You are on page 1of 7

Confidentiality level:

Telkomsel Project:Model Site/Good Example (indoor) For internal use only

Model Site/Good Example of Installation (indoor-BTS3900).


Part A: Double Tiers

-Overview of outside the cabinet -Overview of inside the cabinet

-Color ring of the feeder cable -Color ring of the feeder cable
(front view) (side view)

Huawei Confidential. No disclosure without permission. Page 1 of 7


Confidentiality level:
Telkomsel Project:Model Site/Good Example (indoor) For internal use only

-Labeling at same direction and tidy -Labeling at same direction and tidy
(top tier) (lower tier)
-CPRI cable(optical) installed smoothly -CPRI cable(optical) installed smoothly

-feeder cable at lower tier and - Grounding between DCDU and


Its color ring cabinet
-BBU on the top of DCDU

Huawei Confidential. No disclosure without permission. Page 2 of 7


Confidentiality level:
Telkomsel Project:Model Site/Good Example (indoor) For internal use only

-Grounding between cabinet and door -Grounding btw BBU and cabinet

-Grounding at the cabinet to -Grounding at the grounding bar.


grounding bar(with PGND label). (with PGND label)

Huawei Confidential. No disclosure without permission. Page 3 of 7


Confidentiality level:
Telkomsel Project:Model Site/Good Example (indoor) For internal use only

Grounding between 2 tiers

-Power cable and grounding -Power cable connection at


(straight and smooth) upper tier.(with -48V label)
-Power cable size:≥16mm ²

Huawei Confidential. No disclosure without permission. Page 4 of 7


Confidentiality level:
Telkomsel Project:Model Site/Good Example (indoor) For internal use only

-Power cable connection at top tier -Power cable connection at rectifier


(with -48V label) (with -48V label)

-Redundancy of E1 cable (tidy) -Connection at DDF

Huawei Confidential. No disclosure without permission. Page 5 of 7


Confidentiality level:
Telkomsel Project:Model Site/Good Example (indoor) For internal use only

Part B: Single Tier

-Feeder cable connection -Connection and labeling inside the


cabinet

-Feeder cable connection -Feeder cable connection


(bending radius:20x its diameter)

Huawei Confidential. No disclosure without permission. Page 6 of 7


Confidentiality level:
Telkomsel Project:Model Site/Good Example (indoor) For internal use only

Power/Ground cable must be separated minimum 3cm from signal cable

Prepared by Foo Siang Hooi

Huawei Confidential. No disclosure without permission. Page 7 of 7