Contents:
01. High/Low Pressure Level Detection ......................................... 02
02. DC Injection / Dwell Modifications ............................................ 08
03. Undertorque Detection ............................................................. 13
04. Overtorque (OL4) Detection Time & Restart ............................ 18
05. Automatic Fault Restart Modifications...................................... 21
06. UV1 Automatic Fault Restart Modification ............................... 23
07. Speed Step ............................................................................... 24
08. Low Speed Fault Detection ...................................................... 27
09. Scalable Monitors ..................................................................... 30
10. Custom Run Sequence ............................................................ 32
11. Overvoltage Suppression ......................................................... 34
12. Home Display Modification ....................................................... 38
13. Application Macro and Parameter Changes ............................ 40
Revision History:
Rev Date Author Description
Comments:
VSA910100-DS.DOCX 1 / 46
DRV-F-6002,R1
Function Design Specification
Provide pressure level detection either through an analog input or through the digital inputs. The digital inputs have
to be flexible such that they can be either normally-open or normally-closed. Pressure level faults will be generated
depending on inputs and the detection time limit.
2. Basic concept/principle
Configure an analog input for the pressure level detection sensor as well as digital inputs for high/low
normally-open/normally closed operation.
Provide a parameter to set whether analog or digital inputs are used for the pressure detection.
Provide a scalable pressure monitor dependent on the analog input.
Generate a high or low pressure fault based on the inputs and a programmable detection time limit.
Disallow low pressure detection for a settable amount of time during a start condition (including coming
out of sleep or zero-speed).
Memobus
V/f w/ PG
Address
Change
Default
Parameter Name
Range
OLV
CLV
No.
V/f
Digital Operator Description
Display
VSA910100-DS.DOCX 2 / 46
DRV-F-6002,R1
During Run
Parameter
Memobus
V/f w/ PG
Address
Change
Default
Parameter Name
Range
OLV
CLV
No.
V/f
Digital Operator Description
Display
Function Name
Function No.
Digital Operator Display
Pressure Detection
P1 Pressure Detect
(PresiónDetección)
VSA910100-DS.DOCX 3 / 46
DRV-F-6002,R1
(3) Monitors
Memobus Address
Monitor No.
V/f w/ PG
Monitor Name
OLV
CLV
Analog output
Unit
V/f
Digital Operator Description
scaling
Display
V/f w/ PG
OLV
CLV
V/f
Setting Description
VSA910100-DS.DOCX 4 / 46
DRV-F-6002,R1
(6) Faults
Fault Indication
[LED]
LCD Description Cause Countermeasures
(Spanish)
<Memobus>
Pressure detected via the
Check the signal connected
“Pressure” analog input has
While the drive is running, a to the analog input
[HiPr) exceeded the P1-03 level
High Pressure has been programmed for Pressure
HIPR for more than the P1-06
detected via the “Pressure” (H3-XX = 20).
High Pressure time.
analog input or on one of the
(Alta Presión) One of the digital inputs set Check the pressure switch
digital inputs set to “High
<3Ch> to “High Pressure” has been connected to the digital input
Pressure”.
opened or closed for more programmed for Low
than the P1-06 time. Pressure (H1-XX = 85 or 87)
Pressure detected via the
Check the signal connected
“Pressure” analog input has
While the drive is running, a to the analog input
[LoPr] dropped below the P1-04
Low Pressure has been programmed for Pressure
LOWPR level for more than the P1-
detected via the “Pressure (H3-XX = 20).
Low Pressure 07 time.
analog input or on one of the
(Baja Presión) One of the digital inputs set Check the pressure switch
digital inputs set to “Low
<3Dh> to “Low Pressure” has been connected to the digital input
Pressure”.
open or closed for more programmed for Low
than the P1-07 time. Pressure (H1-XX = 84 or 86)
6. Function description
When P1-01 = 0 (analog), the drive will read off the analog pressure level from the analog input set as 20: “Pressure
Input”. This value will be scaled according to P1-02, displayed on the U7-02 monitor as “Pressure” and compared to
both P1-03 and P1-04. If this input is greater than P1-03 for the time limit set in P1-06, then a “High Pressure” fault
will occur. Conversely, if this input is less than P1-04 for the time limit set in P1-07, then a “Low Pressure” fault will
occur.
When P1-01 = 1 (digital), the drive will read off the pressure levels from the digital inputs set inside the range of 84
up to 87. When a digital input is set to 84 (Low Pressure N.O.), and that input is closed for the time limit set in P1-07,
then a “Low Pressure” fault will occur. Similarly, if a digital input is set to 85 (High Pressure N.O.), and that input is
closed for the time limit set in P1-06, then a “High Pressure” fault will occur. The logic is simply reversed when using
the normally-closed (N.C.) settings.
The entire pressure detection functionality will be disabled when the drive is at zero speed, not running, or within a
PID sleep state.
During start-up from a zero-speed condition, setting P1-05 will disable low pressure detection for that time period.
VSA910100-DS.DOCX 5 / 46
DRV-F-6002,R1
7. Implementation (Block diagram, timing chart, etc.)
P1-01 = 0 (Analog)
P1-06
P1-03 - High Pressure
Analog
Pressure
P1-04 - Low Pressure
Coast To
Output Stop
Frequency
HIPR FAULT
High Pressure
Fault
P1-05 P1-07
P1-03 - High Pressure
Analog
Pressure
P1-04 - Low Pressure
Coast To
Output Stop
Frequency
LOWPR FAULT
Low Pressure
Fault
VSA910100-DS.DOCX 6 / 46
DRV-F-6002,R1
P2-01 = 1 (Digital)
9. Adjustment procedures
10. References
VSA910100-DS.DOCX 7 / 46
DRV-F-6002,R1
Function Design Specification
DC Injection at Start (B2 Group) can stop the turning rod, but if the loads are high, the drive can trip on an
Overtorque Detection Fault (OL3), which is used in this application to protect the pump. An Overvoltage (OV) trip
can also occur due to the stored energy of the rod.
During an Auto-Restart of a PCP, Speed Search should never be used and the drive should always start at 0Hz.
Performing DC Injection and then Dwell at start, and during an auto-restart would help bring the speed down.
2. Basic concept/principle
Anytime a fault is restarted, DC Injection will be applied, followed by Dwell (the standard Fault Restart function does
not apply DC Injection). After the DC Injection, while the drive ramps up to the dwell frequency and during the dwell
P1-05 will be used as the torque limit. DC injection and Dwell are disabled both for start and Automatic Fault Restart
when the Disable Controlled Restart digital input is closed.
When Dwell is enabled, the maximum carrier frequency is 2.0 kHz. An OPE11 will occur if the carrier is set
above 2.0 kHz, or if a Swing-type carrier is selected.
Memobus
V/f w/ PG
Address
Change
Default
Parameter Name
Range
OLV
CLV
No.
V/f
VSA910100-DS.DOCX 8 / 46
DRV-F-6002,R1
During Run
Parameter
Memobus
V/f w/ PG
Address
Change
Default
Parameter Name
Range
OLV
CLV
No.
V/f
Digital Operator Description
Display
Dwell Reference at
Sets the frequency reference 0.0 to 0.0
B6-01 1B6h Start No Y Y Y Y
during the B6-02 dwell time 400.0 Hz
Dwell Ref @ Start
During Run
Parameter
Memobus
V/f w/ PG
Address
Change
Default
Parameter Name
Range
OLV
CLV
No.
V/f
Digital Operator Description
Display
Function Name
Function No.
Digital Operator Display
VSA910100-DS.DOCX 9 / 46
DRV-F-6002,R1
(4) Multi-function input settings (H1-XX)
V/f w/ PG
OLV
CLV
V/f
Setting Description
6. Function description
The table below shows the difference in drive software behavior depending on the setting of the DC Injection / Dwell
Sequence (P2-01):
VSA910100-DS.DOCX 10 / 46
DRV-F-6002,R1
P2-01 = 0 (Disabled) P2-01 = 1 (Enabled)
Drive Function
Standard DC Inj/Dwell Sequence
Drive will perform a speed search at start
Speed search is disabled and will not run
depending on B3-01.
Speed Search at start (regardless of the B3-01 setting) or
Drive will always perform a speed search
during an automatic fault restart.
during an automatic fault restart.
Drive will perform DC Injection at start
Drive will always perform DC Injection at
when B2-03 is set.
DC Injection start and during an automatic fault restart
Drive will bypass DC Injection during an
when B2-03 is set.
automatic fault restart.
Drive will perform Dwell at start when B6-
Because speed search is disabled, drive
02 is set.
will always perform Dwell at start and
Dwell Drive may bypass Dwell during an
during an automatic fault restart when B6-
automatic fault restart because of speed
02 is set.
search.
If the drive is started or performs an automatic fault restart while the Disable Controlled Restart Digital Input (H1-XX
= 81) is closed, the P2-01 setting is ignored and neither DC Injection nor Dwell will occur.
When the Dwell function is occurring, the Forward and Reverse Torque Limit will both be set to the P2-02 Dwell
Torque Limit setting. This includes both during ramp up to the dwell frequency and during dwell. During DC Injection
standard torque limit parameters will be used. P2-02 is internally limited at 100% of the inverter rated torque.
When dwell is active and the drive is under the torque limit for the time specified in P2-03, the drive will automatically
end the dwell operation and continue accelerating normally. However, if the drive is still in torque limit when the B6-
02 dwell timer expires, a Dwell Time-out (DTO) fault occurs.
VSA910100-DS.DOCX 11 / 46
DRV-F-6002,R1
7. Implementation (Block diagram, timing chart, etc.)
9. Adjustment procedures
10. References
VSA910100-DS.DOCX 12 / 46
DRV-F-6002,R1
Function Design Specification
However, during initial well installation or after extended downtime, the column of the oil in the well shaft is high,
which results in low torque levels during initial pumping. These torque levels are below the broken rod detection
levels, which cause false trips (broken rod torque detection levels are normally set around 6 ~ 8% while initial
pumping torque levels are 0 ~ 3%). This low torque condition lasts for approximately 30 minutes after initial run as
the excess oil is pumped from the well shaft.
2. Basic concept/principle
The Undertorque Detection (UL3) function is modified to include a delay timer at start that is activated by a multi-
function digital input. The UL3 condition will be ignored for the delay time to allow for the low torque condition at
initial start to end. After the delay timer has expired, the UL3 detection will be activated.
A frequency reference bias is employed that will increase the frequency reference during a low torque condition at
initial start. This will reduce the time it takes to pump off the excess oil in the well shaft and results in increased
production. After the delay timer has expired, the frequency bias will be deactivated.
The upper limit of Torq Det 1 Time (L6-03) has been increased from 10.0s to 300.0s.
VSA910100-DS.DOCX 13 / 46
DRV-F-6002,R1
5. Related parameters and functions (including multi-function selections)
(1) Related/Modified Parameters
During Run
Parameter
Memobus
V/f w/ PG
Address
Change
Default
Parameter Name
Range
OLV
CLV
No.
V/f
Digital Operator Description
Display
0: Disabled
1: oL3 detection only active
during speed agree,
operation continues after
detection
2: oL3 detection always
active during run, operation
continues after detection
3: oL3 detection only active
during speed agree, output
shuts down on an oL3
fault
4: oL3 detection always
Torque Detection active during run, output
L6-01 04A1h Selection 1 shuts down on an oL3 fault 0~8 0 No Y Y Y Y
Torq Det 1 Sel 5: UL3 detection only active
during speed agree,
operation continues after
detection
6: UL3 detection always
active during run, operation
continues after detection
7: UL3 detection only active
during speed agree, output
shuts down on a UL3
fault
8: UL3 detection always
active during run, output
shuts down on a UL3 fault
Torque Detection
Sets the overtorque and 0~
L6-02 04A2h Level 1 0% Yes Y Y Y Y
undertorque detection level. 300%
Torq Det 1 Lvl
Sets the time an overtorque
Torque Detection 0.0 ~
or undertorque condition 0.1
L6-03 04A3h Time 1 300.0 No Y Y Y Y
must exist to trigger sec
Torq Det 1 Time sec
torque detection 1.
VSA910100-DS.DOCX 14 / 46
DRV-F-6002,R1
(2) Additional Parameters
During Run
Parameter
Memobus
V/f w/ PG
Address
Change
Default
Parameter Name
Range
OLV
CLV
No.
V/f
Digital Operator Description
Display
(3) Monitors
Memobus Address
Monitor No.
V/f w/ PG
Monitor Name
OLV
CLV
Analog output
Unit
V/f
Digital Operator Description
scaling
Display
VSA910100-DS.DOCX 15 / 46
DRV-F-6002,R1
(4) Multi-function input settings (H1-XX)
V/f w/ PG
OLV
CLV
V/f
Setting Description
6. Function description
Undertorque Detection Fault Delay Time
The Undertorque Detection Fault (UL3) Delay Time (P2-04) is used to prevent nuisance UL3 trips caused by the
excess oil low torque condition at initial start. The delay time allows the UL3 trip level to be set for a broken rod
condition, which is above the initial start condition. This function is only enabled when the Undertorque Detection
Fault (UL3) Delay Command (H1-0X = 80) is present at the time the run command is issued or when auto-fault
restart occurs. After the P2-04 time expires, the UL3 fault detection will be activated.
The Undertorque Speed Bias (P2-05) is used to reduce the time necessary to pump off the excess oil in the well
shaft at initial start. This function is only enabled when the Undertorque Detection Fault (UL3) Delay Command (H1-
0X = 80) is present at the time of the run command or when auto-fault restart occurs. If the U1-09 Torque Reference
is less than the Undertorque Detection Level (L6-02), the Undertorque Speed Bias (P2-05) will be added to the
frequency reference (the total not to exceed the Maximum Output Frequency, E1-04). The speed bias is dependent
on the frequency reference:
New Frequency Reference = Incoming Frequency Reference + (Incoming Frequency Reference x P2-05%)
If the U1-09 Torque Reference rises above the Undertorque Detection Level (L6-02) before the Undertorque
Detection Delay Time (P2-04) expires, the Undertorque Speed Bias (P2-05) will be removed. After the Undertorque
Detection Delay Timer (P2-04) expires, the Undertorque Speed Bias (P2-05) will be removed unconditionally.
VSA910100-DS.DOCX 16 / 46
DRV-F-6002,R1
7. Implementation (Block diagram, timing chart, etc.)
9. Adjustment procedures
10. References
VSA910100-DS.DOCX 17 / 46
DRV-F-6002,R1
Function Design Specification
A parameter is added to select whether or not Overtorque Detection 2 (OL4) faults can be automatically restarted.
2. Basic concept/principle
The upper limit of Torq Det 2 Time (L6-06) has been increased from 10.0s to 300.0s.
VSA910100-DS.DOCX 18 / 46
DRV-F-6002,R1
5. Related parameters and functions (including multi-function selections)
During Run
Parameter
Memobus
V/f w/ PG
Address
Change
Default
Parameter Name
Range
OLV
CLV
No.
V/f
Digital Operator Description
Display
0: Disabled
1: oL4 detection only active
during speed agree,
operation continues after
detection
2: oL4 detection always
active during run, operation
continues after detection
3: oL4 detection only active
during speed agree, output
shuts down on an oL4
fault
4: oL4 detection always
Torque Detection active during run, output
L6-04 04A4h Selection 2 shuts down on an oL4 fault 0~8 0 No Y Y Y Y
Torq Det 2 Sel 5: UL4 detection only active
during speed agree,
operation continues after
detection
6: UL4 detection always
active during run, operation
continues after detection
7: UL4 detection only active
during speed agree, output
shuts down on a UL4
fault
8: UL4 detection always
active during run, output
shuts down on a UL4 fault
Torque Detection
Sets the overtorque and 0~
L6-05 04A5h Level 2 0% No Y Y Y Y
undertorque detection level. 300%
Torq Det 2 Lvl
Sets the time an overtorque
Torque Detection 0.0 ~
or undertorque condition 0.1
L6-06 04A6h Time 2 300.0 No Y Y Y Y
must exist to trigger sec
Torq Det 2 Time sec
torque detection 2.
VSA910100-DS.DOCX 19 / 46
DRV-F-6002,R1
(2) Additional Parameters
During Run
Parameter
Memobus
V/f w/ PG
Address
Change
Default
Parameter Name
Range
OLV
CLV
No.
V/f
Digital Operator Description
Display
6. Function description
OL4 Restart Selection L5-52 sets the behavior of the automatic restart feature during OL4 faults.
• L5-52 = 0, automatic fault restart is disabled for OL4.
• L5-52 = 1, automatic fault restart is enabled for OL4.
9. Adjustment procedures
10. References
VSA910100-DS.DOCX 20 / 46
DRV-F-6002,R1
Function Design Specification
2. Basic concept/principle
Add a parameter that sets how long the drive has to operate without faulting before the Restart counter is
automatically cleared. Standard A1000 software has this fixed at 10s.
Add a monitor that shows how many auto-restarts are remaining
Increase the upper limit of L5-04 from 600.0s to 6000.0s.
During Run
Parameter
Memobus
V/f w/ PG
Address
Change
Default
Parameter Name
Range
OLV
CLV
No.
V/f
Digital Operator Description
Display
Memobus
V/f w/ PG
Address
Change
Default
Parameter Name
Range
OLV
CLV
No.
V/f
VSA910100-DS.DOCX 21 / 46
DRV-F-6002,R1
(3) Monitors
Memobus Address
Monitor No.
V/f w/ PG
Monitor Name
OLV
CLV
Analog output
Unit
V/f
Digital Operator Description
scaling
Display
Number of Automatic
Displays the number of
Restarts Remaining
U7-08 0667H automatic restarts N/A - Y Y Y Y
Rstrts Remaining
remaining
(RearranqPorHacer)
6. Function description
9. Adjustment procedures
10. References
VSA910100-DS.DOCX 22 / 46
DRV-F-6002,R1
Function Design Specification
2. Basic concept/principle
UV1 fault can be restarted even when L2-01 = 0 (Power Loss Ride-through disabled).
During Run
Parameter
Memobus
V/f w/ PG
Address
Change
Default
Parameter Name
Range
OLV
CLV
No.
V/f
Digital Operator Description
Display
0: Disabled
Momentary Power 1: Enabled w/ Timer
Loss Operation 2: CPU Power active
L2-01 0485h Selection 3: KEB decel w/ Timer 0~5 0 No Y Y Y Y
PwrL Selection 4: KEB decel CPU Power
(Selec/ PerdEn ) active
5: KEB decel to stop
6. Function description
This change allows UV1 to be automatically restarted when L5-01 (Num of Restarts) > 0 and L2-01 (Power Loss
Ride-through) = 0 (Disabled).
9. Adjustment procedures
10. References
VSA910100-DS.DOCX 23 / 46
DRV-F-6002,R1
Function Design Specification
Provide a programmable Speed Step feature during acceleration. This feature is used to limit the accelaration and
reduce the possibility of sand and debris being clogged into the system.
2. Basic concept/principle
Add parameters that will allow accelerating to step frequencies (holding it for a set time) to reach the target
frequency reference. Since the U1-01 monitor will be forced to the step frequency, a new monitor, U1-91, will show
the target frequency.
During Run
Parameter
Memobus
V/f w/ PG
Address
Change
Default
Parameter Name
Range
OLV
CLV
No.
V/f
Digital Operator Description
Display
VSA910100-DS.DOCX 24 / 46
DRV-F-6002,R1
(2) Function Text
Function Name
Function No.
Digital Operator Display
Speed Jump
P3 Speed Jump
(SaltoD Velocidad)
(3) Monitors
Memobus Address
Monitor No.
V/f w/ PG
Monitor Name
OLV
CLV
Analog output
Unit
V/f
Digital Operator Description
scaling
Display
6. Function description
When Speed Step Select P3-01=1, the drive will accelerate in the following fashion:
1. When starting from zero-speed and Frequency Reference Lower Limit D2-02 > 0, accelerating frequency
reference will be set to D2-02.
2. When starting from zero-speed and D2-02 = 0, accelerating frequency reference will be set to P3-02.
3. When the accelerating frequency reference is reached, the drive will wait for the time set in Delta Time
Delay P3-03, after which the drive will increment the accelerating frequency reference by the Delta Speed
P3-02 value, and repeat this process until the target frequency reference (U1-91) is reached.
If P3-03 is changed while the drive is performing speed step, the drive will finish the current step using the previous
time, and apply the new time to the next step and thereafter.
Frequence Reference Bias (H3-XX = D) and Frequency Reference Gain (H3-XX = 1) will interact with Speed Search
as such:
If the gain input is changed resulting in an increased frequency reference, speed step will be active until the
new frequency reference is reached
If the bias input is changed resulting in an increased frequency reference, speed step will not be active until
bias effect has been accounted for.
VSA910100-DS.DOCX 25 / 46
DRV-F-6002,R1
7. Implementation (Block diagram, timing chart, etc.)
Run Command
P3-02
P3-02
P3-02
P3-02
Output Frequency Target
Frequency
D2-02
0.0 Hz
Frequency Reference
U1-01
P3-02
Target
Frequency
D2-02
0.0 Hz
Target Frequency
U7-03 Target
Frequency
0.0 Hz
9. Adjustment procedures
10. References
VSA910100-DS.DOCX 26 / 46
DRV-F-6002,R1
Function Design Specification
A low speed detection function is added to detect a stalled motor when the drive is started.
2. Basic concept/principle
If the drive output frequency never reaches the frequency reference lower limit (used as the minimum pump speed)
a set amount of time after the drive is started.
This function is only enabled when the frequency reference lower limit D2-02 > 0.
This function is disabled while Dwell is active.
During Run
Parameter
Memobus
V/f w/ PG
Address
Change
Default
Parameter Name
Range
OLV
CLV
No.
V/f
Digital Operator Description
Display
Determines minimum
frequency reference, set as a
percentage of maximum
Frequency
output frequency (E1-04). If
Reference Lower
the frequency reference is 0.0 ~
D2-02 028Ah Limit 0.0% N Y Y Y Y
below this value, actual Drive 110.0
Ref Lower Limit
speed will be limited to this
(LímInfReferencia)
value. This parameter
applies to all frequency
reference sources.
VSA910100-DS.DOCX 27 / 46
DRV-F-6002,R1
(2) Additional Parameters
During Run
Parameter
Memobus
V/f w/ PG
Address
Change
Default
Parameter Name
Range
OLV
CLV
No.
V/f
Digital Operator Description
Display
Function Name
Function No.
Digital Operator Display
Miscellaneous Features
P4 Miscellaneous
(Misceláneo)
(4) Faults
Fault Indication
[LED]
LCD Description Cause Countermeasures
(Spanish)
<Memobus>
[LSPd]
The drive output frequency
LSPD
did not reach the Frequency
Low Speed Stalled motor. Check motor/system.
Reference Lower Limt (D2-
(Baja Velocidad)
02) during start.
<3Eh>
6. Function description
When the Frequency Reference Lower limit D2-02 > 0.0% and the Low Speed Detection Time P4-01 > 0.0sec, the
Low Speed Fault detection function is enabled and the drive will continuously check the output frequency. If the
output frequency falls below D2-02 – P4-02 (Low Speed Detection Bandwidth) for the P4-01 time, a Low Speed
(LSPD) fault will occur.
Low Speed Fault detection is disabled when the drive is initially started until it is assumed to have arrived at the
D2-02 frequency, based on the active accel time. When the drive is issued a run command and is not in a zero
VSA910100-DS.DOCX 28 / 46
DRV-F-6002,R1
speed condition (due to a zero frequency reference or DC injection), the drive starts a timer. When the timer
reaches the following value:
E1-04
the drive assumes it has reached the D2-02 speed and enables Low Speed Fault detection.
Run
Frequency
Reference
D2-02
P4-02
Output Freq
LSPD Fault
Fault Reset
Detecting
Low Speed
9. Adjustment procedures
10. References
VSA910100-DS.DOCX 29 / 46
DRV-F-6002,R1
Function Design Specification
2. Basic concept/principle
Add consecutive monitors for Speed, Current and Torque so that all three can be displayed at the same
time.
Add a scaling factor for the speed and torque for PCP applications
Adjust the current monitor by specifying a ratio
During Run
Parameter
Memobus
V/f w/ PG
Address
Change
Default
Parameter Name
Range
OLV
CLV
No.
V/f
Digital Operator Description
Display
VSA910100-DS.DOCX 30 / 46
DRV-F-6002,R1
(2) Function Text
Function Name
Function No.
Digital Operator Display
Miscellaneous Features
P4 Miscellaneous
(Misceláneo)
(3) Monitors
Memobus Address
Monitor No.
V/f w/ PG
Monitor Name
OLV
CLV
Analog output
Unit
V/f
Digital Operator Description
scaling
Display
6. Function description
9. Adjustment procedures
10. References
VSA910100-DS.DOCX 31 / 46
DRV-F-6002,R1
Function Design Specification
A custom run sequence is created which allows both the terminals and Memobus master to run or stop the drive at
any time without switching the run source.
2. Basic concept/principle
When b1-02 = 5, the drive run command status is determined by the most recent change of state of Terminal Run
FWD (H1-XX = 40), Terminal Run REV (H1-XX = 41), Memobus FWD run bit or Memobus REV run bit.
During Run
Parameter
Memobus
V/f w/ PG
Address
Change
Default
Parameter Name
Range
OLV
CLV
No.
V/f
Digital Operator Description
Display
0: Operator (Operador)
1: Terminals (Terminales)
2: Memobus Communication
Run Command
(Comunicación)
B1-02 0181h Selection 1 0~5 0 N Y Y Y Y
3: Option PCB (PCB
Run Source 1
opcional)
5: Terminal/Comm
(Terminales/Com)
6. Function description
When B1-02 = 5 (Terminal/Comm), Terminal FWD/REV and the Memobus FWD/REV run command bits (0001H
bits 0 & 1) are modified to function as edge triggered commands instead of level triggered commands. The drive
run state is determined by the most recent state change. This operation is described in the table below.
VSA910100-DS.DOCX 32 / 46
DRV-F-6002,R1
Memobus REV 0 -> 1 Issue REV Run 5
0001H bit 1 1 -> 0 Remove Run (if present) 1
Note: In the event that there is more than one state change at the same time, the drive determines which
command(s) are acknowledged based on the “Priority” column in the previous table. All state changes which result
in removing either a FWD or REV run command (stopping) are treated with equal and highest priority.
9. Adjustment procedures
10. References
VSA910100-DS.DOCX 33 / 46
DRV-F-6002,R1
Function Design Specification
This feature was included so that Pump Jack oil wells (which are typically unbalanced) can run without the need for
dynamic braking.
2. Basic concept/principle
The software monitors the level of torque-producing current (Iq) in the motor, and regulates this against an Iq
setpoint. If it sees that the torque producing current is below the set-point, the output frequency is increased to force
a higher (positive) Iq.
Memobus
V/f w/ PG
Address
Change
Default
Parameter Name
Range
OLV
CLV
No.
V/f
VSA910100-DS.DOCX 34 / 46
DRV-F-6002,R1
During Run
Parameter
Memobus
V/f w/ PG
Address
Change
Default
Parameter Name
Range
OLV
CLV
No.
V/f
Digital Operator Description
Display
Function Name
Function No.
Digital Operator Display
Overvoltage Suppression
P5
OV Suppression
(3) Faults
Fault Indication
(LED)
Description Cause Countermeasures
LCD
<Memobus>
(bbrK) Drive output was at the
B-BRK maximum frequency (E1-
Belt Break Fix belt / coupling.
Belt Break 04) for more than 30
<40h> seconds.
6. Function description
Overvoltage Regulator:
The level of torque-producing current is detected in the motor and subtracted from a setpoint (Iq Setpoint), then the
result is submitted to a PI algorithm (overvoltage regulator). The PI algorithm will add frequency to the frequency
reference in order to maintain a constant Iq setpoint. The PI algorithm will NOT subtract frequency from the
frequency reference. This is done to keep the torque producing current positive to prevent regeneration and
subsequent overvoltage faults.
VSA910100-DS.DOCX 35 / 46
DRV-F-6002,R1
When parameters P5-06 & P5-07 are used, the gain of the overvoltage suppression regulator is automatically
increased when the drive’s output goes higher than motor base frequency (E1-06). Shown below is an example
when P5-06 = 60.00 Hz, and P5-07 = 2.000.
VSA910100-DS.DOCX 36 / 46
DRV-F-6002,R1
7. Implementation (Block diagram, timing chart, etc.)
9. Adjustment procedures
10. References
VSA910100-DS.DOCX 37 / 46
DRV-F-6002,R1
Function Design Specification
2. Basic concept/principle
Add a parameter that will set the Power-On monitor as the Home display.
During Run
Parameter
Memobus
V/f w/ PG
Address
Change
Default
Parameter Name
Range
OLV
CLV
No.
V/f
Digital Operator Description
Display
Memobus
V/f w/ PG
Address
Change
Default
Parameter Name
Range
OLV
CLV
No.
V/f
6. Function description
9. Adjustment procedures
10. References
VSA910100-DS.DOCX 39 / 46
DRV-F-6002,R1
Function Design Specification
2. Basic concept/principle
Allow parameters E1-05 (Max Voltage), E1-06 (Base Frequency) and E1-13 (Base Voltage) to be
changed during run when in V/f or V/f w/ PG modes.
Allow parameters L3-06 (StallP Run Level) and L7-01 (Torq Limit Fwd) to be changed during run.
Add application macro (A1-06) for ESP, PCP w/ Dwell, Pump Jack, and PCP w/ Speed Search.
Remove application macro settings 1 to 5.
During Run
Parameter
Memobus
V/f w/ PG
Address
Change
Default
Parameter Name
Range
OLV
CLV
No.
V/f
Digital Operator Description
Display
0: General-purpose
1: Water supply pump
2: Conveyor
3: Exhaust fan
Application Preset 4: HVAC fan
A1-06 0127h 0 ~ 10 0 N Y Y Y Y
Application Sel 5: Air compressor
8: ESP Application
9: PCP w/ Dwell
10: Pump Jack OVS
11: PCP w/ Spd Search
Determines whether an
Run Command at external Run command that
Power Up is active during power up will
B1-17 01C6h 0~1 1 N Y Y Y Y
Run Cmd @ Pwr start the drive.
On 0: Cycle Ext Run
1: Accept Ext Run
0.0 ~
Maximum Voltage Refer to the A1000 Technical <2> <4>
E1-05 0304h 255.0V Y Y Y Y Y
Max Voltage Manual for more information. <1>
VSA910100-DS.DOCX 40 / 46
DRV-F-6002,R1
During Run
Parameter
Memobus
V/f w/ PG
Address
Change
Default
Parameter Name
Range
OLV
CLV
No.
V/f
Digital Operator Description
Display
0.0 ~
Base Voltage <3> <4>
E1-13 030Ch 255.0V Y Y Y Y Y
Base Voltage <1>
<1>
Values shown are specific to 200V class drives. Double the value for 400V class drives. Multiply the value
by 2.875 for 600V class drives.
<2>
Default setting is dependent on parameters A1-02, Control Mode Selection, C6-01, Drive Duty Selection,
and o2-04, Drive Model Selection.
<3>
When Auto-Tuning is performed, E1-13 and E1-05 will be set to the same value.
<4>
Parameters can be changed while running only in V/f (A1-02 = 0) and V/f w/ PG modes (A1-02 = 1).
VSA910100-DS.DOCX 41 / 46
DRV-F-6002,R1
6. Function description
The following table shows which parameters are set depending on the A1-06 selection:
ESP Function PCP w/ Dwell Pump Jack OVS PCP w/ Spd Search
(A1-06 = 8) (A1-06 = 9) (A1-06 = 10) (A1-06 = 11)
Parameter Value Parameter Value Parameter Value Parameter Value
A1-02 0 A1-02 2 A1-02 2 A1-02 2
C6-01 0 b1-01 0 C6-01 0 b1-01 0
C6-02 1 b2-03 10.00sec C6-02 1 b2-03 0.00sec
L5-05 0 b6-01 0.5Hz L5-05 0 b2-04 0.00sec
L5-51 10min b6-02 300.0sec L5-51 10min b3-01 1
L5-52 1 C1-01 30.0sec L5-52 1 b3-24 1
o1-99 0 C1-02 30.0sec o1-99 0 C1-01 30.0sec
P2-01 0 C6-01 0 P2-01 0 C1-02 30.0sec
P5-01 0 C6-02 1 P5-01 1 C6-01 1
H1-06 7B C6-02 1
L2-01 4 H1-06 7B
180VDC
L2-05 <1> L2-01 4
180VDC
L2-29 1 L2-05 <1>
L5-01 3 L2-29 1
L5-04 60.0sec L5-01 3
L5-05 1 L5-04 60.0sec
L5-51 60min L5-05 1
L5-52 0 L5-51 60min
L6-01 8 L5-52 0
L6-02 7% L6-01 8
L6-03 10.0sec L6-02 7%
L6-04 4 L6-03 10.0sec
L6-05 100% L6-04 4
L6-06 0.5sec L6-05 100%
L7-01 94% L6-06 0.5sec
L7-02 10% L7-01 94%
L7-03 10% L7-02 10%
L7-04 30% L7-03 10%
L7-06 80ms L7-04 30%
L7-07 1 L7-06 80ms
N2-01 1.50 L7-07 1
o1-01 704 N2-01 1.50
o1-02 5 o1-01 704
o1-99 1 o1-02 5
o2-06 0 o1-99 1
P1-06 5.0sec o2-06 0
P1-07 20.0sec P1-06 5.0sec
P2-01 1 P1-07 20.0sec
P4-01 40.0sec P2-01 0
P4-06 0 P4-01 40.0sec
P5-01 0 P4-06 0
P4-07 10.00sec
P5-01 0
<1>
Values shown are specific to 200V class drives. Double the value for 400V class drives. Multiply the value
by 2.875 for 600V class drives.
VSA910100-DS.DOCX 42 / 46
DRV-F-6002,R1
The following table shows which parameters are shown on the Quick Setting menu depending on the A1-06
selection:
ESP Application PCP w/ Dwell Pump Jack OVS PCP w/ Spd Search
(A1-06 = 8) (A1-06 = 9) (A1-06 = 10) (A1-06 = 11)
A1-02 A1-02 A1-02 A1-02
b1-01 b1-01 b1-01 b1-01
b1-02 b1-02 b1-02 b1-02
b1-03 b1-03 b1-03 b1-03
C1-01 C1-01 C1-01 C1-01
C1-02 C1-02 C1-02 C1-02
C6-01 C6-01 C6-01 C6-01
C6-02 C6-02 C6-02 C6-02
d1-01 d1-01 d1-01 d1-01
d1-02 d1-02 d1-02 d1-02
d1-03 d1-03 d1-03 d1-03
d1-04 d1-04 d1-04 d1-04
d1-17 d1-17 d1-17 d1-17
E1-01 E1-01 E1-01 E1-01
E1-03 E1-03 E1-03 E1-03
E1-04 E1-04 E1-04 E1-04
E1-05 E1-05 E1-05 E1-05
E1-06 E1-06 E1-06 E1-06
E1-09 E1-09 E1-09 E1-09
E1-13 E1-13 E1-13 E1-13
E2-01 E2-01 E2-01 E2-01
E2-04 E2-04 E2-04 E2-04
E2-11 E2-11 E2-11 E2-11
H4-02 H4-02 H4-02 H4-02
L1-01 L1-01 L1-01 L1-01
L3-04 L3-04 L3-04 L3-04
9. Adjustment procedures
10. References
VSA910100-DS.DOCX 43 / 46
DRV-F-6002,R1
Function Design Specification
2. Basic concept/principle
Suppress UV2 faults when using Kinetic Energy Braking w/ CPU power loss ride-through (L2-01 = 4).
Change access level of KEB Start Offset (L2-31) to Advanced.
Add a parameter to allow automatic disabling of the AVR when KEB is running.
Add a parameter that allows Speed Search to be performed when KEB deactivates.
During Run
Parameter
Memobus
V/f w/ PG
Address
Change
Default
Parameter Name
Range
OLV
CLV
No.
V/f
Digital Operator Description
Display
0: Disabled
1: Enabled with Timer
Momentary Power
2: CPU power-active
L2-01 0485h Loss Operation 0~5 0 No Y Y Y Y
3: KEB mode
PowerL Selection
4: KEB Stop mode
5: KEB Decel to Stop
KEB Start Level KEB activates when the DC 0 ~ 100 100
L2-31 045Dh Offset Bus Level goes below the VDC VDC No Y Y Y Y
<1> <1>
KEB Start Offset L2-05 setting plus this value.
<1>
Values shown are specific to 200V class drives. Double the value for 400V class drives. Multiply the value
by 2.875 for 600V class drives.
VSA910100-DS.DOCX 44 / 46
DRV-F-6002,R1
(2) Additional Parameters
During Run
Parameter
Memobus
V/f w/ PG
Address
Change
Default
Parameter Name
Range
OLV
CLV
No.
V/f
Digital Operator Description
Display
AVR Selection
0: Disabled
P4-06 0625h during KEB 0~1 1 Yes Y Y Y Y
1: Enabled
AVR Sel dur KEB
Sets the amount of time that
the drive will be base blocked
0.00 ~
Delay After KEB after KEB deactivates. 2.00
P4-07 0626h 360.00 Yes Y Y Y Y
Delay After KEB sec
sec
A setting of 0.00 disables
Speed Search after KEB.
6. Function description
When P4-06 = 0, the Automatic Voltage Regulator (AVR) is disabled when the drive enters KEB-mode. Setting P4-
06 = 1 leaves the AVR enabled just like standard A1000.
When P4-07 = 0.00sec, the drive acts like standard A1000: when KEB completes and the soft starter output (U1-16)
is below the minimum operating frequency, the drive does not do a Speed Search attempt and always tries to start
at 0Hz
When P4-07 > 0.00sec, the drive will base block the drive after KEB completes if the soft starter output (U1-16) is
below the minimum operating frequency. The base block time is set by P4-07. After base block completes, the drive
will do a Speed Search if enabled.
VSA910100-DS.DOCX 45 / 46
DRV-F-6002,R1
7. Implementation (Block diagram, timing chart, etc.)
Figure 1: KEB to Speed Search (L2-01 = 4, P4-07 > 0)
9. Adjustment procedures
10. References
VSA910100-DS.DOCX 46 / 46
DRV-F-6002,R1