Professional Documents
Culture Documents
FRAX Demo Guide: Sweep Frequency Response Analysis
FRAX Demo Guide: Sweep Frequency Response Analysis
FDB 101
1
AC0089AE / 2013-02-07
Transformer Demo Box Guide
2
SFRA Analysis (Power Transformer)
Frequency shifts (also small shifts) indicates electrical or mechanical changes
Difference in magnitude < 3 dB is normally not of interest
3
Transformer Demo Box compared to a real-world power
transformer
> x10…
7 February, 2013 4
Transformer Demo Box Layout
Coaxial (BNC) connectors
Iron core LV winding, 200 turns HV (A+N), LV (a+n)
Z3
5
Measurement set-up
Bluetooth or USB
communication
Coaxial cables
switch on
FRAX
6
FRAX for Windows screen after start
7
Configuration menu, measurement settings
8
Change present band setting
1 (click)
9
Set band: 1 kHz to 10 MHz
OPTIMIZING TEST
2
1 3
10
File menu Menu Command
Edit nameplate... (Ctrl+E) Opens the Measurements file structure Nameplate allow
editing
11
Template for PAX Transformer Demo Box
12
Fill in the Nameplate
13
Ready to connect to FRAX-101
14
Connect
15
Ready for first sweep
16
Measure HV winding, LV winding open
Coaxial cables
FDB 101
FRAX Demo Box
17
Response from HV winding, LV winding open
18
Measure HV winding, LV winding shorted
Coaxial cables
FDB 101
FRAX Demo Box
19
Response from HV winding, LV winding shorted
HV winding,
LV winding
shorted
HV winding
(LV winding
open)
20
Measure LV winding
Coaxial cables
FDB 101
FRAX Demo Box
21
Response from LV winding
LV winding
HV winding
22
Measure HV winding, shorted turns in LV winding
Coaxial cables
Switch Shorted Turns = ON
FDB 101
FRAX Demo Box
23
Response from HV winding, shorted turn in LV
HV winding,
shorted turn
in LV
HV winding
24
Measure LV winding, shorted turn in LV winding
FDB 101
FRAX Demo Box
25
Response from LV winding, shorted turn in LV
LV winding,
shorted turn
in LV
LV winding
26
Measure LV winding, loss of turns in LV winding
FDB 101
FRAX Demo Box
27
Response from LV winding, lost turns in LV
LV winding,
lost turns
in LV
LV winding
28
Measure LV winding, bad connection in LV winding
FDB 101
FRAX Demo Box
29
Response from LV winding,
bad contact in measurement circuit
LV winding
LV winding,
bad contact, 50 Ω LV winding,
bad contact 1kΩ
(old model 2007)
30
Measure HV winding, damaged core
Coaxial cables
FDB 101
FRAX Demo Box
31
Response from HV, damaged core
HV winding,
damaged
core
HV winding
32
Measure LV winding, damaged core
Coaxial cables
FDB 101
FRAX Demo Box
33
Response from LV, damaged core
LV winding,
damaged
core
LV winding
34