You are on page 1of 2

300 SERIES

Model 330
Data Sheet

Features:
•• UL 1449 Fourth Edition Listed
•• 160kA per phase rating
•• All UL required OCP & Safety Coordination included inside
–– Type 2 SPDs intended for Load Side of Main Disconnect
•• 10kA Inominal
•• 65kA SCCR
•• Voltage Specific Design – Highly configurable
•• 5 Year Warranty (longer optional)

Performance Specifications Design Attributes


Surge Capacities L-N L-G N-G Designed, Manufactured & Tested Consistent with:
–– ANSI/IEEE C62.41.1-2002, C62.41.2-2002, C62.45-2002,
160kA Per Phase (80kA Per Mode) 80kA 80kA 80kA
C62.62-2010, C62.72-2016, IEEE SA 1100-2005 (Emerald
UL 1449 Fourth Edition Listed Type 2 Book)
UL 1449 Fourth Edition tested Inominal (In): 10kA –– NEC® Article 285
–– NEC® Articles 620.51(E), 645.18, 670.6, 695.15, 700.8 & 708
UL 1449 Fourth Edition tested SCCR: 65kA requiring SPDs
UL 1449 Fourth Edition Voltage Protection Ratings (VPRs): High Energy Parallel Design for Category C High Applications
−− 208Y/120V: as low as 600V
−− 480Y/277V: as low as 1000V (data table on back) For external Mounting on Electrical Distribution Equipment,
Motor Control Centers, Panelboards, etc.
Less than 1 nanosecond response time
Fused and Thermally Protected Robust 25mm MOVs
Solid State Bidirectional Operation
Physical Specifications
Relative Humidity Range: 0 – 95% non-condensing
Diagnostic Monitoring
Operating Frequency: 47-63Hz
Green LED Status indicator per phase
Maximum Operating Temperature: -40˚C (104˚F) to 60˚C (140˚F)
Red LED Service indicator
Standard NEMA 1 Steel Enclosure (includes Green Phase LEDs
plus Red Service LED) Form C Dry Contacts 250V, 5A, includes 18 AWG pigtails
−− Size: 6.95” W x 9.5” L x 3.78” D (excluding offset nipple)
[176.65mm x 241.30mm x 96.04mm]
−− Weight: 14lb [6.3kg]
Quality, Standards & Validation
Type 2 UL 1449 Fourth Edition, cUL for Canada
Standard Flexible Conduit Included
UL file: VZCA.E324279 at www.UL.com
Standard Included 10 AWG Conductors (18”)
ISO 9001:2008 Quality Management System
Typical connection: #10 AWG and 30A breaker
ISO 17025:2005 Laboratory Qualification
Model 330 Number Configurator & Options

330  P 16 A W R D 2 
Model 330 Voltage Codes Per Phase kA Rating Modes of Connection Monitoring Enclosure UL 1449 Post Part Number
Product Line kA Rating Per Phase Protection Type Options Type1/Type 2 Accessory/Option(s)
System

Common Systems A = All Standard R = LEDs, Dry 2 = Type 2


Modes for that Contact Relay (Includes
120S =
240/120V Split Phase - 1Ø, 3W+Grnd, (Fig 1) Voltage Code cUL
120Y =
208Y/120V Wye - 3Ø 4W+Grnd, (Fig 2) Delete Mode Marking for
240H =
240/120V High Leg Delta (B High), (Fig 3) Options & Alt. Canada)
Configura- W = Wire
277Y =
480Y/277V Wye - 3Ø 4W+Grnd, (Fig 2) Leads
tions: Contact
480V Delta - 3Ø 3W+Grnd, (Fig4) & HRG Factory 10 AWG
480D =
Wye
Other Available Systems - Confirmation Encouraged 0 = No Trailing
16 = 160kA Per Phase D = NEMA 1 Accessory/Option
120N = 120V Single Phase (Fig 5) (80kA Per Mode) Steel X = Yes, Trailing
208D = 208V Delta - 3Ø, 3W+Grnd (Fig 4)
Accessory/Option
230Y = 400Y/230V Wye - 3Ø 4W+Grnd (Fig 2)
230N = 230V Single Phase (Fig 5)
240V B Corner Grnd Delta, 3Ø 3W+Grnd
240C =
(Fig 6)
240D = 240V Delta - 3Ø 3W+Grnd (Fig 4)
277N = 277V Single Phase (Fig 5)
480/240V Split Phase, or Two legs of Wye,
277S =
(Call)
400D = 400V Delta - 3Ø, 3W+Grnd (Fig 4)
480V B Corner Grnd Delta - 3Ø 3W+Grnd
480C =
(Fig 6)
480H = 480/240V High Leg Delta (B High), (Fig 3)

ASCO
®

Figure 1 Figure 2 Figure 3 Figure 4 Figure 5 Figure 6

}
Phase A (Black)
} }V
Phase A (Black) Phase A (Black) Phase A (Black)
}V A B Phase B (Black) Phase B (Orange)
V Phase A (Black) Phase A (Black)

V
}V Neutral (White)
N
Neutral (White) }V Phase B (Black)
Neutral (White)
Phase C (Black)

}
Phase B (Black) Phase C (Black)
V Phase C (Black) Ground (Green)
Phase C (Black) Neutral (White) Ground (Green)
Ground (Green) Ground (Green) Ground (Green)
C Ground (Green)

SPLIT WYE HIGH LEG DELTA DELTA & HRG WYE SINGLE POLE CORNER GROUND
2 Phases, 1 Neutral, 3 Phases, 1 (B High) 3 Phases, 3 Phases, 1 1 Phase, 1 Neutral, DELTA (B grounded)
1 Ground Neutral, (B High),1 Neutral, Ground 1 Ground 2 Phases, 1 Ground
1 Ground 1 Ground

Performance Data
UL 1449 Fourth Edition Test Data
Common Power Systems Voltage Protection Ratings (VPR - 3kA)
In SCCR MCOV
L-N L-G N-G L-L
120S = 240/120V Split Phase 600 600 600 900 10kA 65kA 150
120Y = 208Y/120V 3Ø Wye 600 600 600 900 10kA 65kA 150
240/120V B High Leg
240H = 600/1000 600/1000 600 900/1500 10kA 65kA 150/320
Delta
277Y = 480Y/277V 3Ø Wye 1000 1000 900 1800 10kA 65kA 320
480D = 480V 3Ø Delta - 1800 - 1800 10kA 65kA 640

ASCO Power Technologies surge.ascopower.com


14550 58th St. North, Clearwater, FL 33760 customercare@ascopower.com • 1-800-237-4567
© Copyright May 2019. Publication DS-70146 RevA

You might also like