Professional Documents
Culture Documents
6LTAA8.9 - G3 Derating
6LTAA8.9 - G3 Derating
Model PDG250S
250 KVA / 3 - Phase Alternator
Make & Model Powercity SLG-274J
Frequency Hz 50 60
Output Rating Prime 250 250
(KVA) Standby 275 275
Phase 3-Phase (4 Wires)
Rated Voltage V 200-240 / 380-440
Power Factor 0.8 (Lagging)
Voltage
% Within +/- 1.5
Regulation
Brushless rotating exciter
Excitation with Automatic Voltage
Regulator (AVR)
Insulation Class H
Engine
CUMMINS
Make & Model
6LTAA8.9-G3
Powercity generators are designed in conformance Vertical inline; water
cooled; 4 stroke; direct
with European Standards certified by independent Type
injected; turbo-
certifying agency the Materials Industrial Research intercooled
and Technology Center (MIRTEC) with certificate Output Rating Kw/rpm 230/1500 255/1800
number MC/TH-C-269/08. The principles in design, No. of cylinders-
mm 6 – 114 X 145
Bore X Stroke
safety, rating and performance are in accordance Piston
L 8.9
with European Standards EN 12601:2001, EN 60204- Displacement
1:2006, EN 60034-1:2004, EN ISO 12100-1:2003 and Fuel ASTM No. 2 Diesel
Fuel
EN ISO 12100-2:2003. Generators are designed and
Consumption @ L/h 34 37
built to provide electrical power for stand-by or 75% Load
continuous use. Comes with 2 years or 2,000 run Lube Oil
L 30
hours limited warranty whichever comes first. Capacity
Coolant
L 45
Features: Capacity
Battery Capacity V-Ah 12V-150Ah (2 pcs)
MANUAL or AUTOMATIC starting and Fuel Tank
L 330
Capacity
stopping capability. Unit
Digital controller. Length mm 3670
Direct injection diesel engine for fuel Dimensions Width mm 1250
efficiency. Height mm 1700
Dry Weight Kg 3000
Brushless rotating field generator with class Sound Level
H insulation. dB @ 7 m 70 75
NEMA 3R enclosure suitable for outdoor use.
Integral vibration isolators. Note: Due to continuous product improvement, the generator
Silent type generator. set manufacturer reserves the right to change the design or
specifications without notice and without any obligation or
liability whatsoever.
Engine:
GENERAL GUIDELINES FOR DERATION:
Altitude: Derate 0.5% per 100 meter (328 ft.) elevation above
1000 meter (3279 ft.).
FUEL: Use clean diesel fuel only. Diesel fuel quality should
meet the specifications of ASTM D975 and the Worldwide Fuel
Charter.