Professional Documents
Culture Documents
Technical Note
on
Synchronizing Panel
2nd Floor, Plot No.49 Patel Nagar , Cantonment ,Varanasi 221002(U.P.) India
Contact No. : 0542-2500156
Email: tcsvns@gmail.com
S.No. Content
1 What is DG Synchronizing?
2 Sequence of operation
3 DG Set synchronizing Panels
4 Application of parallel Operation
5 Advantage of parallel Operation
6 Type of Synchronizing Panel
7 Manual Synchronization
8 Auto Synchronization
9 PLC based DG synchronization
10 Engine Protection
11 Alternator Protection
12 Feature of PLC
13 Technical Specification
DG Synchronizing
DG Synchronizing System to be used to power saving and Start and Stop DG as per required
load in auto AMF function. From this system we can save fuel consumption of DG, wastage
of power, DG protection, auto load sharing. On AGC controller screen we can see the status of
system as below.
If voltage, frequency, Phase sequence/Phase angle, of both DG set is same & all the
required data is ok then Controller will start DG otherwise it will not start.
DG Synchronizing Panel System to be Start DG as per required load. Basically it
can be operated By Auto Mode and Manual Mode. As per required Load we can
change Consumption mode to 2nd DG will be start automatically and start load
sharing with already running 1st DG.
Auto Mains Failure (AMF): Auto mains failure means disconnecting the load from the
utility mains when the supply fails, automatic powering up of the DG set and feeding
the load from the DGs and vice-versa.
Load Dependent Start/Stop: Load depended Start/Stop is a functionality available in the
DG Controller, wherein the controller will decide the number of DGs to be continued
in service based on the present load in the system. If the load on the bus decreases below
the set value in the controller, the controller issues stop command to highest run hour
DG and vice-versa.
DG Synchronization Controller: It is a multi-functional programmable controller
used to control, monitor, and synchronize DGs. It also has functions for the protection
of engine and alternator. Each DG requires one controller for its operation. DG Sync.
Controller will have input terminals for accepting the voltage, current inputs from the
alternator and bus. Programmable discrete inputs of the DG Sync. Controller will be
provided with the feedback from generator circuit breaker, feedback from protective
relays, neutral isolating contactor, DG instrumentation sensors etc. for logical
functioning. Programmable output relays of the controller will be used for DG
Start/Stop, GCB Open/Close and Emergency Stop etc. Also, the controller will have
analog output ports for voltage/speed bias signals etc. Leading controllers available in
the market are from Woodward, DIEF, Deep Sea, Cummins PCC, SICES etc.
Electrically Operated ACBs for the Utility and DG Incomer feeders with under volt
coil, closing coil and shunt coil
Line Voltage Monitor
DG Sync. Controller
Current transformers in the alternator circuit and voltage inputs from alternator and
bus circuits
Basic electrical protective relays for the protection of alternator like Reverse/Reverse
reactive power relay, Earth fault relay, restricted earth fault relay/Differential
protection relay etc.
Temperature scanner for monitoring winding and bearing temperatures of the DG
(Optional based on the size of the rating of DG)
Battery charger circuit for DG battery
Instrumentation circuitry from DG to DG control panel for voltage bias, speed bias,
DG Start/Stop, RTD & BTD connection, High lube oil pressure, Oil temperature, Fuel
levels, Coolant temperature sensor, DC supply from battery charger to battery
Sequence of Operation:
For ease of understanding, we are discussing only about 2 nos. of DG sets syncing into a
common bus in AMF and Load dependent Start/Stop Mode.
Upon failure of the utility supply, the line voltage monitor gives feedback to all DG Sync.
Controllers. After preset time delay, the DG Sync. Controller gives Start command to
respective DG's starting circuit. Both the DGs will be started and upon healthy supply
feedback from DG (Rated Voltage and Frequency), the Controller issues close command to
first healthy DG's incoming breaker to close to the de-energized bus. This DG will be treated
as Master DG. Second DG breaker will be closed to the bus after matching the voltage and
frequency, upon getting close command from the respective controller. This DG will be
called Slave DG.
Controller keeps on watching the load in the system and tries to equalize the active and
reactive load on both the DGs equally by adjusting the engine speed governor and AVR. Both
these two DGs will run in synchronism for the pre-defined time sets in the controller. After
the pre-defined time is elapsed, the controller start initiates the load dependent Start/Stop
functionality.
If the total load on the bus goes less than the pre-defined value (Say 70% of DG Capacity)
sets in the controller, least run hour DG will run continuously, and the other DG's load will be
transferred to the previous one by the controller. After ensuring the transfer of whole load,
controller issue open command to second DG's breaker and accordingly the same will be
opened. Finally, second DG will be given stop command after running it for pre-defined
cooling period (Normally 3-5 Minutes). During the cooling period, if the load on the bus goes
high value set in the controller (Say >90%), the second DG will again come online after
satisfying the pre-requisite condition for synchronization as explained earlier.
When the utility supply is resumed, the LVM gives the feedback to the controller and the DG
breaker will be allowed to open after pre-defined time set in the controller (Say 15 Seconds).
After opening of the DG breakers, the EB breaker will be allowed to close automatically
through the electrical interlocking circuitry.
The whole process will complete within 15-30 seconds based on the number of DG sets and
the response time of engine.
At any point of time, if there is any internal or external fault in the system, the DG controller
will issue stop command to DG Set thereby shutdown the system.
While talking about the DG Synchronsiation, the need and working of neutral isolating
contactor cannot be unspoken.
When the alternators are paralleled, there always exists a small difference in the voltage
generated (Even though the RMS Voltages remains same) which will be different at different
points in time, this will cause a circulating current to flow between the machines. This
circulating current will be like a third harmonic current in nature, circulating through the
neutral circuit, will cause heating effects in the alternators and hence the effective loading
capacity of the alternators would be reduced.
Above situation could be eliminated by providing neutral isolating contactor (NIC) for all
DGs and connect only one NIC to bus at a time. The neutral of all the DGs are interconnected
in such a way that the neutral isolating contactor of only the highest capacity DG/Master DG
will be connected to the bus. NICs are also interlocked with the DG breakers and sequenced
in such manner that the NIC will be closed first followed by breaker. Also, reverse sequence
will be applied while opening the breaker. i e. breaker will be allowed to open first followed
by NIC. Arrangement will also made in the circuitry that in case the NIC of Master DG is
opened/damaged due to any reason, immediately the NIC of slave DG will come online and if
the same is not happened DG breaker is allowed to trip the circuit, as the system cannot be
made operational without neutral.
Though the article explains the DG synchronsing process in a simple way, the actual
operation and circuitry is much more complicated due to the presence of logical circuitry
using contactors and timers for different protective interlocking, protective and metering
circuits etc. Hence careful and diligent reasoning is essential for understanding the whole
system.
Theme & System Advantages
• Hotels Offices
• Institutions Etc
3
Advantages of DG sets in Parallel operations
• Fuel saving
• Manual synchronizing
• Automatic synchronizing
5
Manual Synchronizing- Types of Synchronizing panels
Syncroscope Lamps
Killo-Watt meter
Manual Synchronizing- Types of Synchronizing panels
Cont. …..
Protections relay
• Panel for synchronization of 4-6 nos. of dg set (250kva to 600kva) with AMF logic
can be supplied as per customer requirement i.e. automatic or manual.
PLC based DG Synchronization System
Isochronous Load Sharing
Unit A Unit B
1000 KW 800 KW
50 Hz 50 Hz
0 25 50 75 100 % 0 25 50 75 100 %
( 500 KW ) ( 400 KW )
Bump less Load Transfer
Gen 1
Gen 2
ISO LOAD
LOAD SHARING
Unload Gen 1 Initiated
Gen 2 Breaker
Opens ( Gen 1)
Gen1 Breaker
Gen 2 Closes ( Gen 2 ) TIME
Kirloskar Green Offers
• Automatic DG Synchronization
• Automatic Isochronous Load Sharing
• Bump less Load Transfer
• AMF Function
• Inbuilt Engine Protections
• Inbuilt Alternator Protections
• Load Management System
• Auxiliary Control
Synchronizing
• Over/Under Voltage
• Over/Under Frequency
• Reverse Power (Inverse Time Delay)
• Reverse KVAR
• Over Current (Inverse Time Delay)
• Load Surge
• Speed/Frequency Mismatch
Automatic Sequencing
• Easy to expand
– PCMCIA cards can be easily added to the Type I
PCMCIA slot on the front of the CPU, minimizing
maintenance time.
• Backup memory
– Program, constants, module parameters
– Easy field updates
DIRECT INTERFACE
Electronic
Governor
Faster Response
High Reliability
Adjustable Load/Unload ramps
Load Sharing
electronic keying
broken wire detection,
terminal block detection