contents
Medium-voltage Equipment 14-2 – 14-26
5–15 kV Types GM-SG and GM-SG-AR and
38 kV Type GM38 Metal-Clad Switchgear 14-2 – 14-4
5–15 kV Types GM-SG and GM-SG-AR Switchgear Overview 14-5 – 14-15
Type GM-SG Switchgear 14-5
Arc-Resistant Type GM-SG-AR Switchgear 14-6
Type GMSG Vacuum Circuit Breakers 14-7 – 14-8
Types GM-SG and GM-SG-AR Switchgear Dimensions 14-9 – 14-11
Types GM-SG and GM-SG-AR Switchgear Accessories 14-12 – 14-13
Types GM-SG and GM-SG-AR Switchgear End Views 14-14 – 14-15
38 kV Type GM38 Metal-Clad Switchgear 14-16 – 14-18
Type GM-SG Metal-Clad Switchgear 38 kV Gas-Insulated Metal-Clad Switchgear 14-19
OEM Component Offering 14-20
14
5–15 kV SIEBREAK™ Metal-Enclosed Load-Interrupter Switchgear 14-21
Types SIMOVAC™ and SIMOVAC-AR™ MVC up to 7.2 kV 14-22 – 14-25
Motor Protection 14-26
SWITCHGEAR
Protective Relays & SCADA Systems 14-27 – 14-33
SCADA/Substation Automation 14-27
SIPROTEC Protective Relays 14-28 – 14-31
Competitor Comparison 14-32 – 14-33
Replacement Breakers & Retrofit Products 14-34 – 14-35
Medium-voltage Replacement Circuit Breakers 14-34
Safety Racking Solutions 14-35
Field Services 14-36 – 14-39
Start-up/Commissioning/Engineer-by-the-Day Services 14-36 – 14-37
5-MSV Replacement Breaker Power System Studies 14-38
Arc Flash Study 14-39
Secondary Unit Substations 14-40 – 14-51
Overview 14-40
Type SIEBREAK Metal-Enclosed Load-Interrupter Primary Switch 14-41
Transformers—Dry Type 14-44 – 14-45
Transformers—Liquid-Filled Type 14-46
Type WL Low-voltage Switchgear Substation Secondaries 14-47
Switchboard Substation Secondaries (See Switchboard Section 13) 14-48
Transformer Diagrams 14-49 – 14-51
Low-voltage Switchgear 14-52 – 14-94
Standard WL Low-voltage Switchgear 14-52 – 14-80
Construction Details 14-53 – 14-55
WL Circuit Breakers 14-56, 14-58
Electronic Tripping Units 14-57, 14-59
Technical Information 14-60 – 14-71
Section Configuration/Dimensions 14-73 – 14-80
Type WL Low voltage Sm@rtGear Mobile App 14-81 – 14-82
Metal-Enclosed Switchgear Sm@rtGear WL Low-voltage Switchgear 14-83 – 14-84
Marine WL Low-voltage Switchgear 14-85
Arc Resistant WL Low-voltage Switchgear 14-86 – 14-88
Scan to connect
online to the Arc Flash Solutions 14-89 – 14-94
most up-to-
date version of All statements, technical information and recommendations contained herein are based on information and tests we
this Section of believe to be reliable. The accuracy or completeness hereof is not guaranteed. Since conditions of use are outside our
SPEEDFAX. control, the user should determine the suitability of the product for its intended use and assumes all risk and liability
whatsoever in connection herewith.
(Section was last modified on 07/12/19) Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 14-1
Medium-voltage Equipment
5 – 15 kV Types GM-SG and GM-SG-AR and 38 kV Type GM38 Metal-Clad Switchgear General
Single Source Responsibility The mechanism includes an indicator to equipment design, including both the
Single source responsibility is assured show the racking mechanism position switchgear structure and the circuit
since the complete equipment with the door closed. For racking, a breaker removable element. Certified
SWITCHGEAR
is designed by Siemens and is manual drive crank or an optional electric test data can be furnished to customers
manufactured and tested in a single motor drive may be used. upon request.
facility. The vacuum circuit breakers are
checked in the switchgear cells as part Automatic Shutters UL or C-UL Listing
of production testing, and to assure Automatically operated grounded steel When specified, if the component
interchangeability. shutters are included to allow or block configuration allows, the switchgear can
access to the stationary primary be provided with the UL or C-UL (for
Features disconnects. The shutters are opened use in Canada) Listed label, indicating
by the circuit breaker as it moves conformance to the requirements
Siemens Type 3AH3 Operating toward the connected position. The
Mechanism of ANSI/IEEE C37.54 and ANSI/IEEE
shutters close as the circuit breaker C37.55.
The types GMSG and 38-3AH3 is racked away from the connected
circuit breakers use the proven position. The shutters remain closed Quality Systems
Siemens type 3AH3 stored-energy until they are forced open by insertion
operating mechanism. This operator of the circuit breaker. This design Facilities involved with application,
is an evolution of the type 3A family enhances protection for personnel engineering, design and production are
of operators first introduced in 1976. compared to shutters that are linked to certified to ISO 9001 requirements.
Over 120,000 type 3AH3 operating the racking mechanism.
mechanisms have been produced since Siemens Relays, see Relaying section
1998. on page 14-28
Siemens types GM-SG and GM-SG- The switchgear structure and the “Universal” Spare Circuit Breaker
AR 5, 7.2 and 15 kV and type GM38 drawout vacuum circuit breaker are The physical configuration and interlock
38 kV metal-clad power switchgear an integrated design, with dielectric, logic allow the use of a single circuit
assemblies with horizontal drawout thermal and interruption integrity built breaker to serve as a “universal” spare
vacuum circuit breakers take advantage directly into the basic design, not added breaker at an installation site for up to
of the latest developments in vacuum as an afterthought. 50 kA for type GM-SG or type GM-SG-
interrupter technology. Up to two circuit AR, or for up to 40 kA in type GM38
breakers can be stacked in a single Siemens Vacuum Interrupters switchgear. The universal spare breaker
vertical section, allowing significant The vacuum interrupters used in the (63 kA) type GMSG vacuum circuit
space savings in the types GM-SG and types GMSG and 38-3AH3 circuit breaker is designed such that a circuit
GM-SG-AR switchgear. In the type breakers are manufactured by Siemens breaker can be installed in any type
GM38 switchgear, circuit breaker are and have been proven in thousands of GM-SG circuit breaker cell rated 63 kA.
available only in the lower compartment. installations since 1976. The chrome- Circuit breakers rated 63 kA cannot
copper contact design used in these be used in equipment rated 50 kA
The equipment meets or exceeds the vacuum interrupters assures low and lower. The interlock logic checks
latest standards of ANSI, IEEE and chopping levels, eliminating the need the principal rating characteristics
NEMA. for surge protection on most circuits. (continuous current, maximum voltage,
and interrupting current), and allows
Types GM-SG, GM-SG-AR and Front Mounted Operating a circuit breaker to be inserted in any
14
GM38 switchgear are designed for Mechanism circuit breaker cell, provided that the
use in industrial plants, commercial The simple type 3AH3 operating circuit breaker equals or exceeds the
buildings, electric utility systems, mechanism makes maintenance and ratings required by the cell.
SWITCHGEAR
cogeneration installations and other inspection easy. The mechanism is
electrical systems. It is commonly located on the front of the circuit Full ANSI and IEEE Design
used for protection and switching of breaker, rather than underneath. Background
transformers, motors, generators, Full design integrity is assured. ANSl
capacitors, buses, distribution feeder Maintenance Intervals C37.09 and C37.20.2 require design
lines and, in general, for protection of tests on circuit breakers and structures
If applied under ANSl “usual service”
any medium-voltage power circuit. together. The 3AH3 operator design
conditions, maintenance of the circuit
breaker mechanism is only needed at is controlled in our global center
Siemens’ experience gained in over 80 of competence for circuit breakers
10-year intervals for type GMSG circuit
years of supplying metal-clad switchgear in Berlin, and final assembly of both
breakers and at five-year intervals for
in the U.S. has been captured in the the drawout circuit breaker and the
type 38-3AH3 circuit breakers.
switchgear designs. The objective has switchgear structures occurs in a
been to incorporate features designed single facility. Siemens controls the
Maintenance of the switchgear cubicle
to provide safety, while simplifying entire process, from design concept to
is recommended at five-year intervals,
operation and maintenance, and production. Records are maintained to
and primarily consists of cleaning
minimizing installation cost. document compliance with ANSl/IEEE
insulation.
standards.
4
8 10
5 2
The front portion of the vertical section contains a lower cell
9
for circuit breaker, auxiliary devices, VTs, CPT (if primary fuses
SWITCHGEAR
Enclosure Design
1 Upper type GMSG circuit breaker 6 Ground bar
2 Standard accuracy current 7 Ground sensor CT The switchgear designs include full ANSI/IEEE C37.20.2
transformers (CTs)-two per 8 Main bus bars Metal-Clad construction. This means complete enclosure of
bushing 9 Power cable duct all live parts and separation of major portions of the circuit to
3 Isolated protective relay and 10 Removable barrier retard the spread of faults to other compartments.
instrument compartment 11 Surge arresters
4 Inter-unit wiring 12 Outgoing cable lugs The type GM-SG-AR design includes full ANSI/IEEE C37.20.7-
5 Lower type GMSG circuit breaker (downfeed shown) 2007, accessibility type 2B. The ground bus extends the entire
length of the complete switchgear lineup, and to all circuit
breaker cells.
Structural Flexibility for Types GM-SG and GM-SG-AR
Exhaust System for Type GM-SG-AR
Siemens metal-clad switchgear provides enhanced flexibility
in locating circuit breaker, auxiliary, and metering cells within The top-mounted pressure relief channel (PRC) is factory-
the structure layout. Circuit breakers rated 1,200 A and installed for reduced installation time. An outlet from the
2,000 A may be located in upper or lower cell positions. switchgear room is supplied with each lineup of equipment.
Bus sectionalizing (tie) circuit breaker cells may be located on Circuit Breaker Interchangeability
the upper or lower levels and are located next to an auxiliary The switchgear cubicle and the removable circuit breaker
cell on the same level for the transition bus work. element are both built to master fixtures so circuit breakers
of the same ratings are interchangeable with each other
The types GM-SG and GMSG-AR offer significant flexibility for even if the circuit breaker is required for use with a cell with
stacking breakers. See page 14-12 for more information. The “provisions only” supplied years earlier. A circuit breaker of
3,000 A circuit breaker can be used for 4,000 A continuous higher rating can be used in a cell of equal or lower rating.
current applications, with the addition of fan cooling equipment The GMSG circuit breaker is not interchangeable with the
in the auxiliary cell above or below the circuit breaker. This older designs. 63 kA rated type GMSG circuit breakers can
application of fan cooling is well suited if loads above 3,000 A only be used in 63 kA rated cells and lower rated circuit
are infrequent, as for example, in the case of a fan-cooled breakers cannot be used in 63 kA rated cells. The type
rating on a power transformer. 38-3AH3 circuit breaker is interchangeable with the type
38-3AF circuit breaker, provided the ratings are equal. The
type 38-3AF circuit breaker is not interchangeable with the
40 kA type 38-3AH3.
14
n Floor rollout circuit breaker in lower n 10,000 operations to overhaul
cell without a dolly n Three-cycle interrupting time
n Visible secondary disconnect (optional)
SWITCHGEAR
n Circuit breaker ships inside of cell, n Meets or exceeds the latest ANSI,
thus reducing installation cost and IEEE and NEMA standards
transit damage n UL or C-UL Listing available
n Pair with Siemens protective relays to
match any typical application
Maximum Rated Maximum Voltage Insulation levels dielectric Close & latch (kA)
Historic design interrupting interrupting and range rms Peak
“MVA” class voltage kV rating kA short-time kA factor Continuous current 60 Hz BIL 1.55 KI 2.6 KI
— 4.76 40 40 1.0 1,200, 2,000, 3,000 19 60 62 104
— 4.76 50 50 1.0 1,200, 2,000, 3,000 19 60 78 130
— 4.76 63 63 1.0 1,200, 2,000, 3,000 19 60 98 164
— 8.25 40 40 1.0 1,200, 2,000, 3,000 36 95 62 104
— 15.0 25 25 1.0 1,200, 2,000 36 95 39 65
— 15.0 40 40 1.0 1,200, 2,000, 3,000 36 95 62 104
— 15.0 50 50 1.0 1,200, 2,000, 3,000 36 95 78 130
— 15.0 63 63 1.0 1,200, 2,000, 3,000 36 95 98 164
4,000 A fan-cooled available using a 3,000 A circuit breaker together with a modified
switchgear structure incorporating fan cooling equipment.
Maximum Rated Maximum Voltage Insulation levels dielectric Close & latch (kA)
Historic design interrupting interrupting and range rms Peak
“MVA” class voltage kV rating kA short-time kA factor Continuous current 60 Hz BIL 1.55 KI 2.6 KI
— 4.76 40 40 1.0 1,200, 2,000, 3,000 19 60 62 104
— 4.76 50 50 1.0 1,200, 2,000, 3,000 19 60 78 130
— 4.76 63 63 1.0 1,200, 2,000, 3,000 19 60 98 164
— 8.25 40 40 1.0 1,200, 2,000, 3,000 36 95 62 104
— 15.0 25 25 1.0 1,200, 2,000 36 95 39 65
— 15.0 40 40 1.0 1,200, 2,000, 3,000 36 95 62 104
— 15.0 50 50 1.0 1,200, 2,000, 3,000 36 95 78 130
— 15.0 63 63 1.0 1,200, 2,000, 3,000 36 95 98 164
4,000 A fan-cooled available using a 3,000 A circuit breaker together with a modified
switchgear structure incorporating fan cooling equipment.
Type GM-SG-AR
switchgear available as:
n Indoor (Type GM-SG-AR)
n Outdoor walk-in Shelter-Clad (Type SGM-SG-AR)
n Single-aisle
n Factory insulated and assembled aisle (optional).
14
n F loor rollout Floor Rollout
n F ront-mounted operator When located in the lower cell, the circuit breakers are
SWITCHGEAR
n C ommon operator family arranged to rollout directly on the floor in front of the
n S imple outer-phase barriers switchgear if the switchgear is not located on a
“housekeeping” pad. No adapter, hoist, or lift truck is
n “ Universal” spare circuit breaker concept necessary.
n N on-sliding current transfer
n R ugged secondary disconnects.
Type GMSG and GM-SG-AR Circuit Breaker Ratings (New “Constant kA” Ratings Basis)
These ratings are in accordance with the following standards:
n A
NSI/IEEE C37.04-1999 Standard Rating Structure for AC High-Voltage Circuit Breakers
n A
NSI C37.06-2009 AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis - Preferred Ratings and Related
Required Capabilities for Voltages Above 1,000 Volts
n A
NSI/IEEE C37.09-1999 Standard Test Procedure for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis
n A
NSI/IEEE C37.010-1999 Application Guide for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis
Rated Values Units 5-GMSG- 5-GMSG- 5-GMSG- 7-GMSG- 15-GMSG- 15-GMSG- 15-GMSG- 15-GMSG-
40- 50- 63- 40- 25- 40- 50- 63-
xxxx-104 xxxx-130 xxxx-164 xxxx-104 xxxx-65 xxxx-104 xxxx-130 xxxx-164
Maximum Design Voltage (V)b kV rms 4.76 4.76 4.76 8.25 15.0 15.0 15.0 15.0
14
Voltage Range Factor (k)c — 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
Power
kV rms 19 19 19 36 36 36 36 36
SWITCHGEAR
Frequency
Withstand
Voltage Levels Lightning
kV crest 60 60 60 95 95 95 95 95
Impulse (BIL)
ms 83 83 83 83 83 83 83 83
Interrupting Timeg
cycles 5 5 5 5 5 5 5 5
Maximum Symmetrical
kA rms sym 40 50 63 40 25 40 50 63
Interrupting (I)
% dc Component % 47 47 47 47 47 47 47 47
a xxxx” in type designation refers to the continuous current rating 1,200 A, 2,000 A,
“ e ll values apply to polyphase and line-to-line faults.
A
or 3,000 A, as appropriate. The 4,000 A fan-cooled rating is achieved using a 3,000 A f Standard duty cycle is O - 0.3s - CO - 3 min. - CO.
circuit breaker, in combination with fan cooling as indicated in Footnote 4. g Standard rated interrupting time is five cycles (83 ms)/Optional rated interrupting
b Maximum design voltage for which the circuit breaker is designed, and the upper time of three cycles (50 ms) 63 kA is available (except with 24 Vdc tripping).
limit for operation.
c K is listed for informational purposes only. For circuit breakers rated on a “constant
kA basis”, the voltage range factor is 1.0.
d 4,000FC indicates that fan cooling is included in the switchgear structure for this
rating. 4,000 A rating is not available in outdoor equipment.
Dimensions 72” (1,829 mm) aisle space recommended allows room for interchange of circuit
are approximate.
Add 6” (152 mm) to each end of the lineup for aisle extension 12” (304 mm) total. breakers. Minimum aisle space required for handling circuit breaker with lift truck is
65” (1,651 mm). Minimum aisle space required if all circuit breakers are at floor level
14
Dimensions are approximate size of floor footprint.For outdoor equipment, enclosure
overhangs floor frame. Refer to Footnote 5. is 55” (1,397 mm).
If indoor switchgear is installed on a raised housekeeping pad, the pad must not Add 9” (229 mm) to length of the lineup for end trims.
The switchgear must have at least 6” (152 mm) horizontal clearance:
extend farther than 3” (75 mm) from the front of the switchgear to avoid interference
SWITCHGEAR
with the use of the portable lift truck. • From left and right sides to nearest wall or equipment, and
Add for roof and enclosure overhang: • From rearmost extension of vents on rear to nearest wall or equipment.
No obstructions permitted within 10” (254 mm) of top of switchgear structure.
• Rear (cable side):
Add 4.5” (114 mm) to depth for front and rear doors.
• Non-walk-in: 3.6” (92 mm)
Add 1.0” (25 mm) for GM-SG-AR equipment rated 63 kA.
• Shelter-Clad: 3.6” (92 mm).
Add weight of circuit breakers from Table 13.
• Front (drawout side):
• Non-walk-in: 3.7” (94 mm)
• Shelter-Clad: 1.7” (43 mm).
Stacking versatility
Auxiliary
1,200 A 1,200 A C 1,200 A 2,000 A 2,000 A
circuit circuit circuit circuit circuit
breaker breaker breaker breaker breaker
Auxiliary
A A D A A A
Auxiliary
1,200 A 1,200 A 2,000 A 1,200 A 2,000 A
E
14
B F B B B B
Auxiliary Auxiliary
C 2,000 A Vented7 Fan7 3,000 A C
circuit circuit
breaker breaker
Auxiliary Auxiliary
D A A A A D
Footnotes for GM-SG non-arc-resistant (up to 63 kA) and GM-SG-AR arc-resistant (up to 50 kA) :
Main bus sizes 1,200 A, 2,000 A, 3,000 A or 4,000 A (self-cooled).
No rollout auxiliaries allowed in upper cell (C or D) if lower cell (B) has 3,000 A circuit breaker. If 3,000 A circuit breaker is located in upper cell (A), one rollout auxiliary may be
located in lower cell F.
Auxiliary cells (C, D, E or F) may each contain one rollout (except as indicated in Footnotes 2 and 7).
Fuse rollout for stationary CPT must be located in lower rollout cell F, if CPT is located in rear or is remote.
Stacking arrangements are available as shown for all types of equipment in the GM-SG family. Total circuit breaker loading in a vertical unit may not exceed main bus rating.
Consult Siemens for specific application assistance regarding total load limits in each unit or refer to ANSI/IEEE C37.20.2.
Generator circuit breakers (type GMSG-GCB) conform to same stacking rules as standard (nongenerator) circuit breakers.
For fan-cooled 4,000 A rating, circuit breaker (3,000 A self-cooled, 4,000 A fan-cooled) may be located in lower cell (B) with fan cooling in cell A.
-
GM-SG-AR arc-resistant 63 kA
14
circuit circuit circuit circuit circuit
breaker breaker breaker breaker breaker
SWITCHGEAR
B B B B B B
Auxiliary
2,000 A Vented7 Fan7 Auxiliary
circuit
breaker
D A A A A
Accessories
Standard accessories include:
n Manual racking crank
n Spring charging crank
n Drawout extension rails (to enable
handling of circuit breakers or
auxiliary rollouts in upper cells or
above floor level)
n Lift sling (for circuit breakers or
rollout trays above floor level)
n Split plug jumper (standard unless
test cabinet is furnished)
n Contact lubricant
n Touch-up paint
n Auxiliary rollout tray insertion/
14
resistant up to 63 kA).
14
Type GMSG-MO manually operated ground and test device Type GMSG-EO electrically operated
ground and test device
SWITCHGEAR
Manually operated ground and test Electrically operated ground and test
Note: Due to the special nature of ground
and test devices, each user must develop device (up to 50 kA), type GMSG-MO device (for up to 50 kA and for 63 kA),
definitive operating procedures for incor- The type GMSG-MO ground and test type GMSG-EO
porating safe operating practices. Only device (up to 50 kA) is a drawout An electrical ground and test device
qualified personnel should be allowed to element that can be inserted into a includes a power-operated switch
use ground and test devices. circuit breaker cell rated for a short- (derived from a type GMSG circuit
circuit current of 50 kA or lower. The breaker) arranged to allow grounding
type GMSG-MO device opens the one set of disconnect stabs. These
shutters, connects to the cell primary devices are able to close and
disconnecting contacts and provides a latch against short-circuit currents
means to make the primary disconnect corresponding to the ratings of the
stabs available for testing or grounding. equipment.
The type GMSG-MO device is suitable
for high-potential testing of outgoing The electrically operated ground and test
circuits of the switchgear main bus device rated for a short-circuit current of
or for phase sequence checking. The 50 kA can be used in any type GM-SG
type GMSGMO device also provides a family circuit breaker compartment rated
means to connect temporary grounds up to 50 kA.
to de-energized circuits for maintenance
purposes. The 63 kA device can be used only
in type GM-SG family circuit breaker
The manual ground and test compartments rated 63 kA.
incorporates three-position, single-pole
switches (upper stabs to ground, neutral Neither the 50 kA device nor the 63 kA
and lower stabs to ground), eliminating device require any adapters for use in
the need for userfurnished ground cells.
cables. The switches are hookstick
operable and, in the closed position, Two devices, one each for the upper
are rated for the full momentary and and lower stabs, are required if
short-time ratings of the associated grounding is desired to either side of
switchgear. User-furnished grounding the unit. The type GMSG-EO device
cables and commercially available also provides a means of access to the
ground clamps seldom have ratings primary circuits for high potential tests
equal to those of the switchgear. or for phase sequence checking.
107.0 (2,718)
line
SWITCHGEAR
179.7 (4,564)
Front
panel 3.6 (92)
116.4
(2,957)
14
SWITCHGEAR
102.8 (2,611)
Type GM-SG-AR indoor switchgear
179.7 (4,564)
Factory assembly 70.6 (1,796) Factory assembly 109.1 (2,771)
3.0 (76.2)
Exhaust
plenum
2.0 (51.6)
location
135.6
127.2 44 (1,117) door (2,802)
41.6 (1,056) 2.0 (51.6) 105.7
(3,231) 115.0
opening (2,685)
(2,921)
72 (1,929) aisle
40.8
(1,036)
Type 38-3AH3-1500 ratings are in accord with ANSI C37.06-1987. Types 38-3AH3-31 and 38-3AH3-40 ratings conform to ANSI/IEEE C37.06-2009 ratings.
Maximum voltage for which the circuit breaker is designed and the upper limit for operation.
K is the ratio of rated maximum voltage to the lower limit of the range of operating voltage in which the required symmetrical and asymmetrical inter-
rupting capabilities vary in inverse proportion to the operating voltage.
3,000 A ratings are achieved using forced air cooling in the switchgear cubicle.
To obtain the required symmetrical interrupting capability of a circuit breaker at an operating voltage between 1/K times rated maximum voltage and
rated maximum voltage, the following formula shall be used.
Rated Maximum Voltage
Required Symmetrical Interrupting Capacity = Rated Short Circuit Current × Operating Voltage
For operating voltages below 1/K times rated maximum voltage, the required symmetrical interrupting capability of the circuit breaker shall be equal to
K times rated short circuit current.
With the limitations stated in 5.10 of ANSI/IEEE Standard C37.04-1979, all values apply for polyphase and line-to-line faults. For single phase-to-ground
faults, the specific conditions stated in 5.10.2.3 of ANSI Standard C37.04-1979 apply.
Current values in this row are not to be exceeded even for voltages below 1/K times rated maximum voltage. For voltages between rated maximum
voltage and 1/K times rated maximum voltage, follow 5 above.
Current values in this row are independent of operating voltage up to and including rated maximum voltage.
Included for reference only—not listed in ANSI/IEEE C37.06.
Enclosure Dimensions
Cubicle Dimensions—Per Vertical Section Type 38-3AH3 Circuit Breaker
Dimensions in inches (mm) Weights in lbs. (kg)
Weight
Type in lbs. (kg) Height Width Depth Drawout Aisle Cont.
Current Circuit BreakerType
5,000 110.0 48.0 130.0 96.0 (2,438)
Indoor GM38 Amps 38-3AH3-1500 38-3AH3-31 38-3AH3-40
(2,273) (2,794) (1,219) (3,302) Recommended
Shelter-Clad 6,400 132.5 48.0 234.5 96.0 (2,438) 1,200 800 (364) 800 (364) 850 (387)
SGM38
Single-Aisle (2,909) (3,366) (1,219) (5,956) Included
Shelter-Clad 11,700 132.5 48.0 363.75 96.0 (2,438) 2,000 900 (409) 900 (409) 950 (432)
SGM38
Common- Aisle (5,318) (3,366) (1,219) (9,239) Included
3,000 1,000 (455) 1,000 (455) 1,050 (478)
Aisle-less 5,800 130.5 48.0 139.35 96.0 (2,438)
OGM38
non-walk-in (2,636) (3,315) (1,219) (3,539) Recommended
Add 6" (152 mm) to each end of lineup Add for roof overhang Non-Walk-in Shelter-Clad
for aisle extension, 12" (305 mm) total. Rear (Cable Side) 3.875" (98 mm) 3.875" (98 mm)
Front 6.875" (175 mm) 1.5" (38 mm)
14
130.0 6.78 139.35
(3,302) (172) (3,539)
SWITCHGEAR
130.5 126.87
(3,315) (3,223)
110.0
(2,794)
8.0
(203)
127.0
(3,226)
Type GM38 indoor switchgear Type OGM38 non-walk-in outdoor switchgear
234.5 (5,956)
96.0
(2,438)
132.5 126.87
Front panel
(3,366) (3,223)
Aisle
Aisle floor
Switchgear base 8.0
Floor line (203)
229.0 (5,817)
363.75 (9,239)
3.87
Factory assembly Field assembly Factory assembly
(98)
3.87
(98)
96.0
(2,438)
Front panel
Front panel
132.5 (3366)
Aisle
126.87 (3,223)
8.0
(203)
Floor line
356.0 (9,042)
110
(2.794)
A. Surge arrester
14
Auxiliary/1,200A, 2,000 A or 3,000 A circuit breaker (no drawout Circuit breaker 1,200 A or 2,000 A with VT auxiliary (downfeed
SWITCHGEAR
D
B
C
B. Drawout D. Drawout
primary primary
current limiting current
fuses for VTs limiting fuses
C. VTs E for CPT
E. Control power
(1Ø or 3Ø)
VT auxiliary/1,200 A or 2,000 A circuit breaker (upfeed cables) CPT fuse truck/stationary CPT (1Ø or 3Ø)
K
F
L J. Feeder circuit
breaker
M
K. Main bus to
G right side
L. Transition bus
F. Main bus to M. Main bus to
left side J left side (bus
H
G. Main bus to tie circuit
right side breaker
H. Bus tie circuit section)
breaker
Auxiliary/Bus tie circuit breaker Auxiliary/feeder circuit breaker (adjacent to right side of bus tie
circuit breaker section)
Gas-Insulated Switchgear
Types 8DA10 and 8DB10 medium- Features include:
voltage, gas-insulated switchgear are gas- n Tested for arc-resistance to IEEE
insulated, vacuum circuit breaker designs C37.20.7-2007, type 2A
with a voltage range of 4.16 kV to 38 kV.
n Significantly reduced PPE needs
Lightning impulse withstand voltage
ratings up to 200 kV BIL and interrupting n Compact – up to 80% smaller
ratings up to 40 kA are available. than air-insulated switchgear
The types 8DA10 and 8DB10 medium- n 20-year internal maintenance
voltage, gas-insulated switchgear designs cycle
feature fixed-mounted, vacuum circuit n Meets IEEE and IEC standards
breakers, connectable to the main bus n UL or C-UL Listing available
through three-position (closed-open-ready
to ground) switches. The position of the n Single-phase design eliminates
switches is externally observable from phase-to-phase faults
the front of the unit using a convenient n Meets NEC visible disconnect
14
camera system. Medium-voltage, gas- requirement
insulated switchgear is suitable for n Well suited for contaminated
systems where small size, arc resistance, environments
SWITCHGEAR
environmental immunity or reduced
n Pair with Siemens protective
maintenance needs are important.
Depending upon the voltage rating, relays to match any application.
medium-voltage, gas-insulated switchgear
is approximately 1/5th the size of
conventional air-insulated switchgear.
Rated Values
Maximum Design Voltage kV 15 27 38 42*
Frequency Hz 60 60 60 60
Power-Frequency Withstand Voltage (1 min.) kV rms 36 60 80 80
Lightning Impulse Withstand Voltage kV peak 95 125 170; 200* 185; 200*
Short-Circuit Interrupting Current kA 40 40 40 40
Short-Time Withstand Current, 3 s kA 40 40 40 40
Short-Circuit Making Current (close and latch) kA peak 104 104 104 104
Peak Withstand Current kA peak 104 104 104 104
Continuous Current of Main Bus A 4,000 4,000 4,000 4,000
Continuous Current of Circuit Breakers A 2,500 2,500 2,500 2,500
Type 8DA dimensions in inches (mm) Type 8DB dimensions in inches (mm)
82.7
47.2 (2,100) 47.2
73
(1,200) (1,200)
(1,850)
106.3 106.3
(2,700) (2,700)
59 59
(1,500) (1,500)
n Rollouts
n Bus Boots / Insulation Products
n Lifting devices and other accessories
SION 3AE5 IEC MV Breaker
For more information, please contact
1-800-241-4453, email: info.us@
siemens.com, or your local sales office.
GMSG Skeleton
14
n Upper and lower ventilation louvers
n Glass-polyester bus supports Modular configurations to mount:
SWITCHGEAR
n Non-corrosive nameplate n Surge arresters
n Space heater with thermostat n Instrument transformers
n NEMA CC1 hole patterns for cable n Control power transformers
termination. n Power meters
n Meets or exceeds applicable n Other auxiliary equipment.
standards from ANSI, IEEE, CSA,
EEMAC, and NEMA. Applications:
n Standalone bay
n Transformer primary
n Lineups.
SIEBREAK Specifications
Rated voltage Type 5 kV 15 kV
Rated frequency 50/60 Hz
Rated duration power frequency withstand voltage 19 kV 36 kV
Rated lightning impulse withstand voltage (BIL) 60 kV 95 kV
Fuse short circuit current rating Current Limiting 50 kA 50 kA
Expulsion 37.5 29.4
Switch rating Continuous Current 600 A and 1200 A
Interrupting rms 25 kA and 38 kA
Momentary rms 40 kA, 61 kA, 80 kA
Assembly rating Main bus continuous current 1200 A and 2000 A
Short-time 2 second 25kA and 38 kA
The Siemens SIMOVAC-AR and Two-high compartment 340 A top 340 A top 340 A top
SIMOVAC medium-voltage controller with 12SVC400 controller 400 A bottom 400 A bottom 380 A bottom
allows the user to combine vacuum One-high compartment 400 A top 380 A top
contactors, latched contactors and load- 400 A top or bottom
with 12SVC400 controller or bottom or bottom
break switches in one lineup. The user One-high compartment
720 A 720 A 630 A
can also connect directly to Siemens with 12SVC800 controller
type GM-SG-AR or GM-SG medium-
voltage switchgear with a transition Controller assembly ratings
section. This provides extreme flexibility Insulation
in systems design. Short-circuit level Main bus
Maximum current class (impulse) continuous Short-time current Internal arc resistance
voltage kV E2 kA
kV current A duration (main bus) (SIMOVAC-AR only)
1,200, 2,000, 10 cycles Accessibility
5.0 63 60
3,000, 4,000 (2-seconds optional) type 2B 0.5 seconds
1,200, 2,000, 10 cycles Accessibility
7.65 63 60
3,000, 4,000 (2-seconds optional) type 2B 0.5 seconds
All c Insulationlevel is for the controller, with inductive
main bus ratings are on a self-cooled,
ventilated basis. transformers disconnected for testing (per UL 347).
b Short-time duration for controllers without main bus is d 50 kA with certain contactor/ fuse combinations.
e Type 12 up to 2,000 A. Type 3R up to 3,000 A.
limited to contactor capability (with fuses).
Contactor/controller ratings
Enclosed Interrupting capacity Motor horsepower rating (three-phase) Transformer loads
System Vacuum continuous
voltage contactor ampere rating Unfused class E1 Fused class E2 Synchronous motors Induction motors Max motor Max three- phase Max fuse
kV Type A kA kA 0.8 PF 1.0 PF HP fuse rating kVA rating
2.3 12SVC400 400 4.8 63 1,500 1,750 1,500 24R 1,500 450E
2.3 12SVC800 720 7.2 63 3,000 3,500 3,000 57X 2,500 900E
4.0 12SVC400 400 4.8 63 2,500 3,000 2,500 24R 2,500 450E
4.0 12SVC800 720 7.2 63 5,500 6,000 5,500 57X 5,000 900E
4.6 12SVC400 400 4.8 63 3,000 3,500 3,000 24R 3,000 450E
4.6 12SVC800 720 7.2 63 6,000 7,000 6,000 57X 5,000 900E
6.9 12SVC400 400 4.8 63 4,000 5,000 4,000 24R 2,000 -3,500 200E -18R
6.9 12SVC800 720 7.2 63 8,000 10,000 8,000 57X 4,000-6,000 400E -57X
Refer With24R fuse, interrupting capacity is 50 kA. Fuse shown will not permit transformer forced cooling
to Controller maximum current capability table
for further detail. With48X or 57X fuse, interrupting capacity is 50 kA. rating of 133 percent of self-cooled rating.
Based on self-cooled transformer rating. Maximum fuse is 18R.
14
accessibility type 2B
n UL 347 5th edition/CSA C22.2 No.
SWITCHGEAR
253-09
n 400 A bolt-in or plug-in (optional) or
720 A bolt-in vacuum contactor
n 400 A or 720 A non-load-break
isolation switch
n 2.4 kV, 4.16 kV and 6.9 kV (up to 7.65
kV) system voltage ratings
n 1,200 A, 2,000 A, 3,000 A or 4,000 n Isolation switch mechanically
A main bus with standard epoxy interlocked with the access door
insulation on bus bars, and with to prevent user access to primary
optional boots for insulating joints compartment when isolation switch is
n Tin- or silver-plated bus available closed
n Front accessible n Low-voltage compartment is
isolated from the medium-voltage
n Main bus and ground bus are
compartment
supported and braced up to 63 kA
two-second short-time capability n All components are front accessible,
facilitating routine inspection or parts
n Top-mounted pressure relief channel
replacement
shipped installed for reduced site
installation time n Current-limiting fuses, contactor
assembly and isolating switch
n Isolation switch with visible indication
assembly are easily removed from
through viewing window to verify that
the enclosure
the power cell is isolated from line-
side source – no need to open panel n The main bus compartment is top,
door side and front accessible for easy
installation and extension.
General description A
(2,413 mm) tall, while SIMOVAC-AR its own door, and has the following
indoor sections are normally 36” (914 features:
mm) wide, 40” (1,016 mm) deep and D
are similar but are usually 48” (1,218 grounded metal barriers and provides
mm) wide. ample space for relays, terminal
14
Item Description
Isolating switch
A
operating handle
Primary current-limiting
B
fuses
G
C Contactor
Phase current
D
transformers
F
Ground sensor A
E H
transformer
Primary fuses for control B B B
F
power transformer
Control power
G
transformer D
C
Outgoing cable E
terminations D
H I
(with optional ball-type C
A
ground studs) F
Optional voltage
I
transformers
G
12SVC400 12SVC800
A A A A A
B B
C D
D G C I
H
E F E
F F
B
F
C C D C
J
D
E
F
14
One-high Load-interrupter Incoming line Two-high Side view
controller switch - 600 A controllers
SWITCHGEAR
Item Description Item Description Item Description
A Main bus compartment E Isolating switch handle I Upper controller compartment
B Isolating switch blade viewing window F High-voltage door J Lower controller compartment
C High-voltage door handle G Interrupter switch blade viewing window
D Low-voltage door H Interrupter switch handle
K K K K K
A A A A A
B B
C D C
D G I
H
E
E F
F F
B
F D
C C C
J
D
E
F
600A load-interrupter switches are 36” (914 mm) wide. Foroutdoor non-arc-resistant configurations, add 6”
1,200 A switches are 48” (1,218 mm) wide. (151 mm) per section.
Overload protection –
types 3RU or 3RB
Running overcurrent (overload)
protection for the motor must also
be provided according to NEMA
standards. This overload (or longtime)
protection can be provided by the
Siemens type 3RU (OLR) bimetallic
thermal overload relay. This three-phase
adjustable relay provides inherent
singlephase protection and phase
unbalance protection with NEMA class
10 tripping characteristics, providing
optimum protection for motors having
acceleration times of six seconds or
less and allowable hot locked rotor
times of five seconds or more. It is
equipped with an isolated normally
14
14
visualization. Specifically designed
n Fully compliant with the IEC 61850
before the switchgear is deployed for energy applications, it assists the
industry design standard. in the substation, which significantly operating personnel in optimizing the
reduces the project schedule and
SWITCHGEAR
n Automated Power Quality and
operations management. It provides
on-site integration risk. quick visualization and response to
protection relay fault record retrieval
n Plant owners can see savings through substation conditions. SICAM SCC is
and data reporting (supports NERC
PRC-002 and 005). automated power quality reporting. based on SIMATIC WinCC, one of the
leading process visualization systems
n Substation Human Machine Interface
SICAM PAS Substation Server that is used in industrial automation
(HMI) for visualization, alarm handling world. The client-server architecture
and control using graphical displays. SICAM PAS works on industrial-
allows for up to 16 client off of a signal
standard hardware with the Microsoft
n NERC CIP cyber security compliance server for extensive visualization of
Windows operating systems. The
tools. the power system throughout the
advantages of this platform are low
n Redundant server option for greater substation and industrial plant.
hardware and software costs, ease
reliability of operation, scalability, flexibility and
n Communications redundancy via constantly available support. With the
Parallel Redundancy Protocol (PRP) powerful real-time data distribution
and High Availability Redundancy system, applications can be allocated
Protocol (HSR) among several computers, thus
n Fully complient with IEC 61850
boosting performance, connectivity
Edition 2 and availability of over 600 intelligent
Unmatched reliability
Siemens SIPROTEC protective relays average a 600-year
mean time between failures (MTBF), meaning for every
600 relays you own, you can expect one or fewer failures High reliability measured on more than one million digital
per year. This measurement is the result of over 1.2 million relays in service.
relays installed worldwide, and it includes “out-of-the-box” or Important: SIPROTEC quality data does not exclude “out-of-
“initial” failures. the-box” or “initial” failures.
14
SIGRA event analysis software provides viewing and calculations for
SWITCHGEAR
Comtrade event files
For more information, please visit http://automation.usa.siemens.com/consultant/ or contact your local sales office.
Breaker management
Pilot wire differential
Voltage, frequency
Motor protection
motor protection
Line differential
Breaker failure
Generator and
Synchronizing
Overcurrent
Differential
Distance
7RW600
7SA522
7SD600
7SD610
7UT612
7UT613
7SV600
7SJ600
7SJ602
7UM61
7UM62
7VH60
7UT63
7VK61
7SK80
7SS60
7SS52
7SJ45
7SJ46
7SJ80
7SJ61
7SJ62
7SJ63
7SJ64
7SA6
7SD5
7VE6
ANSI
No.* Protection functions
14 Locked rotor protection — — — — — — — — — — l l l l ■ — — — — — — ■ ■ — — — —
21 Distance protection, phase ■ ■ — l — — — — — — — — — — — — — — — — — ■ ■ — — — —
Distance protection, earth
21N ■ ■ — l — — — — — — — — — — — — — — — — — — — — — — —
(ground)
21FL Fault locator ■ ■ — l — — — — — l — l l l — — — — — — — — — — — — —
14
27 Undervoltage l l — l l — — — — l — l l l l — — — l — — ■ ■ l l — ■
n Standard function
l Optional
] ANSI/IEEE C37.2: IEEE Standard Electrical Power System Device Function Numbers
For more information, please visit http://automation.usa.siemens.com/consultant/ or contact your local sales office.
Breaker management
Pilot wire differential
Voltage, frequency
Motor protection
motor protection
Line differential
Breaker failure
Generator and
Synchronizing
Overcurrent
Differential
Distance
7RW600
7SA522
7SD600
7SD610
7UT612
7UT613
7SV600
7SJ600
7SJ602
7UM61
7UM62
7VH60
7UT63
7VK61
7SK80
7SS60
7SS52
7SJ45
7SJ46
7SJ80
7SJ61
7SJ62
7SJ63
7SJ64
7SA6
7SD5
7VE6
ANSI
No.* Protection functions
67 Directional overcurrent — — — — l — — — — l — l l l — — — — — — — ■ ■ — — — —
Directional earth-fault
67N l l — l l — — — ■ l — l l l l — — — — — — ■ ■ — — — —
overcurrent
Stator earth-fault directional
67G — — — — — — — — — — — — — — — — — — — — — ■ ■ — — — —
overcurrent
14
68 Power swing detection l l — l — — — — — — — — — — — — — — — — — — l — — — —
SWITCHGEAR
78 Out-of-step protection — — — — — — — — — — — — — — — — — — — — — — ■ — — — —
79 Auto-reclosure l l — l l — — l l l l l l l — — — — — — — — — ■ — — —
81 Frequency protection ■ ■ — l l — — — — l — l l l l — — — l — — ■ ■ — l — ■
Rate-of-frequency-change
81R — — — — — — — — — l — l — — l — — — — — — l l — l — l
protection
Vector jump supervision — — — — — — — — — — — — — — — — — — — — — l l — l — —
86 Lockout function ■ ■ ■ ■ ■ — — — — ■ ■ ■ ■ ■ ■ — ■ ■ ■ ■ — ■ ■ ■ l — —
Differential protection
87G — — — — — — — — — — — — — — — — ■ ■ ■ — — — ■ — — — —
generator
Differential protection
87T — — ■ l l — — — — — — — — — — ■ ■ ■ ■ — — — ■ — — — —
transformer
87BB Differential protection busbar — — — — — — — — — — — — — — — — ■ ■ ■ ■ ■ — — — — — —
n Standard function
l Optional
] ANSI/IEEE C37.2: IEEE Standard Electrical Power System Device Function Numbers
For more information, please visit http://automation.usa.siemens.com/consultant/ or contact your local sales office.
Feeder Protection
Model Siemens Equivalent Typical Catalog Number
ABB CO (4 single phase) 7SJ45 (1 three phase) 7SJ4505-1EA00-1AA1 (1 three phase)
7SJ46 (1 three phase) 7SJ4605-1EA00-1AA0 (1 three phase)
7SJ601 (1 three phase) 7SJ6015-4EA01-0AA0 (1 three phase)
ABB Microshield 7SJ600 7SJ6005-4EA00-0DA1
7SJ602 7SJ6025-4EB00-1FA0
7SJ80 7SJ8041-5EC96-3FC1+L0G
7SJ61 7SJ6115-5EC90-1FA0+L0D
14
7SJ62 7SJ6215-5EC90-1FE0+L0D
ABB DPU-1500 7SJ62 7SJ6215-5EC90-1FE0+L0D
7SJ63 7SJ6315-5EC90-1FE0+L0D
SWITCHGEAR
7SJ64 7SJ6405-5EC92-1FE4+L0D
ABB DPU-2000R 7SJ62 7SJ6215-5EC90-1FE0+L0D
7SJ63 7SJ6315-5EC90-1FE0+L0D
7SJ64 7SJ6405-5EC92-1FE4+L0D
Basler BE3-51 (4 single phase) 7SJ45 (1 three phase) 7SJ4505-1EA00-1AA1 (1 three phase)
7SJ46 (1 three phase) 7SJ4605-1EA00-1AA0 (1 three phase)
Basler BE1-51 (4 single phase) 7SJ45 (1 three phase) 7SJ4505-1EA00-1AA1 (1 three phase)
7SJ46 (1 three phase) 7SJ4605-1EA00-1AA0 (1 three phase)
7SJ601 (1 three phase) 7SJ6015-4EA01-0AA0 (1 three phase)
Basler BE1-851 7SJ600 7SJ6005-4EA00-0DA1
7SJ602 7SJ6025-4EB00-1FA0
7SJ80 7SJ8041-5EC96-3FC1+L0G
7SJ61 7SJ6115-5EC90-1FA0+L0D
Basler BE1-951 7SJ62 7SJ6215-5EC90-1FE0+L0D
7SJ63 7SJ6315-5EC90-1FE0+L0D
7SJ64 7SJ6405-5EC92-1FE4+L0D
GE MDP 7SJ45 7SJ4505-1EA00-1AA1
7SJ46 7SJ4605-1EA00-1AA0
7SJ601 7SJ6015-4EA01-0AA0
7SJ80 7SJ8041-5EC96-3FC1+L0G
GE 735 7SJ600 7SJ6005-4EA00-0DA1
7SJ602 7SJ6025-4EB00-1FA0
7SJ80 7SJ8041-5EC96-3FC1+L0G
7SJ61 7SJ6115-5EC90-1FA0+L0D
GE 750 7SJ62 7SJ6215-5EC90-1FE0+L0D
7SJ63 7SJ6315-5EC90-1FE0+L0D
7SJ64 7SJ6405-5EC92-1FE4+L0D
GE F60 7SJ62 7SJ6215-5EC90-1FE0+L0D
7SJ63 7SJ6315-5EC90-1FE0+L0D
7SJ64 7SJ6405-5EC92-1FE4+L0D
SEL 351A 7SJ62 7SJ6215-5EC90-1FE0+L0D
7SJ63 7SJ6315-5EC90-1FE0+L0D
7SJ64 7SJ6405-5EC92-1FE4+L0D
SEL 351 7SJ62 7SJ6215-5EC90-1FE0+L0D
7SJ63 7SJ6315-5EC90-1FE0+L0D
7SJ64 7SJ6405-5EC92-1FE4+L0D
SEL 351S 7SJ62 7SJ6215-5EC90-1FE0+L0D
7SJ63 7SJ6315-5EC90-1FE0+L0D
7SJ64 7SJ6405-5EC92-1FE4+L0D
SEL 501 7SJ600 7SJ6005-4EA00-0DA1
7SJ602 7SJ6025-4EB00-1FA0
7SJ80 7SJ8041-5EC96-3FC1+L0G
7SJ61 7SJ6115-5EC90-1FA0+L0D
SEL 551 7SJ600 7SJ6005-4EA00-0DA1
7SJ602 7SJ6025-4EB00-1FA0
7SJ80 7SJ8041-5EC96-3FC1+L0G
7SJ61 7SJ6115-5EC90-1FA0+L0D
*Siemens catalog numbers in Bold are the preferred equivalent model.
Siemens does not accept any liability for the information contained in this document.
For more information, please visit http://automation.usa.siemens.com/consultant/ or contact your local sales office.
General Protection
Model Siemens Equivalent Typical Catalog Number
ABB GPU2000 7UM62 7UM6215-5EC90-0BA0+L0D
Basler BE1- GPS100 7UM61 7UM6115-5EC90-0CA0+L0D
7UM62 7UM6215-5EC90-0BA0+L0D
Beckwith M-3420 7UM61 7UM6115-5EC90-0CA0+L0D
7UM62 7UM6215-5EC90-0BA0+L0D
Beckwith M-3425 7UM62 7UM6215-5EC90-0CA0+L0D
GE 489 7UM61 7UM6115-5EC90-0CA0+L0D
7UM62 7UM6215-5EC90-0BA0+L0D
SEL 300G 7UM61 7UM6115-5EC90-0CA0+L0D
7UM62 7UM6215-5EC90-0BA0+L0D
Bus Protection
Model Siemens Equivalent Typical Catalog Number
ABB HU 7VH60 7VH6002-0EA20-0AA0
ABB CA 7VH60 7VH6002-0EA20-0AA0
ABB TPU2000R 7UT513 7UT5135-4GB11-1AA0
14
7UT612 7UT6125-5EC00-1AA0
Basler BE1-87 7UT513 7UT5135-4GB11-1AA0
7UT612 7UT6125-5EC00-1AA0
SWITCHGEAR
(3) 7VH60 7VH6002-0EA20-0AA0
GE PVD 7VH60 7VH6002-0EA20-0AA0
GE B30 7UT513 7UT5135-4GB11-1AA0
7UT612 7UT6125-5EC00-1AA0
SEL 387 7UT513 7UT5135-4GB11-1AA0
7UT612 7UT6125-5EC00-1AA0
Transformer Protection
Model Siemens Equivalent Typical Catalog Number
ABB HU (3) 7UT512 (1) 7UT5125-4GB11-0AA0
7UT513 (1) 7UT5135-4GB11-1AA0
7UT612 (1) 7UT6125-5EC00-1AA0
ABB CA (3) 7UT512 (1) 7UT5125-4GB11-0AA0
7UT513 (1) 7UT5135-4GB11-1AA0
7UT612 (1) 7UT6125-5EC00-1AA0
ABB TPU2000R 7UT512 7UT5125-4GB11-0AA0
7UT513 7UT5135-4GB11-1AA0
7UT612 7UT6125-5EC00-1AA0
Basler BE1-CDS 7UT513 7UT5135-4GB11-1AA0
7UT612 7UT6125-5EC00-1AA0
GE 745 7UT513 7UT5135-4GB11-1AA0
7UT612 7UT6125-5EC00-1AA0
GE T60 7UT513 7UT5135-4GB11-1AA0
7UT612 7UT6125-5EC00-1AA0
SEL 387 7UT513 7UT5135-4GB11-1AA0
7UT612 7UT6125-5EC00-1AA0
SEL 587 7UT512 7UT5125-4GB11-0AA0
7UT513 7UT5135-4GB11-1AA0
7UT612 7UT6125-5EC00-1AA0
Voltage/Frequency Protection
Model Siemens Equivalent Typical Catalog Number
Basler BE1-27 7RW600 and 7RW80 7RW60000-4EA00-0DA0 and 7RW8020-5EC96-1DA0+L0G
Basler BE1-59 7RW600 and 7RW80 7RW60000-4EA00-0DA0 and 7RW8020-5EC96-1DA0+L0G
Basler BE1-27/59 7RW600 and 7RW80 7RW60000-4EA00-0DA0 and 7RW8020-5EC96-1DA0+L0G
Basler BE1-81O/U 7RW600 and 7RW80 7RW60000-4EA00-0DA0 and 7RW8020-5EC96-1DA0+L0G
GE IAV 7RW600 and 7RW80 7RW60000-4EA00-0DA0 and 7RW8020-5EC96-1DA0+L0G
GE IFV 7RW600 and 7RW80 7RW60000-4EA00-0DA0 and 7RW8020-5EC96-1DA0+L0G
GE MIV 7RW600 and 7RW80 7RW60000-4EA00-0DA0 and 7RW8020-5EC96-1DA0+L0G
GE NGV 7RW600 and 7RW80 7RW60000-4EA00-0DA0 and 7RW8020-5EC96-1DA0+L0G
GE DFF 7RW600 and 7RW80 7RW60000-4EA00-0DA0 and 7RW8020-5EC96-1DA0+L0G
GE MFF 7RW600 and 7RW80 7RW60000-4EA00-0DA0 and 7RW8020-5EC96-1DA0+L0G
GE SFF 7RW600 and 7RW80 7RW60000-4EA00-0DA0 and 7RW8020-5EC96-1DA0+L0G
*Siemens catalog numbers in Bold are the preferred equivalent model.
Ratings from 5–38 kV, 250–1500 MVA, Siemens Medium-voltage Replacement Circuit Breakers
1200-3000 Amperes The following circuit breakers are available as pre-engineered designs. Other
Replacement circuit breakers provide a manufacturers, models, and ratings can be engineered by Siemens.
cost-effective way to upgrade your
system capabilities while saving you from Transformer Protection
costly maintenance and lost productivity
Manufacturer Model kV Ratings AMP
and preserving your investment in MVA
existing cubicles and cables. Allis-Chalmers AM 5 150 1200, 2000
Whether your equipment was originally (All Air-Magnetic) 250 1200, 2000
MB 7 250 1200, 2000
manufactured by Allis-Chalmers,
500 1200, 2000
Westinghouse, GE, Federal Pacific, ITE, MC/MCV 15 150 1200
or another manufacturer, we will assist 250 1200, 2000
you to evaluate the Siemens replacement 500 1200, 2000
options which best meet your needs. MA 5 250 1200, 2000
Why Replacement Breakers? 350 1200, 2000
FA 5 350 3000
n Increased Reliability and Performance
FB 7 500 1200, 2000, 3000
n Reduced Operating and Maintenance FC/FCV 15 500 1200, 2000
Expenditures 750 1200, 2000
14
14
In addition to eliminating the need for arc flash With the Operator’s Station in hand, the As the breaker is being racked, the operator
suits during racking, SARRACS also streamlines operator moves to a location safely beyond receives precise real-time location and
SWITCHGEAR
the procedure. First, the unit is positioned the flash zone. The object, switchgear and movement readings. Should a problem occur,
and secured. Then, the operator connects the breaker are selected on the touch screen. Next, fault-indicating screens are displayed, and the
breaker’s racking mechanism to SARRACS’ the starting position is input and the racking racking process is terminated immediately.
Racking Adaptor. operation initiated.
For more information, please visit http://automation.usa.siemens.com/consultant/ or contact your local sales office.
14
SWITCHGEAR
Motor Control Center Startup Service
n Ensure that all protective devices have
been properly set and locked
n Review power fuse selection and
installation procedures
n Conduct a general physical inspection
of MCC power and control
connections. Check tightness of
connections
Now, you can take advantage of the n Dry type transformers Siemens Industry is committed to
expertise of a Siemens factory-trained n Insulated case circuit breakers ensuring that your equipment is up and
engineer to startup your Siemens power running...when you need it. Siemens
n Molded case circuit breakers
distribution and control equipment Industrial Services provides expert
purchases. n Panelboards factoryauthorized equipment startup at
Engineer-by-the-Day is available in n Sensitrip circuit breakers a special rate when you purchase the
complete one-day increments for setup service before your product is delivered.
n Switchboards
of the following products*: Get your equipment up and running on
n Switches
n ACCESS power monitoring time. Contact your local distributor or
n More Siemens Industry sales office to learn
n Busway
more.
For more information, please visit http://automation.usa.siemens.com/consultant/ or contact your local sales office.
14
faults.
enhance the safety of your personnel
Arc Flash Hazards 3. Arc Flash Hazard Calculations and the reliability of your operation.
The incident energy level, the flash
SWITCHGEAR
In the fraction of a second that it takes SARRACS — Complete arc flash
hazard boundary, and the PPE required
copper to expand to vapor, an arc flash protection for switchgear racking.
are then calculated for each location.
can generate skin-searing heat — four After completion of your Arc Flash Hazard
times hotter than the surface of the sun. 4. Documentation
Study and Equipment Labeling efforts,
The information above is compiled for
Recent revisions to NFPA70E require why not consider another aspect to your
you into a comprehensive report,
that an Arc Flash Hazard Analysis be personnel safety initiatives? Why not
which contains information necessary
performed prior to working on or near consider Siemens’ SARRACS remote
to comply with regulatory
electrical equipment containing exposed circuit breaker racking system? Racking
requirements.
energized conductors. The analysis medium-voltage circuit breakers (>1000V)
determines the arc flash boundaries 5. Unsafe Work Locations into and out of a live bus is one instance
(AFB), incident energy levels and the The report will identify work locations where the PPE required may not be
required level of personal protective having incident energy levels in excess adequate to protect personnel from arc
equipment (PPE). The recommendations of available PPE ratings. flash. Siemens SARRACS effectively
in the analysis can be used to determine 6. Arc Flash Hazard Mitigation removes the operator from the arc flash
hazards in your workplace. Implementing Recommendations will be made to boundary by allowing for remote
the recommendations will help protect minimize Arc Flash Hazards by installation or removal. In addition,
your workers and help you satisfy OSHA changes in system protection or SARRACS provides torque monitoring to
requirements. operational procedures. detect improper breaker connection.
7. Arc Flash Hazard Labels
In addition to the report, our customers
will receive a field label containing the
flash hazard boundary distance,
incident energy level, PPE category
and shock hazard for each location.
For more information, please visit http://automation.usa.siemens.com/consultant/ or contact your local sales office.
For more information, please visit http://automation.usa.siemens.com/consultant/ or contact your local sales office.
SIEBREAK Specifications
Standard Optional
n Indoor type 1 enclosure n UL or C-UL Listing
n Large 8” x 18” (203 mm x 457 mm) n Current-limiting or explusion fuses
viewing window n Indoor type 2 drip-proof enclosure
n Hinged, grounded metal barrier in n Indoor type 12 dust-resistant
front of switch blades enclosure
n Provisions for key interlocking n Outdoor non-walk-in type 3R
n Upper and lower ventilation louvers enclosure
n Glass-polyester bus supports n Motor-operated mechanism
n Non-corrosive nameplate n Tin-plated copper bus.
n Space heater with thermostat n Auxiliary switches (2 NO-2 NC)
n NEMA CC1 hole patterns for cable n Mimic bus
14
termination. n Ground studs
n Meets or exceeds applicable n Screens and filters (indoor)
SWITCHGEAR
standards from ANSI, IEEE, CSA,
EEMAC, and NEMA.
Dimensions
Indoora Depth 62 inches (1581 mm) 72 inches (1829 mm) 56 inches (1422 mm)
Widthbde 54 inches (1372 mm) 90 inches (2286 mm) 54 inches (1372 mm) not available
Notes:
a Incoming cables available top or bottom entry
b Transformer connection available left side or right side
c Auxiliary devices not available with selector and front access
d Outdoor width include 18-inch (457 mm) liquid-filled transformer termination section
e For outdoor dry type transformer, add 2.67 inches (67 mm) to the width for termination
Technical Data
Rated voltage Type 5 kV 15 kV
Rated frequency 50/60 Hz
Rated duration power frequency withstand voltage 19 kV 36 kV
Rated lightning impulse withstand voltage (BIL) 60 kV 95 kV
Fuse short circuit current rating Current Limiting 50 kA 50 kA
Expulsion 37.5 29.4
Switch rating Continuous Current 600 A and 1200 A
Interrupting rms 25 kA and 38 kA
Momentary rms 40 kA, 61 kA, 80 kA
Assembly rating Main bus continuous current 1200 A and 2000 A
Short-time 2 second 25kA and 38 kA
14
Voltage typea Interrupting kA MVA 500 kVA 750 kVA 1000 kVA 1500 kVA 2000 kVA 2500 kVA 3000 kVA 3750 kVA 5000 kVA
2400 CL-14 50 260 200 250 400 500 600 — — — —
RBA400 37.5 155 200 250 400 — — — — — —
RBA800 37.5 155 — — — 540 720 — — — —
4160 CL-14 50 450 100 125 200 300 500 500 — — —
RBA400 37.5 270 100 150 200 300 400 — — — —
RBA800 37.5 270 — — — — 540 540 — —
4800 CL-14 50 520 80 125 200 250 400 450 — — —
RBA400 37.5 310 100 125 200 250 400 400 — — —
RBA800 37.5 310 — — — — — — 540 — —
7200 CL-14 50 620 65 80 125 200 250 300 — — —
RBA400 29.4 365 65 80 125 200 250 300 400 — —
RBA800 29.4 365 — — — — — — — 450 —
12470 CL-14 50 1079 40 50 65 100 125 200 200 250 —
RBA400 29.4 635 40 50 80 100 150 200 200 250 400
RBA800 29.4 635 — — — — — — — — —
13200 CL-14 50 1143 30 50 65 100 125 150 200 250 300
RBA400 29.4 672 30 50 65 100 125 150 200 250 300
RBA800 29.4 672 — — — — — — — — —
13800 CL-14 50 1195 30 50 65 100 125 150 200 250 300
RBA400 29.4 702 30 50 65 100 125 150 200 250 300
RBA800 29.4 702 — — — — — — — — —
Notes:
a Incoming cables available top or bottom entry
b Transformer connection available left side or right side
c Auxiliary devices not available with selector and front access
d Outdoor width include 18-inch (457 mm) liquid-filled transformer termination section
e For outdoor dry type transformer, add 2.67 inches (67 mm) to the width for termination
14
volts) incoming power
n Transformer: reduces incoming
voltage to utilization voltage (600 volts
SWITCHGEAR
or less)
n Secondary: distributes power to, Primary Switch Dry-Type Transformer Type SB3 Switchboard
and provides protection for, outgoing
feeders (600 volts and less).
4 in. 4 in.
D
Plan view
W
Fan
control
HV-terminal panel
Danger
Front
Fan
control
HV when req. LV
air N.P. air
H terminal terminal Ground
chamber chamber bus
(optional) (optional)
14
18 in. 18 in. W
(457 mm) Front view (457 mm)
indoor Front view
Std. Std. outdoor
SWITCHGEAR
Type = VPI/VPE
Primary Volts = 2400-13800
Sec_Volts = 208-600
Temperature Rise = 150C for Aluminum Windings, 80/115C for Copper Windings
Standard kV BIL (HV/LV) = 60/30 for Aluminum Windings, 95/30 for Copper Windings
14
Aluminum 2500 112 126 60 16200
Aluminum 3000 118 132 60 19200
SWITCHGEAR
Aluminum 3750 126 138 66 25000
Aluminum 5000 132 144 66 28000
Copper 300 90 90 60 6200
Copper 500 90 96 60 7000
Copper 750 90 102 60 9100
Copper 1000 96 112 60 10600
Copper 1500 102 118 60 14300
Copper 2000 108 118 66 18200
Copper 2500 118 126 66 19500
Copper 3000 126 132 66 23500
Copper 3750 126 144 66 28000
Copper 5000 132 160 66 35000
H
8
G
C
A
H3 X3
X2 D E
J H F
2 X1
H1 X0
14
SWITCHGEAR
Weights, gallons of fluid and dimensions are for reference only, and not for construction.
Please contact Siemens Industry Inc. for exact dimensions
14
Product Scope
Equipment ratings:
SWITCHGEAR
n
635 Vac maximum
Three-phase, three-wire
Three-phase, four-wire
50/60 Hz
6,000 A maximum horizontal bus
5,000 A maximum vertical bus.
n Enclosure options:
NEMA 1 indoor
NEMA 3R outdoor walk-in
NEMA 3R outdoor non walk-in.
Product Overview
SWITCHGEAR
92.0 (2,337)
with
transformer
9.0 9.0 A A
9.0 9.0
(229) (229)
(229) (229)
14
Swgr Swgr
gnd gnd
(X0) H1 H2 H3 H1 H2 H3 (X0)
SWITCHGEAR
(X1) (X2) (X3) (X3) (X2) (X1)
56.0 (1,422), 62.0 (1,575), 72.0 (1,829), or 56.0 (1,422), 62.0 (1,575), 72.0 (1,829), or
82.0 (2,083) transformer to left of switchgear 82.0 (2,083) transformer to left of switchgear
(flush front transformer mounting) (flush front transformer mounting)
Footnotes:
1. This arrangement applies to indoor SIEBREAK switch 5 kV-15 kV up to 1,200 A termination with dry-type transformer termination.
2. Filler strips at the ends of the transformer must be provided by the transformer supplier in case the transformer exceeds 92” (2,337
mm) height and 56” (1,422 mm) depth.
3. If cables are to be used for connections to transformer, transformer supplier to provide and install cable connections including lugs
and insulation on terminals if required. Maximum 2 x 500 kcmil cables per phase.
4. If bus bars are to be used for connections to transformer, transformer supplier to provide and install required bus connections.
Transformer supplier also to provide and install flex connectors for connections to switchgear as well as insulation for flex
connectors.
5. Connect switchgear ground when continuous ground is required.
6. Transformer supplier to provide necessary hardware (except PEM nuts) for joining switchgear with transformer.
Termination on
left-hand side Transformer
symmetrical to flange
cL transformer right-hand side Termination on
throat except phase right-hand side
H1 H2 H3 reversal symmetrical to H1 H2 H3
(X1) (X2) (X3) cL transformer Z Z left-hand side (X3)(X2) (X1)
92.0 (2,337)
except phase
92.0 (2,337)
throat
reversal
55.0 (1,397)
55.0 (1,397)
Swgr 8.0 8.0
8.0 8.0
14
33.55 (852)
33.55 (852) 56.0 (1,422)
56.0 (1,422), 62.0 (1,575), 18.0 36.0 18.0
72.0 (1,829), or 82.0 (2,083) (457) (914) (457)
transformer to left of switchgear
Footnotes:
1. This arrangement applies to indoor SIEBREAK switch 5 kV-15 kV up to 1,200 A termination with liquid-filled type transformer
termination.
2. This arrangement applies to bar-type connection to transformer only.
3. Filler strips at the ends of the transformer must be provided by the transformer supplier in case the transformer exceeds 92” (2,337
mm) height and 56” (1,422 mm) depth.
4. Transformer supplier to provide necessary hardware (except PEM nuts) for joining switchgear with transformer.
Swgr gnd
Termination on
(X0)
left-hand side
Transformer
symmetrical to
105.0 (2,667)
flange
cL transformer right-hand side Termination on
throat except phase right-hand side
H3 H2 H1 reversal symmetrical to H1 H2 H3
(X1) (X2) (X3) cL transformer Z Z left-hand side (X3)(X2) (X1) Swgr
105 (2,667)
98.9 (2,512)
64.12 (1,629)
98.7 (2,507)
Five 3/8-16
14
61.0 (1,549)
52.8 (1,341)
61.0 (1,549)
8.0 8.0 8.0 8.0
PEM nuts for
(203) (203) (203) (203)
joining
cL transformer
SWITCHGEAR
switchgear
throat
with
transformer
33.55 (852)
33.5 (851) 18.0 36.0 18.0
72.0 (1,829) transformer to (457) (914) (457) 72.0 (1,829) transformer
left of switchgear on right side of switchgear
Footnotes:
1. This arrangement applies to outdoor SIEBREAK switch 5 kV-15 kV up to 1,200 A termination with liquid-filled type
transformer termination.
2. This arrangement applies to bar-type connection to transformer only.
3. Transformer supplier to provide necessary hardware (except nuts) for joining switchgear with transformer.
Type WL Low-voltage
Metal-Enclosed Switchgear
Siemens Type WL low-voltage metal-
enclosed switchgear is designed,
constructed and tested to provide
superior power distribution, power
monitoring and control. At the heart of
the Type WL low-voltage switchgear is
the World Class Siemens WL breaker.
Siemens Type WL low-voltage
switchgear can be utilized in the
following applications:
n Industrial
14
Semiconductor
Petrochemical
Automotive
SWITCHGEAR
Biotech
Pharmaceutical Type WL Low-voltage
n Institutional Metal-Enclosed Switchgear
Water treatment
Airports
Universities Industry Standards
Medical facilities Type WL switchgear with power circuit n ANSI C37.17 — Trip Devices for AC
Correctional facilities breakers are designed, tested and and General Purpose DC Low-voltage
n Critical power constructed in accordance with: Power Circuit Breakers
Data Processing n UL 1558 — Metal-Enclosed Low- n NEMA SG3 - Low-voltage Power
Continuous industrial process voltage Power Circuit Breaker Circuit Breakers
Hospitals Switchgear Features and modifications required
n Utility and co-generation by NEC are incorporated when the
n ANSI C37.20.1 — Metal-Enclosed
n Commercial Low-voltage Power Circuit Breaker assembly is designated as “Service
Large office buildings Switchgear Equipment.”
Distribution centers n ANSI C37.50 — Test Procedure
Large warehouses
UL Listing
for Low-voltage AC Power Circuit Underwriters’ Laboratories listing mark
Breakers Used in Enclosures (UL) is supplied for each vertical section
Product Scope: n ANSI C37.51 — Conformance Testing provided all devices within a vertical
n Equipment ratings of Metal-Enclosed Low-voltage AC section are UL Listed or UL Recognized
635VAC Maximum Power Circuit Breaker Switchgear and suitable for the intended use. All
3 Phase 3 Wire, Assemblies circuit breaker drawout elements are
3 Phase 4 Wire n NEMA SG5 - Power Switchgear UL Listed.
50/60 Hz Assemblies Optional CSA compliance with cUL
6000 amp maximum horizontal bus labeling is available.
n Applicable requirements of the
6000 amp maximum vertical bus
National Electric Code (NEC) Arc Resistant
n Enclosure options
WL drawout circuit breakers are in Optional Type WL arc resistant low-
NEMA 1 Indoor
accordance with: voltage switchgear is available and is
NEMA 3R Outdoor Walk-In
NEMA 3R Outdoor Non Walk-in n UL 1066 — Low-voltage AC and UL listed to ANSI/IEEE C37.20.7. Type
DC Power Circuit Breakers Used in 2B arc resistant accessibility rating with
Siemens WL breakers can be manually maximum internal acring short-circuit
Enclosures
or electrically operated, fused or current rating of 100kA @508V and
unfused and are available in the n ANSI C37.13 — Low-voltage AC
Power Circuit Breakers Used in 85kA @ 635V.
following rating designations – N, S, H,
L, M and F. Refer to tables on Page 13 Enclosures Seismic Qualification
for interrupt and withstand ratings for n ANSI C37.16 — Preferred Ratings, Seismic qualification to all major seismic
each rating designation. Related Requirements, and construction standards (IBC, UBC, CBC,
Application for Low-voltage Power SBC, BOCA and IEEE 693) is available.
Circuit Breakers and AC Power Circuit
Protectors
General Standard finish color is light gray ANSI Each complete vertical section contains
The Siemens Type WL switchgear 61. The standard painting process is a three compartments.
assembly consists of one or more UL approved electrostatic powder coat (1) Front compartment containing
metal-enclosed vertical sections. The paint system utilizing a polyester breakers and/or auxiliary equipment
end sections are designed to allow powder coat paint. The completed finish (2) Bus compartment containing
installation of future sections. has a nominal 2 mils dry film thickness. horizontal and vertical bus
(3) Rear cable compartment containing
Each vertical section consists of up to Assembly Construction the load side runbacks connecting
four individually enclosed breaker or Siemens Type WL metal-enclosed low the load side of the breaker to the
auxiliary compartments which are sized voltage switchgear is constructed of load cable terminals
to provide uniform height. a rigid internal frame structure that
minimizes the possibility of damage Within the front compartment, each
Included in each assembly are various during shipment and supports multiple breaker is barriered and compartmented
components such as circuit breakers, installation methods – rolling or lifting. from all other breakers in the front
instrumentation and control equipment, Lifting eyes are integrated into the compartment. This design also isolates
transformers, relays, three-phase bus internal frame design and ensure the breakers in the front compartment
work, and all internal wiring, connectors, the structural integrity of the lifting from the bus compartment.
and other supporting equipment. assembly is always adequate for the
14
weight of the total structure. Optional barriers can be supplied to
In accordance with ANSI C37.20.1, the isolate the bus compartment from the
SWITCHGEAR
maximum temperature for parts that If requested in advance, the switchgear rear cable compartment. Other optional
are handled is 50°C. The main bus structure can be shipped so that the barriers include: (1) Full depth section
maximum temperature rise is 65°C unit can be tilted onto its back during barriers to isolate one section from the
above 40°C ambient. The temperature installation. This is an option that must adjacent section(s). (2) Barriers to isolate
rise of the air surrounding the cable be specified at order entry. the incoming line side connections to
connection points is limited to 45°C the main breaker(s) from the load side
above 40°C ambient. bus and connections in the switchgear
section. (Line/load barriers are provided
Finish as a standard feature for service
During construction, the structural steel equipment main breakers.)
parts, panels, and compartments are all
prepared for painting by a five-stage
wash system.
1
Breaker Hoist and Track 2
2 Ventilation and Lifting Structure
3 Quarter Turn Door Latch
4 Secondary Disconnect Access Door
3
5 Channel Sill Base (Optional)
6 Breaker Compartment 7
7 Auxiliary Instrument Compartment 4
8 Secondary Disconnect
9 Breaker Cradle (Guide Frame)
Breaker Drawout Rail
6
TOC Switch Operator
9
5
Main and Ground Bus Control and Communication Wiring Circuit Breaker Compartments
The standard main bus is silver-plated Standard control and communication Typical circuit breaker compartments
copper. Tin-plated copper bus is wiring is #14 AWG extra-flexible, include primary disconnects, drawout
optionally available. Vertical and stranded copper type SIS. Control rails, secondary disconnects, vertical
horizontal bus bar utilize a channel and communication wiring is installed wireway, horizontal wireway and,
shape design to maximize short circuit and accessed from the front of the if applicable, TOC switch operator,
withstand capability and minimize heat switchgear structure. Each breaker MOC switch operator and associated
rise. All bus joints include Grade 5 bolts compartment has a dedicated horizontal interlocks. Draw-out rails allow the
and conical spring washers. Provisions and vertical wireway. breaker to be withdrawn from the
for future extension of the main bus compartment without additional
include plated joints and high tensile For devices not having screw-type extensions or adapters. Up to six (2
strength steel hardware. terminals, pressure terminals are used. sets of three) current transformers for
metering or relaying can be mounted
The main three-phase horizontal bus Insulation in each compartment.
is arranged vertically one phase above The insulation used is a UL recognized
the other with edge-to-edge alignment thermoset material that has excellent heat A variety of auxiliary devices such as
to provide high, short circuit strength. resistance, flame retardance, dimensional breaker control switches, indicating
14
Insulated main bus with isolated vertical stability and low moisture absorption. lights and pushbuttons can be mounted
bus is optional. on the breaker compartment door.
SWITCHGEAR
5 6 7 8
14
closed). lighting, receptacles, switches and load
(RBRD) is available as an optional centers offered as options.
Shutters accessory that allows maintenance
SWITCHGEAR
These provide protection against personnel to safely rack Siemens
accidental contact with primary Type WL breakers into the Connect,
disconnects in a compartment when Test and Disconnect positions from
the breaker is removed. Shutters up to 30 feet away from the breaker.
automatically close when the breaker This allows the operator to be outside
is withdrawn and are pad-lockable and the arc flash hazard boundary and
field installable. thereby providing additional personnel
protection.
Key Interlock • 4” high formed steel channel sills
This provides a mechanical means are available for indoor switchgear
for operating circuit breakers and enclosures.
other devices only when predescribed
conditions are met. Outdoor Switchgear
Type WL switchgear is available in two
Test Set outdoor (NEMA 3R) enclosures. Walk-in
A portable breaker test set is available and non walk-in versions are available
as an option and supports testing the to meet your particular application.
full range of functions and protective
settings supplied with the breaker trip For protection from snow, rain and
unit. other foreign matter, both outdoor Side View
enclosures rest on a six-inch high,
Metering and Auxiliary Compartments formed steel base which provides rigid
Compartments are available to house support and a tight bottom seal. A
devices such as voltage transformers, heavy duty protective under-coating is
metering, control power transformers, applied to the underside of all outdoor
and supervisory devices. enclosures to protect against moisture
and corrosion. Shielded ventilation
Instrument and Control Transformers housings permit proper air circulation
Voltage transformers and control power while excluding dirt and foreign matter.
transformers are mounted in auxiliary
compartments. These transformers In the walk-in outdoor enclosure a
are protected by primary pull-out type lighted, unobstructed service aisle is
current-limiting fuses and secondary provided at the front of the switchgear
fuses. Current transformers are allowing inspection and maintenance
normally mounted on the compartment without exposure to the elements.
primary disconnect studs where they An access door equipped with an
are readily accessible. See Tables on emergency bar release is located at
Page 31 for available ratings. each end of the aisle.
Rear View
WL Circuit Breaker
Superior individual products for low-voltage power distribution systems
2 6 7
5
3
4 8
14
9
SWITCHGEAR
1
21
25
22
23
24
Guide Frame (for drawout version only) 9 Multiple Secondary Connections Complete Trip Unit Family
2 Vertical to Horizontal BUS Connector Auxiliary Switch Block Remote Reset
3 Position Signaling Switch (TOC) Door Sealing Frame Breaker Data Adapter (BDA) for
4 Breaker / Guide Frame Grounding Interlocking Set Base Plate Internet Connection
Contact Protective Cover for 21 Multi Angle LCD Module
5 Shutter (locking) OPEN/CLOSE Buttons 22 Ground Fault Protection Module
6 MODBUS or PROFIBUS Multiple Key Locking Accessories 23 Rating Plug
Communications Single Bolt Motor Operator Installation 24 Metering Function (+ wave forms
7 External CubicleBUS I/O Module Operations Counter and harmonics)
8 Plug-In Open and Closed Solenoids Breaker Status Sensor (BSS) 25 Circuit Breaker
14
is especially important because of the also allows application of the WL on
units are completely interchangeable
wide spread outage that will occur if modern power systems with extremely
independent of breaker ratings.
one of these breakers trips high levels of available fault current.
SWITCHGEAR
unnecessarily.
Rating Plug
A further benefit offered by EIP, over a
The Rating Plug is a replaceable module Conventional practice is to specify standard LS trip unit equipped breaker,
that enables users to reduce the rated electronic trip beakers with “LS” type is that it provides an extra measure of
device current for optimum adaptation trip units in critical power systems. protection in the event that the available
to the system; e.g. during startup of a These ‘Long-Time’ and ‘Short-Time’ fault current increases at some time
plant section. The Rating Plug should be only trip units forgo the fast tripping during the life of the system beyond
selected so that it corresponds to the times given by an ‘Instantaneous’ the withstand level. This would typically
rated current of the system. function. The justification for this delay be due to a utility transformer change
is the benefit of allowing a downstream but could also be due to the addition
Switch-selectable I2t or I4t breaker to open first to clear a high of generators or large motors that
Characteristic Curve Improved magnitude fault. The main or feeder contribute fault current. EIP provides
Overload Protection stays closed to keep the remainder of the breaker the ability to react in an
The best possible protection is assured the loads operating. instantaneous fashion to a high level
when all protective devices in the fault instead of having to rely on the
system are optimally coordinated. However, a circuit breaker with an slower reaction time of the short-time
To achieve optimum selectivity LS-only trip unit may never be applied function.
and coordination, the long-time on a system capable of delivering
characteristic can be switched between fault current higher than the breaker’s
l2t and l4t. withstand rating, commonly 85kA or
less. Where the available fault current
Switchable Parameter Sets is above this level, a breaker with
To allow the protection to adapt to an additional function must be used
changes in system needs such as — an instantaneous override. This
switching between utility and generator instantaneous override function trips the
feeds, WL Circuit Breakers support breaker instantly when the fault current
ETUs with two independent parameter reaches a pre-determined level below
sets. Switching between the parameter the withstand rating, usually around
sets occurs in less than 100 ms and can 20% lower. The benefit of this override
be done remotely or via a contact input is to allow application of the breaker up
to an optional CubicleBUS module. to the interrupting rating, which may be
as high as 150kA. The disadvantage is
Extended Instantaneous Protection that it compromises the coordination
The electronic trip units designed benefit because the main will probably
for use with the WL circuit breaker trip at the same time as a downstream
provide a feature we call “Extended branch breaker in that 20% lower
Instantaneous Protection” (Patent override window.
Pending).
The basic criteria for selecting circuit Ambient Temperature of the circuit Dynamic Arc-Flash Sentry (DAS)
breakers is: breaker. employs the unique dual protective
setting capability of the 776 trip units,
Maximum Available Short Circuit Design of the circuit breaker. coupled with the ability to easily toggle
at the installation point. This value to a lower arc flash parameter set. A
determines the short circuit current Protective Functions of the circuit normal operation parameter set can be
interrupting rating or short circuit breaker.These are determined by the optimized for selective trip coordination,
current withstand rating of the circuit selection of the appropriate trip unit. while the second set is optimized for
breaker. lower arc flash energy levels. The
Dynamic Arc-Flash Sentry (Patent dynamic action comes from the ability
Rated Current In which is to flow Pending) A unique feature of the WL to switch from the normal operation
through the respective circuit breaker trip unit allows the system designer to set to the arc flash limiting set based
continuously. This value may not be achieve lower levels of arc flash energy on the presence of personnel as they
greater than the maximum rated current and delayed tripping for selective trip approach the flash protection boundary.
of the circuit breaker. The rated current coordination purposes. A wide variety of switching methods
for the WL is determined by the rating may used based on the needs of a
plug, up to the maximum frame rating. particular facility. The capabilities range
from fully automatic switching using
appropriate occupancy sensors to
manual switching via a key operation.
14
Basic Protective Functions ETU745 ETU748 ETU776
Long-time overcurrent protection L
SWITCHGEAR
Short-time delayed overcurrent protection S
Instantaneous overcurrent protection I --
Neutral protection N
Ground fault protection G
Additional Functions
Selectable neutral protection
Defeatable short-time delay
Defeatable instantaneous protection --
Selectable thermal memory
Zone selective interlocking
Selectable I2t or fixed short-time delay
Adjustable instantaneous pick-up --
Selectable I2t or I4t long-time delay
Adjustable short-time delay and pick-up
Selectable and adjustable neutral protection
Dual protective setting capability -- --
Extended instantaneous protection
Communication
CubicleBUS
Communication via PROFIBUS-DP
Communication via the MODBUS
Communication via the Ethernet (BDA)
Tripping Characteristics
Every trip unit and every trip function To obtain a complete release before tripping. If the overcurrent
has its own characteristic. You will find characteristic, the appropriate trip takes place immediately after
just a small section of these illustrated characteristic functions must be closing and the overcurrent release is
below. The characteristics show the determined. therefore not yet activated, the opening
respective greatest and smallest setting time is prolonged by about 3 to 10
range of WL Circuit Breakers. The characteristics show the behavior ms, depending on the value of the
of the overcurrent release when it is overcurrent.
activated by a current already flowing
14
SWITCHGEAR
Tripping Characteristics
14
SWITCHGEAR
Breaker Ratings
Frame Size II
Frame Rating 800 1600 2000 3200
Rating Class N S H L F N S H L F S H L F S H L
Instantaneous Short-circuit Current 1 254VAC 50 65 85 100 200 50 65 85 100 200 65 85 100 200 65 85 100
(kA RMS) 50/60 Hz 508VAC 50 65 85 100 200 50 65 85 100 200 65 85 100 200 65 85 100
635VAC 50 65 65 85 200 50 65 65 85 200 65 65 85 200 65 65 85
Short-time Withstand
Current Icw
(kA RMS) 50/60 Hz 0.5s 50 65 65 85 — 50 65 65 85 — 65 65 85 — 65 65 85
Extended Instantaneous
Protection
(kA RMS -0% to +20%) 50 65 65 85 — 50 65 65 85 — 65 65 85 — 65 65 85
14
200, 225, 250, 300, 315, 350, 200, 225, 250, 300, 315, 350, 200, 225, 250, 300, 315, 200, 225, 250,
400, 450, 500, 600, 630, 700, 400, 450, 500, 600, 630, 700, 350, 400, 450, 500, 600, 300, 315, 350,
800 amps 800, 1000, 1200, 1250, 630, 700, 800, 1000, 400, 450, 500,
1600 amps 1200, 1250, 1600, 600, 630, 700,
2000 amps 800, 1000, 1200,
1250, 1600, 2000,
2500, 3000,
3200 amps
Endurance Rating
(switching operations Mechanical 15,000 15,000 15,000 15,000
with maintenance) 2 Electrical 15,000 15,000 15,000 15,000
Ratings
14
WL Circuit Breakers
Frame Size II Frame Size III
SWITCHGEAR
Frame Rating 800 1600 2000 3200 3200 4000 5000 6000
Rated current In
at 40°C, at 50/60Hz A 800 1600 2000 3200 3200 4000 5000 6000
Rated operational
(nominal) voltage VAC 600 600 600 600 600 600 600 600
Rated maximum voltage VAC 635 635 635 635 635 635 635 635
Permissible ambient
temperature
operation
(for operation with
LCD max. 55°C) °C -25 / +70 -25 / +70 -25 / +70 -25 / +70 -25 / +70 -25 / +70 -25 / +70 -25 / +70
Storage
(observe special
conditions for LCD) °C -40 / +70 -40 / +70 -40 / +70 -40 / +70 -40 / +70 -40 / +70 -40 / +70 -40 / +70
Power loss at Rated Current 85 320 500
with 3-phase2 130 520 850
symmetrical load W (fused) (fused) (fused) 1150 700 1100 1650 2475
Operating times
Make-time ms 35 35 35 35 35 35 35 35
3
Break-time (with active ETU) ms 34 34 34 34 34 34 34 34
Break-time
4
(without active ETU) ms 50 50 50 50 50 50 50 50
Total clearing time
(with active ETU)3 ms 50 50 50 50 50 50 50 50
Total clearing time
(without active ETU)4 ms 65 65 65 65 65 65 65 65
Make-time, electrical
(via closing solenoid) ms 50 50 50 50 50 50 50 50
Break-time, electrical
(via shunt trip) ms 40 40 40 40 40 40 40 40
(via instantaneous UVR) ms 73 73 73 73 73 73 73 73
1 Interrupting rating is equal to 200kA based on the rating of the fuse
.
2 Consult factory for fuse carriage power loss
.
3 ETU with external control power .
4 ETU without external control power .
WL Circuit Breakers
WL Circuit Breakers
Frame Size II Frame Size III
Frame Rating 800 1600 2000 3200 3200 4000 5000 6000
Endurance
Mechanical operating
(without maintenance) cycles 12,500 12,500 10,000 10,000 5,000 5,000 5,000 5,000
Mechanical operating
(with maintenance) 1 cycles 15,000 15,000 15,000 15,000 10,000 10,000 10,000 10,000
Electrical operating
(without maintenance) cycles 7,500 7,500 4,000 4,000 2,000 2,000 2,000 2,000
Electrical operating
(with maintenance ) 1 cycles 15,000 15,000 15,000 15,000 10,000 10,000 10,000 10,000
Switching frequency 1/h 60 60 60 60 60 60 60 60
Minimum interval
between breaker trip and
14
1 Maintenance consists of replacing main contacts and arc chutes (see operating instructions
.)
2 For use only with Siemens supplied ring terminals (WL10RL)
.
3 Fused Breaker Weights (kg/lb) Frame Size II (fused) Frame Size III (fused)
Breaker 103/227 same as table above
Guide Frame 68/150 130/275
Fuse Carriage – 102/225
0DQXDO2SHUDWLQJ0HFKDQLVPZLWK0HFKDQLFDO&ORVLQJ
&ORVLQJFKDUJLQJVWRUHGHQHUJ\PHFKDQLVP
0D[LPXPDFWXDWLQJIRUFHUHTXLUHGRQKDQGOHYHU OEV
1XPEHURIKDQGOHYHUVWURNHVUHTXLUHG
0DQXDO2SHUDWLQJ0HFKDQLVPZLWK0HFKDQLFDODQG(OHFWULFDO&ORVLQJ
&KDUJLQJVWRUHGHQHUJ\PHFKDQLVP
&ORVLQJVROHQRLG &RLOYROWDJHWROHUDQFH 9'& 9'&
DQG6KXQW7ULS 9'& 9'&
9$&9'& 9'&
9$&
9$&9'& 9'&
9$&
<9$&
<9$&
14
3RZHUFRQVXPSWLRQGXW\F\FOH :
0LQLPXPFORVLQJVROHQRLGDFWXDWLRQVLJQDOUHTXLUHG PV
SWITCHGEAR
0RWRU2SHUDWLQJ0HFKDQLVPZLWK0HFKDQLFDODQG(OHFWULFDO&ORVLQJ
6SULQJFKDUJLQJPRWRU
0RWRUYROWDJHWROHUDQFHDW9$&9$&
([WHQGHGWROHUDQFHIRUEDWWHU\RSHUDWLRQDW9'&9'&9'&9'&
3RZHUFRQVXPSWLRQRIWKHPRWRU :
7LPHUHTXLUHGIRUFKDUJLQJWKHVWRUHGHQHUJ\PHFKDQLVP V
&ORVLQJVROHQRLG
)RUPRWRUDQGFORVLQJVROHQRLG
VKRUWFLUFXLWSURWHFWLRQ
6KRUWFLUFXLWSURWHFWLRQ
6WDQGDUGVORZEORZFDUWULGJHIXVH 9 $
9 $
$X[LOLDU\5HOHDVH
8QGHUYROWDJHUHOHDVH 2SHUDWLQJ
YDOXHV FLUFXLWEUHDNHUFDQEHFORVHG
895 FLUFXLWEUHDNHURSHQV
$&&RLOYROWDJHWROHUDQFHDW9$&9$&
'&([WHQGHGWROHUDQFHIRUEDWWHU\RSHUDWLRQDW9'&9'&9'&9'&
5DWHGFRQWUROVXSSO\YROWDJH $&+] 9
'& 9
3RZHUFRQVXPSWLRQLQUXVKFRQWLQXRXV $& 9$
'& :
2SHQLQJWLPHRIWKHFLUFXLWEUHDNHUIRU$&'& PV
895QRWLPHGHOD\VHWWLQJV
6HWWLQJ PV
6HWWLQJ PV
895ZLWKWLPHGHOD\
$GMXVWDEOHGHOD\ V WR
5HVHWE\DGGLWLRQDO1&GLUHFWRSHQLQJ PV
$X[LOLDU\&RQWDFWVDQG0HFKDQLVP2SHUDWHG&RQWDFWV02&
&RQWDFWUDWLQJ $OWHUQDWLQJFXUUHQW
+] 5DWHGRSHUDWLRQDOYROWDJH 9
5DWHGRSHUDWLRQDOFXUUHQWFRQWLQXRXV $
5DWHGRSHUDWLRQDOFXUUHQWPDNLQJ $
5DWHGRSHUDWLRQDOFXUUHQWEUHDNLQJ $
'LUHFWFXUUHQW 5DWHGRSHUDWLRQDOYROWDJH 999
5DWHGRSHUDWLRQDOFXUUHQWFRQWLQXRXV $
5DWHGRSHUDWLRQDOFXUUHQWPDNLQJ $DW9$DW9$DW9
5DWHGRSHUDWLRQDOFXUUHQWEUHDNLQJ $DW9$DW9$DW9
%HOO$ODUP6ZLWFKDQG5HDG\WR&ORVH6LJQDO&RQWDFW
&RQWDFWUDWLQJ $OWHUQDWLQJFXUUHQW
+] 5DWHGRSHUDWLRQDOYROWDJH 9
5DWHGRSHUDWLRQDOFXUUHQWFRQWLQXRXV $
14
5DWHGRSHUDWLRQDOFXUUHQWPDNLQJ $
5DWHGRSHUDWLRQDOFXUUHQWEUHDNLQJ $
'LUHFWFXUUHQW 5DWHGRSHUDWLRQDOYROWDJH 999 9'&
SWITCHGEAR
)XQFWLRQ2YHUYLHZRIWKH(OHFWURQLF7ULS8QLWV
%DVLF)XQFWLRQV (78
/RQJWLPHRYHUFXUUHQWSURWHFWLRQ ü
)XQFWLRQFDQEHVZLWFKHG212)) ²
6HWWLQJUDQJH, 5 ,Q[«
6ZLWFKVHOHFWDEOHRYHUORDGSURWHFWLRQ
,Q
/ , WRU, WGHSHQGHQWIXQFWLRQ ü
6HWWLQJUDQJHRIWLPHGHOD\FODVVW 5DW, W
VHFRQGV
6HWWLQJUDQJHRIWLPHGHOD\W 5DW, W
14
VHFRQGV
7KHUPDOPHPRU\ üYLDVOLGHVZLWFK
SWITCHGEAR
3KDVHORVVVHQVLWLYLW\ DWWVG PV0
1HXWUDOSURWHFWLRQ ü
1 )XQFWLRQFDQEHVZLWFKHG212)) üYLDVOLGHVZLWFK
1FRQGXFWRUVHWWLQJUDQJH,1 ,Q[« «
6KRUWWLPHGHOD\HGRYHUFXUUHQWSURWHFWLRQ ü
)XQFWLRQFDQEHVZLWFKHG212)) üYLDURWDU\VZLWFK
6HWWLQJUDQJH,VG ,Q[«
6HWWLQJUDQJHRIWLPHGHOD\WVGIL[HG
6 VHFRQGV 0
2))
6ZLWFKVHOHFWDEOHVKRUWWLPHGHOD\
VKRUWFLUFXLWSURWHFWLRQ
, WGHSHQGHQWIXQFWLRQ üYLDURWDU\VZLWFK
6HWWLQJUDQJHRIWLPHGHOD\WVGDW, W
VHFRQGV
=RQH6HOHFWLYH,QWHUORFNLQJ=6,IXQFWLRQ SHU&XELFOH%86PRGXOH
,QVWDQWDQHRXVRYHUFXUUHQWSURWHFWLRQ ü
)XQFWLRQFDQEHVZLWFKHGRQRII
([WHQGHG,QVWDQWDQHRXV3URWHFWLRQ
, LVHQDEOHGZKHQ2)) üYLDURWDU\VZLWFK
6HWWLQJUDQJH,L ,Q[«
[,FZ PD[2)) , FZ (,3
*URXQGIDXOWSURWHFWLRQ ¶ILHOGLQVWDOODEOHPRGXOH
7ULSDQGDODUPIXQFWLRQ ü
'HWHFWLRQRIWKHJURXQGIDXOWFXUUHQW
E\UHVLGXDOVXPPLQJPHWKRG ü
'HWHFWLRQRIWKHJURXQGIDXOWFXUUHQW
E\GLUHFWVXPPLQJPHWKRG ü
6HWWLQJUDQJHRIWKH,JIRUWULS $%&'(
*
6HWWLQJUDQJHRIWKH,JIRUDODUP $%&'(
6HWWLQJUDQJHRIWKHWLPHGHOD\
VHFRQGV
6ZLWFKVHOHFWDEOH
JURXQGIDXOWSURWHFWLRQ
, WIL[HG ü
6HWWLQJUDQJHWLPHGHOD\WJDW, W
=6,JURXQGIXQFWLRQ SHU&XELFOH%86PRGXOH
Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 14-67
Type WL Low Voltage Metal-Enclosed Switchgear
%UHDNHU7HFKQLFDO'DWD
Low-voltage Switchgear
WL Low-voltage Metal-Enclosed Switchgear Technical Information
)XQFWLRQ2YHUYLHZRIWKH(OHFWURQLF7ULS8QLWV
%DVLF)XQFWLRQV (78
3DUDPHWHUVHWV
6HOHFWDEOHEHWZHHQ
SDUDPHWHUVHW$DQG% ²
/&'
/&'DOSKDQXPHULFOLQH m
/&'JUDSKLF ²
&RPPXQLFDWLRQ
&XELFOH%86LQWHJUDWHG ü
&RPPXQLFDWLRQFDSDELOLW\YLD
02'%86RU352),%86 ü
0HWHULQJIXQFWLRQ
0HWHULQJIXQFWLRQFDSDELOLW\ZLWK
0HWHULQJ)XQFWLRQ3/86 ü
14
'LVSOD\E\/('
7ULSXQLWDFWLYH ü
$ODUP ü
SWITCHGEAR
(78HUURU ü
/WULS ü
6WULS ü
,WULS ü
1WULS ü
*WULS üRQO\ZLWKJURXQGIDXOWPRGXOH
*DODUP üRQO\ZLWKJURXQGIDXOWPRGXOH
7ULSSHGE\H[WHQGHGSURWHFWLRQRU
SURWHFWLYHUHOD\IXQFWLRQ ü
&RPPXQLFDWLRQ ü
6LJQDOFRQWDFWVZLWKH[WHUQDO&XELFOH%86PRGXOHV
2SWRRUUHOD\
2YHUFXUUHQWZDUQLQJ ü
/RDGVKHGGLQJ2))21 ü
(DUO\VLJQDORIORQJWLPHWULSPV ü
7HPSHUDWXUHDODUP ü
3KDVHXQEDODQFH ü
,QVWDQWDQHRXVWULS ü
6KRUWWLPHWULS ü
/RQJWLPHWULS ü
1HXWUDOFRQGXFWRUWULS ü
*URXQGIDXOWSURWHFWLRQWULS üRQO\ZLWKJURXQGIDXOWPRGXOH
*URXQGIDXOWDODUP üRQO\ZLWKJURXQGIDXOWPRGXOH
$X[LOLDU\UHOD\ ü
(78HUURU ü
6WHSIRU6HWWLQJVYLD&RPPXQLFDWLRQVRU(78.H\3DG 6HWWLQJUDQJHRIWKH,J
IURP«WR VWHS IURP«WR VWHS
« « )UDPH6L]H,, )UDPH6L]H,,,
« « $ $ $ ü DYDLODEOH
² QRWDYDLODEOH
« «PD[ % $ $
m RSWLRQDO
« & $ $
' $ $
( $ $
Low-voltage Switchgear
WL Low-voltage Metal-Enclosed Switchgear Technical Information
)XQFWLRQ2YHUYLHZRIWKH(OHFWURQLF7ULS8QLWV
%DVLF)XQFWLRQV (78 (78
/RQJWLPHRYHUFXUUHQWSURWHFWLRQ ü ü
)XQFWLRQFDQEHVZLWFKHG212)) ² ²
6HWWLQJUDQJH,5 ,Q[« «VWHS$
6ZLWFKVHOHFWDEOHRYHUORDGSURWHFWLRQ
,Q
/ , WRU, WGHSHQGHQWIXQFWLRQ ü ü
6HWWLQJUDQJHRIWLPHGHOD\FODVVW`5DW, W
VHFRQGV «VWHSV
6HWWLQJUDQJHRIWLPHGHOD\W 5DW, W
VHFRQGV «VWHSV
7KHUPDOPHPRU\ üYLDVOLGHVZLWFK üRQRIIYLDNH\SDG
RUFRPPXQLFDWLRQV
14
3KDVHORVVVHQVLWLYLW\ DWWVG PV0 üRQRIIYLDNH\SDG
RUFRPPXQLFDWLRQV
1HXWUDOSURWHFWLRQ ² ü
SWITCHGEAR
1 )XQFWLRQFDQEHVZLWFKHG212)) ² üYLDVOLGHVZLWFK
1FRQGXFWRUVHWWLQJUDQJH,1 ,Q[« ² «
6KRUWWLPHGHOD\HGRYHUFXUUHQWSURWHFWLRQ ü ü
)XQFWLRQFDQEHVZLWFKHG212)) üYLDURWDU\VZLWFK üYLDNH\SDGRUFRPPXQLFDWLRQV
6HWWLQJUDQJH,VG ,Q[« «[,FZ PD[
VWHS$
6HWWLQJUDQJHRIWLPHGHOD\WVGIL[HG
6 VHFRQGV 0 0«2))VWHSV
6ZLWFKVHOHFWDEOHVKRUWWLPHGHOD\
VKRUWFLUFXLWSURWHFWLRQ
, WGHSHQGHQWIXQFWLRQ üYLDURWDU\VZLWFK üYLDNH\SDGRUFRPPXQLFDWLRQV
6HWWLQJUDQJHRIWLPHGHOD\WVGDW,W
VHFRQGV «VWHSV
=RQH6HOHFWLYH,QWHUORFNLQJ=6,IXQFWLRQ SHU&XELFOH%86PRGXOH SHU&XELFOH%86PRGXOH
,QVWDQWDQHRXVRYHUFXUUHQWSURWHFWLRQ ü ü
)XQFWLRQFDQEHVZLWFKHG212))
, ([WHQGHG,QVWDQWDQHRXV3URWHFWLRQ
LVHQDEOHGZKHQ2)) ² üYLDNH\SDGRUFRPPXQLFDWLRQV
6HWWLQJUDQJH,L ,Q[« ²,L ,FZ (,3 [,Q«[,FV PD[2)) ,FZ (,3
*URXQGIDXOWSURWHFWLRQ mILHOGLQVWDOODEOHPRGXOH mILHOGLQVWDOODEOHPRGXOH
7ULSDQGDODUPIXQFWLRQ ü üYLDNH\SDGRUFRPPXQLFDWLRQV
'HWHFWLRQRIWKHJURXQGIDXOWFXUUHQW
E\UHVLGXDOVXPPLQJPHWKRG ü ü
'HWHFWLRQRIWKHJURXQGIDXOWFXUUHQW
E\GLUHFWVXPPLQJPHWKRG ü ü
6HWWLQJUDQJHRIWKH,JIRUWULS $%&'( $«(VWHS$
* 6HWWLQJUDQJHRIWKH,JIRUDODUP $%&'( $«(VWHS$
6HWWLQJUDQJHRIWKHWLPHGHOD\WJ
VHFRQGV «VWHSV
6ZLWFKVHOHFWDEOH
JURXQGIDXOWSURWHFWLRQ
, WIL[HG ü ü
6HWWLQJUDQJHWLPHGHOD\WJDW, W «VWHSV
=6,JURXQGIXQFWLRQ SHU&XELFOH%86PRGXOH SHU&XELFOH%86PRGXOH
)XQFWLRQ2YHUYLHZRIWKH(OHFWURQLF7ULS8QLWV
%DVLF)XQFWLRQV (78 (78
3DUDPHWHUVHWV
6HOHFWDEOHEHWZHHQ
SDUDPHWHUVHW$DQG% ² ü
/&'
/&'DOSKDQXPHULFOLQH m ²
/&'JUDSKLF ² ü
&RPPXQLFDWLRQ
&XELFOH%86LQWHJUDWHG ü ü
&RPPXQLFDWLRQFDSDELOLW\YLD
02'%86RU352),%86 ü ü
0HWHULQJIXQFWLRQ
0HWHULQJIXQFWLRQFDSDELOLW\ZLWK
0HWHULQJ)XQFWLRQ3/86 ü ü
14
'LVSOD\E\/('
7ULSXQLWDFWLYH ü ü
$ODUP ü
SWITCHGEAR
ü
(78HUURU ü ü
/WULS ü ü
6WULS ü ü
,WULS ü
1WULS ü ü
*WULS üRQO\ZLWKJURXQGIDXOWPRGXOH üRQO\ZLWKJURXQGIDXOWPRGXOH
*DODUP üRQO\ZLWKJURXQGIDXOWPRGXOH üRQO\ZLWKJURXQGIDXOWPRGXOH
7ULSSHGE\H[WHQGHGSURWHFWLRQRU
SURWHFWLYHUHOD\IXQFWLRQ ü ü
&RPPXQLFDWLRQ ü ü
6LJQDOFRQWDFWVZLWKH[WHUQDO&XELFOH%86PRGXOHV
2SWRRUUHOD\
2YHUFXUUHQWZDUQLQJ ü ü
/RDGVKHGGLQJ2))21 ü ü
(DUO\VLJQDORIORQJWLPHWULSPV ü ü
7HPSHUDWXUHDODUP ü ü
3KDVHXQEDODQFH ü ü
,QVWDQWDQHRXVWULS ü ü
6KRUWWLPHWULS ü ü
/RQJWLPHWULS ü ü
1HXWUDOFRQGXFWRUWULS ü ü
*URXQGIDXOWSURWHFWLRQWULS üRQO\ZLWKJURXQGIDXOWPRGXOH üRQO\ZLWKJURXQGIDXOWPRGXOH
*URXQGIDXOWDODUP üRQO\ZLWKJURXQGIDXOWPRGXOH üRQO\ZLWKJURXQGIDXOWPRGXOH
$X[LOLDU\UHOD\ ü ü
(78HUURU ü ü
0HWHULQJDQG3URWHFWLYH5HOD\LQJ$FFXUDFLHV
3URWHFWLYH5HOD\LQJ 3LFNXS$FFXUDF\ 0HWHULQJ9DOXHV $FFXUDF\
3KDVH8QEDODQFH, «,Q ,DW[,Q ü DYDLODEOH
3KDVH8QEDODQFH9 «9Q 9DW[9Q ² QRWDYDLODEOH
7+',XSWRWK «9Q 3DW[,Q m RSWLRQDO
7+'9XSWRWK «9Q 6DW[,Q
2YHUYROWDJH «9Q 4DW[,Q
8QGHUYROWDJH «9Q
8QGHU2YHU)UHTXHQF\ +]
14
SWITCHGEAR
22
Siemens Industry, Inc. SPEEDFAX™ 2017 Product Catalog 14-71
Low-voltage Switchgear
Type WL Circuit Breakers General
WL Communication Overview
Connection Diagram
1 Breaker Data Adapter 13 13
(BDA)
2 Browser-capable input WinPM.Net WinPM.Net
Server Web Client Ethernet /Internet / Intranet
and output device
(e.g. notebook)
3 WL Circuit Breaker
4 COM 16 MODBUS
Ethernet
module or COM 15
PROFIBUS module
5 Breaker Status Sensor 9510 Meter*
(BSS) MODBUS Master (Ethernet
PLC or Supervisory Gateway)
14
15 BDA Plus
Features
n Industry standard MODBUS or n The ability to connect additional input n Innovative software products for local
PROFIBUS communication available on and output modules to the breaker configuration, operation, monitoring and
all WL breakers from 200A to 6000A. internal CubicleBUS of the WL opens diagnostics of WL Circuit Breakers using
up a range of opportunities to reduce MODBUS, PROFIBUS or via Ethernet/
n The high modularity of the WL Circuit
secondary device count and wiring and Intranet/Internet.
Breakers and accessories allows
to increase functionality implemented in n Complete integration of WL Circuit
simple retrofitting of all communication
switchgear. Breakers in all Totally Integrated Power
components.
and Totally Integrated Automation
Solutions.
Section Configurations
Low-voltage Switchgear
WL Low-voltage Metal-Enclosed Switchgear Section Configurations
14
Switchgear Depth Dimensional Information
(Dimensions below are for internal frames –
not total structure depth)
SWITCHGEAR
• Non-fused indoor – 60” standard, 70” and Main Sections – Non-Fused Breakers
80” optional
• Fused indoor – 65” standard, 75” and
80” optional 22 in. Blank or
Instrument
Feeder Breaker
800, 1600,
Blank or
Instrument
Blank or
Instrument
Blank or
Instrument Auxiliary
• Non-fused
22 in. non-walk-in
(559 m m ) outdoor – 60” Compartment 2000 Compartment Compartment Compartment Compartment
standard
(559 mm) and 75” optional
• Fused non-walk-in outdoor – 65” standard Main Breaker
800, 1600,
Feeder Breaker
800, 1600,
Blank or
Instrument
Main Breaker
4000, 5000
Blank or
Instrument
and 75” optional 2000, 3200 2000, 3200 Compartment Compartment Main Breaker
22 in. 6000
•(559Non-fused
22min.
m) walk-in
22 in. outdoor – 60” standard Feeder Breaker
(559and
m m ) 75” optional
(559 m m ) Feeder Breaker Main Breaker Main Breaker Main Breaker
800, 1600, 800, 1600, 2000,
800, 1600, 800, 1600, 4000, 5000
• Fused walk-in outdoor – 65” standard and 2000, 3200 2000, 3200 2000, 3200 3200, 4000 Refer to Note 3
Refer to Note 1
75” optional Feeder Breaker
Auxiliary
Feeder Breaker Blank or Feeder Breaker
• Walk-in outdoor aisle is 42” deep 800, 1600, Instrument 800, 1600, 800, 1600, 2000 Feeder Breaker
800, 1600, 2000
Compartment
• Sections with cable connected main, tie 2000 Compartment 2000 Refer to Note 1
and/or feeder breakers that are 3200 amp 22 in . 22 in . 22 in. 32 in. 32 in . 32 in .
(559 mm)
or greater must be minimum depth of (559 mm) (559 mm) (813 mm) (813 mm) (813 mm)
24
Feeder Breaker
Tie Breaker Feeder Breaker Tie Breaker Tie Breaker
800,
22 i1 600, 2000,
n. 22 in. 22 i800, 1600,
n.
800, 1600, 800, 1600,
)HHGHU%UHDNHU
4000, 3200, 4000
(559 min.
m) (Main Breaker
559
2000, 3200 2000 22 in. 22min.
m) 22 in.(559
22min.
m 2000
) 22 in.
5000 22
Refer to Note 2
(559 m m(559
) 6000 (559 m m(559
) mm) (559 m m ) Tie Breaker
(559 m m ) mm)
Feeder Breaker 3200, 4000
Feeder Breaker Tie Breaker 800, 1600, 2000, Tie Breaker Feeder Breaker 7LH%UHDNHU Tie Breaker
800, 1600, 800, 1600, 3200, 4000 4000, 5000 800, 1600, 5000
2000, 3200 2000, 3200 Refer to Note 1 2000
Feeder Breaker Blank or Auxiliary
Feeder Breaker Feeder Breaker Feeder Breaker Compartment Feeder Breaker Feeder Breaker
800, 1600, 800, 1600, 800, 1600, 2000 800, 1600, 800, 1600,
)HHGHU%UHDNHU
Refer to Note 1
800, 1600, 2000
2000 2000 2000 2000
22 in . 22 in. 32 in. 32 in. 22 in . 32 in . 32 in .
32 in .
(559 mm) (559 mm) (813 mm) (813 mm) (559 mm) (813 mm)
LQ
(813 mm) PP (813 mm)
14
Main and Tie Sections – Non-Fused Breakers Main and Tie Sections – Fused Breakers
SWITCHGEAR
Feeder Breaker
Tie Breaker Main Breaker Tie Breaker Main Breaker Tie Breaker Tie Breaker Main Breaker
800, 1600, 2000,
800, 1600, 800, 1600, 800, 1600, 4000 800, 1600, 800, 1600, 800, 1600,
3200, 4000 2000 2000 2000
2000, 3200 2000, 3200 2000, 3200
Refer to Note 1
Feeder Sections – Non-Fused Breakers (see Note 7 on page 24) Feeder Sections – Fused Breakers (see Note 7 on page 24)
25
Siemens Type WL Low Voltage Switchgear assembly with a 60 in . (1524 mm) internal
can be configured in many ways by structure is 82 .3 in . (2090 mm) and the
combining different section types . Up depth of a walk-in outdoor assembly with
to five vertical sections plus a transition a 60 in . (1524 mm) internal structure is
section can be shipped together as a unit . 110 .7 in . (2812 mm) . Maximum shipping
Maximum shipping split length for indoor split length for outdoor structures is 66 in .
structures is 110 in . (2794 mm) . If all (1676 mm) .
vertical sections are not to be shipped as
a unit, specifications need to be provided The major assembly sections include:
that describe the limiting factors (e .g ., • Transition Sections — used as
low door or narrow hallway) . transition to liquid filled transformer
or to outdoor dry type transformers .
Normal indoor vertical sections are 96 in .
(2438 mm) high and a minimum 60 in .
• Auxiliary Sections — used as incoming
bus duct or cable entrance when a
(1524 mm) deep for non-fused breakers main breaker is not used .
and 65 in . (1651 mm) deep for fused
breakers . A top-mounted hoist, which • Main Sections — used to contain main
breaker and may house metering and
14
is shipped as an accessory in a separate feeder breakers .
container, adds 6 .2 in . (157 mm) for a
total installed height of 102 .2 in . • Feeder Sections — used to contain
feeder breakers and other equipment
SWITCHGEAR
(2596 mm) .
such as instrumentation .
The outdoor switchgear assembly • Tie Sections — used to contain tie Transition Section For Liquid Filled and
Outdoor Dry Type Transformers
contains the indoor assembly in an breaker and other equipment such
outdoor housing . The overall height is as feeder breakers .
112 .8 in . (2865 mm) for non walk-in Dimension A Weight
designs and 114 in . (2896 mm) for in inches (mm) in lbs. (kg)
walk-in designs . The depth of a Indoor 55 (1397) 500 (227)
non walk-in outdoor Outdoor 61 (1549) 550 (250)
Section Type 22” 22” 32” 32” 38” 38” 48” 48”
Indoor Outdoor Indoor Outdoor Indoor Outdoor Indoor Outdoor
26
1.50 5.86
(38) (149) 7.88 1
.86 (200)
(22)
Note 4.82
3 B
(122)
4.00
(102)
Transformer
Throat
Liquid filled &
14
4.40 (112)
2.37 (60)
1.00 (25)
Note 4
2.00 (51)
1.00 (25) W
W = 22 (559) or 32 (813)
Low-voltage Switchgear
WL Low-voltage Metal-Enclosed Switchgear Dimensional Information
Optional Hoist
Lifting Holes (3) Vent stack
4.0 (102)
24 .9
(632)
hoist
Extension
14
102.2 Front Bus Cable
(2596) Compartment Compartment Compartment
top of E 17 .8 F
Hoist (452)
SWITCHGEAR
92 .0
(2337)
42.0 (1067)
Minimum
Aisle Space
Recommended
Floor Line
2 .37 G
(60)
A
A E F G
Equipment Depth Breaker Compartment Depth Rear Compartment Depth Anchor Bolt Spacing
60 (1524) Non-fused breakers 19 .8 (503) 22 .4 (569) 59 .13 (1502)
65 (1651) Fused breakers 24 .8 (630) 22 .4 (569) 64 .13 (1629)
70 (1778) Non-fused breakers 19 .8 (503) 32 .4 (823) 69 .13 (1756)
75 (1905) Fused breakers 24 .8 (630) 32 .4 (823) 74 .13 (1883)
80 (2032) Non-fused breakers 19 .8 (503) 42 .4 (1077) 79 .13 (2010)
80 (2032) Fused breakers 24 .8 (630) 37 .4 (950) 79 .13 (2010)
Note: Dimensions shown in inches and (mm) .
28
2
14
SWITCHGEAR
1 60” is representative for a 60” deep switchgear internal structure . For other 3 Refer to appropriate indoor plan view for available customer conduit informa-
internal structure depths (65 or 75) add extra depth to 60” that is shown . tion .
2 75 .37 is representative for a 60” deep internal structure . For other internal
structure depths (65 or 75) add extra depth to 75 .37 that is shown .
Low-voltage Switchgear
WL Low-voltage Metal-Enclosed Switchgear Dimensional Information
1
2
14
SWITCHGEAR
1 60” is representative for a 60” deep switchgear internal structure . For other 3 Refer to appropriate indoor plan view for available customer conduit informa-
internal structure depths (65 or 75) add extra depth to 60” that is shown . tion .
2 103 .8” is representative for a 60” deep internal structure . For other internal
structure depths (65 or 75) add extra depth to 103 .8” that is shown .
Dimensions shown in inches (mm) 3 60 .43 dimension is based on 60” internal frame structure and if a deeper
1 110 .7 dimension is based on 60” internal frame structure and if a deeper internal frame structure is used (65 or 75) the extra depth should be added
internal frame structure is used (65 or 75) the extra depth should be added to the 60 .43 dimension .
to the 110 .7 dimension . 4 102 .2 dimension is based on 60” internal frame structure and if a deeper
2 103 .8 dimension is based on 60” internal frame structure and if a deeper internal frame structure is used (65 or 75) the extra depth should be added
internal frame structure is used (65 or 75) the extra depth should be added to the 102 .2 dimension .
to the 103 .8 dimension .
30
Primary Secondary
kVA Phase Voltage Voltage
3
5
Single 240/480 120/240
14
10 1
15 1
SWITCHGEAR
Current Transformers for FSII WL Breaker Applications - External Metering and Relaying 2
Current Transformers for FSIII WL Breaker Applications – External Metering and Relaying 2
31
Switchboard Monitoring
Sm@rtGear™ Mobile App Selection
Switchgear Switchboard
Take control of your gear
from your smart device
Remotely monitor, configure, and control using
mobile phone or tablet (wireless or hardwired)
14
Ease of commissioning
n Set
breaker settings via touchscreen using mobile
phone or tablet
SWITCHGEAR
Security
n Localsecurity enabled WPA2 WIFI network only
allowing local access
Switchboard Monitoring
Sm@rtGear™ Mobile App Selection
Wireless Hardwire
Mobile Devices Running Siemens Sm@rt Mobile App Mobile Devices Running Siemens Sm@rt Mobile App
— Ethernet
— ULP
14
Network Network
Switch Switch
SWITCHGEAR
Wireless
Router
Modbus Modbus
Gateway Gateway
WL/VL Electronic Trip Unit Power Meter SEM3 Modular WL/VL Electronic Trip Unit Power Meter SEM3 Modular
ETU Metering ETU Metering
n Ethernet switch and WIFI access point with WPA2 encryption n Current monitoring
n Breaker status
Power/Insulated Case Circuit Breaker Feature
n ETU 776 with Sm@rt Dynamic Arc Sentry (DAS) Sm@rtGear™ Mobile Optional Features
n MODBUS communication n PAC Digital meter integration
n Protective settings and alarm functions n SEM3™ submetering integration
14
SWITCHGEAR
The future
The past
Why settle for partial control when you can have All of the Sm@rtGear™ LVS communication
total control and pay less? Traditional hard wired backbone is installed and tested at the Siemens
remote control panels provide additional safety factory and the user only has to physically connect
for your personnel but Siemens Sm@rtGear™ the three communication cables that connect the
LVS can provide the same breaker remote low-voltage switchgear to the remotely mounted
control plus remote monitoring and configuration touch screen interface panel (HMI).
of all embedded intelligent devices.
The remote HMI allows the user to access the
Siemens Sm@rtGear™ LVS is pre-configured intelligent devices embedded in the low-voltage
and pre-programmed low-voltage metal- switchgear. Using the HMI, the user can monitor,
enclosed switchgear that provides out-of-the-box configure and control the intelligent devices. The
remote monitoring, configuration and control of Sm@rtGear™ LVS CPU acts as the local master
embedded intelligent devices. and can also be a remote slave tied into an
upstream supervisory system.
Type WL Low-voltage Switchgear for Marine and Offshore Applications General Information
14
n 3 phase 3 wire, 3 phase 4 wire
Breakers Used in Enclosures n ANSI C37.17 — Trip Devices for AC
n 50/60 Hz
n ANSI C37.51 — Conformance Testing and General Purpose DC Low-voltage
n 6000 amp maximum horizontal bus
of Metal-Enclosed Low-voltage AC Power Circuit Breakers
SWITCHGEAR
n 6000 amp maximum vertical bus
Power Circuit Breaker Switchgear n NEMA SG3 — Low-voltage Power
n Silver plated copper bus standard – tin
Assemblies Circuit Breakers
plated copper optional
n NEMA SG5 — Power Switchgear
n Standard bus bracing 100kA –optional
up to 200kA Assemblies
n NEC — Applicable requirements of
the National Electric Code (NEC)
Seismic Qualification
n CSA — Optional CSA compliance
Seismic qualification to all major seismic with cUL labeling is available.
construction standards (IBC, UBC, CBC, n ANSI C37.20.7 — Optional Type WL
SBC, BOCA and IEEE 693) is available. arc resistant low-voltage switchgear
is available and is UL listed to ANSI/
For additional Type WL low-voltage IEEE C37.20.7. Type 2B arc resistant
switchgear product information, accessibility rating with maximum
including configuration information, internal arcing short-circuit current
refer to the WL Low-voltage Metal- rating of 100kA @508V and 85kA @
Enclosed Switchgear Selection and 635V
Application Guide – Siemens Document
No. LVSA-LVMES-0313.
means.
n One piece circuit breaker
compartment doors with insert panels
for control devices such as fuses,
indicating lights and circuit breaker
control switches when required.
n Reinforced bolted rear covers.
Enhanced Safety n Insulated/Isolated bus bar system.
Siemens now offers arc resistant, gassing of arc byproducts from the arc n Integrally designed circuit breaker
metal-enclosed, low-voltage switchgear chutes is contained by the switchgear door sealing frame that allows the
designed to provide an additional as verified by interruption tests. user to rack a circuit breaker to
degree of protection for personnel connect, test or disconnect position
performing normal operating duties in Siemens arc resistant low-voltage
without having to install additional
proximity to the energized equipment. switchgear provides an added degree
hardware (bellows, shrouds, etc) and
Such duties include opening or closing of protection over standard metal-
still maintain arc resistant rating of the
circuit breakers, closed door circuit enclosed switchgear. In addition to
apparatus.
breaker racking, reading instruments, bolted faults, Siemens WL arc resistant
low-voltage switchgear is designed n Shutters in circuit breaker
or other activities that do not require compartments.
cover removal or opening doors (other and performance tested to ANSI/IEEE
than auxiliary/ instrument compartment C37.20.7 to provide protection from n Riser Base with integrated arc
doors). the hazards of internal arcing faults. plenum.
An internal arcing fault can be caused n Four high power circuit breaker
Why Arc Resistant Switchgear by insulation degradation, insulation stacking capability. No additional
contamination, entrance of vermin, stacking/configuration restrictions.
Standard metal-enclosed switchgear is
foreign objects coming into contact
designed to withstand the mechanical n All section configurations available.
with the energized bus, or any other
forces generated by bolted faults on Available in solidly grounded or
unplanned condition that creates an
the load terminals until a power circuit resistance grounded configurations.
electrical discharge path through air.
breaker or other protective device can
During an arcing fault, the voltage at n Non-fused non current-limiting
interrupt the flow of fault current. This
the fault location is essentially the circuit breakers allow full power
capability is verified by short-circuit
system voltage and the fault energy coordination.
and short-time withstand tests on the
is focused within the switchgear
equipment and interruption tests on the Recommended Optional Features
enclosure. Arc temperatures can
power circuit breakers. During a bolted
exceed 20,000 degrees Kelvin, rapidly Overhead plenum with exhaust duct.
fault, the voltage at the fault location
heating the air and vaporizing metal The system is designed to transfer the
is essentially zero and the fault energy
parts. The expanding plasma creates byproducts of the arcing event (smoke,
is dissipated throughout the power
severe mechanical and thermal stress particulate matter, heat, etc.) away
system. The arc generated within the
in the equipment which can blow open from the immediate vicinity of the low-
power circuit breaker during interruption
doors and covers and burn through or voltage switchgear when an internal
is cooled and extinguished by the circuit
fragment the enclosure. arcing fault occurs. Typically, the
breaker arc chutes. The minimal out
14
second set is optimized for lower arc Dimensional Data
flash energy levels. The dynamic action
comes from the ability to switch from
SWITCHGEAR
1.25 (32) Rear
(Typ.)
CL
range of selectivity with the short delay Plan View (WL Arc Resistant Switchgear Side View
time of tzsi = 50 ms. By shortening the without Optional Overhead Plenum)
9. The area outside the exhaust duct vent needs to be kept clear of personnel
Aux/Bkr Aux/Bkr and equipment due to the potential for pressurized exhaust gases being
Comp Comp
expelled in the area as a result of arc fault in the switchgear. An area of 4
Floor or Pad Surface feet X 4 feet centered on exhaust duct vent needs to be clear at all times.
Riser Base Riser Base 10. Exhaust duct is not self supporting, recommended support every 6 linear
Front View: WL Arc Resistant Switchgear with Overhead Plenum feet minimum. The duct supports are not supplied by Siemens and must be
supplied by the purchaser or the installing contractor.
11. LV Arc Resistant switchgear with and without overhead plenum should be
installed on a solid surface to maintain the arc ratings.
14
SWITCHGEAR
Front view
Type 2B accessibility rating
allows auxiliary/control
compartment door to be open
and still maintain arc resistant
Door gaskets and sealing trims rating
Extra hinges
Rear view
Extra bolts on
end trim sheets
BUS 1
TX-4
One of the trip units available for the Siemens WL Family of equipment is an effective way to minimize arc flash dangers.
GEN 1
GEN 1
BUS 2 BUS 3
breakers is the ETU 776. It offers dual parameter sets that If one is concerned about the effects of temporarily inhibiting
Vs:480 V
BUS 2 BUS 3
Vs:480 V
enable the trip unit to automatically lower the instantaneous selectivity, then rest assured that with the ETU 776 single
setting and thereby lower the available energy in a fault step changes are possible giving engineers the ability to clear
condition. Commonly referred to as “maintenance mode”, faults faster with minimum effect on coordination. In the
making a breaker trip faster while engaged in any form example below the effects of the DAS system may be seen.
of maintenance or just by being in proximity to energized
Example 1
SWGR 1
SWGR 1
PPE: 3 PPE: 0
AHE: 10.6 cal/cm^2(100%) AHE: 0.74 cal/cm^2(100%) 1600
1600 AFB: 17.38 in WL
AFB: 105.68 in WL 1600 1600
WD: 24 in WD: 24 in
1000
1000
14
100
100
10
10
Time in Seconds
Time in Seconds
DLA: 1600
1
DLA: 1600
DLA: 1600 Man.: SIEMENS
Man.: SIEMENS Type: WLL
Type: WLL Size: WLL 800A
Size: WLL 800A Trip: ETU 776 LSIG
Trip: ETU 776 LSIG Max A/Plug/Setting: 800 / 800
Max A/Plug/Setting: 800 / 800
.1
.1
PANEL 1
PANEL 1
.01
.01
Dual Parameter
sets enable
“maintenance
mode” - can be
set remotely via
software or
automatically via
WL Breaker with ETU 776 digital input.
Under normal conditions, the switchgear’s calculated arc flash Below is another example of the benefit of the DAS, or even
energy will require PPE level 3 protection for anyone within manual switching, of breaker parameter set. The reduced
the arc flash boundary. Incorporating the features built into settings set available in the ETU 776 can also be used to
the DAS system, and using the ETU776 trip unit, the system reduce the arc flash energy at downstream equipment. In the
changes to parameter set B. In the second figure the first figure on the left with normal settings the arc energy at
instantaneous has been changed to a lower setting and the panel 1 requires PPE level 2. After switching to the parameter
calculation shows a reduction of arc flash energy. The B settings, the PPE level at Panel 1 is reduced to 0.
resultant PPE level has been reduced to 0.
Example 2
SWGR 1 WL 1600
1600
14
WL 800
800
SWITCHGEAR
PANEL 1
PPE: 2
AHE: 5.9 cal/cm^2(85%)
AFB: 47.36 in
WD: 17.9 in
1000
SWGR 1 Main
SWGR 1 Main
SIEMENS WLL ETU 776 LSIG
SIEMENS WLL ETU 776 LSIG
WLL 1600A 1600 Amp
WLL 1600A 1600 Amp
800A FEEDER
800A FEEDER
SIEMENS WLL ETU 776 LSIG
SIEMENS WLL ETU 776 LSIG
WLL 800A 800 Amp
WLL 800A 800 Amp
100
100
10
10
Time in Seconds
Time in Seconds
.1
PANEL 1 PANEL 1
.01
.01
C:\EDSA2005\Projects\SAFETYSWITCHGEARWHITEPAPER.PDC
C:\EDSA2005\Projects\SAFETYSWITCHGEARWHITEPAPER.PDC
14
Remote Racking Device
SWITCHGEAR
Remote Operator Pendant
This hand held pendant allows a user to remotely operate
(open/close) a WL breaker without being in front of the
switchgear. Standard cable lengths are 30 feet with other
lengths available. This pendant, along with the Remote
Racking device, can be used to improve personnel safety by
putting operators outside the arc flash boundary. Maintenance
personnel can remotely open breakers and close breakers,
without being in front of the equipment. The Remote
Operator Pendant can be used in combination with the
Remote Racking Device for added personnel safety.
TEST PULSE
RELAY RELAY
RES RES
TEST METER
RES RELAY RES
TEST RESISTOR
PULSE
RELAY RELAY
SYSTEM
SWITCH SYSTEM AM
RES RES
SWITCH
PULSE SW
CONTROL PULSE SW
CIRCUIT CONTROL
CIRCUIT