² The controller measure and display all output electric Button (parameters setting)
parameters for generator, and measure and display Button (scroll down menu/ value descend)
rpm, oil pressure, coolant temperature, DC source Button (scroll up menu/ value ascend)
voltage and running hours for engine. And the voltage
and current adopted true RMS measure to make sure
data exact.
Panel LED:
² Optional Chinese and English menu, large LCD
Charge fail
display.
Fail to start
² Optional kinds of preset PT-sensor, and can configure
Low oil pressure failure
parameters.
High coolant temp failure
² User defines auxiliary control relay output.
Overspeed failure
² Buttons on control panel are used for selecting control
Emergency stop
modes, starting the running procedure, displaying
LED for AUTO operation mode
data, and modifying the parameters of running and
LED for MAN operation mode
protection. LED indicators are used for indicating the
LED for Test operation mode
operation mode of controller and the running status of
LED for Unit start running
Genset, and LCD displays each measuring parameter
LED for stop/fail to stop
and status.
Mute LED
² Optional communication interface of RS485 or RS232,
realizing long distance monitor, or communication with Digital Input:
PC, fully realizing functions of remote signaling,
telemetering and remote control, can read and set the Genset remote signal
running parameters of controller. Emergency stop signal
² The controller is closely combined by panel and High coolant temp signal (warning/stop)
powder coated steel enclosure, and the panel is Low oil pressure signal (warning/stop)
die-casting by flame-retarded and high strength Pickup sensor
plastic. All connections of controller are connected by Auxiliary switch input status signal
pin-like and locked up terminal, easier and more
convenient to connect, move, maintain and replace Control Relay Output:
the device.
Fuel controls output
Measure and Display Data: Start control output
DC charger exciting output
Generator normal running
Gen 3-phase phase voltage L1-N, L2-N, L3-N
Definable auxiliary control relay output(total 3 ways)
Gen 3-phase line voltage L1- L2, L2- L3, L3- L1
Gen 3-phase current L1, L2, L3
Gen frequency Hz(L1)
Other Parameters:
Gen 3-phase apparent power AL1, AL2, AL3 DC working power source
Gen 3-phase power and total power P L1, P L2, P L3, ∑P Voltage range: 12V/24V (8-35VDC continuous)
Gen 3-phase reactive and total reactive power QL1, QL2, QL3 ∑Q Max. operation working current:@12V 0.4A ,@24V 0.2A
Gen 3-phase power factor PFL1, PFL2, PFL3 AC input voltage:phase voltage10-300VAC RMS(AC
frequency ≥ 40 Hz)
Gen active energy (KWh) ∑E
AC input frequency:3-70HZ( voltage≥10V)
Gen reactive energy (KVArh) ∑E Pickup sensor input frequency:Max.10000Hz
Genset running speed RPM Pickup sensor input voltage:1-70VAC
Engine oil pressure Kpa Fuel/ start control relay output 10A/30VDC
Engine coolant temp℃ Auxiliary relay output 3A/30VDC
Running ambient temp -20 to 50℃
Fuel level %
Storage ambient temp -40 to 80℃
Batter voltage VDC
Genset running time HOUR
-1-
GU320B Controller Brief Introduction Harsen
F1 F2 F3
1 2 3 4 5 6 7 8
GU320B
+CI485=RS485
+CI232=RS232
RS-CONNECTOR
DC power Source
(12/24VDC) RL1 RL2 RL3 RL4 RL5 RL6
WL
27 28 29 9 12 10 11 13 14 15 16 20 21 22 23 24 17 18 19 25 26
F4 F5
(2A) (16A)
Charger
Fuel sensor
P-sensor
T-sensor
Aux contact
Temp switch
DCV
Fuel Crank
-2-
GU320B Controller Brief Introduction Harsen
Version:059B081112
-3-