– Start PCM600. Select File - New Project. Fill in the project name and
description to the dialog window. Click Create.
If you later want to rename a project, use the File – Open/Manage
project dialog. The project must be closed while renaming
Step 1.2.1 Create a new project structure.
If you do not see the Object Types in PCM600, select View - Object
Types
You can give your own names to the plant structure objects. To do this,
either right-click the object and select rename from the context menu,
or edit the caption in the Object Properties window.
If you do not see the Object Properties in PCM600, select View - Object
Properties
Step 1.3.1 Add and configure a protection relay.
– Add a relay to a project. You can either drag and drop the relay from
Object Types library OR use the context menu: right click on the Bay
element and choose New – Feeder IEDs – REF615.
If the needed relay is not listed in the context menu, it means that the
corresponding connectivity package is not installed. Connectivity
packages might be installed from Update manager tool
Step 1.3.2 Add and configure a protection relay.
Once you have selected the relay REF615, the Configuration Wizard will
guide you. The communication setting window opens as soon as the
relay is placed.
– Select the option: Online configuration and go Next
Step 1.3.3 Add and configure a protection relay.
– Click Next
Step 1.3.6 Add and configure a protection relay.
– Go Next
Step 1.3.7 Add and configure a protection relay.
When adding a relay in the project you need to select IEC 61850 edition.
If there are already other relays in the project, the currently selected
edition will be picked automatically.
In real life project check IEC 61850 edition preferences from system
integrator/SCADA engineer because this option is mainly related to
vertical communication
– Choose “Edition 1“ in this training
– Go Next
Step 1.3.8 Add and configure a protection relay.
– Add REF620 relay with Empty configuration into the project under the
new Bay in a same way as for REF615. Check again the correct IP
address of your REF620 relay from the training material document you
have received (IP_GOOSE_SV_Settings_615&620.txt).