Instructions 8380 DPC, 8381 DPS

Pressure switch with display

Technical specification
Mounting torque: 15 ... 20 Nm
Ambient temperature: – 25°C ... +85°C
Media temperature: – 25°C ... +85°C
Protection: IP67
Display pressure unit: bar, psi, MPa, kPa, mWC, mmWC, inchWC, %, user scale
Switching current: Max. 0.5 A per switching output
Parametrisation: With 3 buttons and menu navigation or via NFC - Smartphone App Sensor Master by Trafag AG

Type label description


Measuring range Serial number Type code Manufacturing date (W/Y) Max. overpressure

Type 838X.XX.XXXX
SWITZERLAND

S/N YYYYYY-ZZZ | 16/16


Range -1...9 bar-G | max.: 20 bar
Us (1) 15...30V DC | Us (3) | Out (2) | SP1 (4) | SP2 (5)

Supply positive Supply voltage Analogue Switching Pin assignment


output output

Electrical connection

Ingress Protection IP67*) IP67*)

M12x1 M12x1
Designation
5-pole 4-pole
Type code 838X.XX.XXXX.35 838X.XX.XXXX.32

3 2
5 3 2
Pin configuration
4 4
1 1

*) Provided female connector is mounted according to instructions

Output signal / supply voltage


Output ISUPPLY USUPPLY
4 ... 20 mA ≤ 30 mA 15 ... 30 VDC
0 ... 10 VDC ≤ 30 mA 15 ... 30 VDC
0 ... 5 VDC ≤ 30 mA 15 ... 30 VDC
1 ... 6 VDC ≤ 30 mA 15 ... 30 VDC

www.trafag.com
Connection of the measuring equipment 4...20mA: min./max resistor vs. supply voltage @ Pmax = 100%
1200

R max @ 85°C
Us + 1000
P P US+

Customer Load Resistor (Ohm)


Us US –
R min @ 85°C
Out analogue
U/I SP1
800

Out I
SP2 SP1, SP2
RL 600

Shield *** )
earth US –
400

***) The use of a shielded Connection of loads


200
cable is recommended to switching output
0
0 5 10 15 20 25 30

Customer Supply Voltage (V)

Mounting Display indication


Tighten the device
Description
The measured pressure is >3% above the measuring range end-point
OL
The indication disappears as soon as the pressure is reduced again
The measured pressure is >3% below the measuring range zero-point
UL
The indication disappears as soon as the pressure is reduced again
Signal processing is faulty.
Perr
Please replace measuring device
Incorrect access code
FALS
Enter the correct access code
max. 2.5 Nm
Sensor break; the sensor element is defective
Sbrk
Please replace the pressure measuring device
Internal device communication is interrupted
Fi2c
max. 5 Nm Please replace the pressure measuring device
Internal memory damage occured
Ecrc Execute a factory reset. If the recovery is not successful, replace the

ü
pressure measuring device
15 ... 20 Nm Internal memory damage occurred
FE2P Execute a factory reset. If the recovery is not successful, replace the
pressure measuring device
NFC communication was not successful
EnFc Try again to communicate again. If the error persists, replace the
pressure measuring device
Zero-set out of range
The measured pressure value is outside of the valid range for the zero-set function
E.0FC Press [Enter] on the measuring device to reset the error indication
This error indication does not appear when performing the zero-set function by
means of the Sensor Master App (Android smartphone)
Switching output functions

Hysteresis Window Delay

P P P

SP
SP FH
rP
rP FL

t t t
ON ON
ON
Hno Fno Hno
OFF OFF
OFF

ON ON
ON
Hnc
Hnc Fnc OFF
OFF OFF

dS dr

www.trafag.com
Dimensions

Ø 37 Protective cap Flange adapter


G1/4“x13/19 O-Ring
NBR

(15)
43.5
335° max. 2.5 Nm

30
M12x1

ø 5.3 (2x)
343° max. 5 Nm
93

20±0.1
Ø 43
30

F82054
45.5

Mounting accessory included

54 ... 60

~Ø20
SW27 / Ø 29.5
Ø 32
48

838X.XX.XXXX.35/32.XX.XX 838X.XX.XXXX.XX.XX.33

14 14.5 12 2 12 2 14.5 15 3 20 14.5


M5
G1/4"

EN837
G1/4"

G1/4“

Ø9.5

Ø6
Ø5
Ø21

Ø5.05x3U

12.5
int. damping 2

EN837
G1/4"
M5x7

DIN3869

Ø 0.5

G1/2“
Seal

Ø 29.5
Ø29.5
SW27
20

SW27
4
Ø29.5
SW27

DIN3869
Seal

838X.XX.XX10.XX.XX.XX 838X.XX.XX17.XX.XX.XX 838X.XX.XX15.XX.XX.XX 838X.XX.XX53.XX.XX.XX 838X.XX.XX11.XX.XX.XX

(28.5) 13.5 14.5


15.1 2 14.5 13.5 6.5 14.5 10 14.5
14 3 11.5 11
Ø 5.05x3U
Ø 5.05x3U

Ø5.05x3U

DIN6149-2
Ø5.05x3U
1/4" NPT

DIN3858
DIN3852-E

Ø 29.5
1/2" NPT
Ø5.05x3U

M14x1.5
Ø 29.5
Ø 29.5

SW27
SW27

M5x7
M5x7

Ø29.5

Seal
SW27

SW27
M5x7
R1/4"

Ø29.5
SW27
M5x7
G1/2"
M5x7

DIN3869

838X.XX.XX41.XX.XX.XX 838X.XX.XX30.XX.XX.XX 838X.XX.XX51.XX.XX.XX 838X.XX.XX19.XX.XX.XX 838X.XX.XX31.XX.XX.XX

10
9 2.3 7/16"-20UNF SAE J512
13.5 2.3 14.5
Ø20
M5x7
7/16"-20UNF
7/16“-20UNF

SAE4 (J1926)

SAE6 (J1926)
9/16"-18UNF

1.5
DIN3866

Ø5.05x3U
Ø 29.5
SW27

8.6
Ø29.5
SW27
M5x7

838X.XX.XX18.XX.XX.XX 838X.XX.XX42.XX.XX.XX 838X.XX.XX24.XX.XX.XX 838X.XX.XX61.XX.XX.XX

11.5
16
Bore 2.8
M 2:1
G3/4"
Ø11.3 ... Ø12.5
30°

G3/4"

G3/4"

Ra1.6
R1

16
Ø 23 H8

Ø 23
O-Ring Ø 50
Ø20x1.5
Ø 33.8
SW32

16 Sealing DIN/ISO 3869


23.9x29.2x1.5 Welding flange for
G3/4” frontal membrane (1.4301)
8380.XX.XX52.XX.XX.XX Ordering No. C27805

www.trafag.com
Operating menu
Base Display unit indication actual value Description Value range
pq
SP1 value pq Switch point SP1 (Hysteresis) or Window high FH1 SP1 > rP1, FH1 > FL1
pq Hysteresis ≥ 1 % FS
rP1 value pq Reset point rP1 (Hysteresis) or Window low FL1 rP1 < SP1, FL1 < FH1
pq
Hysteresis ≥ 1 % FS
SP2 value SP2 > rP2, FH2 > FL2
pq Switch point SP2 (Hysteresis) or Window high FH2
pq
Hysteresis ≥ 1 % FS
rP2< SP2, FL2 < FH2
rP2 value pq Reset point rP2 (Hysteresis) or Window low FL2
pq
Hysteresis ≥ 1 % FS
EF rES function pq Reset to factory settings
pq
0SEt function pq Zero set, offset correction 1) ± 2 % FS
pq
dS1 value pq Switching delay time for SP1/FH1 0.01 ... 99.99s
pq
dr1 value pq Switching delay time for rP1/FL1 0.01 ... 99.99s

H73320m Trafag AG 04/2020


pq
dS2 value pq Switching delay time for SP2/FH2 0.01 ... 99.99s
pq
dr2 value pq Switching delay time for rP2/FL2 0.01 ... 99.99s
pq
Hysteresis NO (Hno), Hysteresis NC (Hnc)
ou1 list pq Function switching output 1
Window NO (Fno), Window NC (Fnc)
pq
ou2 list pq Function switching output 2 Hysteresis NO (Hno), Hysteresis NC (Hnc)
Window NO (Fno), Window NC (Fnc)
pq
uni list pq Pressure unit bar / MPa / kPa / psi / mWC / mmWC /
inchWC / % / user scale 1)
pq
EPd display only End-point display value (option user scale unit) -998 ... 9999 1)
pq
nPd display only Zero-point display value (option user scale unit) -999 ... 9998 1)
pq
dEC display only Decimal point (option user scale unit) 0, 1, 2, 3 (value depending)
pq
Lo display only Lowest measured pressure

We reserve the right to make alternations as technical progress may warrant.


pq
Hi display only Highest measured pressure
pq
HLrE function pq Reset highest and lowest pressure value
pq
oAnA list pq Analogue output type I, U, off
pq
P_nP display only Pressure zero-point 0 % ... 50 % FS 1) 2)
pq
P_EP value pq Pressure end-point 50 % ... 100 % FS 2)
pq
display only
Voltage: 0 ... 2 VDC
o_nP Analogue output zero-point
pq
Current loop: 3.9 ... o_EP - 8 mA 1)
o_EP display only Voltage: o_nP + 4 ... 10.5 VDC
Analogue output end-point
pq
Current loop: o_nP + 8 ... 20.1 mA 1)
dAA value Damping analogue output
pq 0.01 ... 3.00 s
pq
rise time 10 ... 90 % nominal pressure
diSr list pq Display rotate no, yes (180°)
pq
actual, highest, lowest, off,
diS list pq Display mode
pq Base Display act. – 1 decimal, act. – 2 dec., act. – 3 dec.
dUPd  list pq Display update rate 1, 2, 5, 20 Hz
pq SP1
diA
function pq Diagnostic mode
pq +
parameter
StiN value pq Sampling time for logger 0.1 ... 999.9 s, off (0)

pq
EF rES
CodE value pq Access code 4-digit code
pq 
+
parameter 1)
optional function package
 2) P_EP – P_nP ≥ 50 % FS
+
parameter
Base Display
By pressing ▲+▼ simultane-
 ously the menu will return to the
SP1 base display or automatically
 after ca. 60 s without operation.
+ parameter list or value pw pw* When performing a parameter change by pres-
parameter sing ▲ or ▼ and if an access code has been defined, it
 has to be entered digit by digit.
EF rES
 After confirming the new parameter value, the menu
+
parameter
item of the changed parameter will be displayed.

+
parameter

www.trafag.com
parameter list or value pw