PART 1 GENERAL
1.2 REFERENCES
.1 American National Standards Institute (ANSI)
.1 ANSI/ASME B1.20.1, Standard for Pipe Threads, General Purpose.
.2 ANSI/ASME B16.3-, Malleable Iron Threaded Fittings Class 300.
.3 ANSI/ASME B16.9-, Factory Made Wrought Steel Buttwelding
Fittings.
.4 ANSI/ASME Section IX, Welding and Brazing Qualifications.
.2 American Society of Mechanical Engineers (ASME)
.1 ASME B31.1, Power Piping Code.
.3 American Society for Testing and Materials (ASTM International)
.1 ASTM A53/A53M, Specification for Pipe, Steel, Black and Hot-
Dipped Zinc Coated, Welded and Seamless.
.2 ASTM A106-, Seamless Carbon Steel Pipe for High-Temperature
Service.
.3 ASTM A197/A197M, Specification for Cupola Malleable Iron.
.4 ASTM A234/A234M, Pipe Fittings of Wrought Carbon Steel and
Alloy Steel for Moderate and Elevated Temperatures.
.4 Factory Mutual - FM Approval Guide.
Ver. 08/20
NL Master Specification Guide
for Public Funded Buildings
Section 21 22 00 – Clean Agent Fire
Re-Issued 2020/08/28 Extinguishing Systems Page 2 of 17
1.4 SAMPLES
.1 Submit samples in accordance with Section 01 33 00 - Submittal
Procedures.
Ver. 08/20
NL Master Specification Guide
for Public Funded Buildings
Section 21 22 00 – Clean Agent Fire
Re-Issued 2020/08/28 Extinguishing Systems Page 3 of 17
Ver. 08/20
NL Master Specification Guide
for Public Funded Buildings
Section 21 22 00 – Clean Agent Fire
Re-Issued 2020/08/28 Extinguishing Systems Page 4 of 17
1.7 WARRANTY
.1 Warranty system for parts and labour for not less than a period of 12
months from date of Substantial Completion.
1.8 COMMISSIONING
.1 Upon acceptance, system shall be commissioned and placed in operation
in accordance with Section 01 91 13.13 – General Commissioning (Cx)
Requirements.
Ver. 08/20
NL Master Specification Guide
for Public Funded Buildings
Section 21 22 00 – Clean Agent Fire
Re-Issued 2020/08/28 Extinguishing Systems Page 5 of 17
PART 2 PRODUCTS
Ver. 08/20
NL Master Specification Guide
for Public Funded Buildings
Section 21 22 00 – Clean Agent Fire
Re-Issued 2020/08/28 Extinguishing Systems Page 6 of 17
Ver. 08/20
NL Master Specification Guide
for Public Funded Buildings
Section 21 22 00 – Clean Agent Fire
Re-Issued 2020/08/28 Extinguishing Systems Page 7 of 17
Ver. 08/20
NL Master Specification Guide
for Public Funded Buildings
Section 21 22 00 – Clean Agent Fire
Re-Issued 2020/08/28 Extinguishing Systems Page 8 of 17
Ver. 08/20
NL Master Specification Guide
for Public Funded Buildings
Section 21 22 00 – Clean Agent Fire
Re-Issued 2020/08/28 Extinguishing Systems Page 9 of 17
Ver. 08/20
NL Master Specification Guide
for Public Funded Buildings
Section 21 22 00 – Clean Agent Fire
Re-Issued 2020/08/28 Extinguishing Systems Page 10 of 17
.8 General Requirements
.1 A signal shall be provided to the fire and gas monitoring system
confirming when the hybrid inert gas micro mist has discharged.
.2 All tubing, piping, and fittings for the complete system shall be
stainless steel, galvanized, or other corrosion resistant materials.
Fittings that do not have wetted surfaces may be ductile iron or
equivalent.
.3 A pressure test of the complete system (discharge pipe, tubing and
fittings) shall be carried out in accordance with the requirements of
NFPA 750 performance based design intent to ensure the system
is free of leaks prior to a final discharge test. A final discharge test
is required on every individual system prior to any machine testing
or operation to ensure piping and fittings do not come loose due to
system shock, that emitters have been positioned correctly with
suitable, unobstructed spray patterns.
.3 Standard:
.1 Manufactured, tested and marked in accordance with DOT/TC
Specification 4BW500, 4BA500, 3AA, 3A.
.2 In accordance with suppression agent manufacturer.
.4 Cylinder Assembly:
.1 Pressure seat type valve equipped with gauge.
.2 Cylinder pressure supervisor switch to provide a signal at the
control panel if the pressure in the cylinder drops to 2206 kPa.
.3 Protective Cap: threaded steel anti-recoil.
.4 Installation: free standing steel racks on solid walls.
.5 Lifting lugs: Cylinders larger than 97 kgs. shall be provided with
lifting lugs for ease of handling.
.6 Brackets: Integral brackets to be provided for secure mounting.
.7 Discharge Valve:
.1 Material: machined brass forging.
.2 Design: Pressure seated, high flow rate design incorporating
a brass piston with seal, pressure releasing for valve
Ver. 08/20
NL Master Specification Guide
for Public Funded Buildings
Section 21 22 00 – Clean Agent Fire
Re-Issued 2020/08/28 Extinguishing Systems Page 11 of 17
.2 Alarms:
.1 Type: horn/strobe.
.3 Locations:
.1 To alert personnel located in the protected areas.
.2 At entrances to protected areas.
.4 Operation:
.1 Automatic release solenoid-operated valve on cylinder that causes
discharge of agent from storage containers in the system.
.2 Program control panel to provide an adequate pre-discharge alarm
period at time of system test to ensure personnel safety.
.5 Supervision: Each releasing device shall be separately series supervised
and activated by an output directly from control panel.
.6 Features:
.1 The releasing device shall be easily removable from container
valve without emptying container.
.2 While removed from container valve, releasing device shall be
capable of being operated, with no replacement of parts required
after this operation.
Ver. 08/20
NL Master Specification Guide
for Public Funded Buildings
Section 21 22 00 – Clean Agent Fire
Re-Issued 2020/08/28 Extinguishing Systems Page 12 of 17
.2 Size: as required.
Ver. 08/20
NL Master Specification Guide
for Public Funded Buildings
Section 21 22 00 – Clean Agent Fire
Re-Issued 2020/08/28 Extinguishing Systems Page 13 of 17
.7 Standards: UL listed.
.3 Pipe junctions:
.1 NPS 2 and smaller to be threaded.
.2 Greater than NPS 2 to be welded or grooved.
.4 Piping design:
.1 To NFPA 2001.
.2 Routing: Layout piping to give maximum flow and to avoid possible
mechanical, chemical or other damage.
.5 Pipe threads: to ANSI B1.20.1.
.2 Material: Schedule 40 steel pipes at two sizes (min.) greater than the pipe
being sleeved.
.4 Extend sleeves through roof slabs to permit clearance for roofing and
flashing material.
Ver. 08/20
NL Master Specification Guide
for Public Funded Buildings
Section 21 22 00 – Clean Agent Fire
Re-Issued 2020/08/28 Extinguishing Systems Page 14 of 17
2.16 ACCESSORIES
.1 Cylinder weighing:
.1 Provide rack uprights with a weigh bar spanning the rack for
support of a portable weighing device.
.2 Provide a portable direct reading beam scale for weighing cylinders
in place by loosening cylinder clamps and disconnecting the
discharge heads without disconnection of any control components.
.2 Cylinders with a capacity of 97 kgs. or more shall be fitted with a liquid
level indicating device.
.1 Provide a graph to translate the device reading to pounds or
kilograms of clean agent at the cylinder temperature.
PART 3 EXECUTION
3.1 INSTALLERS
.1 System components and accessories shall be installed by personnel
trained and certified by clean agent specified manufacturer.
3.2 INSTALLATION
.1 General: to NFPA Standard 2001.
.3 Install cylinders to allow a service aisle for cylinder removal and cylinder
weighing.
3.3 PIPING
.1 Ream pipe after cutting to remove burrs and sharp edges.
Ver. 08/20
NL Master Specification Guide
for Public Funded Buildings
Section 21 22 00 – Clean Agent Fire
Re-Issued 2020/08/28 Extinguishing Systems Page 15 of 17
.2 Thoroughly clean pipe before installation to remove foreign matter and oil
from pipe.
.1 Pull a wire brush through pipe lengths several times.
.2 Follow with clean cloth rags treated with a non-combustible metal
cleaner designed for the purpose.
.3 Blow dry air or nitrogen through piping prior to installation of nozzles.
.7 Pipe reductions: install reductions to permit full flow. Entrance holes from
the main pipe run to the fitting to be of proper size and free of sharp
edges, ridges or burrs.
Ver. 08/20
NL Master Specification Guide
for Public Funded Buildings
Section 21 22 00 – Clean Agent Fire
Re-Issued 2020/08/28 Extinguishing Systems Page 16 of 17
.7 Allow for longitudinal movement of pipe within the U-bolt except where
piping design requires pipe to be anchored.
3.5 TESTING
.1 Thoroughly test installation for correct operation and function.
.3 Room Integrity:
.1 Standard: to NFPA 2001.
.2 Test room integrity in accordance with testing consultant or clean
agent manufacturer's written instructions.
.3 Provide a written test report to Owner’s Representative.
.4 Correct deficiencies and retest.
.4 Pressure Test:
.1 Pneumatically test system discharge piping in a closed circuit for a
period of ten minutes at 2750 kPa.
.2 Pressure drop shall not exceed 20% of the test pressure.
.5 Flow Test:
.1 Perform flow test using nitrogen on the pipe network to verify that
flow is continuous and that the piping and nozzles are
unobstructed.
.2 Install 'telltales' styrofoam cups over each nozzle that will easily
blow off when nitrogen pressure reaches the nozzle.
Ver. 08/20
NL Master Specification Guide
for Public Funded Buildings
Section 21 22 00 – Clean Agent Fire
Re-Issued 2020/08/28 Extinguishing Systems Page 17 of 17
3.6 DEMONSTRATION
.1 Upon completion of installation provide a 'hand-on' site review of system
components and operation.
END OF SECTION