Cascaded SRC Example

You might also like

You are on page 1of 3

MODELLING CASCADED SPLIT RANGE (CASC-SRC) CONTROLLERS IN

ASPEN HYSYS DYNAMICS

The following article demonstrates the use of High Pressure (HP) VFD Operated LNG pumps that controls the
LNG (Liquefied Natural Gas) pressure and a flow control valve a.k.a vaporizer control valve that controls pump
flow. This ensures that the right amount of flow passes through the heater. With some example data, an LNG
0
stream of 7500 kmol/h at 12 bara and -160 C is pumped to a vaporizer at 95 bara. The HP pump rated at 3000
rpm, runs at 2950 rpm while the design flow of the vaporizer is 7534 kmol/h. The vaporizer outlet temperature
0
required is 2.5 C. A split range controller (SRC) is added that alters the pump speed and vaporizer control valve
to maintain the LNG Send Out at 7500 kmol/h.

Figure 1. Cascaded Split Range Controller for LNG Pump Setup


The HP pump operates with a speed controller and the vaporizer control valve operates with a flow controller -
both of which are 'reverse acting'. This means that when the process variable (PV) (speed) goes up, the power
fed to the pump (OP) drops. Similarly, when the LNG flow increases through the vaporizer control valve, the
valve closes accordingly to maintain the required flow. Adding an SRC in HYSYS, the parameters can be
declared as follows,

Page 1 of 3
Upon entering the SCV Flow Controller as the first input and HP Pumps Controller as the second input, under
the configuration window as shown in Fig. 4, enter the PVMin value as 0 kmol/h and 10,000 kmol/h in the PVMax
Window. In the Split Range Setup Tab, the low range and high range values as shown in Fig. 5 are calculated as
shown in Eq. 1 to Eq. 6.

The value computed in Eq. 3 is assigned as the highest fraction to SCV Flow controller as shown in Fig 5 while
the HP Pumps controller high parameter is always assigned 100.

Page 2 of 3
Note that the Low Range Values for both controllers in the Split Range Setup Tab (Fig. 5) is entered as ‘zero’.
Followed by this, the lower fraction of 98.33 is assigned to OP cell in the parameters page (Fig. 6). It is
recommended to use a PI controller with IMC tuning methods as a start and add derivative action (if necessary)
depending on system response to avoid an oscillatory behavior of the controller. Lastly, the individual SCV flow
controller (Fig. 7) and HP Pumps controllers (Fig. 8) are to be transferred to ‘Casc’ mode and the simulation has
to be run for a while.

With the SRC controller being changed to ‘Auto’ mode (Fig. 9), the HYSYS model stabilizes to arrive at a final
operating point similar to the individual controllers’ original set points (SP’s) of 2950 rpm and 7500 kmol/h. As a
check, note that the Split Range Outputs match with the values of Eq. 1 and Eq. 2.

Page 3 of 3

You might also like