Air System Design Load Summary for DPWH New Office

Project Name: DPWH Building ACU Rev. 2 03/08/2021


Prepared by: Department of Public Works and Highways 01:53PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 33.3 °C / 27.9 °C HEATING OA DB / WB 26.2 °C / 22.2 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 508 m² 23094 - 508 m² - -
Wall Transmission 510 m² 16590 - 510 m² 0 -
Roof Transmission 2439 m² 193356 - 2439 m² 0 -
Window Transmission 508 m² 29101 - 508 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 2334 m² 0 - 2334 m² 0 -
Partitions 3941 m² 5 - 3941 m² 0 -
Ceiling 4426 m² 3 - 4426 m² 0 -
Overhead Lighting 53168 W 41948 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 131042 W 114267 - 0 0 -
People 455 24560 27573 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 10% 44292 2757 0% 0 0
>> Total Zone Loads - 487217 30330 - 0 0
Zone Conditioning - 462785 30330 - 0 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Exhaust Fan Load 0 L/s 0 - 0 L/s 0 -
Ventilation Load 2522 L/s 24861 86387 0 L/s 0 0
Ventilation Fan Load 0 L/s 0 - 0 L/s 0 -
Space Fan Coil Fans - 39064 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 526709 116717 - 0 0
Terminal Unit Cooling - 526709 116759 - 0 0
Terminal Unit Heating - 0 - - 0 -
>> Total Conditioning - 526709 116759 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v.4.4 Page 1 of 1