You are on page 1of 11

PROPOSED (2B+G+4BES.

+18) FLOORS) RESIDEN


Fire Sprinkler Reports

for

SHEIKH ABDULAZIZ ABDULRAHMAN AL-THANI

AL-DAFNA - DOHA
DOHA

Prepared By:

GULF CONSULTING GROUP


GULF CONSULTING GROUP
DOHA
DOHA,QATAR

13 DEC, 2009
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Class nr 666 PROPOSED (2B+G+4BES.+18) FLOORS) RESIDEN Page 2

General Project Data Report


General Data

Project Title: PROPOSED (2B+G+4BES.+18) DEMAND MODE BASEMENT FLOOR


Project File Name:
FLOORS) RESIDEN SPRI..fiw
Designed By: GULF CONSULTING GROUP Date: 13 DEC, 2009
Code Reference: NFPA -13 Approving Agency: CIVIL DEFENCE
CALCULATION FOR ORDINARY HAZARD AT 1ST BASEMENT DEMAND MODE
Client Name: SHEIKH ABDULAZIZ ABDULRAHMAN
Phone:
AL-THANI
Address: AL-DAFNA - DOHA City, State Zip Code: DOHA
Company Name: GULF CONSULTING GROUP Representative: AHMED M.SAMI
Company Address: DOHA City And State: DOHA,QATAR
Phone:
Building Name: PROPOSED (2B+G+4BES.+18) SHEIKH ABDULAZIZ ABDULRAHMAN
Building Owner:
FLOORS) RESIDEN AL-THANI
Contact at Building: GULF CONSULTING GROUP Phone at Building:

Project Data

Description Of Hazard: Ordinary 1 Sprinkler System Type: Wet


Design Area Of Water Application: 120 ft² Maximum Area Per Sprinkler: 130 ft²
Default Sprinkler K-Factor: 5.65 K Default Pipe Material: SCHED 40 WET STEEL
Inside Hose Stream Allowance: 250.00 gpm Outside Hose Stream Allowance: 500.00 gpm
In Rack Sprinkler Allowance: 0.00 gpm

Sprinkler Specifications
Make: VIKING Model: VK-
Size: 1/2" Temperature Rating: 155 F

Water Supply Test Data

Source Of Information: GOVERNEMET


Test Hydrant ID: 38 Date Of Test: 13 DEC, 2009

Hydrant Elevation: 0 ft Static Pressure: 0.00 psi


Test Flow Rate: 0.00 gpm Test Residual Pressure: 0.00 psi
Calculated System Flow Rate: 1054.37 gpm Calculated Inflow Residual Pressure: 48.63 psi
Available Inflow Residual Pressure: 0 psi

Calculation Project Data

Calculation Mode: Demand


HMD Minimum Residual Pressure: 7.50 psi Minimum Desired Flow Density: 0.15 gpm/ft²
Maximum Water Velocity: 23.00 ft/s Maximum Frictional Loss / 100 feet: 20.00 psi
Number Of Active Nodes: 24
Number Of Active Pipes: 23 Number Of Inactive Pipes: 0
Number Of Active Sprinklers: 13 Number Of Inactive Sprinklers: 0

Active Version 6.0.168 1000 Pipe Capacity


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Class nr 666 PROPOSED (2B+G+4BES.+18) FLOORS) RESIDEN Page 3

Fire Sprinkler Input Data


Node Input Data

Non-Sprinkler
Sprinkler Pressure Node Elevation
Node No. Node Description Area Group Discharge
KFactor (K) Estimate (psi) (feet)
(gpm)

1 Sprinkler 5.65 13.43 24.60 0.00

2 Sprinkler 5.65 14.77 24.60 0.00

3 Sprinkler 5.65 17.15 24.60 0.00

4 No Discharge N/A 18.33 24.60 0.00

5 Sprinkler 5.65 11.91 24.60 0.00

6 Sprinkler 5.65 13.10 24.60 0.00

7 Sprinkler 5.65 17.61 24.60 0.00

8 Sprinkler 5.65 20.43 24.60 0.00

9 Sprinkler 5.65 20.76 24.60 0.00

10 No Discharge N/A 22.18 24.60 0.00

11 Sprinkler 5.65 13.75 24.60 0.00

12 Sprinkler 5.65 15.12 24.60 0.00

13 Sprinkler 5.65 20.38 24.60 0.00

14 Sprinkler 5.65 23.66 24.60 0.00

15 Sprinkler 5.65 24.04 24.60 0.00

16 No Discharge N/A 25.66 24.60 0.00

17 No Discharge N/A 30.52 24.60 0.00

18 No Discharge N/A 31.40 24.60 0.00

19 Non-Sprinkler N/A 31.90 24.60 750.00

20 No Discharge N/A 33.92 24.60 0.00

21 No Discharge N/A 40.63 12.50 0.00

22 No Discharge N/A 44.27 6.00 0.00

23 No Discharge N/A 45.36 6.00 0.00

24 No Discharge N/A 48.63 0.00 0.00

Active Version 6.0.168 1000 Pipe Capacity


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Class nr 666 PROPOSED (2B+G+4BES.+18) FLOORS) RESIDEN Page 4

Fire Sprinkler Input Data


Pipe Input Data

Nominal Nominal Fitting Total CFactor


Beg. End. Type Fitting
Pipe Description Diameter Length Length Length (gpm/inch-
Node Node Group Data
(inch) (feet) (feet) (feet) psi)

1 2 SCHED 40 WET STEEL 1.000 0 9.64 0.00 9.64 120

2 4 SCHED 40 WET STEEL 1.000 0 L 4.82 2.00 6.82 120

3 4 SCHED 40 WET STEEL 1.000 0 L 4.82 2.00 6.82 120

4 10 SCHED 40 WET STEEL 1.250 0 12.40 0.00 12.40 120

5 6 SCHED 40 WET STEEL 1.000 0 9.54 0.00 9.54 120

6 7 SCHED 40 WET STEEL 1.000 0 9.64 0.00 9.64 120

7 8 SCHED 40 WET STEEL 1.250 0 9.64 0.00 9.64 120

8 10 SCHED 40 WET STEEL 1.500 0 L 4.82 2.00 6.82 120

9 10 SCHED 40 WET STEEL 1.000 0 L 4.82 2.00 6.82 120

10 16 SCHED 40 WET STEEL 2.000 0 12.40 0.00 12.40 120

11 12 SCHED 40 WET STEEL 1.000 0 9.64 0.00 9.64 120

12 13 SCHED 40 WET STEEL 1.000 0 9.84 0.00 9.84 120

13 14 SCHED 40 WET STEEL 1.250 0 9.84 0.00 9.84 120

14 16 SCHED 40 WET STEEL 1.500 0 L 4.82 2.00 6.82 120

15 16 SCHED 40 WET STEEL 1.000 0 L 4.82 2.00 6.82 120

16 17 SCHED 40 WET STEEL 2.500 0 T 3.64 12.00 15.64 120

17 18 SCHED 40 WET STEEL 6.000 0 2T 166.50 60.00 226.50 120

18 19 SCHED 40 WET STEEL 6.000 0 3LTBG 58.00 70.00 128.00 120

19 20 SCHED 40 WET STEEL 8.000 0 3L 158.80 39.00 197.80 120

20 21 SCHED 40 WET STEEL 8.000 0 3L 105.30 39.00 144.30 120

21 22 SCHED 40 WET STEEL 8.000 0 3LTG 3.00 78.00 81.00 120

22 23 Alarm Check Valve 1.000 Loss

23 24 SCHED 40 WET STEEL 8.000 0 BGC 5.00 61.00 66.00 120

Active Version 6.0.168 1000 Pipe Capacity


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Class nr 666 PROPOSED (2B+G+4BES.+18) FLOORS) RESIDEN Page 5

Fire Sprinkler Output Data


Overall Node Groupings Output Data

Pipe Segment Pipe Pipe Sprinkler Flow Non-Sprinkler Flow Beg. Node Imbalance
Beg. End. Type At Beg. Node Out (+) In (-) Residual Flow At Beg.
Flow Rate (gpm)
Node Node Group (gpm) (gpm) (gpm) Pressure (psi) Node (gpm)

1 2 0 -20.70 20.70 0.00 0.00 13.43 0.00000

2 1 0 20.70 21.71 0.00 0.00 14.77 0.00000


2 4 0 -42.41

3 4 0 -23.40 23.40 0.00 0.00 17.15 0.00001

4 2 0 42.41 0.00 0.00 0.00 18.33 0.00000


4 3 0 23.40
4 10 0 -65.81

5 6 0 -19.50 19.50 0.00 0.00 11.91 0.00000

6 5 0 19.50 20.45 0.00 0.00 13.10 0.00000


6 7 0 -39.95

7 6 0 39.95 23.71 0.00 0.00 17.61 0.00001


7 8 0 -63.67

8 7 0 63.67 25.54 0.00 0.00 20.43 0.00002


8 10 0 -89.20

9 10 0 -25.74 25.74 0.00 0.00 20.76 0.00001

10 4 0 65.81 0.00 0.00 0.00 22.18 0.00000


10 8 0 89.20
10 9 0 25.74
10 16 0 -180.76

11 12 0 -20.95 20.95 0.00 0.00 13.75 0.00000

12 11 0 20.95 21.97 0.00 0.00 15.12 0.00000


12 13 0 -42.92

13 12 0 42.92 25.51 0.00 0.00 20.38 0.00001


13 14 0 -68.43

14 13 0 68.43 27.48 0.00 0.00 23.66 0.00002


14 16 0 -95.91

15 16 0 -27.70 27.70 0.00 0.00 24.04 0.00002

16 10 0 180.76 0.00 0.00 0.00 25.66 0.00000


16 14 0 95.91
16 15 0 27.70
16 17 0 -304.37

17 16 0 304.37 0.00 0.00 0.00 30.52 0.00000


17 18 0 -304.37

18 17 0 304.37 0.00 0.00 0.00 31.40 0.00000


18 19 0 -304.37

19 18 0 304.37 0.00 750.00 0.00 31.90 0.00005


19 20 0 -1054.37

20 19 0 1054.37 0.00 0.00 0.00 33.92 0.00000


20 21 0 -1054.37

21 20 0 1054.37 0.00 0.00 0.00 40.63 0.00000


21 22 0 -1054.37

22 21 0 1054.37 0.00 0.00 0.00 44.27 -48.20394


22 23 0 -1102.57

23 22 0 1102.57 0.00 0.00 0.00 45.36 48.20394

Active Version 6.0.168 1000 Pipe Capacity


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Class nr 666 PROPOSED (2B+G+4BES.+18) FLOORS) RESIDEN Page 6

Fire Sprinkler Output Data


Overall Node Groupings Output Data (cont'd)

Pipe Segment Pipe Pipe Sprinkler Flow Non-Sprinkler Flow Beg. Node Imbalance
Beg. End. Type At Beg. Node Out (+) In (-) Residual Flow At Beg.
Flow Rate (gpm)
Node Node Group (gpm) (gpm) (gpm) Pressure (psi) Node (gpm)

23 24 0 -1054.37

24 23 0 1054.37 0.00 0.00 0.00 48.63

Active Version 6.0.168 1000 Pipe Capacity


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Class nr 666 PROPOSED (2B+G+4BES.+18) FLOORS) RESIDEN Page 7

Fire Sprinkler Output Data


Overall Pipe Output Data

F. L./ft Pipe-Len.
Beg. Nodal Spk/Hose Residual Nom. Dia. Q (gpm) PF-(psi) PE-
Elevation (psi/ft) Fit-Len. Tot-
End. KFactor (K) Discharge Pressure Inside Dia. Velocity (psi) PV-
(feet) Fittings Len. (ft)
Node (gpm) (psi) C-Value (fps) (psi)
Type-Grp

1 5.65 24.60 20.70 13.43 1.00 20.70 0.13879 9.64 1.338


2 5.65 24.60 21.71 14.77 1.049 7.69 ----- 0.00 0.000
SCHED 40 WET STEEL 120 0 9.64 0.019

2 5.65 24.60 21.71 14.77 1.00 42.41 0.52313 4.82 3.568


4 0.00 24.60 0.00 18.33 1.049 15.75 L 2.00 0.000
SCHED 40 WET STEEL 120 0 6.82 0.039

3 5.65 24.60 23.40 17.15 1.00 23.40 0.17401 4.82 1.187


4 0.00 24.60 0.00 18.33 1.049 8.69 L 2.00 0.000
SCHED 40 WET STEEL 120 0 6.82 0.022

5 5.65 24.60 19.50 11.91 1.00 19.50 0.12426 9.54 1.185


6 5.65 24.60 20.45 13.10 1.049 7.24 ----- 0.00 0.000
SCHED 40 WET STEEL 120 0 9.54 0.018

6 5.65 24.60 20.45 13.10 1.00 39.95 0.46833 9.64 4.515


7 5.65 24.60 23.71 17.61 1.049 14.83 ----- 0.00 0.000
SCHED 40 WET STEEL 120 0 9.64 0.037

7 5.65 24.60 23.71 17.61 1.25 63.67 0.29168 9.64 2.812


8 5.65 24.60 25.54 20.43 1.380 13.66 ----- 0.00 0.000
SCHED 40 WET STEEL 120 0 9.64 0.020

4 0.00 24.60 0.00 18.33 1.25 65.81 0.31013 12.40 3.846


10 0.00 24.60 0.00 22.18 1.380 14.12 ----- 0.00 0.000
SCHED 40 WET STEEL 120 0 12.40 0.020

8 5.65 24.60 25.54 20.43 1.50 89.20 0.25696 4.82 1.752


10 0.00 24.60 0.00 22.18 1.610 14.06 L 2.00 0.000
SCHED 40 WET STEEL 120 0 6.82 0.015

9 5.65 24.60 25.74 20.76 1.00 25.74 0.20771 4.82 1.417


10 0.00 24.60 0.00 22.18 1.049 9.56 L 2.00 0.000
SCHED 40 WET STEEL 120 0 6.82 0.024

11 5.65 24.60 20.95 13.75 1.00 20.95 0.14188 9.64 1.368


12 5.65 24.60 21.97 15.12 1.049 7.78 ----- 0.00 0.000
SCHED 40 WET STEEL 120 0 9.64 0.019

12 5.65 24.60 21.97 15.12 1.00 42.92 0.53473 9.84 5.262


13 5.65 24.60 25.51 20.38 1.049 15.93 ----- 0.00 0.000
SCHED 40 WET STEEL 120 0 9.84 0.040

13 5.65 24.60 25.51 20.38 1.25 68.43 0.33333 9.84 3.280


14 5.65 24.60 27.48 23.66 1.380 14.68 ----- 0.00 0.000
SCHED 40 WET STEEL 120 0 9.84 0.021

10 0.00 24.60 0.00 22.18 2.00 180.76 0.28111 12.40 3.486


16 0.00 24.60 0.00 25.66 2.067 17.28 ----- 0.00 0.000
SCHED 40 WET STEEL 120 0 12.40 0.011

14 5.65 24.60 27.48 23.66 1.50 95.91 0.29386 4.82 2.004


16 0.00 24.60 0.00 25.66 1.610 15.11 L 2.00 0.000
SCHED 40 WET STEEL 120 0 6.82 0.016

15 5.65 24.60 27.70 24.04 1.00 27.70 0.23789 4.82 1.622


16 0.00 24.60 0.00 25.66 1.049 10.28 L 2.00 0.000
SCHED 40 WET STEEL 120 0 6.82 0.026

16 0.00 24.60 0.00 25.66 2.50 304.37 0.31025 3.64 4.852


17 0.00 24.60 0.00 30.52 2.469 20.40 T 12.00 0.000
SCHED 40 WET STEEL 120 0 15.64 0.009

17 0.00 24.60 0.00 30.52 6.00 304.37 0.00390 166.50 0.883

Active Version 6.0.168 1000 Pipe Capacity


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Class nr 666 PROPOSED (2B+G+4BES.+18) FLOORS) RESIDEN Page 8

Fire Sprinkler Output Data


Overall Pipe Output Data (cont'd)

F. L./ft Pipe-Len.
Beg. Nodal Spk/Hose Residual Nom. Dia. Q (gpm) PF-(psi) PE-
Elevation (psi/ft) Fit-Len. Tot-
End. KFactor (K) Discharge Pressure Inside Dia. Velocity (psi) PV-
(feet) Fittings Len. (ft)
Node (gpm) (psi) C-Value (fps) (psi)
Type-Grp

18 0.00 24.60 0.00 31.40 6.065 3.38 2T 60.00 0.000


SCHED 40 WET STEEL 120 0 226.50 0.000

18 0.00 24.60 0.00 31.40 6.00 304.37 0.00390 58.00 0.499


19 0.00 24.60 750.00 31.90 6.065 3.38 3LTBG 70.00 0.000
SCHED 40 WET STEEL 120 0 128.00 0.000

19 0.00 24.60 750.00 31.90 8.00 1054.37 0.01020 158.80 2.018


20 0.00 24.60 0.00 33.92 7.981 6.76 3L 39.00 0.000
SCHED 40 WET STEEL 120 0 197.80 0.000

20 0.00 24.60 0.00 33.92 8.00 1054.37 0.01020 105.30 1.472


21 0.00 12.50 0.00 40.63 7.981 6.76 3L 39.00 5.239
SCHED 40 WET STEEL 120 0 144.30 0.000

21 0.00 12.50 0.00 40.63 8.00 1054.37 0.01020 3.00 0.826


22 0.00 6.00 0.00 44.27 7.981 6.76 3LTG 78.00 2.815
SCHED 40 WET STEEL 120 0 81.00 0.000

22 ACV 6.00 44.27 1102.57


23 1.00 psi 6.00 45.36

23 0.00 6.00 0.00 45.36 8.00 1054.37 0.01020 5.00 0.673


24 0.00 0.00 0.00 48.63 7.981 6.76 BGC 61.00 2.598
SCHED 40 WET STEEL 120 0 66.00 0.000

Active Version 6.0.168 1000 Pipe Capacity


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Class nr 666 PROPOSED (2B+G+4BES.+18) FLOORS) RESIDEN Page 9

Fire Sprinkler Output Data


Overall Sprinkler Output Data

Flowing Sprinkler Residual Flowing Sprinkler


Area Group Sprinkler Flowing Area
Sprinkler Elevation Pressure (psi) Density Discharge
Code KFactor (K) (ft²)
Node No. (feet) (gpm/ft²) (gpm)

1 5.65 24.60 13.43 120.00 0.173 20.70


Sub Totals For Non-Group 120.00 0.173 20.70

2 5.65 24.60 14.77 120.00 0.181 21.71


Sub Totals For Non-Group 120.00 0.181 21.71

3 5.65 24.60 17.15 120.00 0.195 23.40


Sub Totals For Non-Group 120.00 0.195 23.40

5 5.65 24.60 11.91 130.00 0.150 19.50


Sub Totals For Non-Group 130.00 0.150 19.50

6 5.65 24.60 13.10 120.00 0.170 20.45


Sub Totals For Non-Group 120.00 0.170 20.45

7 5.65 24.60 17.61 120.00 0.198 23.71


Sub Totals For Non-Group 120.00 0.198 23.71

8 5.65 24.60 20.43 120.00 0.213 25.54


Sub Totals For Non-Group 120.00 0.213 25.54

9 5.65 24.60 20.76 120.00 0.215 25.74


Sub Totals For Non-Group 120.00 0.215 25.74

11 5.65 24.60 13.75 120.00 0.175 20.95


Sub Totals For Non-Group 120.00 0.175 20.95

12 5.65 24.60 15.12 120.00 0.183 21.97


Sub Totals For Non-Group 120.00 0.183 21.97

13 5.65 24.60 20.38 120.00 0.213 25.51


Sub Totals For Non-Group 120.00 0.213 25.51

14 5.65 24.60 23.66 120.00 0.229 27.48


Sub Totals For Non-Group 120.00 0.229 27.48

15 5.65 24.60 24.04 120.00 0.231 27.70


Sub Totals For Non-Group 120.00 0.231 27.70

Totals For All Groups 1570.00 0.194 304.37

Active Version 6.0.168 1000 Pipe Capacity


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Class nr 666 PROPOSED (2B+G+4BES.+18) FLOORS) RESIDEN Page 10

Fire Sprinkler Output Summary


Hydraulically Most Demanding Sprinkler Node

HMD Sprinkler Node Number: 5


HMD Actual Residual Pressure: 11.91 psi
HMD Actual GPM: 20.70 gpm

Sprinkler Summary

Sprinkler System Type: Wet


Specified Area Of Application: 120.00 ft²
Minimum Desired Density: 0.150 gpm/ft²
Application Average Density: 2.536 gpm/ft²
Application Average Area Per Sprinkler: 9.23 ft²
Sprinkler Flow: 304.37 gpm
Average Sprinkler Flow: 23.41 gpm

Flow Velocity And Imbalance Summary

Maximum Flow Velocity ( In Pipe 16 - 17 ) 20.40 ft/sec


Maximum Velocity Pressure ( In Pipe 12 - 13 ) 0.04 psi

Allowable Maximum Nodal Pressure Imbalance: 0.1000 psi


Actual Maximum Nodal Pressure Imbalance: 0.0879 psi
Actual Average Nodal Pressure Imbalance: 0.0073 psi
Actual Maximum Nodal Flow Imbalance: -48.2039 gpm
Actual Average Nodal Flow Imbalance: 4.0170 gpm

Overall Network Summary

Number Of Unique Pipe Sections: 23


Number Of Flowing Sprinklers: 13

Pipe System Water Volume: 335.39 gal

Sprinkler Flow: 304.37 gpm


Non-Sprinkler Flow: 750.00 gpm
Total System Demand Flow: 1054.37 gpm

Minimum Required Residual Pressure At System Inflow Node: 48.63 psi


Demand Flow At System Inflow Node: 1054.37 gpm

Active Version 6.0.168 1000 Pipe Capacity


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr Class nr 666 PROPOSED (2B+G+4BES.+18) FLOORS) RESIDEN Page 11

Fire Sprinkler Output Data


Hydraulic Supply/Demand Graph

50

45

40

35
Pressure psi

30

25

20

15

10

0
0
2 4 6 8 10 12 14 16 18 20
Flowrate(x100) gpm

Adjusted Hydrant Data


Static Pressure: 0 psi
Test Residual Pressure: 0 psi
Test Flow Rate: 0 gpm

Demand Point Data


Calculated Residual Pressure: 48.63 psi
Calculated Flow Rate: 1054.37 gpm
Excess Available Inflow Residual Pressure: -48.63 psi

Active Version 6.0.168 1000 Pipe Capacity