Professional Documents
Culture Documents
Adaptive Ground Distance Protection For
Adaptive Ground Distance Protection For
a r t i c l e i n f o a b s t r a c t
Article history: This paper presents a mathematical deterministic adaptive distance protection formulation for UPFC
Received 22 September 2014 compensated transmission lines. The proposed formulation is developed using a phase component
Received in revised form 24 March 2015 approach and considers and compensates for various UPFC operation conditions and non-zero fault resis-
Accepted 18 April 2015
tances. The proposed methodology is completely adaptive and independent of system characteristics
(such as changes in transmission line impedances) or operating conditions (such as different load condi-
tions and controlled reference parameters). Moreover, the proposed formulation uses local and remote
Keywords:
end voltage and current signals as input data. The comparative test results demonstrate potential bene-
UPFC
Distance protection
ficial aspects of the proposed formulation for real-time applications.
Ground fault Ó 2015 Elsevier Ltd. All rights reserved.
Phase components approach
http://dx.doi.org/10.1016/j.ijepes.2015.04.008
0142-0615/Ó 2015 Elsevier Ltd. All rights reserved.
M.C.R. Paz et al. / Electrical Power and Energy Systems 73 (2015) 124–131 125
This paper presents a ground distance protection mathematical The series converter performs the main task of the UPFC by
deterministic formulation developed using phase coordinates. The injecting a voltage in series with the transmission line through
formulation is developed using phase coordinates to suit both bal- the coupling transformer. The series converter controls the magni-
anced and unbalanced systems as well as UPFC compensated sys- tude and the angle of the injected voltage. The shunt converter per-
tems. The proposed formulation considers the influence of the forms the primary function of absorbing the active power to supply
UPFC-controlled parameter knowledge-based scheme and the fault the series converter. The active component of the current drawn by
impedance estimation, thereby offsetting the influence of these the shunt converter depends on the power balance between the
properties on relay-estimated impedance. Additionally, the pro- series and the shunt part. The shunt converter is independently
posed formulation uses adaptive offset currents and voltages controlled to provide a voltage support to the coupling capacitors
injected by the UPFC located at the sending end. The consideration [2,19].
of balanced and unbalanced systems, as the fault impedance com-
pensation under those conditions, is a significant innovation com- Proposed methodology
pared with previous works and is considered to be the main
contribution of this study to the state of the art. It is important The equation presented in [17] can be adapted based on Fig. 2,
to note that the proposed methodology is completely adaptive and the voltage on bus s in phase k can be calculated as follows:
and independent of system characteristics or operation conditions.
This means that any change in system operation parameters (dif- V F k ¼ V sk þ V sek Z sek I0sk x ½Zlk I0 s ð1Þ
ferent load conditions or different controlled reference parame- where
ters), transmission line impedances, fault impedances and UPFC-
controlled parameters will be automatically compensated. The I0s ¼ Is Ish ð2Þ
proposed formulation is not presented in previous works that
and
addressed the fault impedance compensation of distance relays
for unbalanced systems [17,18]. The faulted circuit impedance
V sk is the phase k sending end voltage in units of ½V;
and fault impedance are obtained using measured signals at the
V sek is the phase k UPFC series injected voltage in units of ½V;
sending end, as well as voltage and current phasors of the remote
V F k is the phase k faulted point voltage in units of ½V;
terminal, and using the UPFC considering the WAMS implementa-
Z sek is the UPFC transformer phase k series impedance in units of
tion. The formulation was developed as an embedded software
½X;
package.
Zlk is the transmission line impedance phase k vector in units of
The remainder of this paper is as follows. Section ‘UPFC
½X;
modeling’ describes the state-of-the-art UPFC model used in this
Is is the sending end current in units of ½A;
work. Section ‘Proposed methodology’ presents and discusses
Ish is the UPFC shunt current in units of ½A;
the proposed distance protection formulation and demonstrates
the derived equations. A case study and the results are I0s is the transmission line current in units of ½A;
presented in Sections ‘Case study’ and ‘Results’, respectively. x is the fault distance in units of line length percent ½%; and
Section ‘Conclusion’ describes the conclusions of this work. k is the faulted phase k ¼ fa; b; cg.
The UPFC controller device was proposed by Gyugyi [1]. This is In addition, the voltage at the fault point can be written as
the most versatile of the FACTS devices and regulates the voltage V F k ¼ IF k Z f ð4Þ
and controls the power flow. Fig. 1 illustrates the basic structure
of the UPFC. The UPFC consists of two Voltage Source Converters where Z f is the fault impedance in units of ½X and IF is the fault cur-
(VSCs), one connected in series and one in shunt. Each converter rent defined by
has a capacitor connected in parallel. When the circuit breakers
IF ¼ I0s þ Ir ð5Þ
that connect two converters are open, each converter can operate
as a STATCOM and as a SSSC [2]. where Ir is the remote end current vector.
Replacing (4) and (5) in (3) and expanding the matrix product of Ish Ir V se Ish
Z map 1 k þ k Z f þ k Z sek 1 k
(3), it is possible to obtain for the phase k I sk I sk I sk Is
k
Isa Isha Isb Ishb Isc Ishc
V sk ¼ I0sk þ Irk Z f V sek þ Z sek I0sk x ¼ p Zlak þ Zlbk þ Zlck
I sk Isk I sk I sk I sk I sk
Zlak I0sa þ Zlbk I0sb þ Zlck I0sc ð6Þ ð9Þ
Fault resistance estimation r i r i r i
N2 ¼ Zlak Iisa þ Zlak Irsa þ Zlak Iisha þ Zlak Irsha þ Zlbk Iisb þ Zlbk Irsb
r i r i r i
The adaptive distance protection formulation presented in the þZlbk Iishb þ Zlak Irshb þ Zlck Iisc þ Zlck Irsc þ Zlck Iishc þ Zlck Irshc
previous section requires the fault impedance estimation to per-
ð18Þ
form the proposed compensation. During a purely resistive fault
Z f ¼ Rf , it is possible to group the terms in Eq. (6) into two equa- The equations for the real and imaginary components can be
tions, one with a real component indicated by the superscript r grouped in the equation matrix (19):
and the other with an imaginary component indicated by the sub-
script i. " # " #
V requ IrF k N1
Rf
V requ ¼ IrF k Rf þ x N 1 ð13Þ ¼ ð19Þ
V iequ IiF k N2 x
Case study
V iequ ¼ V isk þ V isek Z isek Irsk c Z isek Irshc ð16Þ
To validate the proposed formulation, different case studies
r i r i r i
N1 ¼ Zlak Irsa Zlak Iisa þ Zlak Irsha Zlak Iisha þ Zlbk Irsb Zlbk Iisb have been analyzed. Several time simulations were implemented
using Simulink/MatlabÒ [20]. The Resistance Estimator and Relay
r i r i r i
þZlbk Irshb Zlbk Iishb þ Zlck Irsc Zlck Iisc þ Zlck Irshc Zlck Iishc were implemented in Matlab. Fig. 4 illustrates the simulated power
ð17Þ system. Details of the studied system are given in Appendix.
L1_200 km
B6
A A a + + +
N B B b
C C c
Programmable Equiv. 500kV B1 B5 B7 L2_X L2 L-X B3 L3_180 km B4
B2
Voltage Source 8500 MVA
A
A
B
C
A
B
C
300 MW B
Equiv. 500kV
C 9000 MVA
B8
Three-Phase Fault
A
B
C
Equiv. 500kV
6500 MVA
Pulses
Pulses
VdcP
+
VdcP A1
UPFC
A B1
GUI
N Sw N C1
B
A2
+
VdcM B2 Vabc_B1
C VdcM Vabc_B1
C2
Shunt Converter Pulses_SE Vabc_B2 Vabc_B2
Series Converter
500 kV, 100MVA Iabc_SH Iabc_SH
10% injection,
100MVA Iabc_SE Iabc_SE
VdcPM_SH VdcPM_SH
Pulses_SH
VdcPM_SE VdcPM_SE
================= UPFC ====================
2 x 3-level, 48-pulse Converters
UPFC Controller
Fig. 5. Measured impedance trajectory for a phase C to ground fault with x ¼ 15%; b ¼ 30 ; Rf ¼ 40 X and Case 2. Zone1 ¼ 75%.
M.C.R. Paz et al. / Electrical Power and Energy Systems 73 (2015) 124–131 129
Fig. 6. Measured impedance trajectory for a phase C to ground fault with x ¼ 70%; b ¼ 30 ; Rf ¼ 40 X and Case 2. Zone1 ¼ 75%.
Fig. 7. Measured impedance trajectory for a phase C to ground fault with x ¼ 80%; b ¼ 30 ; Rf ¼ 40 X and Case 1. Zone1 ¼ 75%.
Fig. 8. Measured impedance trajectory for a phase C to ground fault with x ¼ 85%; b ¼ 90 ; Rf ¼ 40 X and Case 4. Zone1 ¼ 75%.
130 M.C.R. Paz et al. / Electrical Power and Energy Systems 73 (2015) 124–131
Table 2 The main advantage of our study compared with previous studies
Relay general performance. is the mathematical deterministic formulation presented in this
Total Sub total Proposed relay Traditional relay work. The results show that the proposed formulation is robust
Int/ext Wrong Right [%] Wrong Right [%] for distance protection even for high fault resistances. Several
operation conditions, including SSSC and STATCOM, were simu-
700 420 0 99.43 384 40.00
280 4 36
lated. The proposed formulation demonstrated satisfactory adapt-
ability and provided accurate analyses under each operation
condition. This work also illustrates the effect of the compensation
on the behavior of the traditional distance protection relay and the
ability of the proposed formulation to compensate the effects of
Table 3
Relay performance, fault resistance sensitivity analysis. the UPFC operation and fault impedances. Due to the lack of math-
ematical formulations for this type of system, the proposed formu-
Rf ½X Total Sub total Right [%]
lation was compared to the traditional method. The simulation
Int/ext Wrong results clearly show that the proposed formulation exhibits excel-
0 140 84 0 100 lent performance. Future work will present results for other types
56 0 of faults under other operating conditions.
5 140 84 0 100
56 0 Acknowledgment
10 140 84 0 100
56 0 The authors would like to thank Coordenação de
20 140 84 0 100 Aperfeiçoamente de Pessoal de Nível Superior – CAPES for financ-
56 0 ing this work.
40 140 84 0 97.14
56 4
Appendix A. Test system data
Table A.6
Conclusion UPFC transformers.
R [pu] X [pu]
This paper presented a new formulation for Distance Protection
Series 0.001 0.02
in transmission lines compensated by UPFC devices. The proposed
Shunt 0.001 0.02
formulation is adaptive and also compensates the fault resistance.
M.C.R. Paz et al. / Electrical Power and Energy Systems 73 (2015) 124–131 131
Table A.7
Parameters of transmission lines 1 and 3.