Professional Documents
Culture Documents
00 Minerals Library Product Guide
00 Minerals Library Product Guide
Reproduction, use or disclosure to third parties without express authority is strictly forbidden.
Ó Copyright 2016 ABB. All rights reserved.
Product Guide
Version 6.0/0
Status Viewer
Log Configurations
Legacy Libraries
Function Description
MINERALS (BMI)
In addition to the configuration possible per Object and Graphic Element, Colors
and some Settings can be done per Operator Workplace to re-use the same
Display Graphics for different Environments. Furthermore, Minerals Library
SEQuence
CENtral
LOCal
Out of
Service
All POC are selectable from the operator workplace. The point of control defines from
where the object will be controlled. In order to control an object the corresponding POC
must be selected before giving any command to the object. For safety reason, stopping
an object or closing a gate is always possible, no matter which control mode has been
chosen.
Sequence: The object is controlled by a superior application program e.g. from a drive
group sequence. Sequence mode can be set from the operator station or by the
application program.
Central: The object is controlled by the operator station by means of the start/stop or
open/close push buttons on the faceplate. Start/stop or open/close from a superior
application program is also possible in this mode. The Central mode can be set from
the operator workplace only.
Manual Mode
Auto Mode
Man (default): An object is controlled by a rising edge start / stop command, either
released from the operator station or from the superior application program.
In Central Auto and Sequence Auto mode the operator cannot control the object any
more from the operator station. Stopping a motor and closing a gate is always possible.
Local:
The object is controlled from the field via the pushbuttons on the local control box
(LCB). To operate a drive locally, the drives need the local release from the CCR
operator. The point of control has to be changed in the CCR and can be set for a
complete drive group or for every object individually.
The interlocks are de-activated in this mode except the safety interlock IC (Rope
Switches, Bearing/Winding Temp., Vibrations etc.). Furthermore the two feedback
signals (FB1 and FB2 – for example speed switch) are also de-activated while pressing
and holding the start/open push button. Typically, the Local mode is for maintenance
purposes.
Note: Alarms are disabled when an object is in Local mode (no alarm acknowledgment on
the operator station necessary when object is operated from the field).
Out of Service: The object is not in service and cannot be started from any location. It
also means that the object will be skipped when running a superior group sequence. Out of
Service mode can be set and reset from the operator station only with special user rights.
· The status form child objects are always reported to the parent object and vice versa
· Commands can be sent from parents to children and from children to parents
By clicking on the motor on the HMI the In the faceplate is the PCC Viewer located. A click
faceplate of the motor opens. on this icon brings up the window shown below.
This table provides a complete and consistent
overview of the interlocks acting on the consumer.
By clicking on the navigation button , the The status of the signal is shown with a red
faceplate of the flow switch is opened for a alarm frame (unhealthy condition)
indeep root cause analyize.
The PCC viewer is opened by clicking on the Clicking on the highlighted bar in the PCC will
corresponding icon in the motor faceplate. open the facepalte of the flow switch.
The figure below shows all possible status indications of the group as presented in the
process display.
Off
Starting
Startwarning
Running
Running
restart required as pre-selection has changed
Stopping
Running, warning
in some of connected equipment
on Hold (not off but as well not fully running)
Failure, not ready for start
on Hold
Off
Start interlock
Running
Stop interlock
Off
not ready for start because of Failure in at least
one of the connected consumers
Before starting the group, the pre-selections such as selecting alternative routing,
standby units, set points, etc., may be adjusted. The new settings are indicated in the
process display and the faceplate.
Pressing the “start” button in the faceplate the following steps are executed:
1. An audible start-up warning is activated for all related equipment, optional the start
warning can be configured to be executed prior the start of individual equipment.
The group indicates “Starting / PreWarning”
2. After a certain adjustable time, the start-up warning stops and the equipment starts
to run, respectively moves into the position according to the programmed
sequence and used pre-selections. The group indicates “Starting” and the step
number and tag name of the actually started equipment can be monitored on the
faceplate.
Stopping a group
A group may be stopped in case there is no stop interlock active (e.g. group can’t be
stopped because another group is still not off). Stopping is possible from any status,
even the group “Starting” status.
Pressing the “Stop” button changes the indication to stop and all equipment will be
sequentially stopped or moved to the defined “off” position, leaving the equipment in a
suitable condition for the next start-up – transport systems emptied of material,
dampers turned to safety position. After a successful stop the group indicates “Off /
Ready for Start”.
If an alarm condition arises during the group start sequence (e.g. fault or process
interlock of equipment starting or already running) the start-up will be interrupted
automatically and the group indicates, “Hold / Drive(s) not Ready”. The object name of
the equipment causing the fault is presented in the group faceplate and the operator can
directly link to the equipment faceplate to get more detailed information.
“Hold” means that only a part of the group is in operation (not completely started or
stopped). At this state by pressing the “stop” button, the rest of the group is stopped in
accordance with the stop sequence or if the fault can be removed, the start sequence
may be reactivated by selecting the group and pressing the “start” button again.
A group may be started, if all pre-selected equipment assigned to the group is ready for
start, the pre-selection is set correctly and no group start interlock is active. Initial
starting is possible from status “Off / Ready for Start”. A group restart can be performed
from the status: “Stopping”, “Hold” or “Running”. Additionally a group can be started by
an unconditional start, even with equipment not ready for start, meaning the group will
start until the start step of the equipment which is not ready for start.
Before starting the group, the pre-selections such as selecting alternative routing,
standby units, set points, etc., may be adjusted. The new settings are indicated in the
process display and the faceplate.
Manual Hold
The operator may manually interrupt the starting or stopping or quick stop procedure of
a group at any time by pressing the “hold” button on the faceplate. In this case the group
will indicate hold until the starting or stopping process is continued.
Pre-selections
The pre-selection function allows motors to be included in the start-up process of a
group. By setting and resetting the pre-selections, the operator may define which objects
should be activated or deactivated by the next start command. Even a flying change of
the pre-selection (e.g. automatic change of silo filling) may be programmed. This is a
fully automatic change of the pre-selection during the group running status.
Started / Running
The operator is allowed to change the pre-selections when a group has following status:
If only one pre-selection setting is allowed to be active at the time, the other pre-
selections are deactivated automatically (radio button function). If more pre-selection
settings are possible at the same time, the operator can manually chose the
configuration.
Missing – and wrong pre-selection combinations prevent a group start. There is then an
indication on the group faceplate.
Minerals Library object: GROUP In this process the group contains 3 consumers,
which are the two pumps 1 & 2 and the mill main
Control Module: GR_562_2R
motor. The mill motor has already been used and
Module Parameter “Name”: GR_562_P2 explained in the pcc example. This 3 consumers
are connected by the GCC, hightlighted with blue
colour in the picture showing the code. The GCC to
the mill motor is connected with a grey link
connector.
Minerals Library object: PREBIN The axial plain bearings of the mil are supplied by
oil. The oil pressure is produced by two redundant
Control Module: GR_562_2R_P1
pumps. There is only one out of the 2 pumps
Module Parameter “Name”: GR_562_2R_P1 running at any given moment.
Additional
information about the group stop are revealed by
opening the faceplate of the group. The first The Group status viewer of the group also indicates
consumer not running is written in text. the actual status of the group
Together with forwarding the Setpoint from the Controller to the Actuator Object,
navigation between the Blocks connected by LoopControlConnection is available for the
Operator in the Faceplate, and any Alarm State of the Actuator with corresponding
Color is shown for the related Output Value in the Controller Faceplate as well.
AOS Analog output module for 1 process signal. The Analog Output,
functions are manual / auto mode, tracking of mode Actuator Setpoint
and output changes, 2 output limits.
DIS Digital input module for 1 process signal. The Digital Input, Binary
functions are blocking and forcing of input value, 3 Sensor, Switch
alarm priorities, alarm delay, alarm blocking, alarm
disabling/enabling from application software.
DOS Digital output module for 1 process signal. The Digital Output
functions are manual / auto mode, tracking of mode
and output changes.
MOT2 Control a motor with two directions (two speeds) in a Reversible Belt
drive group or standalone. Conveyor
MOT2_VVVF Control a motor with two direction and variable Reversible Variable
speed in a drive group or standalone. Speed Drive
PIDAdvCtrl PID closed loop controller with advanced Functions, for Cascade loop,
cascade control loops, gain scheduling, adaptive PID Adaptive PID closed
control. loop control
RatioCtrl Calculates an Output (Setpoint) by an Input Signal with Setpoint for Additive
Gain and Offset as Percentage of
Total Feed Setpoint
SplitRange Connect Setpoint from PIDCtrl or RatioCtrl to 2 Objects 2 Valves in Split-
in parallel or split-range configuration Range configuration
· Reset counter value from controller or from the Operator Station (via the
faceplate)
· Adjustment (positive & negative) of counter value and constant from the
Operator Station (via the faceplate)
· Operator Station Interface (graphic element and faceplate)
A detailed description of the report objects and their interfaces is given in the
Reference Manual Report Objects.
Reference Table: Report Objects
The Process Panel 800 Interface provides access and control for the
following Minerals Library AC800 control modules:
· AIS
· AOS
· DIS
· DOS
· AIC
· AOC
· DIC
· DOC
· MOT1
· MOT1VVVF
· MOT2
· MOT2VVVF
· MOTP
· VLV1
· VLVNO1
· GROUP
· DriveGroup
· PREBIN
All Process Panel objects have the following common basic functions:
· Manual control from the Process Panel (via commands and input fields)
· Status and operation indication
· Mode selection from the Process Panel (via commands)
For more info consult the documentation: Process Panel Reference Manual
3BHS240189
Control - AC800M - Minerals Library
Operation - Process Panel - AC800M Connect - Minerals Library
Consumer Objects
Motor Fan Pump Valve Damper Diverter
Starting
Running
Running (Dir X)
Object Interlock
Warning Interlock
(PCC)
Tag name
Descriptio
n
Motor
status
Indication
Start
Change Point of
motor
Control
Stop
motor Seq => Sequence
Cen => Central
Loc => Local
AISandUnit AISBar
Value
Block
Limit Alarm
Signal Error
· Blocking and forcing of input value generating event (even on new forced
values)
· Threshold detection and alarming on 4 alarm limit levels (L2,L1,H1,H2)
· Threshold detection and event on 2 Process Limit levels (Plo, Phi)
· Adjustable Low Pass Filter.
· Filtered Signal Rate of change calculation and alarm. The ROC is
presented in % of Total Range per second.
· All Sub status for DP, PA and FF Field Devices will generate error control
when quality is Bad or Uncertain for AIS Control Module.
· Common or Individual alarm delay for all 6 limits.
· Alarm blocking (from faceplate). All alarm limit levels will be blocked.
· Alarm disabling/enabling of each alarm limit individually (from application
program / Faceplate); generating events when blocked.
· Trend for Signal Value, Filtered Value and Rate of Change
· Signal Error Pre-Warning with adjustable alarm delay
· Process Panel status indication and operation
Manual control
Automatic control
The analog output module for 1 IO signal provides the following features:
DISTxt DIS
Status
Block
Alarm
The digital input module for 1 IO signal provides the following features:
· Blocking and forcing of input value generating event (even on new forced
values)
· Alarming if input value differs from pre-defined (healthy; normal position)
state
· Warning time to be used to generate a pre warning alarm or event before
the main alarm (failure) occurs.
· Ready Delay time to hold the alarm position in order to prevent noisy
signals to clear and re-activate the alarm very often.
· Alarm delay
· Alarm blocking (from faceplate). All alarm limit levels will be blocked.
· Alarm disabling/enabling (from application program)
· On-Line trend with actual input value
· Process Panel status indication
Doc. kind Product Guide Project Minerals Library Standard
Title System 800xA
Minerals Library version 6.0
Document number Lang. Rev. ind. Pages 48
3BHS 161554 en Q 123
ABB Switzerland Ltd No. of p.
DIGITAL OUTPUT (DOS, DOSTXT)
Main purpose of Module: Digital Output Interface
DOSTxt DOS
Status
Manual
Block
Alarm
The digital output module for 1 IO signal provides the following features:
Off
Starting
on Hold
Running
Stopping
GrpCycleCtrl GrpCycleCtrl_Info
Off
Running
Deselected
Selected
Selected (valid)
PREBIN has no faceplate. Clicking on the push button symbol toggles the state. In
case stand-by preselection is configured, an additional button is provided for each
pre-selection to define the current stand-by selection.
The pre-selection module allows the operator to select or de-select a single device
or a set of devices within a group. By e.g. pressing “Silo1” all objects belonging to
the route to silo 1 are pre-selected. This does however, not cause a start-up of
equipment, it is just a selection. When initiating a group sequence start, selected
devices will start up in a sequential order; de-selected devices will shut down in a
sequential order (provided they were in a running state).
In case stand-by pre-selection is active, a pre-selected and running drive will initiate
a switchover (group start) when tripping, automatically starting up the stand-by pre-
selected drives.
Active
The start warning module is integrated with the consumer objects (e.g. MOT1, MOT2,
MOTP, etc.). When a start command for a motor is initiated, the start warning module
first triggers the buzzers and/or flashlights before it returns the actual start release
for the motor. Different buzzers and flashlights can be assigned to appropriate start
warning modules, which in turn are assigned to appropriate consumers.
Starting
Running
Object Interlock
The control module for a reversing motor has basically the same functionality as
MOT1, however with the following adaptations:
The control module for a reversing variable speed motor is a combination of the
MOT2 and MOT1_VVVF modules, with the following features:
Automatic Mode
· Adjustment (positive & negative) of counter value and constant from the
Operator Station (via the faceplate)
· Operator Station Interface (graphic element and faceplate)
And additionally a focused historical archiving for detailed information is also available:
· Actual Shift / Last Shift
· Actual Day / Last Day
· Actual Month / Last Month
Doc. kind Product Guide Project Minerals Library Standard
Title System 800xA
Minerals Library version 6.0
Document number Lang. Rev. ind. Pages 75
3BHS 161554 en Q 123
ABB Switzerland Ltd No. of p.
Such as on kWh consumption for Cement Mills, Tons of material used for
production, running time of production critical equipment.
The library contains a so called Serial Object Framework in form of a composite Control
Module for implementing serial (fieldbus, etc.) connected equipment. The modularity of
the Control Module allows equipment specific adaptation of the communication part to
be used with the standard object (MOTx, VLVx, CircuitBreaker, etc.) functions.
Serially connected, usually intelligent devices have the ability of providing much more
information of their functional status. The faceplate with its limited space is not seen as
a suitable media to present all the additional information, most of which is not process
operation related.
Therefore configurable link buttons have been provided in the Faceplate “Extended Info”
Area to allow direct access to additional aspects of the serial object from the Operator
Station.
ANSI support
For this example, the ForeCast Energy At Interval End shows nicely that is based on the
ActualEnergyInInterval and the TotalPower. It calculates how much Energy will be used at the
end of the Metering Interval if the actual Power is steady till then.
This is the fastest method as shown on the trends : the light blue curves is the first to cross the
Warning Level !
Actual Tariff
conditions
Permanent
conditions
On this exemple, the ForeCast Energy At Interval End shows nicely that is based on the
ActualEnergyInInterval and the TotalPower. It calculates how much Energy will be used at the
end of the Metering Interval if the actual Power is steady till then.
This is the fastest method as shown on the trends : the light blue curves is the first to cross the
Warning Level !
Assumptions
On Average, 1 Minerals Object 10 OPC items
Limitation
· Up to 12000 I/O or 16 simultaneous operator screens (32 000 OPC items) per 1 of 1oo2
Connectivity server with 8GB RAM.
The latest platform values should always be checked with the ABB Products group before any
commitment is made.
Estimation based on Controlled objects
For the following two controller load estimation it is assumed that more than half of the cyclic controller
load is due to “application glue logic”
Expected Results
CPU Execution time
500ms for all objects,
Results in about 45% CPU cyclic load
50 to 150ms for dedicated part of the code (e.g.
stop on limit switch, local start/stop)
S800 I/O on Profibus, DI and DO minimal scan Approximately 120 ms with 1200 I/O per bus
time
200 – 250 Objects / display (= 2000 OPC Items) max 32’000 OPC Items = Max 16 Screens / Server
PP Client PP Client PP Client PP Client PP Client PP Client PP Client PP Client PP Client PP Client
Minerals Lib.
PM861: Up to 500 I/O
Profibus Profibus
PM866: Up to 2500 I/O Profibus
Performance Data
Application Performance Data
The SystemDiagnostics Interaction Window can be used online to check the
Performance of the running Controller with loaded Application. To ensure the
application reliability, you should pay attention of following Points:
Cyclic Load should not exceed 50%. Changing the application task connection
and / or the task properties (Period time) influences the load.
Used memory should not exceed 50%. Otherwise successful download of
changes during running cannot be guaranteed in all cases, and Stop time could
increase if there is not enough free Memory during download.
From the Price List for 1.2 Control and Operation; AC800M; Minerals Library
6.0/x:
System-wide license for 2000 MLPs (350+550+1100) is calculated as follows:
1 of Control;AC800M; MineralsLib6.0/x; BaseLic
3BHS200491R04
20 of Control;AC800M; MineralsLib6.0/x; 100 MLP;<=5000 MLP
3BHS200492R04
From the Price List for 1.2 Control and Operation; AC800M; Minerals Library
6.0/x:
1 of Control; AC800M; MineralsLib6.0/x; BaseLic
3BHS200491R04
50 of Control; AC800M; MineralsLib6.0/x; 100 MLP;<=5000 MLP
3BHS200492R04
30 of Control; AC800M; MineralsLib6.0/x; 5001-20000 MLP
3BHS200493R04
AISandUnit AISBar
Value
Block
Limit Alarm
Signal Error
Manual control
Automatic control
DISTxt DIS
Status
Block
Alarm
DOSTxt DOS
Status
Manual
Block
Alarm
Off
Starting
on Hold
Running
Stopping
Deselected
Selected
Selected (valid)
PREBIN has no faceplate. Clicking on the push button symbol toggles the state.
The pre-selection module allows the operator to select or de-select a single device or a
set of devices within a group. By e.g. pressing “Silo1” all objects belonging to the route
to silo 1 are pre-selected. This does however, not cause a start up of equipment, it is just
a selection. When initiating a group sequence start, selected devices will start up in a
sequential order; de-selected devices will shut down in a sequential order (provided they
were in a running state)
Group
PreWarning
Active
STW has no faceplate. The symbol is mainly used for presentation purposes on the
faceplates for MOT1, MOT2, MOTP, etc.
The start warning module is tight integrated with the control modules for MOT1, MOT2,
MOTP, etc. When a start command for a motor is initiated, the start warning module first
triggers the buzzers and/or flashlights before it returns the actual start release for the
motor. The start warning function can be configured depending on the point of control,
e.g. point of control Sequence and Central with start warning, Local without start warning.
If configured, the graphic symbol is displayed on the corresponding faceplate.
Starting
Running
Object Interlock
Automatic Mode
Automatic Mode
4.2.1 Tag
The licensing system for AC400 Connect is based on calculating Tags. A Tag
represents an object regardless of the number of data points it holds, examples
are:
• signal objects, i.e. AI, AO, etc.
• motor, valve objects
• generic OPC items with one or several OPC properties
• user defined object types
Licenses
Minerals AC400 Connect is an add-on to standard System 800xA AC400M
Connect and both licenses are required.
Minerals AC400 Connect contains display elements and faceplates for the BMI
AC400 objects/type circuits.
Prerequisites for use of this software:
· The System 800xA SV5.x Core System is installed, with the AC400
Connect Option.
· The AC400 controllers have the BMI Type Circuit Library installed.
From the Price List 1.6 Operation; AC400M Connect; Minerals Library 5.1/x:
The CD-ROM with the software for above functions should also be ordered.
1 of Operation;AC400Connect;MineralsLib5.1/x;SW&Doc CD
3BHS200505R02