MLFB: 7SJ64515EB921FG1----0R----------
Parameter-set version: V04.96.02
Device path: C:\Siemens\DIGSI4\D4Proj\Sas_manu\P7DI\GV\ST\00000006
Author:
Creation date: 12.10.20 10:55:18
Last modified: 09.11.20 10:51:25
Operating mode: Online
Comment:
Setting values in: Secondary value description
PRINT - CONTENTS
Page 2 of 146
7SJ645 V4_9 Var_prn_11_08_55
Page 3 of 146
7SJ645 V4_9 Var_prn_11_08_55
Device Configuration
SAS MANUGURU CHANGES / TRAFO
SIMATIC BCPU / 7SJ645 V4.9 Var/7SJ645 09.11.20 11:08:56
1 Device Configuration
Page 4 of 146
7SJ645 V4_9 Var_prn_11_08_55
Configuration - complete (sorted by line)
SAS MANUGURU CHANGES / TRAFO
SIMATIC BCPU / 7SJ645 V4.9 Var/7SJ645 09.11.20 11:08:56
No filter
2.1 Indications
2.1.1 Device
>Synchronize Internal Real Time Clock (SP_Ev - Single point indication event)
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
Configured to destination:
Operation Buffer: IO
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
Configured to destination:
Operation Buffer: IO
System interface
Properties:
System interface IEC 61850
IEC 61850 object PROT/LLN0/Health
IEC 61850 object PROT/LPHD1/PhyHealth
IEC 61850 object PROT/PTRC1/Health
IEC 61850 object PROT/XCBR1/Health
IEC 61850 object PROT/PTOC6/Health
Page 5 of 146
7SJ645 V4_9 Var_prn_11_08_55
Configured to source:
System interface
Configured to destination:
Operation Buffer: IO
System interface
Properties:
Startup: Out of date
Restart: Out of date
System interface IEC 61850
IEC 61850 object PROT/LLN0/Mod
IEC 61850 object PROT/LLN0/Beh
IEC 61850 object PROT/PTRC1/Mod
IEC 61850 object PROT/PTRC1/Beh
IEC 61850 object PROT/XCBR1/Mod
IEC 61850 object PROT/XCBR1/Beh
IEC 61850 object PROT/PTOC6/Beh
IEC 61850 object .
IEC 61850 object .
IEC 61850 object .
Configured to destination:
Operation Buffer: I
System interface
Properties:
System interface IEC 61850
IEC 61850 object PROT/LPHD1/Proxy
IEC 61850 object PROT/XCBR1/Loc
IEC 61850 object PROT/XCBR1/BlkOpn
IEC 61850 object PROT/XCBR1/BlkCls
IEC 61850 object MEAS/LPHD1/Proxy
IEC 61850 object DR/LPHD1/Proxy
Page 6 of 146
7SJ645 V4_9 Var_prn_11_08_55
Configured to destination:
Operation Buffer: I
System interface
Properties:
System interface IEC 61850
IEC 61850 object CTRL/LPHD1/DevStr
Configured to source:
System interface
Configured to destination:
Operation Buffer: I
System interface
Properties:
Startup: Out of date
Restart: Out of date
System interface IEC 61850
IEC 61850 object CTRL/LLN0/LEDRs
Configured to destination:
Operation Buffer: I
System interface
Properties:
System interface IEC 61850
IEC 61850 object CTRL/LPHD1/DevStr
Configured to destination:
Operation Buffer: IO
Page 7 of 146
7SJ645 V4_9 Var_prn_11_08_55
Daylight Saving Time (OUT - Output indication)
SAS MANUGURU CHANGES / TRAFO
SIMATIC BCPU / 7SJ645 V4.9 Var/7SJ645 09.11.20 11:08:56
Configured to destination:
Operation Buffer: IO
Configured to destination:
Operation Buffer: I
Configured to destination:
Operation Buffer: I
Properties:
Fault record: Select in fault record
Configured to destination:
Operation Buffer: IO
Configured to destination:
Operation Buffer: IO
System interface
Properties:
System interface IEC 61850
IEC 61850 object CTRL/CALH1/GrAlm
Configured to destination:
Operation Buffer: IO
System interface
Properties:
System interface IEC 61850
IEC 61850 object CTRL/CALH1/GrWrn
Configured to destination:
Operation Buffer: IO
Page 8 of 146
7SJ645 V4_9 Var_prn_11_08_55
Error 0V (OUT - Output indication)
SAS MANUGURU CHANGES / TRAFO
SIMATIC BCPU / 7SJ645 V4.9 Var/7SJ645 09.11.20 11:08:56
Configured to destination:
Operation Buffer: IO
Configured to destination:
Operation Buffer: IO
Configured to destination:
Operation Buffer: IO
Configured to destination:
Operation Buffer: IO
Configured to destination:
Operation Buffer: IO
Configured to destination:
Operation Buffer: IO
Configured to destination:
Operation Buffer: IO
System interface
Properties:
System interface IEC 61850
IEC 61850 object CTRL/LLN0/Health
IEC 61850 object CTRL/CALH1/ErrBoard1
Page 9 of 146
7SJ645 V4_9 Var_prn_11_08_55
Error Board 2 (OUT - Output indication)
SAS MANUGURU CHANGES / TRAFO
SIMATIC BCPU / 7SJ645 V4.9 Var/7SJ645 09.11.20 11:08:56
Configured to destination:
Operation Buffer: IO
System interface
Properties:
System interface IEC 61850
IEC 61850 object CTRL/LLN0/Health
IEC 61850 object CTRL/CALH1/ErrBoard2
Configured to destination:
Operation Buffer: IO
System interface
Properties:
System interface IEC 61850
IEC 61850 object CTRL/LLN0/Health
IEC 61850 object CTRL/CALH1/ErrBoard3
Configured to destination:
Operation Buffer: IO
System interface
Properties:
System interface IEC 61850
IEC 61850 object CTRL/LLN0/Health
IEC 61850 object CTRL/CALH1/ErrBoard4
Configured to destination:
Operation Buffer: IO
System interface
Properties:
System interface IEC 61850
IEC 61850 object CTRL/LLN0/Health
IEC 61850 object CTRL/CALH1/ErrBoard5
Configured to destination:
Operation Buffer: IO
Page 10 of 146
7SJ645 V4_9 Var_prn_11_08_55
System interface
Properties:
System interface IEC 61850
IEC 61850 object CTRL/LLN0/Health
IEC 61850 object CTRL/CALH1/ErrBoard6
Configured to destination:
Operation Buffer: IO
System interface
Properties:
System interface IEC 61850
IEC 61850 object CTRL/LLN0/Health
IEC 61850 object CTRL/CALH1/ErrBoard7
Configured to destination:
Operation Buffer: IO
System interface
Properties:
Startup: Open
Restart: No default assignment
System interface IEC 61850
IEC 61850 object PROT/LLN0/Mod
IEC 61850 object PROT/LLN0/Beh
IEC 61850 object PROT/PTRC1/Beh
IEC 61850 object PROT/XCBR1/Beh
IEC 61850 object PROT/PTOC6/Beh
IEC 61850 object PROT/PTOC7/Beh
IEC 61850 object PROT/PTOC1/Beh
IEC 61850 object PROT/PTOC8/Beh
IEC 61850 object PROT/PTOC9/Beh
IEC 61850 object PROT/PTOC2/Beh
IEC 61850 object .
IEC 61850 object .
IEC 61850 object .
Configured to destination:
CFC
Properties:
Page 11 of 146
7SJ645 V4_9 Var_prn_11_08_55
Configured to destination:
Operation Buffer: IO
System interface
Properties:
Startup: Open
Restart: No default assignment
System interface IEC 61850
IEC 61850 object PROT/LLN0/Mod
IEC 61850 object PROT/LLN0/Beh
IEC 61850 object PROT/LLN0/OpTmh
IEC 61850 object PROT/LPHD1/Proxy
IEC 61850 object PROT/PTRC1/Beh
IEC 61850 object PROT/PTRC1/Tr
IEC 61850 object PROT/PTRC1/Str
IEC 61850 object PROT/PTRC1/FinTr
IEC 61850 object PROT/XCBR1/Beh
IEC 61850 object PROT/XCBR1/Loc
IEC 61850 object .
IEC 61850 object .
IEC 61850 object .
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
Configured to source:
CFC
Properties:
Startup: No default assignment
Restart: No default assignment
Page 12 of 146
7SJ645 V4_9 Var_prn_11_08_55
Breaker OPENED (IntSP - Internal single point indication)
SAS MANUGURU CHANGES / TRAFO
SIMATIC BCPU / 7SJ645 V4.9 Var/7SJ645 09.11.20 11:08:56
Configured to source:
CFC
Properties:
Startup: No default assignment
Restart: No default assignment
Configured to destination:
Operation Buffer: IO
Properties:
Startup: OFF
Restart: OFF
Configured to source:
CFC
Properties:
Startup: No default assignment
Restart: No default assignment
Configured to destination:
Operation Buffer: IO
Configured to destination:
Operation Buffer: IO
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
Configured to destination:
Operation Buffer: IO
Properties:
Page 13 of 146
7SJ645 V4_9 Var_prn_11_08_55
Configured to destination:
Operation Buffer: IO
Warnings: X
Configured to destination:
Operation Buffer: IO
Warnings: X
Configured to destination:
Operation Buffer: IO
Warnings: X
Configured to destination:
Operation Buffer: IO
Warnings: X
Configured to destination:
Operation Buffer: IO
Warnings: X
Configured to destination:
Operation Buffer: IO
Configured to destination:
Trip log: IO
Page 14 of 146
7SJ645 V4_9 Var_prn_11_08_55
Time from Pickup to TRIP (VI - Value indication)
SAS MANUGURU CHANGES / TRAFO
SIMATIC BCPU / 7SJ645 V4.9 Var/7SJ645 09.11.20 11:08:56
Configured to destination:
Trip log: IO
Configured to destination:
Operation Buffer: IO
Control Menu
Properties:
Startup: OFF
Restart: OFF
2.1.2 User-def.
Configured to source:
BI: H1
Configured to destination:
Operation Buffer: IO
CFC
System interface
Control Display
Default Display
Properties:
Fault record: Select in fault record
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
System interface IEC 61850
Configured to source:
BI: H2
Configured to destination:
Operation Buffer: IO
CFC
System interface
Control Display
Default Display
Properties:
Page 15 of 146
7SJ645 V4_9 Var_prn_11_08_55
Configured to source:
BI: H3
Configured to destination:
Operation Buffer: IO
CFC
System interface
Control Display
Default Display
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
System interface IEC 61850
Configured to source:
BI: H4
Configured to destination:
Operation Buffer: IO
CFC
System interface
Control Display
Default Display
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
System interface IEC 61850
Configured to source:
Page 16 of 146
7SJ645 V4_9 Var_prn_11_08_55
BI: H7
Configured to destination:
Operation Buffer: IO
CFC
System interface
Control Display
Default Display
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
System interface IEC 61850
Configured to source:
BI: H8
Configured to destination:
Operation Buffer: IO
CFC
System interface
Control Display
Default Display
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
System interface IEC 61850
Configured to source:
BI: H5
Configured to destination:
Operation Buffer: IO
CFC
System interface
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
Page 17 of 146
7SJ645 V4_9 Var_prn_11_08_55
Configured to source:
BI: H6
Configured to destination:
Operation Buffer: IO
CFC
System interface
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
System interface IEC 61850
Configured to source:
BI: H9
Configured to destination:
Operation Buffer: IO
CFC
System interface
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
System interface IEC 61850
Configured to source:
BI: H 10
Configured to destination:
Operation Buffer: IO
CFC
System interface
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Page 18 of 146
7SJ645 V4_9 Var_prn_11_08_55
Configured to source:
BI: H 11
Configured to destination:
Operation Buffer: IO
CFC
System interface
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
System interface IEC 61850
Configured to source:
BI: H 13
Configured to destination:
Operation Buffer: IO
CFC
System interface
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
System interface IEC 61850
Configured to source:
BI: H 12
Configured to destination:
Operation Buffer: IO
CFC
System interface
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Page 19 of 146
7SJ645 V4_9 Var_prn_11_08_55
Configured to source:
BI: H 14
Configured to destination:
Operation Buffer: IO
CFC
System interface
Default Display
Properties:
Fault record: Select in fault record
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
System interface IEC 61850
Configured to source:
BI: H 15
Configured to destination:
Operation Buffer: IO
CFC
System interface
Default Display
Properties:
Fault record: Select in fault record
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
System interface IEC 61850
Configured to source:
BI: H 16
Configured to destination:
Operation Buffer: IO
Page 20 of 146
7SJ645 V4_9 Var_prn_11_08_55
CFC
System interface
Default Display
Properties:
Fault record: Select in fault record
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
System interface IEC 61850
Configured to source:
BI: H 17
Configured to destination:
Operation Buffer: IO
CFC
System interface
Default Display
Properties:
Fault record: Select in fault record
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
System interface IEC 61850
Configured to source:
BI: H 18
Configured to destination:
Operation Buffer: IO
CFC
System interface
Default Display
Properties:
Fault record: Select in fault record
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
System interface IEC 61850
Page 21 of 146
7SJ645 V4_9 Var_prn_11_08_55
OTI Trip (SP - Single point indication)
SAS MANUGURU CHANGES / TRAFO
SIMATIC BCPU / 7SJ645 V4.9 Var/7SJ645 09.11.20 11:08:56
Configured to source:
BI: H 19
Configured to destination:
Operation Buffer: IO
CFC
System interface
Default Display
Properties:
Fault record: Select in fault record
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
System interface IEC 61850
Configured to source:
BI: H 22
Configured to destination:
Operation Buffer: IO
CFC
System interface
Default Display
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
System interface IEC 61850
Configured to source:
BI: H 23
Configured to destination:
Operation Buffer: IO
CFC
System interface
Default Display
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Page 22 of 146
7SJ645 V4_9 Var_prn_11_08_55
Configured to source:
BI: H 24
Configured to destination:
Operation Buffer: IO
System interface
Default Display
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
System interface IEC 61850
Configured to source:
CFC
Configured to destination:
BO: U 5,U 19
LED: U8
Operation Buffer: IO
System interface
Default Display
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
System interface IEC 61850
Configured to source:
CFC
Configured to destination:
LED: U9
Operation Buffer: IO
System interface
Page 23 of 146
7SJ645 V4_9 Var_prn_11_08_55
Default Display
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
System interface IEC 61850
Configured to source:
BI: H 25
Configured to destination:
Operation Buffer: IO
CFC
System interface
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
System interface IEC 61850
Configured to source:
CFC
Configured to destination:
BO: U4
LED: L 13
Operation Buffer: IO
System interface
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
System interface IEC 61850
2.1.3 EN100-Modul 1
Properties:
Page 24 of 146
7SJ645 V4_9 Var_prn_11_08_55
Configured to destination:
Operation Buffer: IO
Warnings: X
Properties:
Startup: ON
Restart: ON
Failure EN100 Link Channel 1 (Ch1) (IntSP - Internal single point indication)
Configured to destination:
Operation Buffer: IO
Properties:
Startup: Out of date
Restart: Out of date
Failure EN100 Link Channel 2 (Ch2) (IntSP - Internal single point indication)
Configured to destination:
Operation Buffer: IO
Properties:
Startup: Out of date
Restart: Out of date
Configured to destination:
Operation Buffer: IO
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
Configured to destination:
Operation Buffer: IO
Page 25 of 146
7SJ645 V4_9 Var_prn_11_08_55
Phase Rotation L1L3L2 (OUT - Output indication)
SAS MANUGURU CHANGES / TRAFO
SIMATIC BCPU / 7SJ645 V4.9 Var/7SJ645 09.11.20 11:08:56
Configured to destination:
Operation Buffer: IO
Configured to destination:
CFC
Properties:
Fault record: Select in fault record
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
System interface IEC 61850
Extension (LD / LN / DO): EXT/pdGGIO1/SPCSO4
Configured to destination:
Operation Buffer: I
Configured to source:
CFC
Configured to destination:
Operation Buffer: IO
Properties:
Startup: OFF
Restart: OFF
Fault record: Select in fault record
System interface IEC 61850
Extension (LD / LN / DO): EXT/pdGGIO513/SPCSO27
Configured to destination:
System interface
Properties:
System interface IEC 61850
Page 26 of 146
7SJ645 V4_9 Var_prn_11_08_55
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
Fast Indication Fast Indication
Configured to destination:
Operation Buffer: IO
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
Configured to destination:
Trip log: IO
System interface
Properties:
System interface IEC 61850
IEC 61850 object PROT/XCBR1/SwAphs
Configured to destination:
Trip log: IO
System interface
Properties:
System interface IEC 61850
IEC 61850 object PROT/XCBR1/SwAphs
Page 27 of 146
7SJ645 V4_9 Var_prn_11_08_55
Primary fault current IL3 (VI - Value indication)
SAS MANUGURU CHANGES / TRAFO
SIMATIC BCPU / 7SJ645 V4.9 Var/7SJ645 09.11.20 11:08:56
Configured to destination:
Trip log: IO
System interface
Properties:
System interface IEC 61850
IEC 61850 object PROT/XCBR1/SwAphs
Configured to destination:
Trip log: I
System interface
Properties:
Fault record: Select in fault record
Fast Indication Fast Indication
System interface IEC 61850
IEC 61850 object PROT/PTRC1/Str
Configured to destination:
BO: U5
Trip log: I
CFC
System interface
Properties:
Fault record: Select in fault record
Fast Indication Fast Indication
System interface IEC 61850
IEC 61850 object PROT/PTRC1/Tr
Configured to destination:
Operation Buffer: IO
Configured to destination:
Operation Buffer: IO
System interface
Properties:
Page 28 of 146
7SJ645 V4_9 Var_prn_11_08_55
Configured to destination:
Operation Buffer: IO
System interface
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
System interface IEC 61850
IEC 61850 object PROT/XCBR1/Pos
Protection ON/OFF (via system port) (IntSP - Internal single point indication)
Configured to destination:
Operation Buffer: IO
Properties:
Startup: Close
Restart: No default assignment
Configured to destination:
Trip log: IO
System interface
Properties:
Fault record: Select in fault record
Fast Indication Fast Indication
System interface IEC 61850
IEC 61850 object PROT/PTRC2/Str
Configured to destination:
Page 29 of 146
7SJ645 V4_9 Var_prn_11_08_55
Trip log: I
System interface
Properties:
Fault record: Select in fault record
Fast Indication Fast Indication
System interface IEC 61850
IEC 61850 object PROT/PTRC2/Op
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
Fast Indication Fast Indication
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
Fast Indication Fast Indication
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
Fast Indication Fast Indication
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
Fast Indication Fast Indication
Page 30 of 146
7SJ645 V4_9 Var_prn_11_08_55
>BLOCK Ip (SP - Single point indication)
SAS MANUGURU CHANGES / TRAFO
SIMATIC BCPU / 7SJ645 V4.9 Var/7SJ645 09.11.20 11:08:56
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
Fast Indication Fast Indication
Configured to destination:
Operation Buffer: IO
System interface
Properties:
System interface IEC 61850
IEC 61850 object PROT/PTOC6/Mod
IEC 61850 object PROT/PTOC6/Beh
IEC 61850 object PROT/PTOC7/Mod
IEC 61850 object PROT/PTOC7/Beh
IEC 61850 object PROT/PTOC1/Mod
IEC 61850 object PROT/PTOC1/Beh
IEC 61850 object PROT/PTOC18/Mod
IEC 61850 object PROT/PTOC18/Beh
Configured to destination:
Operation Buffer: IO
Trip log: IO
System interface
Properties:
System interface IEC 61850
IEC 61850 object PROT/PTOC6/Mod
IEC 61850 object PROT/PTOC6/Beh
IEC 61850 object PROT/PTOC7/Mod
IEC 61850 object PROT/PTOC7/Beh
IEC 61850 object PROT/PTOC1/Mod
IEC 61850 object PROT/PTOC1/Beh
IEC 61850 object PROT/PTOC18/Mod
IEC 61850 object PROT/PTOC18/Beh
Page 31 of 146
7SJ645 V4_9 Var_prn_11_08_55
Time Overcurrent Phase is ACTIVE (OUT - Output indication)
SAS MANUGURU CHANGES / TRAFO
SIMATIC BCPU / 7SJ645 V4.9 Var/7SJ645 09.11.20 11:08:56
Configured to destination:
Operation Buffer: IO
System interface
Properties:
System interface IEC 61850
IEC 61850 object PROT/PTOC6/Mod
IEC 61850 object PROT/PTOC6/Beh
IEC 61850 object PROT/PTOC7/Mod
IEC 61850 object PROT/PTOC7/Beh
IEC 61850 object PROT/PTOC1/Mod
IEC 61850 object PROT/PTOC1/Beh
IEC 61850 object PROT/PTOC18/Mod
IEC 61850 object PROT/PTOC18/Beh
Configured to destination:
LED: U1
Trip log: IO
System interface
Properties:
Fault record: Select in fault record
Fast Indication Fast Indication
System interface IEC 61850
IEC 61850 object PROT/PTRC2/Str
Configured to destination:
LED: U2
Trip log: IO
System interface
Properties:
Fault record: Select in fault record
Fast Indication Fast Indication
System interface IEC 61850
IEC 61850 object PROT/PTRC2/Str
Configured to destination:
LED: U3
Page 32 of 146
7SJ645 V4_9 Var_prn_11_08_55
Trip log: IO
System interface
Properties:
Fault record: Select in fault record
Fast Indication Fast Indication
System interface IEC 61850
IEC 61850 object PROT/PTRC2/Str
Configured to destination:
Trip log: IO
System interface
Properties:
Fast Indication Fast Indication
System interface IEC 61850
IEC 61850 object PROT/PTOC18/Str
Configured to destination:
BO: U1
LED: L4
Trip log: I
System interface
Properties:
Fast Indication Fast Indication
System interface IEC 61850
IEC 61850 object PROT/PTOC18/Op
Configured to destination:
Trip log: IO
System interface
Properties:
Fast Indication Fast Indication
System interface IEC 61850
IEC 61850 object PROT/PTOC7/Str
Configured to destination:
BO: U1
Page 33 of 146
7SJ645 V4_9 Var_prn_11_08_55
LED: L4
Trip log: I
System interface
Properties:
Fault record: Select in fault record
Fast Indication Fast Indication
System interface IEC 61850
IEC 61850 object PROT/PTOC7/Op
Configured to destination:
Trip log: IO
System interface
Properties:
Fast Indication Fast Indication
System interface IEC 61850
IEC 61850 object PROT/PTOC6/Str
Configured to destination:
BO: U 1,U 12
LED: L4
Trip log: I
System interface
Properties:
Fault record: Select in fault record
Fast Indication Fast Indication
System interface IEC 61850
IEC 61850 object PROT/PTOC6/Op
Configured to destination:
Trip log: IO
System interface
Properties:
Fast Indication Fast Indication
System interface IEC 61850
IEC 61850 object PROT/PTOC1/Str
Page 34 of 146
7SJ645 V4_9 Var_prn_11_08_55
Ip TRIP (OUT - Output indication)
SAS MANUGURU CHANGES / TRAFO
SIMATIC BCPU / 7SJ645 V4.9 Var/7SJ645 09.11.20 11:08:56
Configured to destination:
BO: U 1,U 12
LED: L4
Trip log: I
System interface
Properties:
Fault record: Select in fault record
Fast Indication Fast Indication
System interface IEC 61850
IEC 61850 object PROT/PTOC1/Op
Properties:
Fast Indication Fast Indication
Configured to destination:
Operation Buffer: IO
Trip log: IO
Configured to destination:
Operation Buffer: IO
Trip log: IO
Configured to destination:
Operation Buffer: IO
Trip log: IO
Page 35 of 146
7SJ645 V4_9 Var_prn_11_08_55
Ip BLOCKED (OUT - Output indication)
SAS MANUGURU CHANGES / TRAFO
SIMATIC BCPU / 7SJ645 V4.9 Var/7SJ645 09.11.20 11:08:56
Configured to destination:
Operation Buffer: IO
Trip log: IO
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
Fast Indication Fast Indication
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
Fast Indication Fast Indication
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
Fast Indication Fast Indication
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
Fast Indication Fast Indication
Page 36 of 146
7SJ645 V4_9 Var_prn_11_08_55
>BLOCK IEp (SP - Single point indication)
SAS MANUGURU CHANGES / TRAFO
SIMATIC BCPU / 7SJ645 V4.9 Var/7SJ645 09.11.20 11:08:56
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
Fast Indication Fast Indication
Configured to destination:
Operation Buffer: IO
System interface
Properties:
System interface IEC 61850
IEC 61850 object PROT/PTOC8/Mod
IEC 61850 object PROT/PTOC8/Beh
IEC 61850 object PROT/PTOC9/Mod
IEC 61850 object PROT/PTOC9/Beh
IEC 61850 object PROT/PTOC2/Mod
IEC 61850 object PROT/PTOC2/Beh
Configured to destination:
Operation Buffer: IO
Trip log: IO
System interface
Properties:
System interface IEC 61850
IEC 61850 object PROT/PTOC8/Mod
IEC 61850 object PROT/PTOC8/Beh
IEC 61850 object PROT/PTOC9/Mod
IEC 61850 object PROT/PTOC9/Beh
IEC 61850 object PROT/PTOC2/Mod
IEC 61850 object PROT/PTOC2/Beh
Configured to destination:
Operation Buffer: IO
System interface
Properties:
Page 37 of 146
7SJ645 V4_9 Var_prn_11_08_55
Configured to destination:
Trip log: IO
System interface
Properties:
Fault record: Select in fault record
Fast Indication Fast Indication
System interface IEC 61850
IEC 61850 object PROT/PTRC2/Str
Configured to destination:
Trip log: IO
Properties:
Fast Indication Fast Indication
Configured to destination:
BO: U2
LED: L5
Trip log: I
Properties:
Fast Indication Fast Indication
Configured to destination:
Trip log: IO
System interface
Properties:
Fast Indication Fast Indication
System interface IEC 61850
IEC 61850 object PROT/PTOC9/Str
Page 38 of 146
7SJ645 V4_9 Var_prn_11_08_55
IE>> TRIP (OUT - Output indication)
SAS MANUGURU CHANGES / TRAFO
SIMATIC BCPU / 7SJ645 V4.9 Var/7SJ645 09.11.20 11:08:56
Configured to destination:
BO: U2
LED: L5
Trip log: I
System interface
Properties:
Fault record: Select in fault record
Fast Indication Fast Indication
System interface IEC 61850
IEC 61850 object PROT/PTOC9/Op
Configured to destination:
Trip log: IO
System interface
Properties:
Fast Indication Fast Indication
System interface IEC 61850
IEC 61850 object PROT/PTOC8/Str
Configured to destination:
BO: U2
LED: L5
Trip log: I
System interface
Properties:
Fault record: Select in fault record
Fast Indication Fast Indication
System interface IEC 61850
IEC 61850 object PROT/PTOC8/Op
Configured to destination:
Trip log: IO
System interface
Properties:
Fast Indication Fast Indication
System interface IEC 61850
Page 39 of 146
7SJ645 V4_9 Var_prn_11_08_55
Configured to destination:
BO: U2
LED: L5
Trip log: I
System interface
Properties:
Fault record: Select in fault record
Fast Indication Fast Indication
System interface IEC 61850
IEC 61850 object PROT/PTOC2/Op
Properties:
Fast Indication Fast Indication
Configured to destination:
Operation Buffer: IO
Trip log: IO
Configured to destination:
Operation Buffer: IO
Trip log: IO
Configured to destination:
Page 40 of 146
7SJ645 V4_9 Var_prn_11_08_55
Operation Buffer: IO
Trip log: IO
Configured to destination:
Operation Buffer: IO
Trip log: IO
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
Fast Indication Fast Indication
Configured to destination:
Trip log: IO
Configured to destination:
Trip log: IO
Configured to destination:
Trip log: IO
Configured to destination:
Trip log: IO
Configured to destination:
Trip log: IO
Properties:
Fast Indication Fast Indication
Page 41 of 146
7SJ645 V4_9 Var_prn_11_08_55
IE> InRush picked up (OUT - Output indication)
SAS MANUGURU CHANGES / TRAFO
SIMATIC BCPU / 7SJ645 V4.9 Var/7SJ645 09.11.20 11:08:56
Configured to destination:
Trip log: IO
Properties:
Fast Indication Fast Indication
Configured to destination:
Trip log: IO
Properties:
Fast Indication Fast Indication
Configured to destination:
Trip log: IO
Properties:
Fast Indication Fast Indication
Configured to destination:
Operation Buffer: IO
Configured to destination:
Operation Buffer: IO
Trip log: IO
Configured to destination:
Trip log: IO
Properties:
Fast Indication Fast Indication
Configured to destination:
Trip log: IO
Properties:
Page 42 of 146
7SJ645 V4_9 Var_prn_11_08_55
Configured to destination:
Trip log: IO
Properties:
Fast Indication Fast Indication
Configured to destination:
Trip log: IO
Properties:
Fast Indication Fast Indication
Configured to destination:
Trip log: IO
Properties:
Fast Indication Fast Indication
Configured to destination:
Trip log: IO
Properties:
Fast Indication Fast Indication
Configured to destination:
Trip log: IO
Properties:
Fast Indication Fast Indication
Configured to destination:
Trip log: IO
Properties:
Fast Indication Fast Indication
Page 43 of 146
7SJ645 V4_9 Var_prn_11_08_55
Earth InRush picked up (OUT - Output indication)
SAS MANUGURU CHANGES / TRAFO
SIMATIC BCPU / 7SJ645 V4.9 Var/7SJ645 09.11.20 11:08:56
Configured to destination:
Trip log: IO
Properties:
Fast Indication Fast Indication
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
Fast Indication Fast Indication
Configured to destination:
Operation Buffer: IO
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
Configured to destination:
Operation Buffer: IO
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
Fast Indication Fast Indication
Configured to destination:
Operation Buffer: IO
Properties:
Page 44 of 146
7SJ645 V4_9 Var_prn_11_08_55
Configured to destination:
Operation Buffer: IO
System interface
Properties:
System interface IEC 61850
IEC 61850 object PROT/PTUV1/Mod
IEC 61850 object PROT/PTUV1/Beh
IEC 61850 object PROT/PTUV2/Mod
IEC 61850 object PROT/PTUV2/Beh
Configured to destination:
Operation Buffer: IO
Trip log: IO
System interface
Properties:
System interface IEC 61850
IEC 61850 object PROT/PTUV1/Mod
IEC 61850 object PROT/PTUV1/Beh
IEC 61850 object PROT/PTUV2/Mod
IEC 61850 object PROT/PTUV2/Beh
Configured to destination:
Operation Buffer: IO
System interface
Properties:
System interface IEC 61850
IEC 61850 object PROT/PTUV1/Mod
IEC 61850 object PROT/PTUV1/Beh
IEC 61850 object PROT/PTUV2/Mod
IEC 61850 object PROT/PTUV2/Beh
Page 45 of 146
7SJ645 V4_9 Var_prn_11_08_55
U< Undervoltage picked up (OUT - Output indication)
SAS MANUGURU CHANGES / TRAFO
SIMATIC BCPU / 7SJ645 V4.9 Var/7SJ645 09.11.20 11:08:56
Configured to destination:
Trip log: IO
System interface
Properties:
Fast Indication Fast Indication
System interface IEC 61850
IEC 61850 object PROT/PTUV1/Str
Configured to destination:
Trip log: IO
System interface
Properties:
Fast Indication Fast Indication
System interface IEC 61850
IEC 61850 object PROT/PTUV1/Str
Configured to destination:
Trip log: IO
System interface
Properties:
Fast Indication Fast Indication
System interface IEC 61850
IEC 61850 object PROT/PTUV2/Str
Configured to destination:
Trip log: IO
System interface
Properties:
Fast Indication Fast Indication
System interface IEC 61850
IEC 61850 object PROT/PTUV2/Str
Configured to destination:
BO: U 11
Page 46 of 146
7SJ645 V4_9 Var_prn_11_08_55
LED: L6
Trip log: I
System interface
Properties:
Fault record: Select in fault record
Fast Indication Fast Indication
System interface IEC 61850
IEC 61850 object PROT/PTUV1/Op
Configured to destination:
Trip log: I
System interface
Properties:
Fast Indication Fast Indication
System interface IEC 61850
IEC 61850 object PROT/PTUV2/Op
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
Fast Indication Fast Indication
Configured to destination:
Operation Buffer: IO
System interface
Properties:
System interface IEC 61850
IEC 61850 object PROT/PTOV1/Mod
IEC 61850 object PROT/PTOV1/Beh
IEC 61850 object PROT/PTOV2/Mod
IEC 61850 object PROT/PTOV2/Beh
Configured to destination:
Operation Buffer: IO
Page 47 of 146
7SJ645 V4_9 Var_prn_11_08_55
Trip log: IO
System interface
Properties:
System interface IEC 61850
IEC 61850 object PROT/PTOV1/Mod
IEC 61850 object PROT/PTOV1/Beh
IEC 61850 object PROT/PTOV2/Mod
IEC 61850 object PROT/PTOV2/Beh
Configured to destination:
Operation Buffer: IO
System interface
Properties:
System interface IEC 61850
IEC 61850 object PROT/PTOV1/Mod
IEC 61850 object PROT/PTOV1/Beh
IEC 61850 object PROT/PTOV2/Mod
IEC 61850 object PROT/PTOV2/Beh
Configured to destination:
Trip log: IO
System interface
Properties:
Fast Indication Fast Indication
System interface IEC 61850
IEC 61850 object PROT/PTOV1/Str
Configured to destination:
BO: U 10
LED: L7
Trip log: I
System interface
Properties:
Fault record: Select in fault record
Fast Indication Fast Indication
System interface IEC 61850
IEC 61850 object PROT/PTOV1/Op
Page 48 of 146
7SJ645 V4_9 Var_prn_11_08_55
U>> picked up (OUT - Output indication)
SAS MANUGURU CHANGES / TRAFO
SIMATIC BCPU / 7SJ645 V4.9 Var/7SJ645 09.11.20 11:08:56
Configured to destination:
Trip log: IO
System interface
Properties:
Fast Indication Fast Indication
System interface IEC 61850
IEC 61850 object PROT/PTOV2/Str
Configured to destination:
Trip log: I
System interface
Properties:
Fast Indication Fast Indication
System interface IEC 61850
IEC 61850 object PROT/PTOV2/Op
U<, U> blocked via operation (IntSP - Internal single point indication)
Configured to destination:
Operation Buffer: IO
Control Menu
Properties:
Startup: OFF
Restart: OFF
Configured to destination:
Operation Buffer: IO
CFC
Properties:
Fast Indication Fast Indication
Configured to destination:
Operation Buffer: IO
CFC
Page 49 of 146
7SJ645 V4_9 Var_prn_11_08_55
Properties:
Fast Indication Fast Indication
Configured to destination:
Operation Buffer: IO
CFC
Properties:
Fast Indication Fast Indication
Configured to destination:
Operation Buffer: IO
CFC
Properties:
Fast Indication Fast Indication
Configured to destination:
Operation Buffer: IO
CFC
Properties:
Fast Indication Fast Indication
Configured to destination:
Operation Buffer: IO
Configured to destination:
Operation Buffer: IO
System interface
Properties:
System interface IEC 61850
IEC 61850 object PROT/PHIZ1/Mod
IEC 61850 object PROT/PHIZ1/Beh
IEC 61850 object PROT/PTUV1/Mod
IEC 61850 object PROT/PTUV1/Beh
IEC 61850 object PROT/PTUV2/Mod
Page 50 of 146
7SJ645 V4_9 Var_prn_11_08_55
Configured to destination:
Operation Buffer: IO
Configured to destination:
Operation Buffer: IO
Configured to destination:
Operation Buffer: IO
Configured to destination:
Operation Buffer: IO
Configured to destination:
Operation Buffer: IO
Configured to destination:
Operation Buffer: IO
Configured to destination:
Operation Buffer: IO
Configured to destination:
Operation Buffer: IO
Page 51 of 146
7SJ645 V4_9 Var_prn_11_08_55
>Failure: Feeder VT (SP - Single point indication)
SAS MANUGURU CHANGES / TRAFO
SIMATIC BCPU / 7SJ645 V4.9 Var/7SJ645 09.11.20 11:08:56
Configured to destination:
Operation Buffer: IO
System interface
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
Fast Indication Fast Indication
System interface IEC 61850
IEC 61850 object PROT/PHIZ1/Mod
IEC 61850 object PROT/PHIZ1/Beh
Configured to destination:
Operation Buffer: IO
System interface
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
Fast Indication Fast Indication
System interface IEC 61850
IEC 61850 object PROT/PHIZ1/Mod
IEC 61850 object PROT/PHIZ1/Beh
Configured to destination:
Operation Buffer: IO
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
Fast Indication Fast Indication
Page 52 of 146
7SJ645 V4_9 Var_prn_11_08_55
>BLOCK IEE>> (SP - Single point indication)
SAS MANUGURU CHANGES / TRAFO
SIMATIC BCPU / 7SJ645 V4.9 Var/7SJ645 09.11.20 11:08:56
Configured to destination:
Operation Buffer: IO
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
Fast Indication Fast Indication
Configured to destination:
Operation Buffer: IO
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
Fast Indication Fast Indication
Configured to destination:
Operation Buffer: IO
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
Fast Indication Fast Indication
Configured to destination:
Operation Buffer: IO
System interface
Properties:
System interface IEC 61850
IEC 61850 object PROT/PSDE1/Mod
IEC 61850 object PROT/PSDE1/Beh
IEC 61850 object PROT/PSDE2/Mod
IEC 61850 object PROT/PSDE2/Beh
Page 53 of 146
7SJ645 V4_9 Var_prn_11_08_55
Configured to destination:
Operation Buffer: IO
System interface
Properties:
System interface IEC 61850
IEC 61850 object PROT/PSDE1/Mod
IEC 61850 object PROT/PSDE1/Beh
IEC 61850 object PROT/PSDE2/Mod
IEC 61850 object PROT/PSDE2/Beh
IEC 61850 object PROT/PSDE3/Mod
IEC 61850 object PROT/PSDE3/Beh
IEC 61850 object PROT/PHIZ1/Mod
IEC 61850 object PROT/PHIZ1/Beh
Configured to destination:
Earth fault indication buffer IO
Trip log: IO
System interface
Properties:
Fast Indication Fast Indication
System interface IEC 61850
IEC 61850 object PROT/PHIZ1/Str
Configured to destination:
LED: L 10
Earth fault indication buffer IO
Trip log: I
System interface
Properties:
Fault record: Select in fault record
Fast Indication Fast Indication
System interface IEC 61850
IEC 61850 object PROT/PHIZ1/Op
Page 54 of 146
7SJ645 V4_9 Var_prn_11_08_55
IEE>> Pickup (OUT - Output indication)
SAS MANUGURU CHANGES / TRAFO
SIMATIC BCPU / 7SJ645 V4.9 Var/7SJ645 09.11.20 11:08:56
Configured to destination:
Earth fault indication buffer IO
Trip log: IO
System interface
Properties:
Fast Indication Fast Indication
System interface IEC 61850
IEC 61850 object PROT/PSDE2/Str
Configured to destination:
Earth fault indication buffer IO
Trip log: I
System interface
Properties:
Fault record: Select in fault record
Fast Indication Fast Indication
System interface IEC 61850
IEC 61850 object PROT/PSDE2/Op
Configured to destination:
Trip log: IO
System interface
Properties:
Fast Indication Fast Indication
System interface IEC 61850
IEC 61850 object PROT/PSDE3/Str
Configured to destination:
BO: U3
LED: L 10
Trip log: I
System interface
Properties:
Fault record: Select in fault record
Fast Indication Fast Indication
System interface IEC 61850
Page 55 of 146
7SJ645 V4_9 Var_prn_11_08_55
Configured to destination:
Operation Buffer: IO
Trip log: IO
System interface
Properties:
System interface IEC 61850
IEC 61850 object PROT/PSDE1/Mod
IEC 61850 object PROT/PSDE1/Beh
IEC 61850 object PROT/PSDE2/Mod
IEC 61850 object PROT/PSDE2/Beh
IEC 61850 object PROT/PSDE3/Mod
IEC 61850 object PROT/PSDE3/Beh
IEC 61850 object PROT/PHIZ1/Mod
IEC 61850 object PROT/PHIZ1/Beh
Configured to destination:
Operation Buffer: IO
Trip log: IO
Configured to destination:
Operation Buffer: IO
Earth fault indication buffer IO
Trip log: I
System interface
Properties:
System interface IEC 61850
IEC 61850 object PROT/PHIZ1/Str
Configured to destination:
Operation Buffer: IO
Earth fault indication buffer IO
Trip log: I
System interface
Properties:
Page 56 of 146
7SJ645 V4_9 Var_prn_11_08_55
Configured to destination:
Operation Buffer: IO
Earth fault indication buffer IO
Trip log: I
System interface
Properties:
System interface IEC 61850
IEC 61850 object PROT/PHIZ1/Str
Configured to destination:
Operation Buffer: IO
Earth fault indication buffer IO
Trip log: I
System interface
Properties:
System interface IEC 61850
IEC 61850 object PROT/PSDE1/Str
IEC 61850 object PROT/PSDE2/Str
IEC 61850 object PROT/PSDE3/Str
IEC 61850 object PROT/PHIZ1/Str
Configured to destination:
Operation Buffer: IO
Earth fault indication buffer IO
Trip log: I
System interface
Properties:
System interface IEC 61850
IEC 61850 object PROT/PSDE1/Str
IEC 61850 object PROT/PSDE2/Str
IEC 61850 object PROT/PSDE3/Str
IEC 61850 object PROT/PHIZ1/Str
Page 57 of 146
7SJ645 V4_9 Var_prn_11_08_55
Sensitive E fault direction undefined (OUT - Output indication)
SAS MANUGURU CHANGES / TRAFO
SIMATIC BCPU / 7SJ645 V4.9 Var/7SJ645 09.11.20 11:08:56
Configured to destination:
Operation Buffer: IO
Earth fault indication buffer IO
Trip log: I
System interface
Properties:
System interface IEC 61850
IEC 61850 object PROT/PSDE1/Str
IEC 61850 object PROT/PSDE2/Str
IEC 61850 object PROT/PSDE3/Str
IEC 61850 object PROT/PHIZ1/Str
Configured to destination:
Earth fault indication buffer IO
Configured to destination:
Earth fault indication buffer IO
Configured to destination:
Earth fault indication buffer IO
Configured to destination:
Earth fault indication buffer IO
Configured to destination:
Earth fault indication buffer IO
Configured to destination:
Page 58 of 146
7SJ645 V4_9 Var_prn_11_08_55
Operation Buffer: IO
System interface
Properties:
Chatter Blocking... Not enabled
Software filter time: 2000 ms
Retrigger filter: Retrigger filter
Intermediate position: Suppress intermediate position
Indication time period: No login time before filtering
System interface IEC 61850
IEC 61850 object CTRL/LLN0/Loc
Configured to destination:
Operation Buffer: IO
Properties:
Chatter Blocking... Not enabled
Software filter time: 2000 ms
Retrigger filter: Retrigger filter
Intermediate position: Suppress intermediate position
Indication time period: No login time before filtering
Configured to destination:
Operation Buffer: IO
Properties:
Startup: Interlocked switching
Restart: Interlocked switching
Configured to destination:
System interface
Configured to source:
BI: X3
Configured to destination:
Operation Buffer: IO
CFC
Page 59 of 146
7SJ645 V4_9 Var_prn_11_08_55
System interface
Control Display
Default Display
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Intermediate position: Does not suppress intermediate position
Indication time period: No login time before filtering
System interface IEC 61850
IEC 61850 object CTRL/Q1XSWI1
IEC 61850 object CTRL/Q1CSWI1
Switch type: Disconnector
Cycle counter: Q1 OpCnt=
Configured to destination:
System interface
Configured to destination:
Operation Buffer: IO
CFC
System interface
Control Display
Default Display
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Intermediate position: Does not suppress intermediate position
Indication time period: No login time before filtering
System interface IEC 61850
IEC 61850 object CTRL/Q8XSWI1
IEC 61850 object CTRL/Q8CSWI1
Switch type: Ground switch
Cycle counter: Q8 OpCnt=
Page 60 of 146
7SJ645 V4_9 Var_prn_11_08_55
Interlocking: Breaker Open (IntSP - Internal single point indication)
SAS MANUGURU CHANGES / TRAFO
SIMATIC BCPU / 7SJ645 V4.9 Var/7SJ645 09.11.20 11:08:56
Configured to source:
CFC
Properties:
Startup: No default assignment
Restart: No default assignment
Fast Indication Fast Indication
Configured to source:
CFC
Properties:
Startup: No default assignment
Restart: No default assignment
Fast Indication Fast Indication
Configured to source:
CFC
Properties:
Startup: No default assignment
Restart: No default assignment
Fast Indication Fast Indication
Configured to source:
CFC
Properties:
Startup: No default assignment
Restart: No default assignment
Fast Indication Fast Indication
Configured to source:
CFC
Properties:
Startup: No default assignment
Restart: No default assignment
Fast Indication Fast Indication
Page 62 of 146
7SJ645 V4_9 Var_prn_11_08_55
Interlocking: Earth switch Close (IntSP - Internal single point indication)
SAS MANUGURU CHANGES / TRAFO
SIMATIC BCPU / 7SJ645 V4.9 Var/7SJ645 09.11.20 11:08:56
Configured to source:
CFC
Properties:
Startup: No default assignment
Restart: No default assignment
Fast Indication Fast Indication
Configured to source:
CFC
Properties:
Startup: No default assignment
Restart: No default assignment
Configured to destination:
Operation Buffer: IO
System interface
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Intermediate position: Does not suppress intermediate position
Indication time period: No login time before filtering
System interface IEC 61850
IEC 61850 object CTRL/Q2XSWI1
IEC 61850 object CTRL/Q2CSWI1
Switch type: Disconnector
Cycle counter: Q2 OpCnt=
Configured to destination:
Operation Buffer: IO
System interface
Properties:
Chatter Blocking... Not enabled
Page 63 of 146
7SJ645 V4_9 Var_prn_11_08_55
Configured to destination:
Operation Buffer: IO
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Intermediate position: Does not suppress intermediate position
Indication time period: No login time before filtering
Configured to source:
BI: X7
Configured to destination:
Operation Buffer: IO
System interface
Control Display
Default Display
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Intermediate position: Does not suppress intermediate position
Indication time period: No login time before filtering
System interface IEC 61850
Switch type:
Cycle counter: Q2 ISO89B
Page 64 of 146
7SJ645 V4_9 Var_prn_11_08_55
ISO89BOpen (IntSP - Internal single point indication)
SAS MANUGURU CHANGES / TRAFO
SIMATIC BCPU / 7SJ645 V4.9 Var/7SJ645 09.11.20 11:08:56
Configured to source:
CFC
Configured to destination:
Operation Buffer: IO
Control Display
Default Display
Properties:
Startup: Out of date
Restart: No default assignment
Configured to source:
CFC
Configured to destination:
Operation Buffer: IO
Control Display
Default Display
Properties:
Startup: Out of date
Restart: No default assignment
Configured to source:
BI: X1
Configured to destination:
Operation Buffer: IO
CFC
System interface
Control Display
Default Display
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Intermediate position: Does not suppress intermediate position
Indication time period: No login time before filtering
System interface IEC 61850
Switch type:
Cycle counter: Q0 OpCnt=
Page 65 of 146
7SJ645 V4_9 Var_prn_11_08_55
CB152IL (IntSP - Internal single point indication)
SAS MANUGURU CHANGES / TRAFO
SIMATIC BCPU / 7SJ645 V4.9 Var/7SJ645 09.11.20 11:08:56
Configured to source:
CFC
Configured to destination:
LED: L 14
Operation Buffer: IO
Properties:
Startup: Out of date
Restart: No default assignment
Configured to destination:
Operation Buffer: IO
System interface
Configured to destination:
CFC
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
Configured to destination:
CFC
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
Configured to destination:
Operation Buffer: IO
CFC
Page 66 of 146
7SJ645 V4_9 Var_prn_11_08_55
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
Configured to destination:
Operation Buffer: IO
CFC
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
Configured to destination:
Operation Buffer: IO
CFC
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
Configured to destination:
Operation Buffer: IO
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
Configured to destination:
Operation Buffer: IO
Properties:
Chatter Blocking... Not enabled
Page 67 of 146
7SJ645 V4_9 Var_prn_11_08_55
Configured to destination:
Operation Buffer: IO
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
Configured to destination:
Operation Buffer: IO
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
Configured to destination:
Operation Buffer: IO
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
Configured to destination:
Operation Buffer: IO
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
Page 68 of 146
7SJ645 V4_9 Var_prn_11_08_55
Set Points (Measured Values)
SAS MANUGURU CHANGES / TRAFO
SIMATIC BCPU / 7SJ645 V4.9 Var/7SJ645 09.11.20 11:08:56
Configured to source:
CFC
Configured to destination:
Operation Buffer: IO
Configured to source:
CFC
Configured to destination:
Operation Buffer: IO
2.1.15 Statistics
Configured to destination:
System interface
Properties:
System interface IEC 61850
IEC 61850 object PROT/LLN0/OpTmh
IEC 61850 object CTRL/LLN0/OpTmh
Configured to destination:
Operation Buffer: IO
Properties:
Chatter Blocking... Not enabled
Software filter time: 0 ms
Retrigger filter: Do not retrigger filter
Indication time period: No login time before filtering
Configured to destination:
System interface
Properties:
System interface IEC 61850
IEC 61850 object PROT/XCBR1/SumSwARsA
Page 69 of 146
7SJ645 V4_9 Var_prn_11_08_55
Accumulation of interrupted current L2 (VI - Value indication)
SAS MANUGURU CHANGES / TRAFO
SIMATIC BCPU / 7SJ645 V4.9 Var/7SJ645 09.11.20 11:08:56
Configured to destination:
System interface
Properties:
System interface IEC 61850
IEC 61850 object PROT/XCBR1/SumSwARsB
Configured to destination:
System interface
Properties:
System interface IEC 61850
IEC 61850 object PROT/XCBR1/SumSwARsC
Configured to destination:
Operation Buffer: IO
2.1.17 Threshold-Switch
Configured to destination:
Operation Buffer: IO
Control Menu
Properties:
Startup: OFF
Restart: OFF
Page 70 of 146
7SJ645 V4_9 Var_prn_11_08_55
Commands
SAS MANUGURU CHANGES / TRAFO
SIMATIC BCPU / 7SJ645 V4.9 Var/7SJ645 09.11.20 11:08:56
2.2 Commands
Configured to source:
System interface
Configured to destination:
BO: Tr 6
CFC
Control Display
Default Display
Control Menu
Properties:
Interlocking:
Check interlocking: On
Release ON command: Control Device ISO89A.Clo
Release OFF command: Control Device ISO89A.Ope
Check substation controller: Off
Enable: Release when interlocking AND zone control
completed.
Further lockings
Blocking by protection: On
Double operation: On
Switching authority at local control: On
Switching authority at remote control: On
Unclearable interlocking
Switching direction (nominal = actual): Off
Password:: <none>
Release ON command: No device interlock signal
Release OFF command: No device interlock signal
Times:
Output time: 200 [1/10 s]
Seal-in timer: 0 [1/10 s]
Feedback monitoring time: 250 [1/10 s]
Operating mode: Pulse output
System interface IEC 61850
IEC 61850 object CTRL/Q1XSWI1
IEC 61850 object CTRL/Q1CSWI1
Switch type: Disconnector
Cycle counter: Q1 OpCnt=
Page 71 of 146
7SJ645 V4_9 Var_prn_11_08_55
Earth Switch (CF_D2 - Double command 2, with feedback)
SAS MANUGURU CHANGES / TRAFO
SIMATIC BCPU / 7SJ645 V4.9 Var/7SJ645 09.11.20 11:08:56
Configured to source:
System interface
Configured to destination:
CFC
Control Display
Default Display
Control Menu
Properties:
Interlocking:
Check interlocking: On
Release ON command: Control Device E Sw Cl.
Release OFF command: Control Device E Sw Open
Check substation controller: Off
Enable: Release when interlocking AND zone control
completed.
Further lockings
Blocking by protection: On
Double operation: On
Switching authority at local control: On
Switching authority at remote control: On
Unclearable interlocking
Switching direction (nominal = actual): On
Password:: <none>
Release ON command: No device interlock signal
Release OFF command: No device interlock signal
Times:
Output time: 200 [1/10 s]
Seal-in timer: 0 [1/10 s]
Feedback monitoring time: 250 [1/10 s]
Operating mode: Pulse output
System interface IEC 61850
IEC 61850 object CTRL/Q8XSWI1
IEC 61850 object CTRL/Q8CSWI1
Switch type: Ground switch
Cycle counter: Q8 OpCnt=
Configured to source:
System interface
Properties:
Interlocking:
Check interlocking: Off
Page 72 of 146
7SJ645 V4_9 Var_prn_11_08_55
Configured to source:
System interface
Properties:
Interlocking:
Check interlocking: Off
Release ON command: No device interlock signal
Release OFF command: No device interlock signal
Check substation controller: Off
Enable: Release when interlocking AND zone control
completed.
Further lockings
Blocking by protection: Off
Double operation: Off
Switching authority at local control: Off
Switching authority at remote control: Off
Unclearable interlocking
Switching direction (nominal = actual): Off
Page 73 of 146
7SJ645 V4_9 Var_prn_11_08_55
Password:: <none>
Release ON command: No device interlock signal
Release OFF command: No device interlock signal
Times:
Output time: 200 [1/10 s]
Seal-in timer: 0 [1/10 s]
Feedback monitoring time: 250 [1/10 s]
Operating mode: Pulse output
System interface IEC 61850
IEC 61850 object CTRL/Q9XSWI1
IEC 61850 object CTRL/Q9CSWI1
Switch type: Disconnector
Cycle counter: Q9 OpCnt=
Properties:
Interlocking:
Check interlocking: Off
Release ON command: No device interlock signal
Release OFF command: No device interlock signal
Check substation controller: Off
Enable: Release when interlocking AND zone control
completed.
Further lockings
Blocking by protection: Off
Double operation: Off
Switching authority at local control: Off
Switching authority at remote control: Off
Unclearable interlocking
Switching direction (nominal = actual): Off
Password:: <none>
Release ON command: No device interlock signal
Release OFF command: No device interlock signal
Times:
Output time: 200 [1/10 s]
Seal-in timer: 0 [1/10 s]
Feedback monitoring time: 250 [1/10 s]
Operating mode: Pulse output
Configured to source:
System interface
Page 74 of 146
7SJ645 V4_9 Var_prn_11_08_55
Configured to destination:
BO: Tr 17
Control Display
Default Display
Properties:
Interlocking:
Check interlocking: On
Release ON command: Control Device ISO89BClos
Release OFF command: Control Device ISO89BOpen
Check substation controller: Off
Enable: Release when interlocking AND zone control
completed.
Further lockings
Blocking by protection: Off
Double operation: Off
Switching authority at local control: On
Switching authority at remote control: On
Unclearable interlocking
Switching direction (nominal = actual): Off
Password:: <none>
Release ON command: No device interlock signal
Release OFF command: No device interlock signal
Times:
Output time: 1 [1/10 s]
Seal-in timer: 0 [1/10 s]
Feedback monitoring time: 1 [1/10 s]
Operating mode: Pulse output
System interface IEC 61850
Switch type:
Cycle counter: Q2 ISO89B
Configured to source:
System interface
Configured to destination:
BO: Tr 13
Control Display
Default Display
Properties:
Interlocking:
Check interlocking: On
Release ON command: Control Device CB152IL
Release OFF command: No device interlock signal
Check substation controller: Off
Page 75 of 146
7SJ645 V4_9 Var_prn_11_08_55
Page 76 of 146
7SJ645 V4_9 Var_prn_11_08_55
Measured values
SAS MANUGURU CHANGES / TRAFO
SIMATIC BCPU / 7SJ645 V4.9 Var/7SJ645 09.11.20 11:08:56
2.3.1 Measurement
Configured to destination:
CFC
System interface
Properties:
Transmission threshold
Threshold: Use Central Threshold (10%):
Switching Object: No threshold switching
System interface IEC 61850
IEC 61850 object MEAS/MMXU1/A
Configured to destination:
CFC
System interface
Properties:
Transmission threshold
Threshold: Use Central Threshold (10%):
Switching Object: No threshold switching
System interface IEC 61850
IEC 61850 object MEAS/MMXU1/A
Configured to destination:
CFC
System interface
Properties:
Transmission threshold
Threshold: Use Central Threshold (10%):
Switching Object: No threshold switching
System interface IEC 61850
IEC 61850 object MEAS/MMXU1/A
Configured to destination:
CFC
System interface
Page 77 of 146
7SJ645 V4_9 Var_prn_11_08_55
Properties:
Transmission threshold
Threshold: Use Central Threshold (10%):
Switching Object: No threshold switching
System interface IEC 61850
IEC 61850 object MEAS/MMXU1/A
Configured to destination:
CFC
System interface
Properties:
Transmission threshold
Threshold: Use Central Threshold (10%):
Switching Object: No threshold switching
System interface IEC 61850
IEC 61850 object MEAS/MSQI1/SeqA
Configured to destination:
CFC
System interface
Properties:
Transmission threshold
Threshold: Use Central Threshold (10%):
Switching Object: No threshold switching
System interface IEC 61850
IEC 61850 object MEAS/MSQI1/SeqA
Configured to destination:
CFC
System interface
Properties:
Transmission threshold
Threshold: Use Central Threshold (10%):
Switching Object: No threshold switching
System interface IEC 61850
IEC 61850 object MEAS/MSQI1/SeqA
Page 78 of 146
7SJ645 V4_9 Var_prn_11_08_55
U L1-E (MV - Measured value)
SAS MANUGURU CHANGES / TRAFO
SIMATIC BCPU / 7SJ645 V4.9 Var/7SJ645 09.11.20 11:08:56
Configured to destination:
CFC
System interface
Properties:
Transmission threshold
Threshold: Use Central Threshold (10%):
Switching Object: No threshold switching
System interface IEC 61850
IEC 61850 object MEAS/MMXU1/PhV
Configured to destination:
CFC
System interface
Properties:
Transmission threshold
Threshold: Use Central Threshold (10%):
Switching Object: No threshold switching
System interface IEC 61850
IEC 61850 object MEAS/MMXU1/PhV
Configured to destination:
CFC
System interface
Properties:
Transmission threshold
Threshold: Use Central Threshold (10%):
Switching Object: No threshold switching
System interface IEC 61850
IEC 61850 object MEAS/MMXU1/PhV
Configured to destination:
CFC
System interface
Properties:
Transmission threshold
Threshold: Use Central Threshold (10%):
Page 79 of 146
7SJ645 V4_9 Var_prn_11_08_55
Configured to destination:
CFC
System interface
Properties:
Transmission threshold
Threshold: Use Central Threshold (10%):
Switching Object: No threshold switching
System interface IEC 61850
IEC 61850 object MEAS/MMXU1/PPV
Configured to destination:
CFC
System interface
Properties:
Transmission threshold
Threshold: Use Central Threshold (10%):
Switching Object: No threshold switching
System interface IEC 61850
IEC 61850 object MEAS/MMXU1/PPV
Configured to destination:
CFC
System interface
Properties:
Transmission threshold
Threshold: Use Central Threshold (10%):
Switching Object: No threshold switching
System interface IEC 61850
IEC 61850 object MEAS/MMXU1/PhV
Configured to destination:
CFC
Page 80 of 146
7SJ645 V4_9 Var_prn_11_08_55
System interface
Properties:
Transmission threshold
Threshold: Use Central Threshold (10%):
Switching Object: No threshold switching
System interface IEC 61850
IEC 61850 object MEAS/MSQI1/SeqV
Configured to destination:
CFC
System interface
Properties:
Transmission threshold
Threshold: Use Central Threshold (10%):
Switching Object: No threshold switching
System interface IEC 61850
IEC 61850 object MEAS/MSQI1/SeqV
Configured to destination:
CFC
System interface
Properties:
Transmission threshold
Threshold: Use Central Threshold (10%):
Switching Object: No threshold switching
System interface IEC 61850
IEC 61850 object MEAS/MMXU1/TotW
Configured to destination:
CFC
System interface
Properties:
Transmission threshold
Threshold: Use Central Threshold (10%):
Switching Object: No threshold switching
System interface IEC 61850
IEC 61850 object MEAS/MMXU1/TotVAr
Page 81 of 146
7SJ645 V4_9 Var_prn_11_08_55
S (apparent power) (MV - Measured value)
SAS MANUGURU CHANGES / TRAFO
SIMATIC BCPU / 7SJ645 V4.9 Var/7SJ645 09.11.20 11:08:56
Configured to destination:
CFC
System interface
Properties:
Transmission threshold
Threshold: Use Central Threshold (10%):
Switching Object: No threshold switching
System interface IEC 61850
IEC 61850 object MEAS/MMXU1/TotVA
Configured to destination:
CFC
System interface
Properties:
Transmission threshold
Threshold: Use Central Threshold (10%):
Switching Object: No threshold switching
System interface IEC 61850
IEC 61850 object MEAS/MMXU1/Hz
Configured to destination:
CFC
System interface
Properties:
Transmission threshold
Threshold: Use Central Threshold (10%):
Switching Object: No threshold switching
System interface IEC 61850
IEC 61850 object MEAS/MSQI1/SeqV
Configured to destination:
CFC
System interface
Properties:
Transmission threshold
Threshold: Use Central Threshold (10%):
Page 82 of 146
7SJ645 V4_9 Var_prn_11_08_55
Configured to destination:
CFC
Configured to destination:
CFC
Configured to destination:
CFC
Configured to destination:
CFC
Configured to destination:
CFC
Configured to destination:
CFC
Configured to destination:
CFC
Configured to destination:
CFC
Page 83 of 146
7SJ645 V4_9 Var_prn_11_08_55
Q, L2 (reactive power, phase L2) (MV - Measured value)
SAS MANUGURU CHANGES / TRAFO
SIMATIC BCPU / 7SJ645 V4.9 Var/7SJ645 09.11.20 11:08:56
Configured to destination:
CFC
Configured to destination:
CFC
Configured to destination:
CFC
Configured to destination:
CFC
Configured to destination:
CFC
Configured to destination:
Measured value window Set Points(MV)
CFC
Properties:
Measured value description
Dimension: %
Conversion Factor: 100
Decimal Places: 1
Startup: 80
Configured to destination:
Measured value window Set Points(MV)
CFC
Page 84 of 146
7SJ645 V4_9 Var_prn_11_08_55
Properties:
Measured value description
Conversion Factor: 1
Decimal Places: 1
Startup: 0.8
Page 85 of 146
7SJ645 V4_9 Var_prn_11_08_55
Metered values
SAS MANUGURU CHANGES / TRAFO
SIMATIC BCPU / 7SJ645 V4.9 Var/7SJ645 09.11.20 11:08:56
2.4.1 Energy
Configured to source:
Measured value: WpDelta=
Configured to destination:
System interface
Metered value window
Properties:
Restore type Cyclic
Cyclical restoring
Trigger via absolute time: ON
Delete restore type: OFF
Restore type time interval: 1 Minute(s)
External restoring
Trigger via binary input: Not configured
Delete restore type: OFF
Energy flow direction: Forward
System interface IEC 61850
IEC 61850 object MEAS/MMTR1/SupWh
Configured to source:
Measured value: WqDelta=
Configured to destination:
System interface
Metered value window
Properties:
Restore type Cyclic
Cyclical restoring
Trigger via absolute time: ON
Delete restore type: OFF
Restore type time interval: 1 Minute(s)
External restoring
Trigger via binary input: Not configured
Delete restore type: OFF
Energy flow direction: Forward
System interface IEC 61850
IEC 61850 object MEAS/MMTR1/SupVArh
Page 86 of 146
7SJ645 V4_9 Var_prn_11_08_55
Wp Reverse (MVMV - Metered value of measured value)
SAS MANUGURU CHANGES / TRAFO
SIMATIC BCPU / 7SJ645 V4.9 Var/7SJ645 09.11.20 11:08:56
Configured to source:
Measured value: WpDelta=
Configured to destination:
System interface
Metered value window
Properties:
Restore type Cyclic
Cyclical restoring
Trigger via absolute time: ON
Delete restore type: OFF
Restore type time interval: 1 Minute(s)
External restoring
Trigger via binary input: Not configured
Delete restore type: OFF
Energy flow direction: Import
System interface IEC 61850
IEC 61850 object MEAS/MMTR1/DmdWh
Configured to source:
Measured value: WqDelta=
Configured to destination:
System interface
Metered value window
Properties:
Restore type Cyclic
Cyclical restoring
Trigger via absolute time: ON
Delete restore type: OFF
Restore type time interval: 1 Minute(s)
External restoring
Trigger via binary input: Not configured
Delete restore type: OFF
Energy flow direction: Import
System interface IEC 61850
IEC 61850 object MEAS/MMTR1/DmdVArh
Configured to destination:
Metered value window
Properties:
Page 87 of 146
7SJ645 V4_9 Var_prn_11_08_55
Configured to destination:
Metered value window
Properties:
Measured value description
Dimension: MVARh
Conversion Factor: 1
Decimal Places: 1
Pulse type Wiping pulse / S0
External Do not use fault input
Restore type Cyclic
Cyclical restoring
Trigger via absolute time: ON
Delete restore type: OFF
Restore type time interval: 1 Minute(s)
External restoring
Trigger via binary input: Not configured
Delete restore type: OFF
Energy flow direction: Import
2.4.2 Statistics
Configured to destination:
System interface
Properties:
Measured value description
Page 88 of 146
7SJ645 V4_9 Var_prn_11_08_55
Conversion Factor: 1
Decimal Places: 0
Pulse type Wiping pulse / S0
External Do not use fault input
Restore type Cyclic
Cyclical restoring
Trigger via absolute time: ON
Delete restore type: OFF
Restore type time interval: 1 Minute(s)
External restoring
Trigger via binary input: Not configured
Delete restore type: OFF
Energy flow direction: Import
System interface IEC 61850
IEC 61850 object PROT/XCBR1/OpCnt
Page 89 of 146
7SJ645 V4_9 Var_prn_11_08_55
Display after fault
SAS MANUGURU CHANGES / TRAFO
SIMATIC BCPU / 7SJ645 V4.9 Var/7SJ645 09.11.20 11:08:56
Page 90 of 146
7SJ645 V4_9 Var_prn_11_08_55
Configuration - short (column-oriented)
SAS MANUGURU CHANGES / TRAFO
SIMATIC BCPU / 7SJ645 V4.9 Var/7SJ645 09.11.20 11:08:56
Binary inputs
Binary inputs No. Group Information Type Configuration
1 User-def. CB152OPEN SP H
1 Control Device CB152 DP X
2 User-def. CB152CLOSE SP H
2 Control Device CB152 DP X
3 User-def. ISO89AOpen SP H
3 Control Device ISO89A DP X
4 User-def. ISO89AClos SP H
4 Control Device ISO89A DP X
5 User-def. 86OPTD SP H
6 User-def. 86Healthy SP H
7 User-def. ISO89BOpen SP H
7 Control Device ISO89B DP X
8 User-def. ISO89BClos SP H
8 Control Device ISO89B DP X
9 User-def. SF6Loss SP H
10 User-def. CBLockout SP H
11 User-def. DC1Healthy SP H
12 User-def. Spring CHR SP H
13 User-def. DC2Healthy SP H
14 User-def. BUCHZTrip SP H
15 User-def. PRV Trip SP H
16 User-def. OSR Trip SP H
17 User-def. WTIHVTRIP SP H
18 User-def. WTILVTRIP SP H
19 User-def. OTI Trip SP H
22 User-def. DC MCBTrip SP H
23 User-def. NR1 MCBTri SP H
24 User-def. 86HVMCBTri SP H
25 User-def. TNC CLOSE SP H
Binary outputs
BO No. Group Information Type Configuration
Page 91 of 146
7SJ645 V4_9 Var_prn_11_08_55
Binary outputs(2)
BO No. Group Information Type Configuration
3.3 LEDs
LEDs
LEDs No. Group Information Type Configuration
Page 92 of 146
7SJ645 V4_9 Var_prn_11_08_55
LEDs(2)
LEDs No. Group Information Type Configuration
3.4 CFC
CFC
No. Group Information Source Destination
Page 93 of 146
7SJ645 V4_9 Var_prn_11_08_55
CFC(2)
No. Group Information Source Destination
Page 94 of 146
7SJ645 V4_9 Var_prn_11_08_55
CFC(3)
No. Group Information Source Destination
nothing allocated
3.6 Buffer
Page 95 of 146
7SJ645 V4_9 Var_prn_11_08_55
Page 96 of 146
7SJ645 V4_9 Var_prn_11_08_55
User-def. CBLockout IO
User-def. DC1Healthy IO
User-def. DC2Healthy IO
User-def. Spring CHR IO
User-def. BUCHZTrip IO
User-def. PRV Trip IO
User-def. OSR Trip IO
User-def. WTIHVTRIP IO
User-def. WTILVTRIP IO
User-def. OTI Trip IO
User-def. DC MCBTrip IO
User-def. NR1 MCBTri IO
User-def. 86HVMCBTri IO
User-def. TrafoFault IO
User-def. 86FLTY IO
User-def. TNC CLOSE IO
User-def. TNCCLCMD IO
009.0100.01 EN100-Modul 1 Failure EN100 Modul IO
009.0101.01 EN100-Modul 1 Failure EN100 Link Channel 1 (Ch1) IO
009.0102.01 EN100-Modul 1 Failure EN100 Link Channel 2 (Ch2) IO
05145 P.System Data 1 >Reverse Phase Rotation IO
05147 P.System Data 1 Phase Rotation L1L2L3 IO
05148 P.System Data 1 Phase Rotation L1L3L2 IO
00203 Osc. Fault Rec. Waveform data deleted I
Osc. Fault Rec. Fault Recording Start IO
02720 P.System Data 2 >Enable 50/67-(N)-2 (override 79 blk) IO
00561 P.System Data 2 Manual close signal detected IO
04601 P.System Data 2 >Breaker contact (OPEN, if bkr is open) IO
04602 P.System Data 2 >Breaker contact(OPEN, if bkr is closed) IO
00126 P.System Data 2 Protection ON/OFF (via system port) IO
01751 Overcurrent Time Overcurrent Phase is OFF IO
01752 Overcurrent Time Overcurrent Phase is BLOCKED IO
01753 Overcurrent Time Overcurrent Phase is ACTIVE IO
10034 Overcurrent I>>> BLOCKED IO
01852 Overcurrent I>> BLOCKED IO
01851 Overcurrent I> BLOCKED IO
01855 Overcurrent Ip BLOCKED IO
01756 Overcurrent Time Overcurrent Earth is OFF IO
01757 Overcurrent Time Overcurrent Earth is BLOCKED IO
01758 Overcurrent Time Overcurrent Earth is ACTIVE IO
10035 Overcurrent IE>>> BLOCKED IO
01854 Overcurrent IE>> BLOCKED IO
Page 97 of 146
7SJ645 V4_9 Var_prn_11_08_55
Page 98 of 146
7SJ645 V4_9 Var_prn_11_08_55
Page 99 of 146
7SJ645 V4_9 Var_prn_11_08_55
Trip log
No. Group Information Buffer
Trip log(2)
No. Group Information Buffer
Trip log(3)
No. Group Information Buffer
nothing allocated
3.7 Display
Display
No. Group Information Control Display Default Display
User-def. CB152OPEN X X
User-def. CB152CLOSE X X
User-def. ISO89AOpen X X
User-def. ISO89AClos X X
User-def. ISO89BOpen X X
User-def. ISO89BClos X X
User-def. BUCHZTrip X
User-def. PRV Trip X
User-def. OSR Trip X
User-def. WTIHVTRIP X
User-def. WTILVTRIP X
User-def. OTI Trip X
User-def. DC MCBTrip X
User-def. NR1 MCBTri X
User-def. 86HVMCBTri X
User-def. TrafoFault X
User-def. 86FLTY X
Display(2)
No. Group Information Control Display Default Display
4 Interfaces
4.2 VD addresses
DIGSI VD address: 3
SIPROTEC VD address: 10007
Proxy VD address: 4
SIPROTEC T103 VD address: 0
Address: 1
Frame: 8 E(ven) 1
Baud rate: 57600
Max. telegram gap (0...50): 0
IP address: 192.168.1.1
Subnet mask: 255.255.255.0
Link layer: PPP (point-to-point, serial)
Access authorization at the port for parameterization: Enabled
Access authorization at the port for test and diagnosis: Enabled
Web Monitor operation: Full access
Address: 1
Frame: 8 E(ven) 1
Baud rate: 38400
Max. telegram gap (0...50): 0
IP address: 192.168.2.1
Subnet mask: 255.255.255.0
Link layer: PPP via star coupler
Access authorization at the port for parameterization: Enabled
Access authorization at the port for test and diagnosis: Enabled
Web Monitor operation: Reading
IP address: 192.168.0.12
Subnet mask: 255.255.255.0
Standard gateway: 192.168.0.200
Link layer: Ethernet
Access authorization at the port for parameterization: Enabled
Access authorization at the port for test and diagnosis: Enabled
Web Monitor operation: Reading
SNMP (Simple Network Management Protocol): ON
Web server: ON
IEC 61850: ON
Supplementary protocol EN100 module: ON
DIGSI via EN100 module: ON
4.6 Redundancy
4.7 Ethernet on PC
IP address: 192.168.0.27
Subnet mask: 255.255.255.0
5 Passwords
0610 Fault Display on LED / LCD Display Targets on every Pickup All
0611 Spontaneous display of flt.annunciations YES All
0617A T103-transfer limeted to 16 meas. values NO All
0625A Minimum hold time of latched LEDs 0 min All
0700 GOOSE-Stop NO All
9 Settings groups
10 Time Synchronization
11 Annunciation
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Spontaneous
Command Issued=Local
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Spontaneous
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Command Issued=Local
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Command Issued=Local
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Com.Issued=AutoLocal
Control Issued
Command Issued=DIGSI
Control Issued
Command Issued=DIGSI
Spontaneous
Command Issued=Local
Spontaneous
Command Issued=Local
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Command Issued=Local
Spontaneous
Command Issued=Local
Spontaneous
Command Issued=Local
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Command Issued=Local
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Command Issued=Local
Spontaneous
Command Issued=Local
Spontaneous
Command Issued=Local
Spontaneous
Command Issued=Local
Spontaneous
Command Issued=Local
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Com.Issued=AutoLocal
Spontaneous
Spontaneous
Spontaneous
Spontaneous
nothing allocated
nothing allocated
12 Measurement
00601 I L1 9A
00602 I L2 9A
00603 I L3 9A
00604 IN 0A
00830 Senstive Earth Fault Current 0A
00831 3I0 (zero sequence) 0A
00605 I1 (positive sequence) 9A
00606 I2 (negative sequence) 0A
00621 U L1-E 79 kV
00622 U L2-E 80 kV
00623 U L3-E 79 kV
00624 U L12 138 kV
00625 U L23 138 kV
00626 U L31 137 kV
00627 Uen 0 kV
00832 U0 (zero sequence) 0 kV
00629 U1 (positive sequence) 79 kV
00630 U2 (negative sequence) 0 kV
00641 P (active power) 2.2 MW
00642 Q (reactive power) -0.3 MVAR
00645 S (apparent power) 2.2 MVA
00901 Power Factor 0.99
00644 Frequency 50.0 Hz
16031 Angle between 3U0 and INsens. .....
00601 I L1 0.06 A
00602 I L2 0.06 A
00603 I L3 0.06 A
00604 IN 0.00 A
00830 Senstive Earth Fault Current 0 mA
00831 3I0 (zero sequence) 0.00 A
00605 I1 (positive sequence) 0.06 A
00606 I2 (negative sequence) 0.00 A
00621 U L1-E 66 V
00622 U L2-E 67 V
00623 U L3-E 66 V
00624 U L12 115 V
00625 U L23 115 V
00626 U L31 114 V
00627 Uen 0V
00832 U0 (zero sequence) 0V
00629 U1 (positive sequence) 66 V
00630 U2 (negative sequence) 0V
16031 Angle between 3U0 and INsens. .....
00601 I L1 6.0 %
00602 I L2 6.0 %
00603 I L3 6.0 %
00604 IN 0.0 %
00830 Senstive Earth Fault Current 0.0 %
00831 3I0 (zero sequence) 0.0 %
00605 I1 (positive sequence) 6.3 %
00606 I2 (negative sequence) 0.0 %
00621 U L1-E 103.9 %
00622 U L2-E 104.7 %
00623 U L3-E 103.7 %
00624 U L12 104.4 %
00625 U L23 104.4 %
00626 U L31 103.5 %
00627 Uen 0.0 %
00832 U0 (zero sequence) 0.0 %
00629 U1 (positive sequence) 104.1 %
00630 U2 (negative sequence) 0.0 %
00641 P (active power) 6.3 %
00642 Q (reactive power) -1.0 %
00645 S (apparent power) 6.3 %
nothing allocated
13 Additional Functions