part of the 32mm hose
assembly.

FM200 Nozzles: Engineered: Brass (UL)


The Discharge Nozzles are available in a 180o and Product Codes
360o pattern and are designed to uniformly 310.205.028
distribute FM200 throughout the hazard area. 10mm x 180/360 Degree (state which)
The 180o type has seven ports and the 360o type 310.205.029
has eight ports. 15mm x 180/360 Degree (state which)
Nozzles are available in seven sizes and are 310.205.030
drilled with the specific design requirement. 20mm x 180/360 Degree (state which)
Where the size of any hazard enclosure 310.205.031
determines that one nozzle does not provide 25mm x 180/360 Degree (state which)
sufficient coverage the hazard should be 310.205.032
theoretically sub divided into appropriately sized 32mm x 180/360 Degree (state which)
modules. 310.205.033
Nozzles are provided in brass as standard, but 40mm x 180/360 Degree (state which)
are available in stainless steel to order. 310.205.034
50mm x 180/360 Degree (state which)

Page 23
ext2.qxd 13/02/01 17:07 Page 24

tyco Fire & Tyco Electronic


Security Product Group
FM200 Manual Release Caution Plate (UL)
The Manual Release Caution Plate provides
instructions to personnel on the use of manual
controls.
One plate is to be fixed adjacent to all positions
from where FM200 can be released manually.
Four 4mm fixing holes are provided.
Technical Specification
Dimensions: 210 x 75 mm

Product Code
314.205.003
Manual release plate

FM200 Door Caution Plate - Lock Off (UL)


The Door Caution Plate (lock-off) provides Product Code
instructions to personnel who may enter an area 314.205.001
protected with FM200. Door caution plate (lock off)
This version of the caution plate is used when it is
necessary to instruct personnel to place the
system on manual control before entering the
protected area.
One plate is to be fixed to all entrance doors into
an FM200 protected area.
Four 4mm fixing holes are provided.
Technical Specification
Dimensions: 210 x 210 mm

FM200 Door Caution Plate - No Lock-Off (UL)


The Door Caution Plate (no lock-off) provides Product Code
instructions to personnel who may enter an area 314.205.002
protected with FM200. Door caution plate (no lock off)
This version of the caution plate is used when it is
permitted to leave the system on automatic
control even while the area is occupied.
One plate is to be fixed to all entrance doors into
an FM200 protected area.
Four 4mm fixing holes are provided.
Technical Specification
Dimensions: 210 x 210 mm

Page 24
ext2.qxd 13/02/01 17:07 Page 25

tyco Fire & Tyco Electronic


Security Product Group
Carbon Dioxide Equipment & Components
Containers EC
Container Details The container valve is fitted with a burst disk rated to operate at 190 bar.
Water Capacity 67.0 Litres (nominal) Containers are painted signal red and are provided with a label providing
CO2 Capacity 45Kg handling and maintenance instructions.
Length 1507mm +/- 10mm Product Codes
Outside Diameter 267mm 303.200.011
Max. Working Pressure 194 Bar 45Kg Container assy complete with solenoid and CO2
Test Pressure 250 Bar 303.200.012
Nominal Tare Weight 76.9Kg 45Kg Container assy complete with CO2
Nominal Gross Weight 122Kg

The standard container is 67 Litre nominal


capacity with a 45Kg fill of Carbon Dioxide.
Containers are manufactured to the EC directive
EEC/84/525 and the complete assembly consists
of:
. CO2 Container
. CO2 Valve & Syphon Tube
. Valve Protection Cap
. 45 Kgs CO2

Local Manual/Pneumatic Actuator (Type D)


Accidental manual release is prevented by means connect the 3/16” pilot hose to the inlet/outlet
of a steel safety pin. The steel safety pin must be ports of the actuator requires the use of 3/16” x
removed to allow the use of the operating lever. 1/8” adaptor (P/C 309.017.005). These adaptors
After removing the safety pin manual operation is must not be omitted as this could cause the
caused by moving the operating lever through system operation to fail. For remote manual
105o. actuation the actuator is fitted with a shear strap
A maximum force of approximately 3kgf is in place of the steel safety pin. This must be
required to operate the actuator. specified at time of order.
Pneumatic operation is possible by means of When operated the actuator latches to keep the
actuation ports in the main body of the actuator. container valve open. The knurled reset plunger
At normal storage conditions ie 20oC must be pulled to reset the actuator after
approximately 8.5 bar is required. operation.
The Local Manual/Pneumatic Actuator may be Two ports are provided at 180o to each other. One Technical Specification
used to operate the CO2 container by means of a port is used as an inlet port and the other as an Net Weight: 0.4Kg
local mechanical action or by pneumatic means. outlet port. Interconnection between adjacent
The actuator is fitted directly onto the top of the actuators is by means of 3/16” pilot hoses. (Either Product Code
container valve and is retained by a steel locating port can be used as the inlet/outlet ports). No 302.200.026
clip. A grub screw in the front of the container port must be left open ie. depending on the Manual/pneumatic actuator
valve may be tightened to secure the actuator in layout required, manual bleed valves, pilot hoses
the preferred orientation. or pneumatic actuation plugs may be fitted. To

Pneumatic Actuator (Type D)


container valve and is retained by a steel locating layout required, manual bleed valves, pilot hoses
clip. A grub screw in the front of the container or pneumatic actuation plugs may be fitted. To
valve may be tightened to secure the actuator in connect the 3/16” pilot hose to the inlet/outlet
the preferred orientation. ports of the actuator requires the use of 3/16” x
Pneumatic operation is through actuation ports in 1/8” adaptor (P/C 309.017.005). These adaptors
the main body of the actuator. A minimum must not be omitted as this could cause the
operating pressure of 31 bar is required at a system operation to fail.
container pressure of 200 bar. At normal storage When operated the actuator latches to keep the
conditions ie. 20 oC approximately 8.5 bar is container valve open. The knurled reset plunger
required. must be pulled to reset the actuator after
Two ports are provided at 180o to each other. One operation.
The Pneumatic Actuator may be used to operate Technical Specification
port is used as an inlet port and the other as an
slave containers by means of pressure from a
outlet port. Interconnection between adjacent Net Weight: 0.3Kg
pilot container or from the system master Product Code
actuators is by means of 3/16” pilot hoses (Either
container. port can be used as the inlet/outlet ports). No 302.200.027
The actuator is fitted directly onto the top of the
port must be left open ie. depending on the Double slave actuator

PIlot Hoses (527mm & 374mm)


The 374mm Pilot Hose is used to take pilot Each end is fitted with a 3/16” Enots (male) swivel
306.200.003 pressure from one pneumatic actuator to the next fitting. A minimum bend radius of 75mm must be
in the container bank. allowed.
The 527mm Pilot Hose is used to take pilot Technical Specification
pressure from the type D check valve to the first Net Weight: 0.04Kg (374mm)
slave container in the container bank and also 0.05Kg (527mm)
between the end actuators of the front and back Product Codes
row on double row systems. 306.200.003
NOTE: Adaptors are required to correctly connect 3/16” x 527mm Pilot hose
the hoses to the local manual/pneumatic actuator 306.200.004
306.200.004
or pneumatic actuator. 3/16” x 374mm Pilot hose

Page 25
ext2.qxd 13/02/01 17:08 Page 26

tyco Fire & Tyco Electronic


Security Product Group
Manual Vent Valve
The Manual Vent Valve serves two functions. Connection to the local manual/pneumatic
Firstly, it acts to relieve a gradual pressure build actuator requires the use of one 3/16” x 1/4” BSP
up occurring, perhaps as a result of a leaking adaptor (P/C 309.017.004), one of 3/16” nipple
pilot container, master container or solenoid. (P/C 309.005.009) and one 3/16” x 1/8” BSP
Secondly, it provides a means by which pressure adaptor (P/C 309.017.005).
trapped in the actuation circuits may be manually Technical Specification
relieved. Net Weight: 0.12Kg
The manual vent valve relieves automatically up
to a pressure of approximately 2 bar and seals at Product Code
pressures above this. 302.200.021
Pressure is relieved manually by pulling the Manual vent valve
knurled reset plunger.

Pilot Line Non Return Valve


The Pilot Non Return Valve is designed to allow Product Code
CO2 pressure into various parts of the pneumatic 302.200.015
actuation system, but prevent that pressure from Pilot line non return valve
being lost when the source pressure diminishes.
It is essential that it is fitted the correct way
round, otherwise the system may not operate.

Technical Specification
Net Weight: 0.02Kg
Thread Size: 3/16” Enots (male)

Pneumatic Actuation Fittings


A variety of pneumatic actuation fittings are
available to connect the various actuation hoses
309.017.004 309.017.005 and devices.
Product Codes
309.017.004
3/16” x 1/4” Adaptor
309.017.005
3/16” x 1/8” Adaptor
309.005.009
309.005.009 3/16” Nipple

Manifold Check Valve


The Manifold Check Valve allows for the container removed. The check valve is designed
temporary removal of a container from the system for use in the vertical position and one check
and is the means to connect the flexible valve is used for each container connected to the
discharge hose to the manifold. It may also be manifold.
used as an adaptor between the pipework and Technical Specification
the end of the flexible discharge hose on single Net Weight: 0.1Kg
container systems.
The manifold check valve is not designed to give Product Code
complete sealing, but will prevent a substantial 302.200.014
loss of CO2 should the system discharge with a Manifold check valve

Manifold Check Valve (Type D)


The type D manifold check valve has a dual
function and is generally used with the master
container to permit operation of slave containers.
Its first function is that of the standard manifold
check valve and its second is to provide a
connection from which CO2 pressure may be
tapped to pneumatically operate slave containers.
Product Code
302.200.020
Type D manifold check valve

Discharge Hose
The 1/2" flexible discharge hose connects the Product Code
container valve outlet to the check valve on the 306.200.005
manifold and is sufficiently flexible to 15mm Discharge hose
accommodate the small variations found in
container heights. Swivel female couplings allow
ease of installation in any orientation.
Technical Specification
Net weight 0.85 kgs.

Page 26
ext2.qxd 13/02/01 17:08 Page 27

tyco Fire & Tyco Electronic


Security Product Group
CO2 Manifolds
Product Code Description Weight
307.200.009 25mm (1”) x 2 Point Manifold 2.5Kg
307.200.010 25mm (1”) x 3 Point Manifold 3.5Kg
307.200.011 25mm (1”) x 4 Point Manifold 4.5Kg
307.200.012 25mm (1”) x 5 Point Manifold 5.5Kg
307.200.013 32mm (1 1/4”) x 2 Point Manifold 3.0Kg
307.200.014 32mm (1 1/4”) x 3 Point Manifold 4.0Kg
307.200.015 32mm (1 1/4”) x 4 Point Manifold 6.0Kg
307.200.016 32mm (1 1/4”) x 5 Point Manifold 7.4Kg
The CO2 manifold is designed to enable all the configuration to suit any number of containers on
containers in a row to be connected to the supply a system.
pipe. Non-standard sizes may be produced to order.
The standard manifolds are for 2, 3, 4 or 5 All manifolds are galvanised inside and out and
containers and are available in two sizes, 25mm pressure tested to 190 bar.
(1”) and 32mm (1 1/4”). The manifolds may be
joined using sockets or tees to produce any

Odouriser 2000
The Odouriser 2000 is designed to give a each 2000Kg of CO2. The odouriser must be
distinctive small to the CO2 and is particularly replaced after each operation of the system.
useful in basements or low lying areas in the Connection to the pipework is 1/2” A.P.I. (male).
vicinity of the system or any place where CO2 Technical Specification
could drift to following a discharge. Net Weight: 0.275Kg
Liquid citrus odour is contained in the body of the
odouriser and is sealed in by a lead disc. Product Code
Pressure of the discharging CO2 causes the disc 305.200.003
to rupture and allows the liquid to escape and mix Odouriser
with the CO2. One type odouriser is used for

Pressure Operated Distribution Valve


The Pressure Operated Distribution Valve is necessary to lock the pressure in. The valve is
designed to be used as a safety stop valve or as provided with switches as standard to provide a
a distribution / selector valve. signal to confirm operation of the valve. Sizes
The valve may be operated either via pilot 20mm to 50mm are provided with NPT screwed
pressure or manually through handwheel connections. Sizes 80mm to 150mm are available
operation. to order and are provided with flanged
A pressure of approximately 11 bar is required to connections. The actuation port is 1/8” A.P.I.
open the valve and keep it open. Removal of the
pilot pressure from the valve will allow it to close
and depending on the requirements it may be

Valve Sizes Product Code


20mm (3/4”) 302.200.028
25mm (1”) 302.200.029
32mm (1 1/4”) 302.200.030
40mm (1 1/2”) 302.200.031
50mm (2”) 302.200.032
80mm (3”) 302.200.033
100mm (4”) 302.200.034
150mm (6”) 302.200.035

‘S’ Type Nozzle


rules governing the number of nozzles that Enclosure Height Nozzle Coverage
should be applied to any type of hazard, however, 3.6m 15m2
nozzle spacing is dependent on the room height, 3.3m 20m2
flow rate, potential obstructions etc., but as a rule 3.0m 30m2
of thumb, the nozzle may be used to cover an 2.7m 40m2
area of approximately 30 square metres in a room 2.4m 50m2
3 metres high, the nozzle coverage table provides 2.1m 60m2
additional guidance. 1.8m 70m2
In order to reduce the possibility of the nozzle 1.5m 80m2
orifice becoming blocked during discharge, 1.2m 90m2
terminal nozzles should be installed in a tee and a 1.0m 100m 2
The ‘S’ Type Nozzle is used in most total flooding
short length of pipe (100mm) capped/plugged Product Code
applications. It is normally recommended that the
should be fitted to act as a dirt trap. 310.200.001
nozzles are uniformly positioned on the ceiling of
an enclosure to ensure a satisfactory distribution Type ‘S’ nozzle 15mm (1/2”) (Code 3-18)
Technical Specification Orifice codes must be stated at the time of order.
of CO2. Where it is not practical to position the
Net Weight: 0.135Kg
nozzles on the ceiling, it may be acceptable
Finish: Satin Chrome
depending on the room dimensions to position
Connection to the pipework is 15mm (1/2”) NPT
them around the perimeter at high level.
(female).
For CO2 total flooding systems there are no strict

Page 27
ext2.qxd 13/02/01 17:09 Page 28

tyco Fire & Tyco Electronic


Security Product Group
Fog Type Nozzle
The fog nozzle is a discharge horn designed to Product Code 310.200.007 describes a two hole
project CO2 in the direction of the fire hazard. version of the nozzle (Orifice Code 3 only) and
CO2 is discharged in the form of a mist or fog Product Code 310.200.008 describes a four hole
and the discharge velocity is relatively low, thus version (Orifice Codes 3.5 to 18).
making it suitable for use in local application Technical Specification
systems particularly where flammable liquids are Net Weight: 0.46Kg
involved and there could be a danger of
splashing from the impingement of CO2. Product Codes
Nozzle positioning is dependent on the type of 310.200.007
hazard, the method employed in calculating the Fog nozzle (code 3 only)
CO2 quantity, the nozzle height and flow required. 310.200.008
Connection to the pipework is 20mm (3/4”) NPT Fog nozzle (code 3.5-18)
(male).

Duct Type Nozzle


The Duct Nozzle is a variation on the fog type Product Code 310.200.009 describes a two hole
nozzle. It is provided with facilities to incorporate version (Orifice Code 3 Only) and Product Code
a flanged mounting plate and one of two types of 310.200.010 describes a four hole version (Orifice
burst disc - an internal (P/C 310.200.011) or Codes 3.5 to 18).
external (P/C 310.200.012) type. Technical Specification
The flanged mounting plate permits the nozzle to Net Weight: 1.1Kg
be mounted on the outside of trunking or steel
enclosures. Product Codes
The burst discs are designed to prevent the 310.200.009
ingress of dirt, insects or other particulate matter Duct nozzle (code 3 only)
which could at some stage block the nozzle. 310.200.010
Connection to the pipework is 20mm (3/4”) NPT Duct nozzle (code 3.5-18)
(male).

Manual By-Pass Valve


The Manual By-Pass Valve is used to allow CO2 Product Code
to be safely vented to atmosphere if it becomes 302.001.008
trapped within a closed pipework section. The 15mm (1/2”) Manual ball valve
valve is available as standard in 15mm (1/2”) NPT.
The valve is used in the normally closed position
and is provided with a locking bracket into which
a standard padlock may be fitted.
Technical Specification
Net Weight: 0.25Kg

Manual Stop Valves - Lockable/Contacted


Product Code Description Weight
302.200.016 15mm (1/2”) Manual locking valve and switches 1.2Kg
302.200.017 20mm (3/4”)Manual locking ball valve and switches 1.42Kg
302.200.018 25mm (1”) Manual locking ball valve and switches 1.6Kg
302.200.019 32mm (1 1/4”) Manual locking ball valve and switches 1.75Kg
Manual Stop Valves are used to isolate the supply closed’ to be given. The valves are also provided
of CO2, (usually at the container manifold with a locking bracket into which a standard
location), from the discharge pipework. padlock may be fitted. Other sizes are available to
The valves and are each fitted with a switchbox to order.
enable an indication of ‘valve open’ or ‘valve

Container Racking - Single Container


The racking is designed to securely fix a single Technical Specification
container to a wall or supporting structure. It Net Weight: 3.0Kg
comprises of two sections of steel channel and
two pairs of universal clamps. Product Code
The steel channel sections are fixed securely to 311.006.015
the wall or supporting structure. The universal Container bracket assy (single container)
clamps have a special slotted section which
allows each half to be fitted into the steel channel.
The two halves are clamped together in position
around the container using a nut and bolt.

Container Racking - Two/Three Containers - Single Row


The racking is designed to securely fix a single Product Codes
row of containers to a wall or supporting 311.006.011
structure. It comprises of two sections of steel Container bracket assy (single row 2 cont.)
channel and two pairs of universal clamps for 311.006.012
each container used. Container bracket assy (single row 3 cont.)
Additional containers may be racked using any
number or configuration of the two and three
container racking assemblies.
Technical Specification
Net Weight: 5.5Kg ( Two containers)
8.5Kg (Three containers)

Page 28