High-efficiency

room air conditioners


UniflairTM air conditioners
designed for precision environmental
control of mission-critical applications

schneider-electric.com
Schneider Electric policy is one of continuous technological innovation and the Company therefore reserves
the right to amend any data herein without prior notice. The images shown in this catalog are for descriptive
purposes only. They may therefore differ from specific models that are selected. Some of the features described may
be available only for some models or configurations. Please refer to the specific technical literature for further details.

2 Life is On | Schneider Electric


Table of contents

Data center needs .............................................................................................Page 4

Uniflair ...............................................................................................................Page 6

Uniflair benefits..................................................................................................Page 8

Uniflair AM-LE configurations ............................................................................Page 11

Room air conditioners portfolio .........................................................................Page 17

Uniflair AM technical data sheets......................................................................Page 24

Uniflair LE technical data sheets .......................................................................Page 36

Uniflair CAP technical data sheets ....................................................................Page 80

Uniflair OCC technical data sheets ...................................................................Page 82

Uniflair Mobile telecom air conditioners ............................................................Page 84

Uniflair WM technical data sheets .....................................................................Page 86

Uniflair MB technical data sheets......................................................................Page 88

Uniflair SP technical data sheets.......................................................................Page 90

Active floor technical data sheets .....................................................................Page 91

Life is On | Schneider Electric 3


Flexibility
Modular and tailored solutions
for any application.

Availability
Continuous operation to safeguard
the customer’s business.

Energy saving
Technological excellence
for efficient performance.

4 Life is On | Schneider Electric


Secure power

Data center

Industry

Life is On | Schneider Electric 5


6 Life is On | Schneider Electric
Uniflair
Perimeter cooling for any data center environment,
with a low cost of ownership.
Uniflair AM and Uniflair LE are leading-edge precision cooling solutions specifically
designed to maintain temperature and humidity within extremely tight tolerances.

Perfect for racked and nonracked IT loads, these products meet the diverse
requirements of any data center environment. These intelligent units monitor
the status of components and environmental parameters to ensure correct
functionality during all modes of operation. When combined with hot-or-cold-aisle
containment solutions, Uniflair products can further improve efficiency and achieve
higher densities.

Life is On | Schneider Electric 7


Facing Data Center challenges
Keeping up with growing heat densities while reducing operating costs is today’s challenge.
Schneider Electric room air conditioners rise to this challenge because energy efficiency, avail-
ability, and flexibility are the priorities.

Efficiency and sustainability


Cooling accounts for up to 40% of the data center total
power. This means that high energy saving is a key
Modularity and flexibility
A simple and flexible infrastructure creates significant
advantage in terms of management costs.
30%*
of annual energy con-
factor in IT cooling and in precision air conditioning. sumption is reduced
Uniflair Room air conditioners achieve this by providing
thanks to innovative
Schneider Electric room air conditioners are designed
with the awareness that low energy consumption • A cooling systems that can be implemented over components like EC
is the result of an exhaustive analysis — from the time and that adapts automatically to the new load fans, VSD and tandem
choice of components to the constant refinement conditions of the room. compressors,
of design solutions. • Simple maintenance. The ease of maintenance of EEV valves, R-410A
Uniflair units is a fundamental factor in reducing refrigerant, and
Uniflair rooms air conditioners offer include
operating costs and avoiding downtime. AFPS systems.
• Free-cooling solutions (direct and indirect) to • Compact dimensions and simple handling/
reduce energy consumption leveraging on low installation. The high cost of space in high-tech
*Average value in a medium
outside air temperature. environments, requires precision air conditioning to data center in Europe.
• Variable Speed Drive technologies to save energy at have the smallest possible footprint and a full frontal
partial loads thanks to the continuous adjustment to component access to enable units to be installed next
load requirements. to each other or next to other equipment.

• Design for high temperature operation to benefit from

CapEx
recent increases in the ASHRAE recommended data
center operation temperature ranges
• Optimum design on heat exchangers to reach SHR
(sensible heat ratio) close to 1 and so to provide CapEx optimization
more useful (sensible) cooling capacity in the can be achieved by
same footprint. using a cooling infra-
• Optimized management system to have all structure that is simply
Schneider Electric cooling resources connected implemented and
for energy maximization based on real, adapted to changing
instantaneous load conditions. site requirements.

Cooling accounts for up to 40% of the data center total power.

8 Life is On | Schneider Electric


A wide range of configurations has been developed to
give maximum design freedom. Versatility, for Uniflair
units, means
Infrastructure management
Data centers are complex environments; providing
99.999%
complete systems composed of integrated elements is the reliability of Tier III
• Different fan configurations – fans in the box or guarantees and Tier IV data centers
underfloor - to cover a wide range of requirements according to Uptime
• full compatibility Institute certification
• Versions available with one or two independent
refrigerant circuits • a single source of responsibility standards. - Uniflair units
• strategic integration of a regulated system are Tier III and Tier IV
• Minimal footprint with frontal access for all
maintenance and minimal service clearance
ready design.
This is a situation where all of the operating parameters
• A control software that enables the units operation can be optimized (both energy and operational) through
to be adapted to every type of installation and to integrated logics (internal units, distribution systems,
communicate with a wide range of BMS systems and external units).

The cooling system must then be able to communicate


with the various building management systems. Uniflair
Reliability rooms air conditioners

A fundamental requirement for each data center is to • adapt to a wide range of supervision and network
guarantee continuous operation. languages and protocols

Reliability is achieved thanks to the design and • can easily interface with a wide range
implementation of cooling systems that are intrinsically of BMS systems
reliable and incorporate an appropriate level of

DCIM
redundancy.

System reliability is based upon several basic

Solutions
considerations, such as a dual source of cooling and
electrical power.

Uniflair units ensure reliability also through: To learn more about


Schneider Data Center
• Monitoring of all components
Infrastructure
• Precise and clear display of any malfunctions or management
abnormal operating conditions Solutions visit
• Management of emergency conditions with ability to www.apc.com/software
maintain basic cooling requirements

Life is On | Schneider Electric 9


Technologies built for
today’s challenges

10 Life is On | Schneider Electric


Total Control
Microprocessor control and display interface
Uniflair AM-LE units are equipped with sophisticated
controls and management software conceived,
developed, implemented, and tested by
Schneider Electric.

Every component of the unit is monitored in real


time, its performance optimized and kept within
design parameters.

New CW and DX air conditioning units are equipped


with the latest generation of graphic 7-inch. IT Touch
screen display interface.

Ultracapacitor Ultra Fan Speed Management


The Ultracapacitor module is an optional electronic Uniflair LE DX units can utilize different fan speed
device integrated in the units that provides temporary management logics to minimize energy consumption.
supply to the control in case of a lack of power. This When combined with an Active Flow Controller (AFC),
function minimizes the restart time of the units, the unit will automatically set the airflow according to
avoiding the reboot time of the microprocessor. the pressure setpoint required under the raised floor.

In case of power failure, capacitors release the stored Alternatively, the unit can adjust the airflow based on a
energy until it is not exhausted, the minimum time combination of the heat load in the room (related to the
ensured with the Ultracapacitor fully charged is two speed of inverter driven compressor) and the airflow
minutes. When power is reset, the capacitors start regulation from minimum to maximum.
re-charging.
MAX

Double power supply


New CW and DX units can be equipped with double
power supply with automatic commutation (upon
request to provide redundancy and to ensure a
Fan Speed

continuous service. Since the power supply is


MIN

equipped with an electromechanical changeover,


it can be connected to two separate electrical lines:
a main line and a secondary line connected to a
generator or emergency line.

MIN MAX
Cooling capacity

Life is On | Schneider Electric 11


Fans and airflow control
RadiCal EC fans 8

• Every component of Uniflair AM and LE ranges has 7 -39%


been chosen in accordance with the design criteria
6

Absorbed power [kW]


of energy saving for maximum efficiency. Just one
example is the selection of fans with electronically 5 -28%
-25% -24%
commutated (EC) direct current motor and blades -23% -23%-23%-22%
4 -22%
made of high tech compound material. This new
type of fan-motor combination offers a number of -16%-16%
3
advantages over traditional types:
2
• Lower power consumption on the fan side
1
• High part-load efficiency
• Lower noise level 0
22 24 33 39 52 63 76 83 100 113 132
• Fan speed adjustment via the microprocessor
Cooling capacity [kW]
control while the unit is running
• Ability to regulate airflow depending on the RadiCal EC fans
actual thermal load Traditional fans
% Energy Saving

Under Floor fans configuration


• Air conditioning units with fans located underneath
the floor allow for more coil area in the unit and less
internal air-side pressure drop. The fan module
beneath the unit can be configured in many different
airflow patterns as well as be placed beneath or
above the raised floor for total flexibility.
• More heat exchanger coil and less pressure drop
equals less power consumption and more capacity
inside a compact footprint.

160 +39%
Cooling capacity [kW]

120 +68%
+112%
80

40

0
Frame 5 Frame 6 Frame 7

Uniflair LE DX (TDAV) Uniflair LE DX with underfloor fans (IXAV)

Data refer to nominal conditions 45°C condensation, return air 24°C

160 +39%
Cooling capacity [kW]

Cooling Categories: 120 +68%


+112%
Chilled Water
80

Direct Expansion 40
12 Life is On | Schneider Electric
0
Frame 5 Frame 6 Frame 7
Active Flow Controller (AFC)
Maintaining correct pressurization of the floor space is
a key factor to ensure that the cooling system operates
with maximum efficiency and that cool air is available
where needed. This process must be guaranteed for the
entire lifetime of a server room that may be upgraded
and changed over time.

The Active Flow Controller (AFC), developed and


tested by Schneider Electric, enables structural
flexibility through automatic adjustment of the airflow
according to the servers that have been installed.
AFC automatically adjusts the airflow of the perimeter
units that are fitted with EC fans during standard and
emergency maintenance, maintaining a constant
pressure under the raised floor and avoiding the
creation of hot spots.

25
-45% -50%

-45%

20 -40%

-24%
-35%

15 -30%

-25%

10 -20%

-15%

0%
5 -10%

-5%

0 0%

70% 85% 100%


Room density %
Configuration without AFC
Configuration with AFC
% Savings with AFC

Active Floor
Active Floor is a flexible and modular system for cooling
data centres with medium- and high-density loads.
Integrated within a modular access floor in front of the
intake section of the rack, the Active Floor fits exactly
into a modular access floor panel measuring 600 mm
x 600 mm. The cold air produced by the Close Control
perimeter units is directly channeled to the source of the
thermal load thanks to the advanced adjustment of the
direction of the airflow.

The Active Floor creates a high-density bubble of air,


which is maintained at a constant temperature along the
whole intake section of the rack, guaranteeing operation
at the nominal design conditions. The airflow varies
according to the actual thermal load and is detected
by two sensors placed on the discharge section of
the servers.

Life is On | Schneider Electric 13


Compressor technologies
Variable speed brushless compressors
Uniflair LE units, series I**V, are equipped with latest
generation variable-speed drive scroll compressors.

These units have been developed in order to


improve further energy efficiency values of brushless
compressors and guarantee high efficiency level
at partial load conditions, compared to units with
fixed-speed or traditional variable capacity solutions.

In order to minimize the operative expense, air-cooled


units are naturally matched with condensers equipped
with EC fans.

Paris -31% Moscow -33%

Beijing -30%

Buenos Aires - 27%

Mumbai -21%

(*) Data calculated comparing IDAV2922 and TDAV3342 for 100 kW net sensible 37° return air

The new generation of inverter scroll compressors are 100


Permanent magnet motor efficiency

equipped with a brushless Interior Permanent Magnet


(IPM) and dedicated variable speed drive designed
to provide maximum efficiency across the full
operating range. 50

High motor efficiency means less heat transferred


from the motor to the refrigerant, providing better
compressor efficiency. 25

0
0 20 40 60 80 100

Speed (rps)

14 Life is On | Schneider Electric


Fixed speed compressors Intermediate Discharge Valves
The optimum combination between Schneider Electric The new generation of fixed speed scroll compressors
technology and new generation of fixed speed scroll is equipped with Intermediate Discharge Valves (IDVs)
compressors results in the following advantage for to mechanically reduce excessive compression of
LDAV units: refrigerant under part-load conditions while maintaining
the same cooling capacity.
• Extended operating map that permits higher
efficiency at high return air temperatures The IDVs adapt the effort of the motor to the pressure
conditions in the system opening when condensing
• No over compression losses
pressure and pressure ratio (part-load) fall below the
• Energy efficiency and seasonal built-in optimization point of the scroll.
efficiency improvement
The compressors equipped with IDVs provide better
• Low starting current
COP compared to compressors without these valves
• Low stress on mechanical parts and the size of this improvement depends on the
• Improved robustness of the complete unit outdoor air temperature.

• Service costs reduction

12
+11%
+10%
OOP improvement (%)

6 +6%
+4%
3
+1%
0
35˚C 30˚C 25˚C 20˚C 15˚C

Outdoor ambient temperature (˚C)

Non-return valve
The non-return valve is integrated in the compressors of
LDAV3822 while on the other LDAV units it’s installed in
the refrigerant circuit. The scope of the non-return valve
is to avoid the refrigerant migration from high-pressure
to low-pressure side after compressor is switched off.

Life is On | Schneider Electric 15


Tandem operation
Main features
In many applications the room load can vary
enormously during the course of a single day or from
season to season. This will cause wide variations in the
amount of cooling required at any given moment. In
these circumstances it is very important to use precision
air conditioning units that are highly energy efficient at
part load.

Uniflair LE models (with suffix **21, **42) are equipped


with two compressors operating in parallel on the same
circuit in order to offer two stages of cooling on a single
circuit of refrigeration.

As the evaporator coil surface area (designed for the


capacity of two compressors) is fixed, one single
compressor in operation (Fig. B) benefits from the
availability of a “double sized” evaporator coil. This
maximization of the cooling effect leads to increases
in part load efficiencies and a rise in the part load (W100%x COP100%) + (W75%x COP75%) + (W50%x COP50%) + (W25%x COP25%)
coefficient of performance (COP).
100

A. 100% full load operation B. Partial load operation

16 Life is On | Schneider Electric


Refrigerant circuit
Refrigerant R-410A Electronic expansion valves
R-410A is similar to a mono-component refrigerant Electronic expansion valves (EEVs) are integrated
(which is near azeotropic), as it is characterized by with the microprocessor range in all Uniflair models
the absence of glide during the change of state. to provide highly efficient electronic control of the
flow of refrigerant.
Thanks to a greater heat exchange capacity and a
notable decrease in pressure drops, it is possible The EEV provides accurate control of the refrigerant
to maximize the size of the exchangers, while superheat to ensure an increase in the COP at low
increasing efficiency. external temperatures; it enables the unit to operate
at much lower condensing pressures than would
• Summarizing the main advantages of R410A be possible with a traditional mechanical valve. The
compared to R407C are: dehumidification function is also controlled through
• R410A has a lower Global Warming Potential index1. the operation of the EEV.
• Units with R410A provide better energy efficiency.
• R410A is not affected by “temperature glide”,
featuring better performances in terms of cooling
capacity and service lifetime.

Percentage annual reduction in energy consumption of


-9.0%
a unit fitted with EEV compared to a traditional version
(cooling capacity: 60 kW, space conditions: 24 °C, 50%
RH at constant load, TDAV1822A + 2 x CAP0801).
-8.0% -8.3% -8.9%
-8.6%
-7.8%

-6.9%

-6.9%

-5.6%
-6.4%
-4.1%

1. GWP (Global Warming Potential) is an index based on CO2 equivalent


tons to measure the impact of a greenhouse gas on the atmosphere

Life is On | Schneider Electric 17


Free-cooling choices
Direct free-cooling
The direct free-cooling is comprised of an air
conditioning unit equipped with a free-cooling plenum
with dampers in order to manage the external air,
the return air from the room and their blending when
necessary.

Direct free-cooling mode leverages on the outdoor


temperature in moderate climate areas. The external
air enters directly the data center removing the
thermal load provided by the IT equipment. The air
must be treated before entering the data center by
means filtration and humidification systems in order to
guarantee the right quality level of the air.

Direct free-cooling operating modes

1 External temperature higher than


the setpoint
The damper is open and the external air enters into
the unit, compressors are switched on to provide
the additional cooling load necessary to reach the
temperature requirement.

2 External temperature between the setpoint


and antifreeze temperature
The damper is open and compressors are switched
off. The external air is cold enough to achieve the
required temperature setpoint, therefore it flows
through the filters and enters directly into the room.

3 External temperature below the antifreeze


temperature
The damper is open and compressors are switched
off. Since the external air temperature is too low, it
is necessary to recirculate the hot air from the Data
Center. The hot air is mixed with external cold air to
provide the required setpoint temperature.

18 Life is On | Schneider Electric


Indirect free-cooling Energy saving units (LDEV, I*EV)
The indirect free-cooling operation leverage on free- Free-cooling is provided without the need to operate
cooling effect when the outdoor temperature is low compressors and does not depend upon pulling
enough to minimize energy consumption and it is not outside air into the space (indirect free-cooling). This
dependent on the quality of the outdoor air since it does guarantees stable humidity and air quality in the space.
not enters directly the data center.
New energy saving units are design to operate in three
different modes (Fig. a, b and c)

The main advantage of the new Patent Pending Solution


is the use of three flow control valves to minimize the
pressure drops.

Fig. a) Mechanical mode Fig. a) Hybrid mode Fig. a) Free-cooling mode

A worldwide perspective: London -31%


Indirect Free-cooling Stockolm -31%
Frankfurt -29%
Paris -29%
(*) Data calculated comparing Moscow -30%
a DX air-cooled unit IXAV4022
and an energy saving unit
IXEV4022, pump consumption
included. 100 kW net sensible
cooling capacity, 35° return air,
30% rH and 30% glycol

Shanghai -17%

Sydney -23%

Buenos Aires -22%

Johannesburg -26%

Chilled water units (L*CV, HDCV) coupled


with free-cooling chillers
Chilled water systems can leverage on the outdoor
temperature to reduce the energy consumption during
the year. In this case the free cooling effect is provided
by the free-cooling coils of chillers.

Life is On | Schneider Electric 19


Designed for
optimum temperatures
ASHRAE Guidelines Discharge temperature control
ASHRAE guidelines permit to operate with higher The control algorithm provides proportional and integral
operating temperatures in order to maximize regulation on the discharge temperature of the CRAC
system efficiency. unit, which manages the regulation of the on-board
three-way valve (chilled water units) or of the speed
Air conditioning units are designed for discharge of the inverter-driven compressor (VSD DX units).
temperature and moisture control and are optimized
according to the recommended water temperature
range and a higher delta T.

High temperature applications


Chilled water units
Room air conditioners offer:

• Part of the range optimized for high water temperatures and discharge temperature control.
• Part of the range optimized for traditional water temperatures.
The optimized design for high Delta T enables to have less consumption on yearly base compared to a unit not optimized.

-22%

-35%

Traditional Traditional Adiabatic Traditional Adiabatic


free-cooling 18/24˚C, free-cooling free-cooling free-cooling free-cooling
unit not optimized 18/24˚C 18/24˚C 18/28˚C 18/28˚C

Direct expansion units


Latest DX generation optimized for high air temperature operation allows:

• +43% cooling capacity in the box with the same power consumption compared to traditional working conditions
• +29% cooling capacity compared to traditional design at the same conditions

+43% +43% +29% +29%


Cooling capacity

Cooling capacity

Cooling capacity

Lagacy Lagacy
Gen 2 Gen 2 Not Optimized Not Optimized
Gen 2 Gen 2

20 Life is On | Schneider Electric


Optimized management
Optimized management
Management of the whole system allows energy
consumption to be optimized and integrated control
strategies to be implemented, which would otherwise
not be possible.

All the Schneider Electric cooling resources can be


linked together in a network to maximize the operating
parameters and the current required. Row and room
cooling units communicate to the chiller, reducing the
energy requirement by means of a “tracking logic” for
the current thermal load.

The chilled water temperature varies dynamically to


minimize compressor consumption and maximize the
use of free-cooling, while maintaining the optimum
temperature in the data center.

How it works

6.0 25
Water Temperature (˚C)

5.0
Energy Efficiency (%)

20

4.0
15
3.0
10
2.0

5
1.0 EER
0 0 Operating Water Temperature
Min Medium Medium Max
Load Load Load Load
Number of units ON

Energy saving improvement


Summer Winter

+28% +39%

+20% +42%
+0% +0%
EER

EER

Min Med Tot Min Med Tot


Load Load

With optimized management


Traditional

Comparison between Summer mode external Free-cooling external Load variation:


a traditional solution temperaturre: 35°C temperature: 8°C 100 kW - 300kW
and an optimized
management logic: Water set point: 12°C

Life is On | Schneider Electric 21


External Condenser
technology
EC fans
The external condenser can be equipped with AC axial
fans or electronically commutated (EC) axial fans.

The regulator works via Modbus commands that allow


the controller to manage all parameters.

Low ambient operation


Uniflair DX air-cooled units can be equipped with a kit
applicable to the external condenser to allow operation
down to -40°C.

The low temperature kit includes a liquid receiver and


flooding valve to control the condensing temperature,
both fit within the overall dimensions of the unit
including leg kits.

The fan speed regulator varies the speed of the fan


motor to maintain constant condensation pressure.
In low temperature condensers, the regulator is
installed inside the indoor cooling unit.

Microchannel coils
The new generation of external condensers can
be equipped with microchannel condensing coils
to reduce the refrigerant charge and minimize
air-side pressure drops.

22 Life is On | Schneider Electric


Room cooling offer overview
Uniflair AM Uniflair LE

5kW 20kW 140kW 250kW


CHILLED WATER

SUCV-SUCC* (Upflow) LUCV (Upflow)


SDCV-SDCC* (Downflow) LDCV (Downflow)

HDCV (Downflow with Underfloor fans)

Uniflair AM Uniflair LE

5kW 20kW 60kW 160kW

Air cooled Air cooled Air cooled


SUAV-SUAC* (Upflow) TUAR-TUAV** (Upflow) LDAV (Downflow)
FIXED SPEED COMPRESSORS

SDAV-SDAC* (Downflow) TDAR-TDAV*(Downflow)


Water cooled Water cooled
TUWR-TUWV* (Upflow) LDWV (Downflow)
Water cooled TDWR-TDWV* (Downflow)
SUWV-SUWC* (Upflow) Energy saving
SDWV-SDWC* (Downflow) Energy saving
TUER-TUEV** (Upflow)
LDEV (Downflow)
TDER-TDEV*(Downflow)
DIRECT EXPANSION

Twin cool air-cooled


TUTR-TUTV* (Upflow)
TDTR-TDTV* (Downflow)
Twin cool water-cooled
TUDR-TUDV* (Upflow)
TDDR-TDDV* (Downflow)

5kW 50kW 160kW


VARIABLE SPEED COMPRESSORS

Air cooled Air Cooled


IDAV (Downflow) IUAV (Upflow)
IDAV (Downflow)
IXAV (Underfloor)

Water cooled
IUWV (Upflow)
IDWV (Downflow)
IXWV (Underfloor)

Energy Saving
IUEV (Upflow)
IDEV (Downflow)
IXEV (Underfloor)

*V suffix = Electronically Commuted (EC) motor fans;C/ R suffix = backward-curved fans with asynchronous motor;

Life is On | Schneider Electric 23


Direct-expansion air-cooled units with asynchronous motor fans

Uniflair AM
SDAC – SUAC

Range
Cooling capacity: 5 ÷ 20 kW
Refrigerant R-410A
Available versions
• Downflow (SDAC)
• Upflow (SUAC) with bottom, front, and rear suction

Standard features
• Advanced microprocessor control system is • Total front access is available for unit maintenance.
included with local or remote user terminal. • Electrical panel is situated in a compartment
• The units are equipped with forward-curved fans separated from the airflow and complies with
and directly coupled asynchronous motor. the Machinery Directive 2006/42/EC (MD)
• The structure of the unit is characterized by directive and related standards.
a self-supporting frame in galvanized steel with • Microprocessor control system includes:
panels. The external panels are coated with - Local user terminal with external accessibility
RAL9003 epoxy-polyester paint and internally - Integrated LAN card for local network connection
lined with heat- and sound-proofing insulation. of a group of CRACs
• The cooling coil is designed for an elevated SHR - Rotation and active stand-by management
and reduced pressure drops in the air section. - Free contact for general alarm and two
The coil is made from copper tubes mechanically for addressable alarms
expanded on aluminum fins, complete with - Remote on/off switch
a hydrophilic treatment.
- Ability to interface with modbus protocol
• Uniflair AM units are in conformity with the following directly on RS485 serial card
directives: Machinery Directive 2006/42/EC (MD),
- Ability to interface with main external communication
Electromagnetic compatibility Directive 2014/30/EU
protocols: BACnetTM, Lonworks, Trend, Metasys,
(EMC), Pressure equipment Directive 2014/68/EU
TCP/IP, SNMP, and StruxureWareTM platform
(PED), Regulation (EU) No 517/2014 on fluorinated
greenhouse gases (F-GAS).
• High-efficiency, EU4-pleated air filters are housed
in a metal frame and equipped with a dirty filter
differential pressure switch and low airflow differential
pressure switch.

24 Life is On | Schneider Electric


TECHNICAL DATA
1
Gross cooling
capacities; fans must
SDAC – SUAC MODEL 0151B 0251B 0151A 0251A 0331A 0351A 0501A 0601A
be deduced to obtain
Fan type Forward-curved centrifugal motor fan
net cooling data.
Power supply V/ph/Hz 230/1/50 400/3/50
Fans nr. 1 1 1 1 2 2 2 2 2
Data refers to nominal
Airflow m3/h 1600 1750 1600 1750 3000 3300 4500 4500 conditions: Room
N° of compressors 1 1 1 1 1 1 1 1 at 24 °C-50% RH,
45 °C condensing
Refrigerating circuits 1 1 1 1 1 1 1 1
temperature,
Gross total cooling
kW 6,6 8,0 6,4 7,9 10,0 13,3 16,9 18,8 and ESP = 20 Pa.
capacity1,2
Gross sensible cooling
kW 5,3 6,1 5,2 6,0 9,1 10,6 14,4 15,4
capacity1,2
DIMENSIONS
Height mm 1740 1740 1740 1740 1740 1740 1740 1740
Length mm 550 550 550 550 850 850 1200 1200
Depth mm 450 450 450 450 450 450 450 450

Construction options Accessories


• Immersed electrode humidifier (D/U versions) The units can be supplied with the following external accessories:
• Low surface temperature electrical heaters with
• Remote, semi-graphic user terminal
extended fans, complete with safety thermostat
and manual resetting (T/H versions) • RS485 serial adapter to communicate with external BMS
• Hot gas and hot water reheating • LON FTT10 serial adapter to communicate with external BMS
managed with LON protocol
• Electronic expansion valve is controlled by the
microprocessor and a dedicated software that • TCP/IP serial adapter to communicate with external BMS
increases the precision of the cooling and managed with SNMP protocol
the energy efficiency of the cooling cycle • AFPS that can be adapted as a kit with installation instructions
• Motorized damper
• Condensate drain pump
• Suction from the top or front discharge plenums
• Adjustable floor stands

Life is On | Schneider Electric 25


Direct-expansion air-cooled units with EC motor fans

Uniflair AM
SDAV – SUAV

Range
Cooling capacity: 5 ÷ 20 kW
Refrigerant R-410A
EC fans
Available versions
• Downflow (SDAV)
• Upflow (SUAV) with bottom, front, and rear suction

Standard features
• Advanced microprocessor control system is • Total front access is available for unit maintenance.
included with local or remote user terminal. • Electrical panel is situated in a compartment
• The units are equipped with EC fans for separate from the airflow and in compliance with
efficiency maximization. the Machinery Directive 2006/42/EC (MD) directive
• The structure of the unit is characterized by and related standards.
a self-supporting frame in galvanized steel with • Microprocessor control system includes:
panels. The external panels are coated with - Local user terminal with external accessibility
RAL9003 epoxy-polyester paint and internally - Integrated LAN card for local network connection
lined with heat- and sound-proofing insulation. of a group of CRACs
• The cooling coil is designed for an elevated SHR - Rotation and active stand-by management
and reduced pressure drops in the air section. - Free contact for general alarm and two for
The coil is made from copper tubes mechanically addressable alarms
expanded on aluminum fins, complete with - Remote on/off switch
a hydrophilic treatment.
- Ability to interface with modbus protocol
• Uniflair AM units are in conformity with the following directly on RS485 serial card
directives: Machinery Directive 2006/42/EC (MD),
- Ability to interface with main external communication
Electromagnetic compatibility Directive 2014/30/EU
protocols: BACnet, Lonworks, Trend, Metasys,
(EMC), Pressure equipment Directive 2014/68/EU
TCP/IP, SNMP, and StruxureWare platform
(PED), Regulation (EU) No 517/2014 on fluorinated
greenhouse gases (F-GAS).
• High-efficiency, EU4-pleated air filters are housed
in a metal frame and equipped with a dirty filter
differential pressure switch and low airflow differential
pressure switch.

26 Life is On | Schneider Electric


TECHNICAL DATA
1
Gross cooling
capacities; fans must
SDAV – SUAV MODEL 0151B 0251B 0151A 0251A 0331A 0351A 0501A 0601A
be deduced to obtain
Fan type EC backward-curved centrifugal motor fan net cooling data.
Power supply V/ph/Hz 230/1/50 400/3/50
Fans nr. 1 1 1 1 2 2 2 2 2
Data refers to nominal
Airflow m3/h 1600 1750 1600 1750 3000 3300 4500 4500 conditions: Room
N° of compressors 1 1 1 1 1 1 1 1 at 24 °C-50% RH,
45 °C condensing
Refrigerating circuits 1 1 1 1 1 1 1 1
temperature,
Gross total cooling
kW 6,4 8,0 6,4 7,9 10,0 13,3 16,9 18,8 and ESP = 20 Pa.
capacity1,2
Gross sensible cooling
kW 5,2 6,1 5,2 6,0 9,1 10,6 14,4 15,4
capacity1,2
DIMENSIONS
Height mm 1740 1740 1740 1740 1740 1740 1740 1740
Length mm 550 550 550 550 850 850 1200 1200
Depth mm 450 450 450 450 450 450 450 450

Construction options Accessories


• Immersed electrode humidifier (D/U versions) The units can be supplied with the following external accessories:
• Low surface temperature electrical heaters with
• Remote, semi-graphic user terminal
extended fans, complete with safety thermostat
and manual resetting (T/H versions) • RS485 serial adapter to communicate with external BMS
• Hot gas and hot water reheating • LON FTT10 serial adapter to communicate with external BMS
managed with LON protocol
• Electronic expansion valve is controlled
by the microprocessor and a dedicated software • TCP/IP serial adapter to communicate with external BMS
that increases the precision of the cooling managed with SNMP protocol
and the energy efficiency of the cooling cycle • AFPS that can be adapted as a kit with installation instructions
• Motorized damper
• Condensate drain pump
• Suction from the top or front discharge plenums
• Adjustable floor stands

Life is On | Schneider Electric 27


Direct-expansion water-cooled units with asynchronous motor fans

Uniflair AM
SDWC – SUWC

Range
Cooling capacity: 5 ÷ 20 kW
Refrigerant R-410A
Available versions
• Downflow (SDWC)
• Upflow (SUWC) with bottom, front, and rear suction

Standard features
• Advanced microprocessor control system is • Total front access is available for unit maintenance.
included with local or remote user terminal. • The electrical panel is situated in a compartment separated
• The units are equipped with forward-curved fans from the airflow and complies with the Machinery Directive
and directly coupled asynchronous motor. 2006/42/EC (MD) directive and related standards.
• The structure of the unit is characterized by • Microprocessor control system includes:
a self-supporting frame in galvanized steel with - Local user terminal with external accessibility
panels. The external panels are coated with - Integrated LAN card for local network connection
RAL9003 epoxy-polyester paint and internally of a group of CRACs
lined with heat- and sound-proofing insulation. - Rotation and active stand-by management
• The cooling coil is designed for an elevated SHR - Free contact for general and two for addressable alarms
and reduced pressure drops in the air section. - Remote on/off switch
The coil is made from copper tubes mechanically
- Ability to interface with modbus protocol
expanded on aluminum fins, complete with
directly on RS485 serial card
a hydrophilic treatment.
- Ability to interface with main external communication
• Uniflair AM units are in conformity with the following
protocols: BACnet,Lonworks, Trend, Metasys,
directives: Machinery Directive 2006/42/EC (MD),
TCP/IP, SNMP, and StruxureWare platform
Electromagnetic compatibility Directive 2014/30/EU
(EMC), Pressure equipment Directive 2014/68/EU
(PED), Regulation (EU) No 517/2014 on fluorinated
greenhouse gases (F-GAS).
• High-efficiency, EU4-pleated air filters are housed
in a metal frame and equipped with a dirty filter
differential pressure switch and low airflow differential
pressure switch.

28 Life is On | Schneider Electric


TECHNICAL DATA
1
Gross cooling
capacities; fans
SDWC – SUWC MODEL 0151B 0251B 0151A 0251A 0331A 0351A 0501A 0601A
must be deduced
Fan type Forward-curved centrifugal motor fan
to obtain net
Power supply V/ph/Hz 230/1/50 400/3/50 cooling data.
Fans nr. 1 1 1 1 2 2 2 2
Airflow m3/h 1600 1750 1600 1750 3000 3300 4500 4500 2
Data refers to nominal
N° of compressors 1 1 1 1 1 1 1 1 conditions: Room
at 24 °C-50% RH,
Refrigerating circuits 1 1 1 1 1 1 1 1
water temperatures
Gross total cooling
kW 6,9 8,3 6,9 8,3 9,8 13,6 17,7 19,4 30 – 35 °C,
capacity1,2 and ESP = 20 Pa.
Gross sensible cooling
kW 5,4 6,2 5,4 6,2 8,7 10,6 14,7 15,6
capacity1,2
DIMENSIONS
Height mm 1740 1740 1740 1740 1740 1740 1740 1740
Length mm 550 550 550 550 850 850 1200 1200
Depth mm 450 450 450 450 450 450 450 450

Construction options Accessories


• Immersed electrode humidifier (D/U versions) The units can be supplied with the following external accessories:
• Low surface temperature electrical heaters with
• Remote, semi-graphic user terminal
extended fans, complete with safety thermostat
and manual resetting (T/H versions) • RS485 serial adapter to communicate with external BMS
• Hot gas and hot water reheating • LON FTT10 serial adapter to communicate with external BMS
managed with LON protocol
• Electronic expansion valve is controlled by the
microprocessor and a dedicated software that • TCP/IP serial adapter to communicate with external BMS
increases the precision of the cooling and the managed with SNMP protocol
energy efficiency of the cooling cycle • Motorized damper
• Condensate drain pump
• Suction from the top or front discharge plenums
• Adjustable floor stands

Life is On | Schneider Electric 29


Direct-expansion water-cooled units with EC motor fans

Uniflair AM
SDWV – SUWV

Range
Cooling capacity: 5 ÷ 20 kW
Refrigerant R-410A
EC fans
Available versions
• Downflow (SDWV)
• Upflow (SUWV) with bottom, front, and rear suction

Standard features
• Advanced microprocessor control system is • Total front access is available for unit maintenance.
included with local or remote user terminal. • The electrical panel is situated in a compartment
• The units are equipped with EC fans for separated from the airflow and complies with
efficiency maximization. the Machinery Directive 2006/42/EC (MD) directive
• The structure of the unit is characterized by and related standards.
a self-supporting frame in galvanized steel with • Microprocessor control system includes:
panels. The external panels are coated with - Local user terminal with external accessibility
RAL9003 epoxy-polyester paint and internally - Integrated LAN card for local network connection
lined with heat- and sound-proofing insulation. of a group of CRACs
• The cooling coil is designed for an elevated SHR - Rotation and active stand-by management
and reduced pressure drops in the air section. - Free contact for general and two for addressable alarms
The coil is made from copper tubes mechanically - Remote on/off switch
expanded on aluminum fins, complete with - Ability to interface with modbus protocol
a hydrophilic treatment. directly on RS485 serial card
• Uniflair AM units are in conformity with the following - Ability to interface with main external communication
directives: Machinery Directive 2006/42/EC (MD), protocols: BACnet, Lonworks, Trend, Metasys,
Electromagnetic compatibility Directive 2014/30/EU TCP/IP, SNMP, and StruxureWare platform
(EMC), Pressure equipment Directive 2014/68/EU
(PED), Regulation (EU) No 517/2014 on fluorinated
greenhouse gases (F-GAS).
• High-efficiency, EU4-pleated air filters are housed
in a metal frame and equipped with a dirty filter
differential pressure switch and low airflow differential
pressure switch.

30 Life is On | Schneider Electric


TECHNICAL DATA
1
Gross cooling
capacities; fans
SDWV – SUWV MODEL 0151B 0251B 0151A 0251A 0331A 0351A 0501A 0601A
must be deduced
Fan type EC backward-curved centrifugal motor fan
to obtain net
Power supply V/ph/Hz 230/1/50 400/3/50 cooling data.
Fans nr. 1 1 1 1 2 2 2 2
Airflow m3/h 1600 1750 1600 1750 3000 3300 4500 4500 2
Data refers to nominal
N° of compressors 1 1 1 1 1 1 1 1 conditions: Room
at 24 °C-50% RH,
Refrigerating circuits 1 1 1 1 1 1 1 1
water temperatures
Gross total cooling
kW 6,9 8,4 6,9 8,3 9,8 13,6 17,7 19,4 30 – 35 °C,
capacity1,2 and ESP = 20 Pa.
Gross sensible cooling
kW 5,4 6,2 5,4 6,2 8,7 10,6 14,7 15,6
capacity1,2
DIMENSIONS
Height mm 1740 1740 1740 1740 1740 1740 1740 1740
Length mm 550 550 550 550 850 850 1200 1200
Depth mm 450 450 450 450 450 450 450 450

Construction options Accessories


• Immersed electrode humidifier (D/U versions) The units can be supplied with the followingexternal accessories:
• Low surface temperature electrical heaters with
• Remote, semi-graphic user terminal
extended fans, complete with safety thermostat
and manual resetting (T/H versions) • RS485 serial adapter to communicate with external BMS
• Hot gas and hot water reheating • LON FTT10 serial adapter to communicate with external BMS
managed with LON protocol
• Electronic expansion valve is controlled
by the microprocessor and a dedicated software • TCP/IP serial adapter to communicate with external BMS
that increases the precision of the cooling managed with SNMP protocol
and the energy efficiency of the cooling cycle • Motorized damper
• Condensate drain pump
• Suction from the top or front discharge plenums
• Adjustable floor stands

Life is On | Schneider Electric 31


CW units with asynchronous motor fans

Uniflair AM
SDCC – SUCC

Range
Cooling capacity: 5 ÷ 20 kW
Refrigerant CW
Available versions
• Downflow (SDCC)
• Upflow (SUCC) with bottom, front, and rear suction

Standard features
• Advanced microprocessor control system is • Total front access is available for unit maintenance.
available with local or remote user terminal. • The electrical panel is situated in a compartment
• The units are equipped with forward-curved fans separated from the airflow and complies
with directly coupled asynchronous motor. with the Machinery Directive 2006/42/EC (MD),
• The structure of the unit is characterized by Regulation (EU) No 517/2014 on fluorinated greenhouse
a self-supporting frame in galvanized steel gases (F-GAS) directive and related standards.
with panels. The external panels are coated with • Microprocessor control system includes:
RAL9003 epoxy-polyester paint and internally - Local user terminal with external accessibility
lined with heat- and sound-proofing insulation. - Integrated LAN card for local network connection of
• The unit can be selected with a two-way a group of CRACs
or three-way valve and an actuator - Rotation and active stand-by management
integrated with the microprocessor. - Free contact for general and two for addressable alarms
• The cooling coil is designed for an elevated SHR - Remote on/off switch
and reduced pressure drops in the air section. - Ability to interface with modbus protocol
The coil is made from copper tubes mechanically directly on RS485 serial card
expanded on aluminum fins, complete with
- Ability to interface with main external communication
a hydrophilic treatment.
protocols: BACnet, Lonworks, Trend, Metasys,TCP/IP,
• High-efficiency, EU4-pleated air filters are housed SNMP, and StruxureWare platform
in a metal frame and equipped with a dirty filter
differential pressure switch and low airflow
differential pressure switch.

32 Life is On | Schneider Electric


TECHNICAL DATA
1
Gross cooling
capacities; fans
SDCC – SUCC MODEL 0200A 3
0250A 3
0300A 3
0400A 3
0600A 3
must be deduced
Fan type Forward-curved centrifugal motor fan
to obtain net
Power supply V/ph/Hz 400/3/50 cooling data.
Fans nr. 1 1 1 2 2
Airflow m3/h 1600 2300 2300 3350 4500 2
Data refers to nominal
Gross total cooling conditions: Room
kW 7,2 10,0 11,3 14,1 20,6 at 24 °C-50% RH,
capacity1,2
water temperature
Gross sensible cooling 7/12 °C, glycol 0%,
kW 6,4 8,9 9,9 12,9 18,2
capacity1,2 and ESP = 20 Pa.
DIMENSIONS 3
Equipped with standard
Height mm 1740 1740 1740 1740 1740 electrical heaters.
Length mm 550 850 850 850 1200
Depth mm 450 450 450 450 450
SDCC – SUCC MODEL 0200B 0250B 0300B 0400B 0600B
Fan type Forward-curved centrifugal motor fan
Power supply V/ph/Hz 230/1/50
Fans 1 1 1 2 2
Airflow m3/h 1600 2300 2300 3350 4500
Gross total cooling
kW 7,2 10,0 11,3 14,1 20,6
capacity1,2
Gross sensible cooling
kW 6,4 8,9 9,9 12,9 18,2
capacity1,2
DIMENSIONS
Height mm 1740 1740 1740 1740 1740
Length mm 550 850 850 850 1200
Depth mm 450 450 450 450 450

Construction options Accessories


• Double power supply with automatic, integrated The units can be supplied with the following external accessories:
management on the active line
• Remote, semi-graphic user terminal
• Immersed electrode humidifier (D/U versions)
• RS485 serial adapter to communicate with external BMS
• Low surface temperature electrical heaters with
extended fans, complete with double safety • LON FTT10 serial adapter to communicate with external BMS
thermostat and manual resetting (T/H versions) managed with LON protocol
• Discharge temperature sensor integrated with the • TCP/IP serial adapter to communicate with external BMS
microprocessor to grant discharge temperature managed with SNMP protocol
control; in combination with D and U version, • Motorized damper
moisture control can be selected • Suction from the top or front discharge plenums
• Adjustable floor stands

Life is On | Schneider Electric 33


CW units with EC motor fans

Uniflair AM
SDCV – SUCV

Range
Cooling capacity: 5 ÷ 20 kW
Refrigerant CW
EC fans
Available versions
• Downflow (SDCV)
• Upflow (SUCV) with bottom, front, and rear suction

Standard features
• Advanced microprocessor control system is • Total front access is included for unit maintenance.
available with local or remote user terminal. • The electrical panel is situated in a compartment separated
• The units are equipped with EC fans from the airflow and complies with the Machinery Directive
for efficiency maximization. 2006/42/EC (MD), Regulation (EU) No 517/2014 on fluorinated
• The structure of the unit is characterized by greenhouse gases (F-GAS) directive and related standards.
a self-supporting frame in galvanized steel with • Microprocessor control system includes:
panels. The external panels are coated with - Local user terminal with external accessibility
RAL9003 epoxy-polyester paint and internally - Integrated LAN card for local network connection
lined with heat- and sound-proofing insulation. of a group of CRACs
• The unit can be selected with a two-way - Rotation and active stand-by management
or three-way valve and an actuator - Free contact for general and two for addressable alarms
integrated with the microprocessor. - Remote on/off switch
• The cooling coil is designed for an elevated SHR - Ability to interface with modbus protocol
and reduced pressure drops in the air section. directly on RS485 serial card
The coil is made from copper tubes mechanically
- Ability to interface with main external communication protocols:
expanded on aluminum fins, complete with
BACnet, Lonworks, Trend, Metasys,
a hydrophilic treatment.
TCP/IP, SNMP, and StruxureWare platform
• High-efficiency, EU4-pleated air filters are housed
in a metal frame and equipped with a dirty filter
differential pressure switch and low airflow
differential pressure switch.

34 Life is On | Schneider Electric


TECHNICAL DATA
1
Gross cooling
capacities; fans
SDCV – SUCV MODEL 0200A 3
0250A 3
0300A 3
0400A 3
0600A 3
must be deduced
Fan type EC backward-curved centrifugal motor fan
to obtain net
Power supply V/ph/Hz 400/3/50 cooling datas.
Fans nr. 1 1 1 2 2
Airflow m3/h 1600 2100 2100 3350 5000 2
Data refer to nominal
Gross total cooling conditions: Room
kW 7,2 9,4 10,6 14,1 22,1 at 24 °C-50% RH,
capacity1,2
water temperature
Gross sensible cooling
kW 6,4 8,3 9,2 12,9 19,7 7/12 °C, glycol 0%,
capacity1,2 and ESP = 20 Pa.
DIMENSIONS
3
Equipped with standard
Height mm 1740 1740 1740 1740 1740 electrical heaters.
Length mm 550 850 850 850 1200
Depth mm 450 450 450 450 450
SDCV – SUCV MODEL 0200B 0250B 0300B 0400B 0600B
Fan type EC backward-curved centrifugal motor fan
Power supply V/ph/Hz 230/1/50
Fans 1 1 1 2 2
Airflow m3/h 1600 2100 2100 3350 5000
Gross total cooling
kW 7,2 9,4 10,6 14,1 22,1
capacity1,2
Gross sensible cooling
kW 6,4 8,3 9,2 12,9 19,7
capacity1,2
DIMENSIONS
Height mm 1740 1740 1740 1740 1740
Length mm 550 850 850 850 1200
Depth mm 450 450 450 450 450

Construction options Accessories


• Double power supply with automatic, integrated The units can be supplied with the following external accessories:
management on the active line
• Remote, semi-graphic user terminal
• Immersed electrode humidifier (D/U versions)
• RS485 serial adapter to communicate with external BMS
• Low surface temperature electrical heaters
with extended fans, complete with double safety • LON FTT10 serial adapter to communicate with external BMS
thermostat and manual resetting (T/H versions) managed with LON protocol
• Discharge temperature sensor integrated with the • TCP/IP serial adapter to communicate with external BMS
microprocessor to allow discharge temperature managed with SNMP protocol
control; in combination with D and U version can be • AFPS that can be adapted as a kit with installation instructions
selected moisture control • Motorized damper
• Suction from the top or front discharge plenums
• Adjustable floor stands

Life is On | Schneider Electric 35


CW units with backward-curved fans equipped with EC motor

Uniflair LE
LDCV – LUCV

Range
Cooling capacity: 20 ÷ 170 kW
Refrigerant CW
EC fans
Available versions
• Downflow (LDCV)
• Upflow (LUCV)

Standard features
• Advanced microprocessor control system UG50 with • A low airflow differential pressure alarm switch is included.
touch-screen human interface is included. • Single coil version with one chilled water circuit.
• The units are equipped with the latest generation • CW inlet temperature measurement is integrated in the microprocessor.
Radical EC fans for efficiency maximization. Impellers • Integrated discharge temperature control and room moisture control.
are made of high-tech compound material with • Zinc-free CW circuit.
optimized flow control, combined with highly efficient • Full frontal accessibility is available for maintenance.
GreenTech EC motors. These fans are designed to
• Electric panel conforms to Machinery Directive 2006/42/EC (MD) and
have easier serviceability with quick removal kit.
Electromagnetic compatibility Directive 2014/30/EU (EMC).
• The structure of the unit is characterized by a self-
• Phase sequence control.
supporting frame in galvanized steel with panels.
• Microprocessor control system includes:
The external panels are coated with RAL9003 epoxy-
- Adjustable fan speed meets energy-saving and load-sharing logics
polyester paint and internally lined with heat- and
- 7-inch, touch-screen LCD display interface
sound-proofing insulation. The internal panels are
featured by captive screws. - Integration with Uniflair Chillers for optimized management logics
• The unit can be selected with a two-way or three- - Integrated LAN card for local network connection of a group of CRACs
way valve and an actuator integrated with the - Rotation and active stand-by management
microprocessor. The actuator is available in two - Free contact for general and two for addressable alarms
versions: basic and premium. - Remote on/off switch
• The cooling coil is designed for an elevated SHR and - Integrated RS485 serial card for direct connection to
reduced pressure drops in the air section. The coil is external BMS (modbus)
made from copper tubes mechanically expanded on - Integrated TCP/IP serial card for BMS connection
aluminum fins, complete with a hydrophilic treatment. - Clock card integrated in the unit
• High-efficiency, EU4-pleated air filters are housed in a - USB integrated in the display interface
metal frame and equipped with a dirty filter - Ability to interface with main external communication protocols: BACnet,
differential pressure switch and low airflow Lonworks, Trend, Metasys, TCP/IP, SNMP, and StruxureWare platform
differential pressure switch.

36 Life is On | Schneider Electric


TECHNICAL DATA
1
Data refers to nominal
conditions: Room
LDCV – LUCV MODEL 0600A 0700A 0800A 1200A 1400A 1700A 1800A
at 24 °C-50% RH,
Fan type EC backward-curved centrifugal motor fan water temperature
Power supply V/ph/Hz 400/3/50 7/12°C, glycol 0%,
Fans nr. 1 1 1 1 1 2 2 and ESP = 20Pa
Airflow m3/h 8000 8000 8000 11500 11500 16000 16000
2
Gross cooling capacities;
Gross total cooling
kW 28,3 32,2 44,8 44,8 62,7 59,2 86,9 fans must be deduced to
capacity 1,2
obtain net cooling data.
Gross sensible cooling
kW 25,5 28,1 35,2 39,5 49,8 52,1 69,1
capacity1,2 3
Only downflow version is
available.
DIMENSIONS
Height mm 1960 1960 1960 1960 1960 1960 1960 4
Cooling capacity refer to only
Length mm 1010 1010 1010 1310 1310 1720 1720 one running CW circuit.
Depth mm 865 865 865 865 865 865 865
TDCV – TUCV MODEL 2000A 2500A 2700A 3000A 3400A 4000A 4300A(3)
Fans nr. 2 2 2 3 3 3 3
Airflow m3/h 19000 19000 19000 25700 25700 25700 29500
Gross total cooling
kW 74,9 100,3 106,4 100,3 131,6 145,5 181,1
capacity1,2
Gross sensible cooling
kW 64,6 80,6 83,7 86,4 106,8 114,3 138,6
capacity1,2
DIMENSIONS
Height mm 1960 1960 1960 1960 1960 1960 2170
Length mm 2170 2170 2170 2582 2582 2852 2852
Depth mm 865 865 865 865 865 865 865
LDCV-LUCV MODEL DUAL COIL (4) 0600A 1200A 1700A 2000A 3000A 4300A3
Fans nr. 1 1 2 2 3 3
Airflow m3/h 8000 11500 16000 19000 25700 29500
Gross total cooling
kW 24,9 37,5 58,8 77,0 104,4 120,1
capacity1,2
Gross sensible cooling
kW 24,9 37,5 56,4 71,1 96,0 110,4
capacity1,2
DIMENSIONS
Height mm 1960 1960 1960 1960 1960 2170
Length mm 1010 1310 1720 2170 2582 2582
Depth mm 865 865 865 865 865 865

Construction options Accessories


• Single power supply with ultracapacitor The units can be supplied with the following external accessories:
• Double power supply with automatic integrated
• Additional RS485 serial adapter to communicate with external BMS.
management on the active line
• Additional TCP/IP serial adapter to communicate with external BMS
• Immersed electrode humidifier (D/U versions)
managed with SNMP protocol
• Low surface temperature electrical heaters with
• LON FTT10 serial adapter to communicate with external BMS
extended fans, complete with double safety thermostat
managed with LON protocol
and manual resetting (T/H versions)
• RS232 modem card
• Dual coil version equipped with two separate chilled
water circuits equipped with 2 or 3 way valve • PCONET card
• CW outlet temperature measurement integrated in the • Motorized damper
microprocessor • Suction from the top or front discharge plenums
• Intelligent dehumidification with cooling capacity • Adjustable floor stands
limiting device • Fire and smoke sensors
• Energy meter and CO2 emission calculator • Water leak detector
• Flow meter • Automatic floor pressurization system (AFPS) through
• Pressure-independent balancing and control valve active floor control (AFC)
(PIBCV)

Life is On | Schneider Electric 37


CW units with backward-curved fans equipped with EC motor; fan module
can be installed under or above raised floor

Uniflair LE
HDCV

Range
Cooling capacity: 30 ÷ 250 kW
Refrigerant CW
EC fans
Available versions
• Downflow Single Coil
• Downflow Dual Coil

Standard features Accessories


• Unit is made of two sections for installation of fan module under the raised floor The units can be supplied with the following
and increase the coil surface for energy efficiency maximization. accessories:
• Advanced microprocessor control system UG50 is included.
• Double power supply with automatic changeover
• The units are equipped with the latest generation Radical EC fans for efficiency
and manual selection with integrated ultracapacitor
maximization. Impellers are made of high-tech compound material with optimized
• Intelligent dehumidification with cooling capacity
flow control, combined with highly efficient GreenTech EC motors.
limiting device
• Large surface copper and aluminum cooling coil is provided for
• Automatic floor pressurization system
pressure drop minimization.
• CW outlet temperature measurement integrated
• EC fan module is equipped with a circular plug in connectors for quick
in the microprocessor
and failure-free installation; the module is supplied with safety protection grills
on the sides in case of underfloor installation. • Energy meter and CO2 emissions calculator integrated
in the unit
• Adjustable fan speed meets energy-saving and load-sharing logics.
• Ultracapacitor for single power supply units
• Electric panel conforms to Machinery Directive 2006/42/EC (MD) and Electromagnetic
compatibility Directive 2014/30/EU (EMC). • Direct free-cooling
• High-efficiency, pleated air filters are housed in a metal frame • Integrated base frame
and filter differential pressure switch. • PIBCV valves
• A low airflow differential pressure alarm switch is included. • Flowmeter
• Full frontal accessibility is available for maintenance.
• CW inlet temperature measurement is integrated in the microprocessor.
• Integrated Discharge Temperature Control and Room Moisture Control.
• Zinc-free CW circuit.
• Immersed electrode humidifier is included.
• Electrical heaters included with aluminum finned heating elements.
• Phase sequence control.
• Microprocessor control system in addition allows:
- Integration with Uniflair Chillers for optimized management logics
- Free contact for general and two for addressable alarms
- Remote on/off switch
- Integrated RS485 serial card for direct connection to external BMS (modbus)
- Second slot for additional serial card for BMS connection (optional)
- Clock card integrated in the unit

38 Life is On | Schneider Electric


TECHNICAL DATA
HDCV MODEL 0800A1 1300A1 1400A1 1700A1 1800A1 2500A1 2900A1 4100A1 4600A1 4800A1 5100A1 5300A1 5500A1
Fan type EC backward-curved centrifugal motor fan
Version Single coil
Power supply V/ph/Hz 400/3/50
Fans nr 1 1 1 2 2 2 2 3 3 3 3 4 4
Airflow m3/h 10000 10000 13000 19000 19000 24000 24000 32000 31000 35000 35000 40000 45000
Net sensible cooling1 kW 34,3 40,5 53,8 59,4 78,4 75,8 98,7 99 136 106 155.8 172.6 191
DIMENSIONS
Height2 mm 2510 2510 2510 2510 2510 2510 2510 2510 2510 2510 2510 2510 2510
Length mm 1010 1310 1310 1720 1720 2170 2170 2570 2570 3100 3100 3100 3405
Depth mm 865 865 865 865 865 865 865 865 865 865 865 865 865

HDCV MODEL 0800A 1400A 1800A 2500A 4500A 5000A


1
Data refer to nominal
conditions: Room
Fan type EC backward-curved centrifugal motor fan
at 35 °C-30% RH
Version Dual coil
water temperature 18/24
Power supply V/ph/Hz 400/3/50 °C, fan module installed
Fans nr 1 1 2 2 3 4 under a 900 mm
Airflow m3/h 7900 13000 17500 24000 30000 40000 raised floor,
Net sensible cooling1,3 kW 28.3 42.1 56.9 81.1 96.7 112.5 and glycol 0%.
DIMENSIONS 2
Includes fan module.
Height2 mm 2510 2510 2510 2510 2510 2510
Length mm 1010 1310 1720 2170 2570 3100 3
Cooling performance
Depth mm 865 865 865 865 865 865 refers to one running
CW circuit.

4
1 Data refer to nominal
HDCV MODEL 0800A1 HT 1400A1 HT 1800A1 HT 2900A1 HT 4600A1 HT 5300A1 HT 5500A1 HT
conditions: Room at
Fan type EC Backward-curved centrifugal motor fan
36 °C-30% RH water
Version High temperature temperature 20/30 °C,
Power supply V/ph/Hz 400/3/50Hz fan module installed
Fans Nr. 1 1 2 2 3 4 4 under a 900 mm raised
Airflow m3/h 7400 11000 17000 25500 28200 33700 36400 floor, and glycol 20%.
Net sensible cooling capacity4 kW 28.4 42.0 64.0 97.7 109.5 130.7 143.2
5
Includes fan module.
DIMENSIONS
Height5 mm 2510 2510 2510 2510 2510 2510 2510
Length mm 1010 1310 1720 2170 2570 3100 3405
Depth mm 865 865 865 865 865 865 865

Construction options
Unit with fan plenum installed
under the raised floor.

Unit with fan plenum installed


above the raised floor.

Life is On | Schneider Electric 39


Direct-expansion air-cooled units with backward-curved fans

Uniflair LE
TDAR – TUAR

Range
Cooling capacity: 20 ÷ 100 kW
Refrigerant R-410A
Available versions
• Downflow (TDAR)
• Upflow (TUAR)

Standard features Construction options


• Advanced microprocessor control system is included with local or remote user terminal. • Immersed electrode humidifier (D/U versions)
• The units are equipped with backward-curved fans with directly coupled • Low surface temperature electrical heaters
asynchronous motor. with extended fans, complete with double safety
• The structure of the unit is characterized by a self-supporting frame in galvanized steel thermostat and manual resetting (T/H versions)
with panels. The external panels are coated with RAL9003 epoxy-polyester paint and • Hot gas and hot water reheating
internally lined with heat- and sound-proofing insulation.
• Electronic expansion valve is controlled by the microprocessor with a dedicated Accessories
software that increases the precision of the cooling and the energy efficiency of the
The units can be supplied with the following
cooling cycle.
external accessories:
• The cooling coil is designed for an elevated SHR and reduced pressure drops in the air
section. The coil is made from copper tubes mechanically expanded on aluminum fins, • Remote, semi-graphic user terminal
complete with a hydrophilic treatment. • RS485 serial adapter to communicate with
• High-efficiency, EU4-pleated air filters are housed in a metal frame and equipped with a external BMS
dirty filter differential pressure switch and low airflow differential pressure switch. • LON FTT10 serial adapter to communicate
• Total front access is included for unit maintenance. with external BMS managed with LON protocol
• The electrical panel is situated in a compartment separated from the airflow and • TCP/IP serial adapter to communicate with external
complies with Machinery Directive 2006/42/EC (MD), Regulation (EU) No 517/2014 on BMS managed with SNMP protocol
fluorinated greenhouse gases (F-GAS) and related standards. • AFPS that can be adapted as a kit
• Microprocessor control system includes: with installation instructions
- Regulation logic of cooling capacity and airflow integration • Motorized damper
- Local user terminal with external accessibility • Suction from the top or front discharge plenums
- Integrated LAN card for local network connection of a group of CRACs • Adjustable floor stands
- Rotation and active stand-by management
- Free contact for general and two for addressable alarms
- Remote on/off switch
- Ability to interface with modbus protocol directly on RS485 serial card
(adding this option)
- Ability to interface with main external communication protocols: BACnet, Lonworks,
Trend, Metasys, TCP/IP, SNMP, and StruxureWare platform

40 Life is On | Schneider Electric


TECHNICAL DATA
1
Gross cooling
capacities; fans must be
TDAR – TUAR MODEL 0511A 0611A 0721A 0722A 0921A 0922A 1021A
deduced to obtain net
Fan type Backward-curved centrifugal motor fan
cooling data.
Power supply V/ph/Hz 400/3/50
Fans nr. 1 1 1 1 1 1 1 2
Data refers to nominal
Airflow m3/h 5833 5833 7933 7933 7933 7933 7933 conditions: Room
N° of compressors 1 1 2 2 2 2 2 at 24 °C-50% RH,
45 °C condensing
Refrigerating circuits 1 1 1 2 1 2 1
temperature,
Gross total cooling
kW 20,4 25,0 25,8 25,6 34,1 33,9 37,1 and ESP = 20 Pa.
capacity1,2
Gross sensible cooling 3
Data refers to
kW 19,8 22,2 25,2 23,9 28,1 27,2 28,7
capacity 1,2 downflow unit.

DIMENSIONS
Height mm 1960 1960 1960 1960 1960 1960 1960
Length mm 1010 1010 1310 1310 1310 1310 1310
Depth mm 750 750 865 865 865 865 865
TDAR – TUAR MODEL 1022A 1121A 1122A 1321A 1322A 1422A 1622A
Fans nr. 1 1 2 2 2 2 2
Airflow m3/h 7933 12267 12267 12267 12267 16406 16406
N° of compressors 2 2 2 2 2 2 2
Refrigerating circuits 2 1 2 1 2 2 2
Gross total cooling
kW 36,9 37,8 37,9 48,0 47,7 51,6 57,5
capacity1,2
Gross sensible cooling
kW 28,0 36,8 36,2 39,3 38,0 51,0 56,8
capacity1,2
DIMENSIONS
Height mm 1960 1960 1960 1960 1960 1960 1960
Length mm 1010 1720 1720 1720 1720 2170 2170
Depth mm 865 865 865 865 865 865 865
TDAR – TUAR MODEL 1822A 2222A3 2242A3 2522A3 2542A3 2842A3 3342A3
Fans nr. 2 3 3 3 3 3 3
Airflow m3/h 16406 21656 21656 21656 22046 22055 22055
N° of compressors 2 2 4 2 4 4 4
Refrigerating circuits 2 2 2 2 2 2 2
Gross total cooling
kW 63,9 75,1 81,2 86,7 88,1 97,4 107,6
capacity1,2
Gross sensible cooling
kW 57,3 75,1 80,3 83,3 84,5 90,8 92,9
capacity1,2
DIMENSIONS
Height mm 1960 2150 2150 2150 2150 2150 2150
Length mm 2170 2580 2580 2580 2580 2580 2580
Depth mm 865 865 865 865 865 865 865
TUAR MODEL 2222A 2242A 2522A 2542A 2842A 3342A
Fans nr. 3 3 3 3 3 3
Airflow m3/h 22154 22154 23467 23467 23068 23068
N° of compressors 2 4 2 4 4 4
Refrigerating circuits 2 2 2 2 2 2
Gross total cooling
kW 75,4 82,7 86,5 87,5 97,9 108,2
capacity1,2
Gross sensible cooling
kW 75,4 81,8 85,5 86,4 93,8 95,6
capacity1,2
DIMENSIONS
Height mm 1960 1960 1960 1960 1960 1960
Length mm 2580 2580 2580 2580 2580 2580
Depth mm 865 865 865 865 865 865

Life is On | Schneider Electric 41


Direct-expansion air-cooled units with backward-curved fans equipped with EC motor

Uniflair LE
TDAV – TUAV

Range
Cooling capacity: 20 ÷ 100 kW
Refrigerant R-410A
EC fans
Available versions
• Downflow (TDAV)
• Upflow (TUAV)

Standard features Construction options


• Advanced microprocessor control system is available with local or remote user terminal. • Immersed electrode humidifier (D/U versions)
• The units are equipped with EC fans for efficiency maximization. • Low surface temperature electrical heaters
• The structure of the unit is characterized by a self-supporting frame in galvanized with extended fans, complete with double safety
steel with panels. The external panels are coated with RAL9003 epoxy-polyester paint thermostat and manual resetting (T/H versions)
and internally lined with heat- and sound-proofing insulation. • Hot gas and hot water reheating
• Electronic expansion valve is controlled by the microprocessor and a dedicated
software that increases the cooling precision and the energy efficiency Accessories
of the cooling cycle.
The units can be supplied with the following
• The cooling coil is designed for an elevated SHR and reduced pressure drops in the air
external accessories:
section. The coil is made from copper tubes mechanically expanded on aluminum fins,
complete with a hydrophilic treatment. • Remote, semi-graphic user terminal
• Uniflair LE units meet the following directives: Machinery Directive 2006/42/EC (MD), • RS485 serial adapter to communicate with
Electromagnetic compatibility Directive 2014/30/EU (EMC), Pressure equipment external BMS
Directive 2014/68/EU (PED), Regulation (EU) No 517/2014 on fluorinated • LON FTT10 serial adapter to communicate
greenhouse gases (F-GAS). with external BMS managed with LON protocol
• High-efficiency, EU4-pleated air filters are housed in a metal frame and equipped with • TCP/IP serial adapter to communicate with external
a dirty filter differential pressure switch and low airflow differential pressure switch. BMS managed with SNMP protocol
• The Uniflair LE range offers the possibility to select units equipped with two • AFPS that can be adapted as a kit
compressors (tandem) for each circuit, granting better efficiency and regulation with installation instructions
capacity at partial loads (models with the **21 or **42 suffix). • Motorized damper
• Total front access is available for unit maintenance. • Condensate drain pump
• The electrical panel is situated in a compartment separated from the airflow and • Suction from the top or front discharge plenums
complies with Machinery Directive 2006/42/EC (MD) and related standards. • Adjustable floor stands
• Microprocessor control system includes:
- Integrated management of the EEV and refrigerating circuit parameters
- Local user terminal with external accessibility
- Integrated LAN card for local network connection of a group of CRACs
- Rotation and active stand-by management
- Free contact for general and two for addressable alarms
- Remote on/off switch
- Ability to interface with modbus protocol directly on RS485 serial card
- Ability to interface with main external communication protocols: BACnet, Lonworks,
Trend, Metasys, TCP/IP, SNMP, and StruxureWare platform

42 Life is On | Schneider Electric


TECHNICAL DATA
1
Gross cooling
capacities; fans must be
TDAV – TUAV MODEL 0511A 0611A 0721A 0722A 0921A 0922A 1021A
deduced to obtain net
Fan type EC backward-curved centrifugal motor fan
cooling data.
Power supply V/ph/Hz 400/3/50
Fans nr. 1 1 1 1 1 1 1 2
Data refers to nominal
Airflow m3/h 5700 5700 8600 8600 8600 8600 8600 conditions: Room
N° of compressors 1 1 2 2 2 2 2 at 24 °C-50% RH,
45 °C condensing
Refrigerating circuits 1 1 1 2 1 2 1
temperature,
Gross total cooling
kW 20,3 24,9 25,6 25,8 34,5 34,2 37,6 and ESP = 20 Pa.
capacity1,2
Gross sensible cooling
kW 19,7 21,9 25,4 25,3 29,6 28,4 30,1 3
Data refers to
capacity1,2
downflow unit.
DIMENSIONS
Height mm 1960 1960 1960 1960 1960 1960 1960
Length mm 1010 1010 1310 1310 1310 1310 1310
Depth mm 750 750 865 865 865 865 865
TDAV – TUAV MODEL 1022A 1121A 1122A 1321A 1322A 1422A 1622A
Fans nr. 1 1 2 2 2 2 2
Airflow m3/h 8600 12320 12320 12320 12320 16300 16500
N° of compressors 2 2 2 2 2 2 2
Refrigerating circuits 2 1 2 1 2 2 2
Gross total cooling
kW 37,3 37,6 37,9 48,1 47,7 51,5 56,5
capacity1,2
Gross sensible cooling
kW 29,2 36,7 36,3 39,4 38,0 50,9 55,8
capacity1,2
DIMENSIONS
Height mm 1960 1960 1960 1960 1960 1960 1960
Length mm 1010 1720 1720 1720 1720 2170 2170
Depth mm 865 865 865 865 865 865 865
TDAV – TUAV MODEL 1822A 2222A3 2242A3 2522A3 2542A3 2842A3 3342A3
Fans nr. 2 3 3 3 3 3 3
Airflow m3/h 16500 21500 21500 21500 21500 21500 21500
N° of compressors 2 2 4 2 4 4 4
Refrigerating circuits 2 2 2 2 2 2 2
Gross total cooling
kW 64,0 75,0 82,7 86,6 87,8 94,8 104,8
capacity1,2
Gross sensible cooling
kW 57,5 75,0 81,8 82,8 83,0 87,5 89,6
capacity1,2
DIMENSIONS
Height mm 1960 2175 2175 2175 2175 2175 2175
Length mm 2170 2580 2580 2580 2580 2580 2580
Depth mm 865 865 865 865 865 865 865
TUAV MODEL 2222A 2242A 2522A 2542A 2842A 3342A
Fans nr. 3 3 3 3 3 3
Airflow m3/h 22000 22000 22500 22500 23000 23000
N° of compressors 2 4 2 4 4 4
Refrigerating circuits 2 2 2 2 2 2
Gross total cooling
kW 75,3 82,6 86,8 88,3 95,6 105,6
capacity1,2
Gross sensible cooling
kW 75,3 81,7 85,8 85,7 91,8 93,6
capacity1,2
DIMENSIONS
Height mm 1960 1960 1960 1960 1960 1960
Length mm 2580 2580 2580 2580 2580 2580
Depth mm 865 865 865 865 865 865

Life is On | Schneider Electric 43


Direct-expansion air-cooled units with backward-curved fans equipped with EC motor

Uniflair LE
LDAV

Range
Cooling capacity: 60 ÷ 140 kW
Fixed speed compressors
Refrigerant R-410A
EC fans
Available versions
• Downflow (LDAV)

Standard features
• Downflow configuration with bottom or front discharge • New generation of hermetic scroll compressor with
and suction from the top. Intermediate Discharge Valves (IDVs), built-in thermal
• Metal structural frame and inside part made with protection and anti-vibration feet
hot-dip zinc-plated sheet steel • Refrigerant R410A
• External panels coated with RAL9003 epoxy-polyester • Electronic Expansion Valve (EEV) to provide accurate
paint and internally lined with heat- and sound- control of the refrigerant superheat ensuring high
proofing insulation to class 1 according to Class energy efficiency also at low external temperatures.
B1 according to DIN 4102, BS 476 part 7,VO • Electrical panel complying with Machinery Directive
according to UL94, ASTM E84, class M1 2006/42/EC (MD) and Electromagnetic compatibility
according to NFP92-501 Directive 2014/30/EU (EMC), Regulation (EU)
• Internal panels for shutting-off the compartments No 517/2014 on fluorinated greenhouse gases (F-GAS),
affected by the airflow, made with hot-dip zinc-plated housed- in a compartment isolated from the airflow and
sheet steel and captive screws including 24V control circuit transformer, metal isolating
• High efficiency EU4 pleated air filters are contained screen for protection from live components, mains
in a metal frame and equipped with a dirty filter switch, thermomagnetic circuit-breakers, terminal board
differential pressure switch and a low airflow for no-voltage signal and control contacts.
differential pressure switch. The filters are housed • 7-inch. IT Touch Screen display interface that allows to
in a dedicated plenum box. set operating parameters, monitor the trend
• The units are equipped with the latest generation of the main working parameters, and read any
Radical EC Fans for efficiency maximization. Impellers alarm messages.
are made of high-tech compound material with • Schneider Electric IT J-Controller (J5 18 DIN),
optimized flow control, combined with highly efficient complying with Machinery Directive 2006/42/EC (MD)
GreenTech EC motors. These fans are designed to and Electromagnetic compatibility Directive 2014/30/
have easier serviceability with quick removability kit. EU (EMC), Regulation (EU) No 517/2014 on fluorinated
• Low airflow differential pressure switch greenhouse gases (F-GAS), where are connected
analogical and digital inputs necessary for control of
• Cooling coil, mounted upstream of the fans,
the unit.
constructed of copper tubes expanded into
hydrophilic aluminum fins, complete with stainless • Control software design to provide a highly accurate
steel tray and a flexible condensate drain hose real-time control of room conditions and the complete
unit management such as:
• Double refrigerant circuit each equipped with a fixed-
speed scroll compressor. - electronic expansion valve complete management
• Refrigerant circuits complying with Pressure - advanced interactivity with the
Equipment Directive 2014/68/EU (PED) including: installation environment
liquid refrigerant receiver, filter-dryer and liquid sight - dehumidification operating mode managed by
glass, electronic expansion valve, high-pressure means of EEV with devised algorithm which
pressostats with manual reset. maintains constant air flow
- double set-point with digital input selection
- emergency operation

44 Life is On | Schneider Electric


TECHNICAL DATA
1
Gross cooling
capacities; fans must
LDWV MODEL 2422A 2522A 2722A 3822A
be deduced to obtain
Fan Type EC Backward-curved centrifugal motor fan
net cooling data.
Power supply V/ph/Hz 400/3/50Hz
Fans Nr. 2 2 2 3 2
Data refers to nominal
Airflow m3/h 20000 24300 26000 27000 conditions: Room
N° of fixed speed compressors 2 2 2 2 at 24 °C-50% RH,
Refrigerating circuits 2 2 2 2 45 °C condensing
Gross total cooling capacity1,2 kW 79,0 83,0 93,1 132,0 temperature and
Gross sensible cooling capacity1,2 kW 74,1 83,0 90,1 110,0 ESP = 20 Pa..

DIMENSIONS
Height mm 2150 2150 2150 2150
Length mm 2082 2650 2650 2650
Depth mm 900 900 900 900

• The design of the IT J-Controller allows to physically • Condensate drain pump


isolate the internal connections from the external • Electrical heaters with aluminum-finned heating
connections. The external connections on the upper elements complete with safety thermostat (for manual
level offer a wide variety of accessibility options: resetting) to cut off the power supply in the event of
- External CAN and Group CAN overheating
- Isolated 2-wire and 4-wire RS485 ports • High efficiency EU5 pleated air filters housed in a
- NetBotz universal sensor ports dedicated plenum box
- Alarm/Shutdown Contacts • Power phase correction capacitors for compressors
- USB ports (Host, Device) • Active Flow Control to improve the balance of airflow
between the cooling structure and IT equipment.
- Ethernet
• Energy meter and CO2 emission calculator
- HDMI display interface
• Motorized damper on the air return side
- Modbus
- Remote shutdown input
Accessories
• Ability to interface with most common external
BMS on communication protocols and boosting on The units can be supplied with the following external
connection towards Schneider monitoring systems: accessories:
- Modbus/RTU RS485 • Suction / discharge plenums
- SNMP • Direct free-cooling plenums
- Modbus Over IP • Floor stands with or without motorized damper
- StruxureWare • Height adjustable base frame
- StruxureON • Room temperature and humidity sensor
- Cooling Tuner as service diagnostic tool • Smoke and fire sensors
• Water leak detectors
Construction options
• Double power supply with automatic integrated
management on the active line to provide redundancy
and ensure a constant power supply
• Standard, cleanable or low conductibility humidifier
with immersed-electrodes for modulating steam
production available as an option for units equipped
with cooling and humidification configuration

Life is On | Schneider Electric 45


Direct-expansion water-cooled units with backward-curved fans

Uniflair LE
TDWR – TUWR

Range
Cooling capacity: 20 ÷ 100 kW
Refrigerant R-410A
Available versions
• Downflow (TDWR)
• Upflow (TUWR)

Standard features
• Advanced microprocessor control system is available • The Uniflair LE range offers the possibility to select units
with local or remote user terminal. equipped with two compressors (tandem) for each circuit,
• The units are equipped with backward-curved fans which grants better efficiency and regulation capacity at
and directly coupled asynchronous motor. partial loads (models with the **21 or **42 suffix).
• The structure of the unit is characterized • Total front access is available for unit maintenance.
by a self-supporting frame in galvanized steel • The electrical panel is situated in a compartment separated
with panels. The external panels are coated from the airflow and complies with the Machinery Directive
with RAL9003 epoxy-polyester paint and internally 2006/42/EC (MD) and related standards.
lined with heat- and sound-proofing insulation. • Microprocessor control system includes:
• Electronic expansion valve is controlled - Integrated management of the EEV
by the microprocessor and a dedicated software and refrigerating circuit parameters
that increases the precision of the cooling - Local user terminal with external accessibility
and the energy efficiency of the cooling cycle. - Integrated LAN card for local network connection of
• The cooling coil is designed for an elevated SHR a group of CRACs
and reduced pressure drops in the air section. - Rotation and active stand-by management
The coil is made from copper tubes mechanically - Free contact for general and two for addressable alarms
expanded on aluminum fins, complete with
- Remote on/off switch
a hydrophilic treatment.
- Ability to interface with modbus protocol directly
• Internal water-cooled condenser braze is welded
on RS485 serial card
and made of AISI 304 stainless steel.
- Ability to interface with main external communication
• Uniflair LE units meet the following directives:
protocols: BACnet, Lonworks, Trend, Metasys, TCP/ IP,
Machinery Directive 2006/42/EC (MD),
SNMP, and StruxureWare platform
Electromagnetic compatibility Directive 2014/30/EU
(EMC), Pressure equipment Directive 2014/68/EU
(PED), Regulation (EU) No 517/2014 on fluorinated
greenhouse gases (F-GAS).
• High-efficiency, EU4-pleated air filters are housed
in a metal frame and equipped with a dirty filter
differential pressure switch and low airflow differential
pressure switch.

46 Life is On | Schneider Electric


TECHNICAL DATA
1
Gross cooling
capacities; fans
TDWR – TUWR MODEL 0611A 0921A 1321A 1622A 1822A
must be deduced
Fan type Backward-curved centrifugal motor fan
to obtain net
Power supply V/ph/Hz 400/3/50 cooling data.
Fans nr. 1 1 2 2 2
Airflow m3/h 5833 7933 12267 16406 16406 2
Data refers to nominal
N° of compressors 1 2 2 2 2 conditions: Room
Refrigerating circuits 1 1 1 2 2 at 24 °C-50% RH,
water temperatures
Gross total cooling
kW 24,1 32,1 45,5 56,8 62,5 30 – 35 °C,
capacity1,2 and ESP = 20 Pa.
Gross sensible cooling
kW 21,7 27,2 38,0 55,2 56,1
capacity1,2
DIMENSIONS
Height mm 1960 1960 1960 1960 1960
Length mm 1010 1310 1720 2170 2170
Depth mm 750 865 865 865 750
TDWR MODEL 2242A 2542A 2842A 3342A
Fans nr. 3 3 3 3
Airflow m3/h 21656 22046 22055 22055
N° of compressors 4 4 4 4
Refrigerating circuits 2 2 2 2
Gross total cooling
kW 85,7 92,6 99,9 111,1
capacity1,2
Gross sensible cooling
kW 82,1 84,2 90,3 92,2
capacity1,2

DIMENSIONS

Height mm 2150 2150 2150 2150


Length mm 2580 2580 2580 2580
Depth mm 865 865 865 865
TUWR MODEL 2242A 2542A 2842A 3342A
Fans nr. 3 3 3 3
Airflow m3/h 22154 23467 23068 23069
N° of compressors 4 4 4 4
Refrigerating circuits 2 2 2 2
Gross total cooling
kW 86,0 93,4 100,5 111,7
capacity1,2
Gross sensible cooling
kW 83,4 87,9 93,1 94,7
capacity1,2
DIMENSIONS
Height mm 1960 1960 1960 1960
Length mm 2580 2580 2580 2580
Depth mm 865 865 865 865

Construction options Accessories


• Immersed electrode humidifier (D/U versions) The units can be supplied with the following external accessories:
• Low surface temperature electrical heaters
• Remote, semi-graphic user terminal
with extended fans, complete with double safety
thermostat and manual resetting (T/H versions) • RS485 serial adapter to communicate with external BMS
• Hot gas and hot water reheating • LON FTT10 serial adapter to communicate
with external BMS managed with LON protocol
• Condensation control on refrigerant side
with constant water flow • TCP/IP serial adapter to communicate with external BMS
managed with SNMP protocol
• AFPS that can be adapted as a kit with installation instructions.
• Motorized damper
• Condensate drain pump
• Suction from the top or front discharge plenums
• Adjustable floor stands

Life is On | Schneider Electric 47


Direct-expansion water-cooled units with backward-curved fans equipped with EC motor

Uniflair LE
TDWV – TUWV

Range
Cooling capacity: 20 ÷ 100 kW
Refrigerant R-410A
EC fans
Available versions
• Downflow (TDWV)
• Upflow (TUWV)

Standard features
• Advanced microprocessor control system with • The Uniflair LE range offers the possibility to select units
a local or remote user terminal. equipped with two compressors (tandem) for each circuit,
• The units are equipped with EC fans for which grants better efficiency and regulation capacity at
efficiency maximization. partial loads (models with the **21 or **42 suffix).
• The structure of the unit is characterized by • Total front access is available for unit maintenance.
a self-supporting frame in galvanized steel • The electrical panel is situated in a compartment separated
with panels. The external panels are coated from the airflow and complies with the Machinery Directive
with RAL9003 epoxy-polyester paint and internally 2006/42/EC (MD) and related standards.
lined with heat- and sound-proofing insulation. • Microprocessor control system includes:
• Electronic expansion valve is controlled by - Integrated management of the EEV and refrigerating
the microprocessor and a dedicated software circuit parameters
that increases the precision of the cooling - Local user terminal with external accessibility
and the energy efficiency of the cooling cycle. - Integrated LAN card for local network connection
• The cooling coil is designed for an elevated SHR of a group of CRACs
and reduced pressure drops in the air section. - Rotation and active stand-by management
The coil is made from copper tubes mechanically - Free contact for general and two for addressable alarms
expanded on aluminum fins, complete with
- Remote on/off switch
a hydrophilic treatment.
- Ability to interface with modbus protocol directly
• Internal water-cooled condenser braze is welded
on RS485 serial card
and made of AISI 304 stainless steel.
- Ability to interface with main external communication
• Uniflair LE units meet the following directives:
protocols: BACnet, Lonworks, Trend, Metasys, TCP/IP,
Machinery Directive 2006/42/EC (MD),
SNMP, and StruxureWare platform
Electromagnetic compatibility Directive 2014/30/EU
(EMC), Pressure equipment Directive 2014/68/EU
(PED), Regulation (EU) No 517/2014 on fluorinated
greenhouse gases (F-GAS).
• High-efficiency, EU4-pleated air filters are housed
in a metal frame and equipped with a dirty filter
differential pressure switch and low airflow differential
pressure switch.

48 Life is On | Schneider Electric


TECHNICAL DATA
1
Gross cooling
capacities; fans must be
TDWV – TUWV MODEL 0611A 0921A 1321A 1622A 1822A
deduced to obtain net
Fan type EC backward-curved centrifugal motor fan
cooling data.
Power supply V/ph/Hz 400/3/50
Fans nr. 1 1 2 2 2 2
Data refers to nominal
Airflow m3/h 5700 8600 12320 16000 16000 conditions: Room at
N° of compressors 1 2 2 2 2 24 °C -50% RH,
water temperatures
Refrigerating circuits 1 1 1 2 2
30 – 35 °C,
Gross total cooling
kW 24,0 32,5 45,6 56,7 62,3 and ESP = 20 Pa.
capacity1,2
Gross sensible cooling
kW 21,3 28,6 38,1 54,3 55,2
capacity1,2
DIMENSIONS
Height mm 1960 1960 1960 1960 1960
Length mm 1010 1310 1720 2170 2170
Depth mm 750 865 865 865 750
TDWV MODEL 2242A 2542A 2842A 3342A
Fans nr. 3 3 3 3
Airflow m3/h 21500 21500 21500 21500
N° of compressors 4 4 4 4
Refrigerating circuits 2 2 2 2
Gross total cooling
kW 85,7 92,3 99,5 110,7
capacity1,2
Gross sensible cooling
kW 81,6 82,8 88,8 90,8
capacity1,2
DIMENSIONS
Height mm 1960 2150 2150 2150
Length mm 2580 2580 2580 2580
Depth mm 865 865 865 865
TUWV MODEL 2242A 2542A 2842A 3342A
Fans nr. 3 3 3 3
Airflow m3/h 22000 22500 23000 23000
N° of compressors 4 4 4 4
Refrigerating circuits 2 2 2 2
Gross total cooling
kW 85,9 92,9 100,4 111,7
capacity1,2
Gross sensible cooling
kW 83,0 85,4 92,9 94,6
capacity1,2
DIMENSIONS
Height mm 1960 1960 1960 1960
Length mm 2580 2580 2580 2580
Depth mm 865 865 865 865

Construction options Accessories


• Immersed electrode humidifier (D/U versions) The units can be supplied with the following external accessories:
• Low surface temperature electrical heaters
• Remote, semi-graphic user terminal
with extended fans, complete with double safety
thermostat and manual resetting (T/H versions) • RS485 serial adapter to communicate with external BMS
• Hot gas and hot water reheating • LON FTT10 serial adapter to communicate with external BMS
managed with LON protocol
• Condensation control on refrigerant side with constant
water flow • TCP/IP serial adapter to communicate with external BMS
managed with SNMP protocol
• AFPS that can be adapted as a kit with installation instructions
• Motorized damper
• Condensate drain pump
• Suction from the top or front discharge plenums
• Adjustable floor stands

Life is On | Schneider Electric 49


Direct-expansion water-cooled units with backward-curved fans equipped with EC motor

Uniflair LE
LDWV

Range
Cooling capacity: 60 ÷ 140 kW
Fixed speed compressors
Refrigerant R-410A
EC fans
Available versions
• Downflow (LDWV)

Standard features
• Downflow configuration with bottom or front discharge • New generation of hermetic scroll compressor with
and suction from the top. Intermediate Discharge Valves (IDVs), built-in thermal
• Metal structural frame and inside part made with hot- protection and anti-vibration feet
dip zinc-plated sheet steel • Refrigerant R410A
• External panels coated with RAL9003 epoxy-polyester • Electronic Expansion Valve (EEV) to provide accurate
paint and internally lined with heat- and sound- control of the refrigerant superheat ensuring high
proofing insulation to class 1 according to energy efficiency also at low external temperatures.
Class B1 according to DIN 4102, BS 476 part 7, • Electrical panel complying with Machinery Directive
VO according to UL94, ASTM E84, class M1 2006/42/EC (MD) and Electromagnetic compatibility
according to NFP92-501 Directive 2014/30/EU (EMC), housed- in a
• Internal panels for shutting-off the compartments compartment isolated from the airflow and including
affected by the airflow, made with hot-dip zinc-plated 24V control circuit transformer, metal isolating screen
sheet steel and captive screws for protection from live components, mains switch,
• High efficiency EU4 pleated air filters are contained thermomagnetic circuit-breakers, terminal board for
in a metal frame and equipped with a dirty filter no-voltage signal and control contacts.
differential pressure switch and a low airflow • 7-inch. IT Touch Screen display interface that allows
differential pressure switch. The filters are housed in a to set operating parameters, monitor the trend of
dedicated plenum box. the main working parameters, and read any alarm
• The units are equipped with the latest generation messages.
Radical EC Fans for efficiency maximization. Impellers • Schneider Electric IT J-Controller (J5 18 DIN),
are made of high-tech compound material with complying with Machinery Directive 2006/42/EC (MD)
optimized flow control, combined with highly efficient and Electromagnetic compatibility Directive 2014/30/
GreenTech EC motors. These fans are designed to EU (EMC), Regulation (EU) No 517/2014 on
have easier serviceability with quick removability kit. fluorinated greenhouse gases (F-GAS), where are
• Low airflow differential pressure switch connected analogical and digital inputs necessary for
control of the unit.
• Cooling coil, mounted upstream of the fans,
constructed of copper tubes expanded into • Control software design to provide a highly accurate
hydrophilic aluminum fins, complete with stainless real-time control of room conditions and the complete
steel tray and a flexible condensate drain hose unit management such as:
• Brazed plate water-cooled condenser made from - electronic expansion valve complete management
stainless steel. - advanced interactivity with the installation
• Double refrigerant circuit each equipped with a fixed- environment
speed scroll compressor. - dehumidification operating mode managed by
• Refrigerant circuits complying with Pressure means of EEV with devised algorithm which
equipment Directive 2014/68/EU (PED) including: maintains constant air flow
liquid refrigerant receiver, filter-dryer and liquid sight - double set-point with digital input selection
glass, electronic expansion valve, high-pressure - emergency operation
pressostats with manual reset.

50 Life is On | Schneider Electric


TECHNICAL DATA
1
Gross cooling
capacities; fans must
LDWV MODEL 2422A 2522A 2722A 3822A
be deduced to obtain
Fan Type EC Backward-curved centrifugal motor fan
net cooling data.
Power supply V/ph/Hz 400/3/50Hz
Fans Nr. 2 2 2 3 2
Data refers to nominal
Airflow m3/h 20000 24300 26000 27000 conditions: Room at 24
N° of fixed speed compressors 2 2 2 2 °C-50% RH, inlet/outlet
Refrigerating circuits 2 2 2 2 water temperatures
Gross total cooling capacity1,2 kW 83,2 86,8 97,2 137,7 30/35°C, 0% glycol
Gross sensible cooling capacity1,2 kW 75,1 86,8 90,9 111,7 and ESP = 20 Pa.

DIMENSIONS
Height mm 2150 2150 2150 2150
Length mm 2082 2650 2650 2650
Depth mm 900 900 900 900

• The design of the IT J-Controller allows to physically • Standard, cleanable or low conductibility humidifier
isolate the internal connections from the external with immersed-electrodes for modulating steam
connections. The external connections on the upper production available as an option for units equipped
level offer a wide variety of accessibility options: with cooling and humidification configuration
- External CAN and Group CAN • Condensate drain pump
- Isolated 2-wire and 4-wire RS485 ports • Electrical heaters with aluminum-finned heating
- NetBotz universal sensor ports elements complete with safety thermostat (for manual
resetting) to cut off the power supply in the event of
- Alarm/Shutdown Contacts
overheating
- USB ports (Host, Device)
• High efficiency EU5 pleated air filters housed in a
- Ethernet dedicated plenum box
- HDMI display interface • Power phase correction capacitors for compressors
- Modbus • Active Flow Control to improve the balance of airflow
- Remote shutdown input between the cooling structure and IT equipment.
• Ability to interface with most common external • Energy meter and CO2 emission calculator
BMS on communication protocols and boosting on • Motorized damper on the air return side
connection towards Schneider monitoring systems:
- Modbus/RTU RS485 Accessories
- SNMP
The units can be supplied with the following external
- Modbus Over IP accessories:
- StruxureWare • Suction / discharge plenums
- StruxureON • Direct free-cooling plenums
- Cooling Tuner as service diagnostic tool • Floor stands with or without motorized damper
• Height adjustable base frame
Construction options
• Room temperature and humidity sensor
• Double power supply with automatic integrated • Smoke and fire sensors
management on the active line to provide
• Water leak detectors
redundancy and ensure a constant power supply
• 2-way pressostatic valve to modulate the water flow
through the braze plate condenser
• Condensing Pressure Regulation Valve (Flooding
Valve) to maintain a minimum condensing pressure
even with low water inlet temperature

Life is On | Schneider Electric 51


Energy-saving units with backward-curved fans

Uniflair LE
TDER – TUER

Range
Cooling capacity: 20 ÷ 100 kW
Refrigerant R-410A
Available versions
• Downflow (TDER)
• Upflow (TUER)

Standard features
• Advanced microprocessor control system is available with local or remote user terminal. - Remote on/off switch
• The units are equipped with backward-curved fans with directly coupled - Ability to interface with modbus protocol directly on
asynchronous motor. RS485 serial card
• The structure of the unit is characterized by a self-supporting frame in galvanized steel - Ability to interface with main external communication
with panels. The external panels are coated with RAL9003 epoxy-polyester paint and protocols: BACnet, Lonworks, Trend, Metasys, TCP/IP,
internally lined with heat- and sound-proofing insulation. SNMP, and StruxureWare platform
• Electronic expansion valve is controlled by the microprocessor and a dedicated software
that increases the precision of the cooling and the energy efficiency of the cooling cycle. Construction options
• The cooling coil is designed for an elevated SHR and reduced pressure drops in the air
• Immersed electrode humidifier (D/U versions)
section. The coil is made from copper tubes mechanically expanded on aluminum fins,
• Low surface temperature electrical heaters
complete with a hydrophilic treatment.
with extended fans, complete with double safety
• The cooling coil is characterized by CW and direct expansion circuits interlaced to
thermostat and manual resetting (T/H versions)
increase the efficiency of the unit in all running conditions.
• Hot gas and hot water reheating
• Unit is equipped with an indirect free cooling system that provides the required
• Condensation control on refrigerant side with
cooling capacity when the external temperature is lower than the internal ambient.
constant water flow
Compressor power consumption is minimized while internal and external environments
are kept separate.
Accessories
• Internal water-cooled condenser braze is welded and made of AISI 304 stainless steel.
• Uniflair LE units meet the following directives: Machinery Directive 2006/42/EC (MD), The units can be supplied with the following
Electromagnetic compatibility Directive 2014/30/EU (EMC), Pressure equipment external accessories:
Directive 2014/68/EU (PED), Regulation (EU) No 517/2014 on fluorinated greenhouse
• Remote, semi-graphic user terminal
gases (F-GAS).
• RS485 serial adapter to communicate with
• High-efficiency, EU4-pleated air filters are housed in a metal frame and equipped with
external BMS
a dirty filter differential pressure switch and low airflow differential pressure switch.
• LON FTT10 serial adapter to communicate
• The Uniflair LE range offers the possibility to select units equipped with two compressors
with external BMS managed with LON protocol
(tandem) for each circuit, which grants better efficiency and regulation capacity at partial
loads (models with the **21 or **42 suffix). • TCP/IP serial adapter to communicate with external
BMS managed with SNMP protocol
• Total front access is available for unit maintenance.
• AFPS that can be adapted as a kit
• The electrical panel is situated in a compartment separated from the airflow
with installation instructions
and complies with the Machinery Directive 2006/42/EC (MD).
• Motorized damper
• Microprocessor control system includes:
• Condensate drain pump
- Integrated management of the EEV and refrigerating circuit parameters
• Suction from the top or front discharge plenums
- Local user terminal with external accessibility
• Adjustable floor stands
- Integrated LAN card for local network connection of a group of CRACs
- Rotation and active stand-by management
- Free contact for general and two for addressable alarms

52 Life is On | Schneider Electric


TECHNICAL DATA
1
Gross cooling
TDER – TUER MODEL 0511A 0611A 0721A 0722A 0921A 0922A 1021A capacities; fans
must be deduced
Fan type Backward-curved centrifugal motor fan
to obtain net
Power supply V/ph/Hz 400/3/50
cooling data.
Fans nr. 1 1 1 1 1 1 1
Airflow m3/h 5827 5827 8541 8541 8541 8541 8541 2
Data refers to nominal
N° of compressors 1 1 2 2 2 2 2 conditions: Room
at 24 °C-50% RH,
Refrigerating circuits 1 1 1 2 1 2 1 water temperatures
Gross total cooling
CW MODE DX MODE

kW 19,2 23,8 27,0 28,5 30,4 32,1 34,6 30 – 35 °C,


capacity1,2 and ESP = 20 Pa.
Gross sensible cooling
kW 19,2 21,1 27,0 28,5 28,5 27,9 30,3
capacity1,2 3
Data refers to nominal
Gross total cooling conditions: Room
kW 20,5 20,5 28,3 28,3 28,3 28,3 28,3
capacity1,3 at 24 °C-50% RH,
Gross sensible cooling water temperature
kW 20,4 20,4 28,2 28,2 28,2 28,2 28,2
capacity1,3 7/12 °C; glycol 0%,
DIMENSIONS and ESP = 20 Pa.

Height mm 1960 1960 1960 1960 1960 1960 1960 4


Data refers to
Length mm 1010 1010 1310 1310 1310 1310 1310 downflow unit.
Depth mm 750 750 865 865 865 865 865
TDER – TUER MODEL 1022A 1121A 1122A 1321A 1322A 1422A 1622A
Fans nr. 1 1 2 2 2 2 2
Airflow m3/h 8541 13277 13277 13277 13277 15906 15906
N° of compressors 2 2 2 2 2 2 2
Refrigerating circuits 2 1 2 1 2 2 2
Gross total cooling
CW MODE DX MODE

kW 37,1 37,3 39,3 47,0 50,2 49,6 55,9


capacity1,2
Gross sensible cooling
kW 30,3 37,3 39,3 42,3 41,5 49,6 55,9
capacity1,2
Gross total cooling
kW 28,3 41,9 41,9 41,9 41,9 54,0 54,0
capacity1,3
Gross sensible cooling
kW 28,2 41,7 41,7 41,7 41,7 53,7 53,7
capacity1,3
DIMENSIONS
Height mm 1960 1960 1960 1960 1960 1960 1960
Length mm 1010 1720 1720 1720 1720 2170 2170
Depth mm 750 750 865 865 865 865 865
TDER MODEL 1822A 2222A4 2242A4 2522A4 2542A4 2842A4
Fans nr. 2 3 3 3 3 3
Airflow m3/h 15906 21809 21809 21809 21809 21809
N° of compressors 2 2 4 2 4 4
Refrigerating circuits 2 2 2 2 2 2
Gross total cooling
CW MODE DX MODE

kW 60,5 78,4 83,6 86,2 87,9 96,0


capacity1,2
Gross sensible cooling
kW 55,8 72,0 78,3 75,0 75,5 77,7
capacity1,2
Gross total cooling
kW 54,0 97,6 97,6 97,6 97,6 97,6
capacity1,3
Gross sensible cooling
kW 53,7 96,7 96,7 96,7 96,7 96,7
capacity1,3
DIMENSIONS
Height mm 1960 2150 2150 2150 2150 2150
Length mm 2170 2580 2580 2580 2580 2580
Depth mm 750 750 865 865 865 865
TUER MODEL 2222A 2242A 2522A 2542A 2842A
Fans nr. 3 3 3 3 3
Airflow m3/h 22160 22160 23194 23194 23194
N° of compressors 2 4 2 4 4
Refrigerating circuits 2 2 2 2 2
Gross total cooling
CW MODE DX MODE

kW 78,5 83,8 86,8 88,7 96,8


capacity1,2
Gross sensible cooling
kW 72,7 79,2 77,8 78,3 80,4
capacity1,2
Gross total cooling
kW 98,8 98,8 102,3 102,3 102,3
capacity1,3
Gross sensible cooling
kW 97,9 97,9 101,3 101,3 101,3
capacity1,3
DIMENSIONS
Height mm 1960 1960 1960 1960 1960
Length mm 2580 2580 2580 2580 2580
Depth mm 750 865 865 865 865
Life is On | Schneider Electric 53
Energy-saving units with backward-curved fans equipped with EC motor

Uniflair LE
TDEV – TUEV

Range
Cooling capacity: 20 ÷ 100 kW
Refrigerant R-410A
EC fans
Available versions
• Downflow (TDEV)
• Upflow (TUEV)

Standard features
• Advanced microprocessor control system is available with local or remote user terminal. - Rotation and active stand-by management
• The units are equipped with EC fans for efficiency maximization. - Free contact for general and two
• The structure of the unit is characterized by a self-supporting frame in galvanized steel for addressable alarms
with panels. The external panels are coated with RAL9003 epoxy-polyester paint and - Remote on/off switch
internally lined with heat- and sound-proofing insulation. - Ability to interface with modbus protocol directly on
• Electronic expansion valve is controlled by the microprocessor and a dedicated software RS485 serial card
that increases the precision of the cooling and the energy efficiency of the cooling cycle. - Ability to interface with main external communication
• Unit is equipped with an indirect free cooling system that provides the required cooling Protocols: BACnet, Lonworks, Trend, Metasys, TCP/IP,
capacity when the external temperature is lower than the internal ambient. SNMP, and StruxureWare platform
Compressor power consumption is minimized while internal and external
environments are kept separate. Construction options
• The cooling coil is designed for an elevated SHR and reduced pressure drops in the air
• Immersed electrode humidifier (D/U versions)
section. The coil is made from copper tubes mechanically expanded on aluminum fins,
• Low surface temperature electrical heaters with extended
complete with a hydrophilic treatment.
fans, complete with double safety thermostat and manual
• The cooling coil is characterized by CW and direct expansion circuits interlaced to
resetting (T/H versions)
increase the efficiency of the unit in all running conditions.
• Hot gas and hot water reheating
• Internal water-cooled condenser braze is welded and made of AISI 304 stainless steel.
• Uniflair LE units meet the following directives: Machinery Directive 2006/42/EC (MD),
Accessories
Electromagnetic compatibility Directive 2014/30/EU (EMC), Pressure equipment
Directive 2014/68/EU (PED), Regulation (EU) No 517/2014 on fluorinated greenhouse The units can be supplied with the following
gases (F-GAS). external accessories:
• High-efficiency, EU4-pleated air filters are housed in a metal frame and equipped with
• Remote, semi-graphic user terminal
a dirty filter differential pressure switch and low airflow differential pressure switch.
• RS485 serial adapter to communicate
• The Uniflair LE range offers the possibility to select units equipped with two
with external BMS
compressors (tandem) for each circuit, which grants better efficiency and regulation
capacity at partial loads (models with the **21 or **42 suffix). • LON FTT10 serial adapter to communicate
with external BMS managed with LON protocol
• Total front access is available for unit maintenance.
• TCP/IP serial adapter to communicate
• The electrical panel is situated in a compartment separated from the airflow and comp
with external BMS managed with SNMP protocol
lies with the Machinery Directive 2006/42/EC (MD).
• AFPS that can be adapted as a kit with
• Microprocessor control system includes:
installation instructions
- Integrated management of the cooling modes monitoring room temperature, external
• Motorized damper
temperature, and glycol circuit temperature
• Condensate drain pump
- Integrated management of the EEV and refrigerating circuit parameters
• Suction from the top or front discharge plenums
- Local user terminal with external accessibility
• Adjustable floor stands
- Integrated LAN card for local network connection of a group of CRACs

54 Life is On | Schneider Electric


TECHNICAL DATA
1
Gross cooling
capacities; fans must be
TDEV – TUEV MODEL 0511A 0611A 0721A 0722A 0921A 0922A 1021A
deduced to obtain net
Fan type EC backward-curved centrifugal motor fan
cooling data.
Power supply V/ph/Hz 400/3/50
Fans nr. 1 1 1 1 1 1 1 2
Data refers to nominal
Airflow m3/h 5700 5700 8600 8600 8600 8600 8600 conditions: Room
at 24 °C-50% RH,
N° of compressors 1 1 2 2 2 2 2
water temperatures
Refrigerating circuits 1 1 1 2 1 2 1 30 – 35 °C,
Gross total cooling
CW MODE DX MODE

and ESP = 20 Pa.


kW 19,1 23,7 27,0 28,4 30,4 32,2 34,6
capacity1,2
Gross sensible cooling 3
Data refers to nominal
kW 19,1 20,8 27,0 28,4 28,7 28,0 30,5
capacity1,2 conditions: Room
Gross total cooling at 24 °C-50% RH,
kW 20,2 20,2 28,5 28,5 28,5 28,5 28,5
capacity1,3 water temperature
Gross sensible cooling 7/12 °C; glycol 0%,
kW 20,1 20,1 28,3 28,3 28,3 28,3 28,3
capacity1,3 and ESP = 20 Pa.
DIMENSIONS
4
Data refers to
Height mm 1960 1960 1960 1960 1960 1960 1960 downflow unit.
Length mm 1010 1010 1310 1310 1310 1310 1310
Depth mm 750 750 865 865 865 865 865
TDEV – TUEV MODEL 1022A 1121A 1122A 1321A 1322A 1422A 1622A
Fans nr. 1 1 2 2 2 2 2
Airflow m3/h 8600 12320 12320 12320 12320 16000 16000
N° of compressors 2 2 2 2 2 2 2
Refrigerating circuits 2 1 2 1 2 2 2
Gross total cooling
CW MODE DX MODE

kW 37,1 36,9 39,2 46,6 49,7 49,7 55,9


capacity1,2
Gross sensible cooling
kW 30,4 36,9 37,4 40,3 39,9 49,7 55,9
capacity1,2
Gross total cooling
kW 28,5 40,1 40,1 40,1 40,1 54,1 54,1
capacity1,3
Gross sensible cooling
kW 28,3 39,9 39,9 39,9 39,9 53,9 53,9
capacity1,3
DIMENSIONS
Height mm 1960 1960 1960 1960 1960 1960 1960
Length mm 1010 1720 1720 1720 1720 2170 2170
Depth mm 750 750 865 865 865 865 865
TDEV MODEL 1822A 2222A4 2242A4 2522A4 2542A4 2842A4
Fans nr. 2 3 3 3 3 3
Airflow m3/h 16000 21500 21500 21500 21500 21500
N° of compressors 2 2 4 2 4 4
Refrigerating circuits 2 2 2 2 2 2
Gross total cooling
CW MODE DX MODE

kW 60,5 78,2 83,5 86,1 87,7 95,8


capacity1,2
Gross sensible cooling
kW 56,0 71,3 77,6 74,4 74,9 77,1
capacity1,2
Gross total cooling
kW 54,1 96,6 96,6 96,6 96,6 96,6
capacity1,3
Gross sensible cooling
kW 53,9 95,7 95,7 95,7 95,7 95,7
capacity1,3
DIMENSIONS
Height mm 1960 2150 2150 2150 2150 2150
Length mm 2170 2580 2580 2580 2580 2580
Depth mm 750 750 865 865 865 865
TUEV MODEL 2222A 2242A 2522A 2542A 2842A
Fans nr. 3 3 3 3 3
Airflow m3/h 22000 22000 22000 22500 22500
N° of compressors 2 4 2 4 4
Refrigerating circuits 2 2 2 2 2
CW MODE DX MODE

Gross total cooling


kW 78,4 83,7 86,3 88,3 96,4
capacity1,2
Gross sensible cooling
kW 72,4 78,8 75,4 76,9 79,0
capacity1,2
Gross total cooling
kW 98,3 98,3 98,3 100,0 100,0
capacity1,3
Gross sensible cooling
kW 97,4 97,4 97,4 99,0 99,0
capacity1,3
DIMENSIONS
Height mm 1960 1960 1960 1960 1960
Length mm 2580 2580 2580 2580 2580
Depth mm 750 865 865 865 865

Life is On | Schneider Electric 55


Direct-expansion energy-saving units with backward-curved fans equipped with EC motor

Uniflair LE
LDEV

Range
Cooling capacity: 70 ÷ 100 kW
Fixed speed compressors
Refrigerant R-410A
EC fans
Available versions
• Downflow (LDEV)

Standard features
• Downflow configuration with bottom or front discharge • New generation of hermetic scroll compressor with
and suction from the top. Intermediate Discharge Valves (IDVs), built-in thermal
• Metal structural frame and inside part made with hot- protection and anti-vibration feet
dip zinc-plated sheet steel • Refrigerant R410A
• External panels coated with RAL9003 epoxy-polyester • Electronic Expansion Valve (EEV) to provide accurate
paint and internally lined with heat- and sound- control of the refrigerant superheat ensuring high
proofing insulation to class 1 according to energy efficiency also at low external temperatures.
Class B1 according to DIN 4102, BS 476 part 7, • Energy saving units are equipped with a new patent
VO according to UL94, ASTM E84, class M1 pending solution. The 3-way valve is replaced by
according to NFP92-501 three flow control devices designed to maximize
• Internal panels for shutting-off the compartments efficiency and minimize water side pressure drops.
affected by the airflow, made with hot-dip zinc-plated • Electrical panel complying with Machinery Directive
sheet steel and captive screws 2006/42/EC (MD) and Electromagnetic compatibility
• High efficiency EU4 pleated air filters are contained Directive 2014/30/EU (EMC), Regulation (EU)
in a metal frame and equipped with a dirty filter No 517/2014 on fluorinated greenhouse gases
differential pressure switch and a low airflow (F-GAS), housed- in a compartment isolated from the
differential pressure switch. The filters are housed in a airflow and including 24V control circuit transformer,
dedicated plenum box. metal isolating screen for protection from live
• The units are equipped with the latest generation components, mains switch, thermomagnetic
Radical EC Fans for efficiency maximization. Impellers circuit-breakers, terminal board for no-voltage signal
are made of high-tech compound material with and control contacts.
optimized flow control, combined with highly efficient • 7-inch. IT Touch Screen display interface that allows
GreenTech EC motors. These fans are designed to to set operating parameters, monitor the trend
have easier serviceability with quick removability kit. of the main working parameters, and read any
• Low airflow differential pressure switch alarm messages.
• Cooling coil, mounted upstream of the fans, • Schneider Electric IT J-Controller (J5 18 DIN),
constructed of copper tubes expanded into complying with Machinery Directive 2006/42/EC
hydrophilic aluminum fins, complete with stainless (MD) and Electromagnetic compatibility Directive
steel tray and a flexible condensate drain hose 2014/30/EU (EMC), Regulation (EU) No 517/2014 on
fluorinated greenhouse gases (F-GAS), where are
• Brazed plate water-cooled condenser made from
connected analogical and digital inputs necessary for
stainless steel.
control of the unit.
• Double refrigerant circuit each equipped with a
fixed-speed scroll compressor.
• Refrigerant circuits complying with Pressure
Equipment Directive 2014/68/EU (PED) including:
liquid refrigerant receiver, filter-dryer and liquid sight
glass, electronic expansion valve, high-pressure
pressostats with manual reset.

56 Life is On | Schneider Electric


TECHNICAL DATA
1
Gross cooling
capacities; fans must
LDEV MODEL 2422A 2722A
be deduced to obtain
Fan Type EC Backward-curved centrifugal motor fan
net cooling data.
Power supply V/ph/Hz 400/3/50Hz
Fans Nr. 2 2 2
Data refers to nominal
Airflow m3/h 20000 26000 conditions: Room at 24
N° of fixed speed compressors 2 2 °C-50% RH, inlet/outlet
Refrigerating circuits 2 2 water temperatures
Gross total cooling capacity1,2 kW 79,1 94,5 30/36°C, 0% glycol
Gross sensible cooling capacity1,2 kW 66,1 82,1 and ESP = 20 Pa.

DIMENSIONS
Height mm 2150 2150
Length mm 2082 2650
Depth mm 900 900

• Control software design to provide a highly accurate Construction options


real-time control of room conditions and the complete
unit management such as: • Double power supply with automatic integrated
management on the active line to provide redundancy
- electronic expansion valve complete management
and ensure a constant power supply
- advanced interactivity with the installation
• Standard, cleanable or low conductibility humidifier
environment
with immersed-electrodes for modulating steam
- dehumidification operating mode managed by production available as an option for units equipped
means of EEV with devised algorithm which with cooling and humidification configuration
maintains constant air flow
• Condensate drain pump
- double set-point with digital input selection
• Electrical heaters with aluminum-finned heating
- emergency operation elements complete with safety thermostat (for manual
• The design of the IT J-Controller allows to physically resetting) to cut off the power supply in the event
isolate the internal connections from the external of overheating
connections. The external connections on the upper • High efficiency EU5 pleated air filters housed in a
level offer a wide variety of accessibility options: dedicated plenum box
- External CAN and Group CAN • Power phase correction capacitors for compressors
- Isolated 2-wire and 4-wire RS485 ports • Active Flow Control to improve the balance of airflow
- NetBotz universal sensor ports between the cooling structure and IT equipment.
- Alarm/Shutdown Contacts • Energy meter and CO2 emission calculator
- USB ports (Host, Device) • Motorized damper on the air return side
- Ethernet
- HDMI display interface Accessories
- Modbus The units can be supplied with the following
- Remote shutdown input external accessories:
• Ability to interface with most common external • Suction / discharge plenums
BMS on communication protocols and boosting on • Direct free-cooling plenums
connection towards Schneider monitoring systems:
• Floor stands with or without motorized damper
- Modbus/RTU RS485
• Height adjustable base frame
- SNMP
• Room temperature and humidity sensor
- Modbus Over IP
• Smoke and fire sensors
- StruxureWare
• Water leak detectors
- StruxureON
- Cooling Tuner as service diagnostic tool

Life is On | Schneider Electric 57


Twin-cool air-cooled units with backward-curved fans

Uniflair LE
TDTR – TUTR

Range
Cooling capacity: 20 ÷ 100 kW
Refrigerant R-410A
Available versions
• Downflow (TDTR)
• Upflow (TUTR)

Standard features
• Advanced microprocessor control system is available • High-efficiency, EU4-pleated air filters are housed
with local or remote user terminal. in a metal frame and equipped with a dirty filter differential
• The units are equipped with backward-curved fans pressure switch and low airflow differential pressure switch.
and directly coupled asynchronous motor. • The Uniflair LE range offers the possibility to select units
• The structure of the unit is characterized equipped with two compressors (tandem) for each circuit,
by a self-supporting frame in galvanized steel which grants better efficiency and regulation capacity at
with panels. The external panels are coated partial loads (models with the **21 or **42 suffix).
with RAL9003 epoxy-polyester paint and internally • Total front access is included for unit maintenance.
lined with heat- and sound-proofing insulation. • The electrical panel is situated in a compartment separated
• Unit is characterized by two independent cooling from the airflow and complies with the Machinery Directive
sources — one CW with related circuit and one direct 2006/42/EC (MD).
expansion air cooled. • Microprocessor control system includes:
• Electronic expansion valve is controlled by the - Integrated management of the EEV
microprocessor and a dedicated software that and refrigerating circuit parameters
increases the cooling precision and the energy - Local user terminal with external accessibility
efficiency of the cooling cycle. - Integrated LAN card for local network connection of
• The cooling coil is designed for an elevated SHR a group of CRACs
and reduced pressure drops in the air section. The coil - Rotation and active stand-by management
is made from copper tubes mechanically expanded on - Free contact for general and two for addressable alarms
aluminum fins, complete with a hydrophilic treatment.
- Remote on/off switch
• Uniflair LE units meet the following directives:
- Ability to interface with modbus protocol
Machinery Directive 2006/42/EC (MD),
directly on RS485 serial card
Electromagnetic compatibility Directive 2014/30/EU
- Ability to interface with main external communication
(EMC), Pressure equipment Directive 2014/68/EU
protocols: BACnet, Lonworks, Trend, Metasys, TCP/IP,
(PED), Regulation (EU) No 517/2014 on fluorinated
SNMP, and StruxureWare platform
greenhouse gases (F-GAS).

58 Life is On | Schneider Electric


TECHNICAL DATA
1
Gross cooling
capacities; fans
TDTR MODEL 0611A 0921A 1321A 1622A 1822A 2242A 4
2542A 4
2842A 4
must be deduced
Fan type Backward-curved centrifugal motor fan
to obtain net
Power supply V/ph/Hz 400/3/50 cooling data.
Fans nr. 1 1 2 2 2 3 3 3
Airflow m3/h 5827 8541 11574 15905 15905 21809 21709 21809 2
Data refers to nominal
N° of compressors 1 2 2 2 2 4 4 4 conditions : Room
at 24 °C-50% RH,
Refrigerating circuits 1 1 1 2 2 2 2 2
water temperatures
Gross total cooling
CW MODE DX MODE

kW 23,6 30,3 46,1 58,5 63,4 82,5 81,7 91,2 30 – 35 °C,


capacity1,2
and ESP = 20 Pa.
Gross sensible cooling
kW 20,9 28,5 38,3 55,3 55,3 78,1 73,8 76,3
capacity1,2 3
Data refers to nominal
Gross total cooling conditions: Room
kW 20,5 28,3 38,6 53,9 53,9 97,6 97,3 97,6
capacity1,3
at 24 °C-50% RH,
Gross sensible cooling water temperature
kW 20,4 28,2 38,4 53,7 53,7 96,7 96,4 96,7
capacity1,3
7/12 °C; glycol 0%,
DIMENSIONS and ESP = 20 Pa.
Height mm 1960 1960 1960 1960 1960 2150 2150 2150
4
Data refers to
Length mm 1010 1310 1720 2170 2170 2580 2580 2580
downflow unit.
Depth mm 750 865 865 865 750 865 865 865
TUTR MODEL 2242A 2542A 2842A
Fans nr. 3 3 3
Airflow m3/h 22160 23194 23194
N° of compressors 4 4 4
Refrigerating circuits 2 2 2
Gross total cooling
CW MODE DX MODE

kW 82,7 82,5 91,9


capacity1,2
Gross sensible cooling
kW 79,0 77,1 79,0
capacity1,2
Gross total cooling
kW 98,8 102,3 102,3
capacity1,3
Gross sensible cooling
kW 97,9 101,3 101,3
capacity1,3
DIMENSIONS
Height mm 1960 1960 1960
Length mm 2580 2580 2580
Depth mm 865 865 865

Construction options Accessories


• Immersed electrode humidifier (D/U versions) The units can be supplied with the following external accessories:
• Low surface temperature electrical heaters
• Remote, semi-graphic user terminal
with extended fans, complete with double safety
thermostat and manual resetting (T/H versions) • RS485 serial adapter to communicate with external BMS
• Hot gas and hot water reheating • LON FTT10 serial adapter to communicate with external BMS
managed with LON protocol
• TCP/IP serial adapter to communicate with external BMS
managed with SNMP protocol
• AFPS that can be adapted as a kit with installation instructions
• Motorized damper
• Condensate drain pump
• Suction from the top or front discharge plenums
• Adjustable floor stands

Life is On | Schneider Electric 59


Twin-cool air-cooled units with backward-curved fans equipped with EC motor

Uniflair LE
TDTV – TUTV

Range
Cooling capacity: 20 ÷ 100 kW
Refrigerant R-410A
EC fans
Available versions
• Downflow (TDTV)
• Upflow (TUTV)

Standard features
• Advanced microprocessor control system is available • Uniflair LE units meet the following directives: Machinery Directive
with local or remote user terminal. 2006/42/EC (MD), Electromagnetic compatibility Directive 2014/30/EU
• The units are equipped with EC fans for (EMC), Pressure equipment Directive 2014/68/EU (PED), Regulation (EU)
efficiency maximization. No 517/2014 on fluorinated greenhouse gases (F-GAS).
• The structure of the unit is characterized • High-efficiency, EU4-pleated air filters are housed in a metal frame and
by a self-supporting frame in galvanized steel equipped with a dirty filter differential pressure switch and low airflow
with panels. The external panels are coated differential pressure switch.
with RAL9003 epoxy-polyester paint and internally • The Uniflair LE range offers the possibility to select units equipped with two
lined with heat- and sound-proofing insulation. compressors (tandem) for each circuit, which grants better efficiency and
• Electronic expansion valve is controlled regulation capacity at partial loads (models with the **21 or **42 suffix).
by the microprocessor and a dedicated software • Total front access is included for unit maintenance.
that increases the cooling precision and the energy • The electrical panel is situated in a compartment separated from the
efficiency of the cooling cycle. airflow and complies with the Machinery Directive 2006/42/EC (MD).
• Unit is characterized by two independent cooling • Microprocessor control system includes:
sources — one CW with related circuit and one - Integrated management of the EEV and refrigerating
direct expansion air cooled. circuit parameters
• The cooling coil is designed for an elevated SHR - Local user terminal with external accessibility
and reduced pressure drops in the air section. The coil - Integrated LAN card for local network connection of
is made from copper tubes mechanically expanded on a group of CRACs
aluminum fins, complete with a hydrophilic treatment. - Rotation and active stand-by management
• The cooling coil is characterized by CW and direct - Free contact for general and two for addressable alarms
expansion circuits interlaced to increase the efficiency
- Remote on/off switch
of the unit in all running conditions.
- Ability to interface with modbus protocol
• The CW circuit is equipped with a three-way valve
directly on RS485 serial card
and an actuator integrated with the microprocessor.
- Ability to interface with main external communication
protocols: BACnet, Lonworks, Trend, Metasys, TCP/IP,
SNMP, and StruxureWare platform

60 Life is On | Schneider Electric


TECHNICAL DATA
1
Gross cooling
capacities; fans
TDTV MODEL 0611A 0921A 1321A 1622A 1822A 2242A 2542A 2842A
must be deduced
Fan type EC backward-curved centrifugal motor fan
to obtain net
Power supply V/ph/Hz 400/3/50 cooling data.
Fans nr. 1 1 2 2 2 3 3 3
Airflow m3/h 5700 8600 12320 16000 16000 21500 21500 21500 2
Data refers to nominal
N° of compressors 1 2 2 2 2 4 4 4 conditions: Room
at 24 °C-50% RH,
Refrigerating circuits 1 1 1 2 2 2 2 2
45 °C condensing
Gross total cooling
CW MODE DX MODE

kW 23,5 30,3 46,5 58,5 63,4 82,4 81,6 91,0 temperature,


capacity1,2
and ESP = 20 Pa.
Gross sensible cooling
kW 20,6 28,7 39,8 55,6 55,5 77,4 73,4 75,7
capacity1,2 3
Data refer to nominal
Gross total cooling conditions: Room
kW 20,2 28,5 40,1 54,1 54,1 96,6 96,6 96,6
capacity1,3
at 24 °C-50% RH,
Gross sensible cooling water temperature
kW 20,1 28,3 39,9 53,9 53,9 95,7 95,7 95,7
capacity1,3 7/12 °C; glycol 0%,
DIMENSIONS and ESP = 20 Pa.

Height mm 1960 1960 1960 1960 1960 2150 2150 2150


Length mm 1010 1310 1720 2170 2170 2580 2580 2580
Depth mm 750 865 865 865 750 865 865 865
TUTV MODEL 2242A 2542A 2842A
Fans nr. 3 3 3
Airflow m3/h 22000 22500 22500
N° of compressors 4 4 4
Refrigerating circuits 2 2 2
Gross total cooling
DX MODE

kW 82,6 82,1 91,5


capacity1,2
Gross sensible cooling
kW 78,6 75,5 77,6
capacity1,2
Gross total cooling
CW MODE

kW 98,3 100,0 100,0


capacity1,3
Gross sensible cooling
kW 97,4 99,0 99,0
capacity1,3
DIMENSIONS
Height mm 1960 1960 1960
Length mm 2580 2580 2580
Depth mm 865 865 865

Construction options Accessories


• Immersed electrode humidifier (D/U versions) The units can be supplied with the following external accessories:
• Low surface temperature electrical heaters
• Remote, semi-graphic user terminal
with extended fans, complete with double safety
thermostat and manual resetting (T/H versions) • RS485 serial adapter to communicate with external BMS
• Hot gas and hot water reheating • LON FTT10 serial adapter to communicate with external BMS
managed with LON protocol
• TCP/IP serial adapter to communicate with external BMS
managed with SNMP protocol
• AFPS that can be adapted as a kit with installation instructions
• Motorized damper
• Condensate drain pump
• Suction from the top or front discharge plenums
• Adjustable floor stands

Life is On | Schneider Electric 61


Twin-cool water-cooled units with backward-curved fans

Uniflair LE
TDDR – TUDR

Range
Cooling capacity: 20 ÷ 100 kW
Refrigerant R-410A
Available versions
• Downflow (TDDR)
• Upflow (TUDR)

Standard features
• Advanced microprocessor control system is available • High-efficiency, EU4-pleated air filters are housed in a metal
with local or remote user terminal. frame and equipped with a dirty filter differential pressure
• The units are equipped with Backward-curved fans switch and low airflow differential
and directly coupled asynchronous motor. pressure switch.
• The structure of the unit is characterized by a self- • The Uniflair LE range offers the possibility to select units
supporting frame in galvanized steel with panels. equipped with two compressors (tandem) for each circuit,
The external panels are coated with RAL9003 which grants better efficiency and regulation capacity
epoxy-polyester paint and internally lined with heat- at partial loads (models with the **21 or **42 suffix).
and sound-proofing insulation. • Total front access is included for unit maintenance.
• Electronic expansion valve is controlled by the • The electrical panel is situated in a compartment separated
microprocessor and a dedicated software that from the airflow and complies with the Machinery Directive
increases the precision of the cooling and the energy 2006/42/EC (MD).
efficiency of the cooling cycle. • Microprocessor control system includes:
• The cooling coil is designed for an elevated SHR and - Integrated management of the EEV and refrigerating
reduced pressure drops in the air section. The coil is circuit parameters
made from copper tubes mechanically expanded on - Local user terminal with external accessibility
aluminum fins, complete with a hydrophilic treatment. - Integrated LAN card for local network connection of
• Internal water-cooled condenser braze is welded and a group of CRACs
made of AISI 304 stainless steel. - Rotation and active stand-by management
• Uniflair LE units meet the following directives: - Free contact for general and two for addressable alarms
Machinery Directive 2006/42/EC (MD), - Remote on/off switch
Electromagnetic compatibility Directive 2014/30/EU
- Ability to interface with modbus protocol
(EMC), Pressure equipment Directive 2014/68/EU
directly on RS485 serial card
(PED), Regulation (EU) No 517/2014 on fluorinated
- Ability to interface with main external communication
greenhouse gases (F-GAS).
protocols: BACnet, Lonworks, Trend, Metasys, TCP/IP,
SNMP, and StruxureWare platform

62 Life is On | Schneider Electric


TECHNICAL DATA
1
Gross cooling
capacities; fans must be
TDDR MODELS 611 921 1321 1622 1822 2242 4
2542 4
2842 4
deduced to obtain net
Fan type Backward-curved centrifugal motor fan
cooling data.
Power supply V/ph/Hz 400/3/50
Fans nr. 1 1 2 2 2 3 3 3 2
Data refers to nominal
Airflow m3/h 5827 8541 11574 15905 15905 21809 21709 21809 conditions: Room
N° of compressors 1 2 2 2 2 4 4 4 at 24 °C-50% RH,
water temperatures
Refrigerating circuits 1 1 1 2 2 2 2 2
30 – 35 °C,
Gross total cooling
CW MODE DX MODE

kW 23,8 30,4 46,2 55,9 60,5 90,5 87,8 96,0 and ESP = 20 Pa.
capacity1,2
Gross sensible cooling Data refers to nominal
kW 21,1 28,5 38,8 55,9 55,8 79,7 75,3 77,7 3
capacity1,2
conditions: Room
Gross total cooling at 24 °C-50% RH,
kW 20,5 28,3 38,6 53,9 53,9 97,6 97,3 97,6
capacity1,3
water temperature
Gross sensible cooling 7/12 °C; glycol 0%,
kW 20,4 28,2 38,4 53,7 53,7 96,7 96,4 96,7
capacity1,3
and ESP = 20 Pa.
DIMENSIONS
Height mm 1960 1960 1960 1960 1960 2150 2150 2150
4
Data refers to
downflow unit.
Length mm 1010 1310 1720 2170 2170 2580 2580 2580
Depth mm 750 865 865 865 750 865 865 865
TUDR MODELS 2242A 2542A 2842A
Fans nr. 3 3 3
Airflow m3/h 22160 23194 23194
N° of compressors 4 4 4
Refrigerating circuits 2 2 2
Gross total cooling
CW MODE DX MODE

kW 90,6 88,7 96,8


capacity1,2
Gross sensible cooling
kW 80,5 78,3 80,4
capacity1,2
Gross total cooling
kW 98,8 102,3 102,3
capacity1,3
Gross sensible cooling
kW 97,9 101,3 101,3
capacity1,3
DIMENSIONS
Height mm 1960 1960 1960
Length mm 2580 2580 2580
Depth mm 865 865 865

Construction options Accessories


• Immersed electrode humidifier (D/U versions) The units can be supplied with the following external accessories:
• Low surface temperature electrical heaters with
• Remote, semi-graphic user terminal
extended fans, complete with double safety
thermostat and manual resetting (T/H versions) • RS485 serial adapter to communicate with external BMS
• Hot gas and hot water reheating • LON FTT10 serial adapter to communicate with external BMS
managed with LON protocol
• Condensation control on refrigerant side with
constant water flow • TCP/IP serial adapter to communicate with external BMS
managed with SNMP protocol
• AFPS that can be adapted as a kit with installation instructions
• Motorized damper
• Condensate drain pump
• Suction from the top or front discharge plenums
• Adjustable floor stands

Life is On | Schneider Electric 63


Twin-cool water-cooled units with backward-curved fans equipped with EC motor

Uniflair LE
TDDV – TUDV

Range
Cooling capacity: 20 ÷ 100 kW
Refrigerant R-410A
EC fans
Available versions
• Downflow (TDDV)
• Upflow (TUDV)

Standard features
• Advanced microprocessor control system is available with local or remote user terminal. • The electrical panel is situated in a compartment
• The units are equipped with EC fans for efficiency maximization. separated from the airflow and complies with the
• The structure of the unit is characterized by a self-supporting frame in galvanized steel Machinery Directive 2006/42/EC (MD).
with panels. The external panels are coated with RAL9003 epoxy-polyester paint and • Microprocessor control system includes:
internally lined with heat- and sound-proofing insulation. - Integrated management of the EEV and refrigerating
• Electronic expansion valve is controlled by the microprocessor and a dedicated circuit parameters
software that increases the precision of the cooling and the energy efficiency of - Local user terminal with external accessibility
the cooling cycle. - Integrated LAN card for local network connection of
• Unit is characterized by two independent cooling sources — one CW with related a group of CRACs
circuit and one direct expansion water cooled. - Rotation and active stand-by management
• The cooling coil is designed for an elevated SHR and reduced pressure drops in the - Free contact for general and two for addressable alarms
air section. The coil is made from copper tubes mechanically expanded on aluminum - Remote on/off switch
fins, complete with a hydrophilic treatment. - Ability to interface with modbus protocol directly on
• The cooling coil is characterized by CW and direct expansion circuits interlaced to RS485 serial card
increase the efficiency of the unit in all running conditions. - Ability to interface with main external communication
• Internal water-cooled condenser braze is welded and made of AISI 304 stainless steel. protocols: BACnet, Lonworks, Trend, Metasys, TCP/IP,
• The CW circuit is equipped with a three-way valve and an actuator integrated with SNMP, and StruxureWare platform
the microprocessor.
• Uniflair LE units meet the following directives: Machinery Directive 2006/42/EC (MD),
Electromagnetic compatibility Directive 2014/30/EU (EMC), Pressure equipment
Directive 2014/68/EU (PED), Regulation (EU) No 517/2014 on fluorinated greenhouse
gases (F-GAS).
• High-efficiency, EU4-pleated air filters are housed in a metal frame and equipped with
a dirty filter differential pressure switch and low airflow differential pressure switch.
• The Uniflair LE range offers the possibility to select units equipped with two compressors
(tandem) for each circuit, which grants better efficiency and regulation capacity at
partial loads (models with the **21 or **42 suffix).
• Total front access is included for unit maintenance.

64 Life is On | Schneider Electric


TECHNICAL DATA
1
Gross cooling
capacities; fans
TDDV MODEL 0611A 0921A 1321A 1622A 1822A 2242A 4
2542A 4
2842A 4
must be deduced
Fan type EC backward-curved centrifugal motor fan
to obtain net
Power supply V/ph/Hz 400/3/50 cooling data.
Fans nr. 1 1 2 2 2 3 3 3
Airflow m3/h 5700 8600 12320 16000 16000 21500 21500 21500 2
Data refers to nominal
N° of compressors 1 2 2 2 2 4 4 4 conditions: Room
at 24 °C-50% RH,
Refrigerating circuits 1 1 1 2 2 2 2 2
water temperatures
DX MODE

Gross total cooling


kW 23,7 30,4 46,6 55,9 60,5 90,3 87,7 95,8 30 – 35 °C,
capacity1,2
and ESP = 20 Pa.
Gross sensible cooling
kW 20,8 28,7 40,3 55,9 56,0 79,0 74,9 77,1
capacity1,2 3
Data refers to nominal
Gross total cooling
CW MODE

kW 20,2 28,5 40,1 54,1 54,1 96,6 96,6 96,6 conditions: Room
capacity1,3
at 24 °C-50% RH,
Gross sensible cooling water temperature
kW 20,1 28,3 39,9 53,9 53,9 95,7 95,7 95,7
capacity1,3
7/12 °C; glycol 0%,
DIMENSIONS and ESP = 20 Pa.
Height mm 1960 1960 1960 1960 1960 2150 2150 2150
4
Data refers to
Length mm 1010 1310 1720 2170 2170 2580 2580 2580
downflow unit.
Depth mm 750 865 865 865 750 865 865 865
TUDV MODEL 2242A 2542A 2842A
Fans nr. 3 3 3
Airflow m3/h 22000 22500 22500
N° of compressors 4 4 4
Refrigerating circuits 2 2 2
Gross total cooling
CW MODE DX MODE

kW 90,6 88,3 96,4


capacity1,2
Gross sensible cooling
kW 80,1 76,9 79,0
capacity1,2
Gross total cooling
kW 98,3 100,0 100,0
capacity1,3
Gross sensible cooling
kW 97,4 99,0 99,0
capacity1,3
DIMENSIONS
Height mm 1960 1960 1960
Length mm 2580 2580 2580
Depth mm 865 865 865

Construction options Accessories


• Immersed electrode humidifier (D/U versions) The units can be supplied with the following external accessories:
• Low surface temperature electrical heaters
• Remote, semi-graphic user terminal
with extended fans, complete with double safety
thermostat and manual resetting (T/H versions) • RS485 serial adapter to communicate with external BMS
• Hot gas and hot water reheating • LON FTT10 serial adapter to communicate with external BMS
managed with LON protocol
• Condensation control on refrigerant side with
constant water flow • TCP/IP serial adapter to communicate with external BMS
managed with SNMP protocol
• AFPS that can be adapted as a kit with installation instructions
• Motorized damper
• Condensate drain pump
• Suction from the top or front discharge plenums
• Adjustable floor stands

Life is On | Schneider Electric 65


Direct-expansion air-cooled units with backward-curved fans equipped with
EC motor and variable speed brushless compressors

Uniflair LE
IDAV

Range
Cooling capacity: 20 ÷ 100 kW
Refrigerant R-410A
Brushless compressors
EC fans
Available versions
• Downflow air cooled

Standard features
• Brushless variable speed scroll DC compressor. • Internal water-cooled condenser braze is welded
• Units in tandem version (models **21) equipped and made of AISI 304 stainless steel.
with one brushless compressor and one fixed • Uniflair LE units meet the following directives:
speed compressor. Machinery Directive 2006/42/EC (MD), Electromagnetic
• Advanced microprocessor control system compatibility Directive 2014/30/EU (EMC), Pressure
with a local or remote user terminal. equipment Directive 2014/68/EU (PED), Regulation (EU)
• The units are equipped with EC fans for No 517/2014 on fluorinated greenhouse gases (F-GAS).
efficiency maximization. • High-efficiency, EU4-pleated air filters are housed in
• The structure of the unit is characterized by a metal frame and equipped with a dirty filter differential
a self-supporting frame in galvanized steel with pressure switch and low airflow differential pressure switch.
panels. The external panels are coated with • Total front access is available for unit maintenance.
RAL9003 epoxy-polyester paint and internally • The electrical panel is situated in a compartment separated
lined with heat- and sound-proofing insulation. from the airflow and complies with the Machinery Directive
• Electronic expansion valve is controlled by the 2006/42/EC (MD).
microprocessor and a dedicated software that • Advanced microprocessor control UG50.
increases the cooling precision and the energy • Free-contact for general alarm and 2 for addressable alarms.
efficiency of the cooling cycle. • Remote on/off switch.
• The cooling coil is designed for an elevated SHR • Integrated RS485 serial card for direct connection
and reduced pressure drops in the air section. external BMS (modbus).
• The coil is made from copper tubes mechanically • Second slot for additional serial card for BMS
expanded on aluminum fins, complete with a connection (optional).
hydrophilic treatment. • Clock card integrated in the unit.
• Discharge temperature control (option).

66 Life is On | Schneider Electric


TECHNICAL DATA
1
Gross cooling
capacities; fans must be
IDAV 0601A 0611A 1021A 1321A 1421A
deduced to obtain net
Fan type EC backward-curved centrifugal motor fan
cooling data.
Power supply V/ph/Hz 400/3/50 Hz
Fans nr. 2 1 1 2 2 2
Data refers to nominal
Airflow m3/h 4500 5700 8600 12320 16500 conditions: Room
Compressors 1 1 1+1 1+1 1+1 at 24 °C-50% RH,
45 °C condensing
Refrigerating circuits 1 1 1 2 2
temperature,
Gross total cooling
kW 23,1 23,4 31,4 39,3 53,4 and ESP = 20 Pa.
capacity1,2
Gross sensible cooling
kW 16,6 20,2 26,3 35,3 53,4
capacity1,2
DIMENSIONS
Height mm 1740 1960 1960 1960 1960
Length mm 1200 1010 1310 1710 2170
Depth mm 450 750 865 865 865

Construction options Accessories


• Intelligent dehumidification integrated in the unit The units can be supplied with the following external accessories:
• Advanced microprocessor control system
• Double power supply with automatic
UG50 is included
changeover and manual selection with
• Integrated discharge temperature control
integrated ultracapacitor (ETO)
and room moisture control
• Automatic floor pressurization system
• Energy meter and CO2 emissions calculator
integrated in the unit (ETO)
• Ultracapacitor for single power supply units.
• Direct free-cooling (on demand)
• Air-cooled condensers equipped with EC fans

Life is On | Schneider Electric 67


Direct-expansion air-cooled units with backward-curved fans equipped with EC motor

Uniflair LE
IDAV - IUAV

Range
Cooling capacity: 50 ÷ 140 kW
1 VSD compressor and 1 fixed speed compressor
Refrigerant R-410A
EC fans
Available versions
• Downflow (IDAV)
• Upflow (IUAV)

Standard features
• Air flow configuration: • Refrigerant circuits complying with Pressure
- Downflow configuration with bottom or front Equipment Directive 2014/68/EU (PED) including:
discharge and suction from the top liquid refrigerant receiver, filter-dryer and liquid sight
glass, electronic expansion valve, high-pressure
- Upflow configuration with top discharge and
pressostats with manual reset.
bottom or front return
• New generation of hermetic scroll compressor:
• Metal structural frame and inside part made with
hot-dip zinc-plated sheet steel - Fixed-speed compressors with Intermediate
Discharge Valves (IDVs), built-in thermal protection
• External panels coated with RAL9003 epoxy-polyester
and anti-vibration feet
paint and internally lined with heat- and sound-
proofing insulation to class 1 according to Class - Variable speed scroll compressors with a
B1 according to DIN 4102, BS 476 part 7,VO brushless Interior Permanent Magnet (IPM)
according to UL94, ASTM E84, class M1 and dedicated variable speed drive designed
according to NFP92-501 to provide maximum efficiency across the full
operating range
• Internal panels for shutting-off the compartments
affected by the airflow, made with hot-dip zinc-plated • Refrigerant R410A
sheet steel and captive screws • Electronic Expansion Valve (EEV) to provide accurate
• High efficiency EU4 pleated air filters are contained control of the refrigerant superheat ensuring high
in a metal frame and equipped with a dirty filter energy efficiency also at low external temperatures.
differential pressure switch and a low airflow • Electrical panel complying with Machinery Directive
differential pressure switch. Downflow units have 2006/42/EC (MD) and Electromagnetic compatibility
filters housed in a dedicated plenum box. Directive 2014/30/EU (EMC), Regulation (EU)
• The units are equipped with the latest generation No 517/2014 on fluorinated greenhouse gases (F-GAS),
Radical EC Fans for efficiency maximization. Impellers housed- in a compartment isolated from the airflow and
are made of high-tech compound material with including 24V control circuit transformer, metal isolating
optimized flow control, combined with highly efficient screen for protection from live components, mains
GreenTech EC motors. These fans are designed to switch, thermomagnetic circuit-breakers, terminal board
have easier serviceability with quick removability kit. for no-voltage signal and control contacts.
• Low airflow differential pressure switch • 7 inch. IT Touch Screen display interface that allows
to set operating parameters, monitor the trend of
• Cooling coil, mounted upstream of the fans,
the main working parameters, and read any alarm
constructed of copper tubes expanded into
messages.
hydrophilic aluminum fins, complete with stainless
steel tray and a flexible condensate drain hose • Schneider Electric IT J-Controller (J5 18 DIN),
complying with Machinery Directive 2006/42/EC
• Single (**11A models) or double (**22A models)
(MD) and Electromagnetic compatibility Directive
refrigerant circuit each equipped with a scroll
2014/30/EU (EMC), Regulation (EU) No 517/2014 on
compressor (one fixed-speed and one brushless
fluorinated greenhouse gases (F-GAS), where are
inverter driven, except the 1511A model that is
connected analogical and digital inputs necessary for
equipped with only one brushless inverter driven
control of the unit.
scroll compressor)

68 Life is On | Schneider Electric


TECHNICAL DATA
1
Gross cooling
capacities; fans must
IDAV MODEL 1511A 1922A 2022A 2422A 2922A 3822A
be deduced to obtain
Fan Type EC Backward-curved centrifugal motor fan
net cooling data.
Power supply V/ph/Hz 400/3/50Hz
Fans Nr. 2 2 2 2 2 3 2
Data refers to nominal
Airflow m3/h 16800 16800 17000 20000 26000 27000 conditions: Room at 24
N° of fixed speed compressors - 1 1 1 1 1 °C-50% RH, inlet/outlet
N° of variable speed compressors 1 1 1 1 1 1 water temperatures
Refrigerating circuits 2 2 2 2 2 2 30/35°C, 0% glycol
Gross total cooling capacity1,2 kW 56,0 61,7 63,8 91,3 101,4 133,2 and ESP = 20 Pa.
Gross sensible cooling capacity1,2 kW 54,9 57,2 60,9 75,8 92,4 108,9
DIMENSIONS
Height mm 2150 2150 2150 2150 2150 2150
Length mm 1777 1777 2082 2082 2650 2650
Depth mm 900 900 900 900 900 900
IUWV MODEL 1511A 1922A 2022A 2422A 2922A 3822A
Fan type EC Backward-curved centrifugal motor fan
Power supply V/ph/Hz 400/3/50Hz
Fans Nr. 2 2 2 2 2 3
Airflow m3/h 16800 16800 17000 20000 26000 27000
N° of fixed speed compressors - 1 1 1 1 1
N° of variable speed compressors 1 1 1 1 1 1
Refrigerating circuits 2 2 2 2 2 2
Gross total cooling capacity1,2 kW 56,0 61,7 63,8 91,3 101,4 133,2
Gross sensible cooling capacity1,2 kW 54,9 57,2 60,9 75,8 92,4 108,9
DIMENSIONS
Height mm 1950 1950 1950 1950 1950 1950
Length mm 1777 1777 2082 2082 2650 2650
Depth mm 900 900 900 900 900 900

• Control software design to provide a highly accurate Construction options


real-time control of room conditions and the complete
unit management such as: • Double power supply with automatic integrated
management on the active line to provide redundancy
- electronic expansion valve complete management
and ensure a constant power supply
- advanced interactivity with the installation
• Standard, cleanable or low conductibility humidifier
environment
with immersed-electrodes for modulating steam
- dehumidification operating mode managed by production available as an option for units equipped
means of EEV with devised algorithm which with cooling and humidification configuration
maintains constant air flow
• Condensate drain pump
- double set-point with digital input selection
• Electrical heaters with aluminum-finned heating
- emergency operation elements complete with safety thermostat (for manual
• The design of the IT J-Controller allows to physically resetting) to cut off the power supply in the event of
isolate the internal connections from the external overheating
connections. The external connections on the upper • High efficiency EU5 pleated air filters. Downflow units
level offer a wide variety of accessibility options: have filters housed in a dedicated plenum box.
- External CAN and Group CAN • Power phase correction capacitors for compressors
- Isolated 2-wire and 4-wire RS485 ports • Active Flow Control to improve the balance of airflow
- NetBotz universal sensor ports between the cooling structure and IT equipment.
- Alarm/Shutdown Contacts • Energy meter and CO2 emission calculator
- USB ports (Host, Device) • Motorized damper on the air return side
- Ethernet
- HDMI display interface Accessories
- Modbus The units can be supplied with the following
- Remote shutdown input external accessories:
• Ability to interface with most common external • Suction / discharge plenums
BMS on communication protocols and boosting on • Direct free-cooling plenums
connection towards Schneider monitoring systems:
• Floor stands with or without motorized damper
- Modbus/RTU RS485
• Height adjustable base frame
- SNMP
• Room temperature and humidity sensor
- Modbus Over IP
• Smoke and fire sensors
- StruxureWare
• Water leak detectors
- StruxureON
• Check and by-pass valves kit
- Cooling Tuner as service diagnostic tool

Life is On | Schneider Electric 69


Direct-expansion air-cooled units with backward-curved fans equipped with EC motor

Uniflair LE
IXAV

Range
Cooling capacity: 70 ÷ 150 kW
1 VSD compressor and 1 fixed speed compressor
FPO Refrigerant R-410A
EC fans
Available versions
• Underfloor (IXAV)

Standard features
• Underfloor configuration with top return and multiple • Refrigerant circuits complying with Pressure
fan module configurations: Equipment Directive 2014/68/EU (PED) including:
- bottom discharge liquid refrigerant receiver, filter-dryer and liquid sight
glass, electronic expansion valve, high-pressure
- rear discharge
pressostats with manual reset.
- front discharge
• New generation of hermetic scroll compressor:
- front and side discharge
- Fixed-speed compressors with Intermediate
- fully open discharge Discharge Valves (IDVs), built-in thermal protection
• Metal structural frame and inside part made with and anti-vibration feet
hot-dip zinc-plated sheet steel - Variable speed scroll compressors with a
• External panels coated with RAL9003 epoxy-polyester brushless Interior Permanent Magnet (IPM)
paint and internally lined with heat- and sound-proofing and dedicated variable speed drive designed
insulation to class 1 according to Class B1 according to provide maximum efficiency across the full
to DIN 4102, BS 476 part 7,VO according to UL94, operating range
ASTM E84, class M1 according to NFP92-501 • Refrigerant R410A
• Internal panels for shutting-off the compartments • Electronic Expansion Valve (EEV) to provide accurate
affected by the airflow, made with hot-dip zinc-plated control of the refrigerant superheat ensuring high
sheet steel and captive screws energy efficiency also at low external temperatures.
• High efficiency EU4 pleated air filters are contained • Electrical panel complying with Machinery Directive
in a metal frame and equipped with a dirty filter 2006/42/EC (MD) and Electromagnetic compatibility
differential pressure switch and a low airflow differential Directive 2014/30/EU (EMC), Regulation (EU)
pressure switch. Air filters are housed in a dedicated No 517/2014 on fluorinated greenhouse gases (F-GAS),
plenum box. housed- in a compartment isolated from the airflow and
• The units are equipped with the latest generation including 24V control circuit transformer, metal isolating
Radical EC Fans for efficiency maximization. Impellers screen for protection from live components, mains
are made of high-tech compound material with switch, thermomagnetic circuit-breakers, terminal board
optimized flow control, combined with highly efficient for no-voltage signal and control contacts.
GreenTech EC motors. These fans are designed to • 7 inch. IT Touch Screen display interface that allows
have easier serviceability with quick removability kit. to set operating parameters, monitor the trend of
• Low airflow differential pressure switch the main working parameters, and read any alarm
messages.
• Cooling coil, mounted upstream of the fans,
constructed of copper tubes expanded into hydrophilic • Schneider Electric IT J-Controller (J5 18 DIN),
aluminum fins, complete with stainless steel tray and a complying with Machinery Directive 2006/42/EC (MD)
flexible condensate drain hose and Electromagnetic compatibility Directive 2014/30/
EU (EMC), Regulation (EU) No 517/2014 on fluorinated
• Double (**22A models) refrigerant circuit each
greenhouse gases (F-GAS), where are connected
equipped with a scroll compressor (one fixed-speed
analogical and digital inputs necessary for control of
and one brushless inverter driven)
the unit.

70 Life is On | Schneider Electric


TECHNICAL DATA
1
Gross cooling
capacities; fans must
IXAV MODEL 2322A 2622A 4022A
be deduced to obtain
Fan type EC Backward-curved centrifugal motor fan
net cooling data.
Power supply V/ph/Hz 400/3/50Hz
Fans Nr. 2 2 3 2
Data refers to nominal
Airflow m3/h 18800 23400 30000 conditions: Room
N° of fixed speed compressors 1 1 1 at 24 °C-50% RH,
N° of variable speed compressors 1 1 1 45 °C condensing
Refrigerating circuits 2 2 2 temperature and
Gross total cooling capacity1,2 kW 90,8 100,8 139,5 ESP = 20 Pa.
Gross sensible cooling capacity1,2 kW 74,6 88,9 119,5
DIMENSIONS
Height mm 1950 1950 1950
Fan module height mm 565 565 565
Length mm 1777 2082 2650
Depth mm 900 900 900

• Control software design to provide a highly accurate Construction options


real-time control of room conditions and the complete
unit management such as: • Double power supply with automatic integrated
management on the active line to provide redundancy
- electronic expansion valve complete management
and ensure a constant power supply
- advanced interactivity with the
• Standard, cleanable or low conductibility humidifier
installation environment
with immersed-electrodes for modulating steam
- dehumidification operating mode managed by production available as an option for units equipped
means of EEV with devised algorithm which with cooling and humidification configuration
maintains constant air flow
• Condensate drain pump
- double set-point with digital input selection
• Electrical heaters with aluminum-finned heating
- emergency operation elements complete with safety thermostat
• The design of the IT J-Controller allows to physically (for manual resetting) to cut off the power
isolate the internal connections from the external supply in the event of overheating
connections. The external connections on the upper • High efficiency EU5 pleated air filters. Air filters are
level offer a wide variety of accessibility options: housed in a dedicated plenum box.
- External CAN and Group CAN • Power phase correction capacitors for compressors
- Isolated 2-wire and 4-wire RS485 ports • Active Flow Control to improve the balance of airflow
- NetBotz universal sensor ports between the cooling structure and IT equipment.
- Alarm/Shutdown Contacts • Energy meter and CO2 emission calculator
- USB ports (Host, Device) • Motorized damper on the air return side
- Ethernet
- HDMI display interface Accessories
- Modbus The units can be supplied with the following
- Remote shutdown input external accessories:
• Ability to interface with most common external BMS on • Suction / discharge plenums
communication protocols and boosting on connection • Direct free-cooling plenums
towards Schneider monitoring systems:
• Fan module shipped separately from the upper unit
- Modbus/RTU RS485
• Height adjustable legs kit
- SNMP
• Room temperature and humidity sensor
- Modbus Over IP
• Smoke and fire sensors
- StruxureWare
• Water leak detectors
- StruxureON
• Check and by-pass valves kit
- Cooling Tuner as service diagnostic tool

Life is On | Schneider Electric 71


Direct-expansion energy-saving units with backward-curved fans equipped with EC motor

Uniflair LE
IDWV - IUWV

Range
Cooling capacity: 50 ÷ 140 kW
1 VSD compressor and 1 fixed speed compressor
Refrigerant R-410A
EC fans
Available versions
• Downflow (IDWV)
• Upflow (IUWV)

Standard features
• Air flow configuration: • Refrigerant circuits complying with Pressure
- Downflow configuration with bottom or front Equipment Directive 2014/68/EU (PED) including:
discharge and suction from the top liquid refrigerant receiver, filter-dryer and liquid sight
glass, electronic expansion valve, high-pressure
- Upflow configuration with top discharge and bottom
pressostats with manual reset.
or front return
• New generation of hermetic scroll compressor:
• Metal structural frame and inside part made with hot-
dip zinc-plated sheet steel - Fixed-speed compressors with Intermediate
Discharge Valves (IDVs), built-in thermal protection
• External panels coated with RAL9003 epoxy-polyester
and anti-vibration feet
paint and internally lined with heat- and sound-proofing
insulation to class 1 according to Class B1 according - Variable speed scroll compressors with a
to DIN 4102, BS 476 part 7,VO according to UL94, brushless Interior Permanent Magnet (IPM)
ASTM E84, class M1 according to NFP92-501 and dedicated variable speed drive designed
to provide maximum efficiency across the full
• Internal panels for shutting-off the compartments
operating range
affected by the airflow, made with hot-dip zinc-plated
sheet steel and captive screws • Refrigerant R410A
• High efficiency EU4 pleated air filters are contained • Electronic Expansion Valve (EEV) to provide accurate
in a metal frame and equipped with a dirty filter control of the refrigerant superheat ensuring high
differential pressure switch and a low airflow energy efficiency also at low external temperatures.
differential pressure switch. Downflow units have • Electrical panel complying with Machinery Directive
filters housed in a dedicated plenum box. 2006/42/EC (MD) and Electromagnetic compatibility
• The units are equipped with the latest generation Directive 2014/30/EU (EMC), Regulation (EU)
Radical EC Fans for efficiency maximization. Impellers No 517/2014 on fluorinated greenhouse gases
are made of high-tech compound material with (F-GAS), housed- in a compartment isolated from the
optimized flow control, combined with highly efficient airflow and including 24V control circuit transformer,
GreenTech EC motors. These fans are designed to metal isolating screen for protection from live
have easier serviceability with quick removability kit. components, mains switch, thermomagnetic
circuit-breakers, terminal board for no-voltage signal
• Low airflow differential pressure switch
and control contacts.
• Cooling coil, mounted upstream of the fans,
• 7-inch. IT Touch Screen display interface that
constructed of copper tubes expanded into
allows to set operating parameters, monitor the
hydrophilic aluminum fins, complete with stainless
trend of the main working parameters, and read
steel tray and a flexible condensate drain hose
any alarm messages.
• Brazed plate water-cooled condenser made from
• Schneider Electric IT J-Controller (J5 18 DIN),
stainless steel.
complying with Machinery Directive 2006/42/EC
• Single (**11A models) or double (**22A models) (MD) and Electromagnetic compatibility Directive
refrigerant circuit each equipped with a scroll 2014/30/EU (EMC), Regulation (EU) No 517/2014 on
compressor (one fixed-speed and one brushless fluorinated greenhouse gases (F-GAS), where are
inverter driven, except the 1511A model that is connected analogical and digital inputs necessary for
equipped with only one brushless inverter driven control of the unit.
scroll compressor)

72 Life is On | Schneider Electric


TECHNICAL DATA
1
Gross cooling
capacities; fans must
IDWV MODEL 1511A 1922A 2022A 2422A 2922A 3822A
be deduced to obtain
Fan type EC Backward-curved centrifugal motor fan
net cooling data.
Power supply V/ph/Hz 400/3/50Hz
Fans Nr. 2 2 2 2 2 3 2
Data refers to nominal
Airflow m3/h 16800 16800 17000 20000 26000 27000 conditions: Room at 24
N° of fixed speed compressors - 1 1 1 1 1 °C-50% RH, inlet/outlet
N° of variable speed compressors 1 1 1 1 1 1 water temperatures
Refrigerating circuits 2 2 2 2 2 2 30/35°C, 0% glycol
Gross total cooling capacity1,2 kW 58 65,1 67,1 93,3 104,1 137,9 and ESP = 20 Pa.
Gross sensible cooling capacity1,2 kW 55,4 58,1 63,8 76,5 93,1 110,5
DIMENSIONS
Height mm 2150 2150 2150 2150 2150 2150
Length mm 1777 1777 2082 2082 2650 2650
Depth mm 900 900 900 900 900 900
IUWV MODEL 1511A 1922A 2022A 2422A 2922A 3822A
Fan type EC Backward-curved centrifugal motor fan
Power supply V/ph/Hz 400/3/50Hz
Fans Nr. 2 2 2 2 2 3
Airflow m3/h 16800 16800 17000 20000 26000 27000
N° of fixed speed compressors - 1 1 1 1 1
N° of variable speed compressors 1 1 1 1 1 1
Refrigerating circuits 2 2 2 2 2 2
Gross total cooling capacity1,2 kW 58 65,1 67,1 93,3 104,1 137,9
Gross sensible cooling capacity1,2 kW 55,4 58,1 63,8 76,5 93,1 110,5
DIMENSIONS
Height mm 1950 1950 1950 1950 1950 1950
Length mm 1777 1777 2082 2082 2650 2650
Depth mm 900 900 900 900 900 900

• Control software design to provide a highly accurate Construction options


real-time control of room conditions and the complete
unit management such as: • Double power supply with automatic integrated
management on the active line to provide redundancy
- electronic expansion valve complete management
and ensure a constant power supply
- advanced interactivity with the installation
• 2-way pressostatic valve to modulate the water flow
environment
through the braze plate condenser
- dehumidification operating mode managed by
• Condensing Pressure Regulation Valve (Flooding
means of EEV with devised algorithm which
Valve) to maintain a minimum condensing pressure
maintains constant air flow
even with low water inlet temperature
- double set-point with digital input selection
• Standard, cleanable or low conductibility humidifier
- emergency operation with immersed-electrodes for modulating steam
• The design of the IT J-Controller allows to physically production available as an option for units equipped
isolate the internal connections from the external with cooling and humidification configuration
connections. The external connections on the upper • Condensate drain pump
level offer a wide variety of accessibility options:
• Electrical heaters with aluminum-finned heating elements
- External CAN and Group CAN complete with safety thermostat (for manual resetting) to
- Isolated 2-wire and 4-wire RS485 ports cut off the power supply in the event of overheating
- NetBotz universal sensor ports • High efficiency EU5 pleated air filters. Downflow units
- Alarm/Shutdown Contacts have filters housed in a dedicated plenum box.
- USB ports (Host, Device) • Power phase correction capacitors for compressors
- Ethernet • Active Flow Control to improve the balance of airflow
between the cooling structure and IT equipment.
- HDMI display interface
• Energy meter and CO2 emission calculator
- Modbus
• Motorized damper on the air return side
- Remote shutdown input
• Ability to interface with most common external
Accessories
BMS on communication protocols and boosting on
connection towards Schneider monitoring systems: The units can be supplied with the following
- Modbus/RTU RS485 external accessories:
- SNMP • Suction / discharge plenums
- Modbus Over IP • Direct free-cooling plenums
- StruxureWare • Floor stands with or without motorized damper
- StruxureON • Height adjustable base frame
- Cooling Tuner as service diagnostic tool • Room temperature and humidity sensor
• Smoke and fire sensors
• Water leak detectors

Life is On | Schneider Electric 73


Direct-expansion water-cooled units with backward-curved fans equipped with EC motor

Uniflair LE
IXWV

Range
Cooling capacity: 70 ÷ 150 kW
1 VSD compressor and 1 fixed speed compressor
Refrigerant R-410A
EC fans
Available versions
• Underfloor (IXWV)

Standard features
• Underfloor configuration with top return and multiple • Brazed plate water-cooled condenser made from
fan module configurations: stainless steel.
- bottom discharge • Double (**22A models) refrigerant circuit each
- rear discharge equipped with a scroll compressor (one fixed-speed
and one brushless inverter driven)
- front discharge
• Refrigerant circuits complying with Pressure
- front and side discharge Equipment Directive 2014/68/EU (PED) including:
- fully open discharge liquid refrigerant receiver, filter-dryer and liquid sight
• Metal structural frame and inside part made with hot- glass, electronic expansion valve, high-pressure
dip zinc-plated sheet steel pressostats with manual reset.
• External panels coated with RAL9003 epoxy-polyester • New generation of hermetic scroll compressor:
paint and internally lined with heat- and sound- - Fixed-speed compressors with Intermediate
proofing insulation to class 1 according to Class B1 Discharge Valves (IDVs), built-in thermal protection
according to DIN 4102, BS 476 part 7,VO according and anti-vibration feet
to UL94, ASTM E84, class M1 according to NFP92- - Variable speed scroll compressors with a
501 brushless Interior Permanent Magnet (IPM)
• Internal panels for shutting-off the compartments and dedicated variable speed drive designed
affected by the airflow, made with hot-dip zinc-plated to provide maximum efficiency across the full
sheet steel and captive screws operating range
• High efficiency EU4 pleated air filters are contained • Refrigerant R410A
in a metal frame and equipped with a dirty filter • Electronic Expansion Valve (EEV) to provide accurate
differential pressure switch and a low airflow control of the refrigerant superheat ensuring high
differential pressure switch. Air filters are housed in a energy efficiency also at low external temperatures.
dedicated plenum box.
• Electrical panel complying with Machinery Directive
• The units are equipped with the latest generation 2006/42/EC (MD) and Electromagnetic compatibility
Radical EC Fans for efficiency maximization. Impellers Directive 2014/30/EU (EMC), Regulation (EU)
are made of high-tech compound material with No 517/2014 on fluorinated greenhouse gases (F-GAS),
optimized flow control, combined with highly efficient housed- in a compartment isolated from the airflow and
GreenTech EC motors. These fans are designed to including 24V control circuit transformer, metal isolating
have easier serviceability with quick removability kit. screen for protection from live components, mains
• Low airflow differential pressure switch switch, thermomagnetic circuit-breakers, terminal board
• Cooling coil, mounted upstream of the fans, for no-voltage signal and control contacts.
constructed of copper tubes expanded into • 7 inch. IT Touch Screen display interface that allows
hydrophilic aluminum fins, complete with stainless to set operating parameters, monitor the trend
steel tray and a flexible condensate drain hose of the main working parameters, and read any
alarm messages.

74 Life is On | Schneider Electric


TECHNICAL DATA
1
Gross cooling
capacities; fans must
IXWV MODEL 2322A 2622A 4022A
be deduced to obtain
Fan type EC Backward-curved centrifugal motor fan
net cooling data.
Power supply V/ph/Hz 400/3/50Hz
Fans Nr. 2 2 3 2
Data refers to nominal
Airflow m3/h 18800 23400 30000 conditions: Room at 24
N° of fixed speed compressors 1 1 1 °C-50% RH, inlet/outlet
N° of variable speed compressors 1 1 1 water temperatures
Refrigerating circuits 2 2 2 30/35°C, 0% glycol
Gross total cooling capacity1,2 kW 92,9 103,4 144,4 and ESP = 20 Pa.
Gross sensible cooling capacity1,2 kW 75,4 89,7 121,1
DIMENSIONS
Height mm 1950 1950 1950
Fan module height mm 565 565 565
Length mm 1777 2082 2650
Depth mm 900 900 900

• Schneider Electric IT J-Controller (J5 18 DIN), Construction options


complying with Machinery Directive 2006/42/EC
(MD) and Electromagnetic compatibility Directive • Double power supply with automatic integrated
2014/30/EU (EMC), Regulation (EU) No 517/2014 on management on the active line to provide redundancy
fluorinated greenhouse gases (F-GAS), where are and ensure a constant power supply
connected analogical and digital inputs necessary for • 2-way pressostatic valve to modulate the water flow
control of the unit. through the braze plate condenser
• Control software design to provide a highly accurate • Condensing Pressure Regulation Valve (Flooding
real-time control of room conditions and the complete Valve) to maintain a minimum condensing pressure
unit management such as: even with low water inlet temperature
- electronic expansion valve complete management • Standard, cleanable or low conductibility humidifier
- advanced interactivity with the installation with immersed-electrodes for modulating steam
environment production available as an option for units equipped
with cooling and humidification configuration
- dehumidification operating mode managed by
means of EEV with devised algorithm which • Condensate drain pump
maintains constant air flow • Electrical heaters with aluminum-finned heating
- double set-point with digital input selection elements complete with safety thermostat
(for manual resetting) to cut off the power supply
- emergency operation
in the event of overheating
• The design of the IT J-Controller allows to physically
• High efficiency EU5 pleated air filters. Air filters are
isolate the internal connections from the external
housed in a dedicated plenum box.
connections. The external connections on the upper
level offer a wide variety of accessibility options: • Power phase correction capacitors for compressors
- External CAN and Group CAN • Active Flow Control to improve the balance of airflow
between the cooling structure and IT equipment.
- Isolated 2-wire and 4-wire RS485 ports
• Energy meter and CO2 emission calculator
- NetBotz universal sensor ports
• Motorized damper on the air return side
- Alarm/Shutdown Contacts
- USB ports (Host, Device)
Accessories
- Ethernet
- HDMI display interface The units can be supplied with the following
external accessories:
- Modbus
• Suction / discharge plenums
- Remote shutdown input
• Direct free-cooling plenums
• Ability to interface with most common external
BMS on communication protocols and boosting on • Fan module shipped separately from the upper unit
connection towards Schneider monitoring systems: • Height adjustable legs kit
- Modbus/RTU RS485 • Room temperature and humidity sensor
- SNMP • Smoke and fire sensors
- Modbus Over IP • Water leak detectors
- StruxureWare
- StruxureON
- Cooling Tuner as service diagnostic tool

Life is On | Schneider Electric 75


Direct-expansion energy-saving units with backward-curved fans equipped with EC motor

Uniflair LE
IDEV - IUEV

Range
Cooling capacity: 50 ÷ 100 kW
1 VSD compressor and 1 fixed speed compressor
Refrigerant R-410A
EC fans
Available versions
• Downflow (IDEV)
• Upflow (IUEV)

Standard features
• Air flow configuration: • Refrigerant circuits complying with Pressure Equipment
- Downflow configuration with bottom or front Directive 2014/68/EU (PED) including: liquid refrigerant
discharge and suction from the top receiver, filter-dryer and liquid sight glass, electronic
expansion valve, high-pressure pressostats with manual
- Upflow configuration with top discharge and bottom
reset.
or front return
• New generation of hermetic scroll compressor:
• Metal structural frame and inside part made with hot-
dip zinc-plated sheet steel - Fixed-speed compressors with Intermediate
Discharge Valves (IDVs), built-in thermal protection
• External panels coated with RAL9003 epoxy-polyester
and anti-vibration feet
paint and internally lined with heat- and sound-proofing
insulation to class 1 according to Class B1 according - Variable speed scroll compressors with a brushless
to DIN 4102, BS 476 part 7,VO according to UL94, Interior Permanent Magnet (IPM) and dedicated
ASTM E84, class M1 according to NFP92-501 variable speed drive designed to provide maximum
efficiency across the full operating range
• Internal panels for shutting-off the compartments
affected by the airflow, made with hot-dip zinc-plated • Refrigerant R410A
sheet steel and captive screws • Electronic Expansion Valve (EEV) to provide accurate
• High efficiency EU4 pleated air filters are contained control of the refrigerant superheat ensuring high
in a metal frame and equipped with a dirty filter energy efficiency also at low external temperatures.
differential pressure switch and a low airflow • Energy saving units are equipped with a new patent
differential pressure switch. Downflow units have pending solution. The 3-way valve is replaced by three
filters housed in a dedicated plenum box. flow control devices designed to maximize efficiency
• The units are equipped with the latest generation and minimize water side pressure drops.
Radical EC Fans for efficiency maximization. Impellers • Electrical panel complying with Machinery Directive
are made of high-tech compound material with 2006/42/EC (MD) and Electromagnetic compatibility
optimized flow control, combined with highly efficient Directive 2014/30/EU (EMC), Regulation (EU)
GreenTech EC motors. These fans are designed to No 517/2014 on fluorinated greenhouse gases (F-GAS),
have easier serviceability with quick removability kit. housed- in a compartment isolated from the airflow and
• Low airflow differential pressure switch including 24V control circuit transformer, metal isolating
screen for protection from live components, mains
• Cooling coil, mounted upstream of the fans,
switch, thermomagnetic circuit-breakers, terminal board
constructed of copper tubes expanded into
for no-voltage signal and control contacts.
hydrophilic aluminum fins, complete with stainless
steel tray and a flexible condensate drain hose • 7-inch. IT Touch Screen display interface that allows to
set operating parameters, monitor the trend of the main
• Brazed plate water-cooled condenser made from
working parameters, and read any alarm messages.
stainless steel.
• Schneider Electric IT J-Controller (J5 18 DIN),
• Single (**11A models) or double (**22A models)
complying with Machinery Directive 2006/42/EC
refrigerant circuit each equipped with a scroll
(MD) and Electromagnetic compatibility Directive
compressor (one fixed-speed and one brushless
2014/30/EU (EMC), Regulation (EU) No 517/2014 on
inverter driven, except the 1511A model that is
fluorinated greenhouse gases (F-GAS), where are
equipped with only one brushless inverter driven
connected analogical and digital inputs necessary for
scroll compressor)
control of the unit.

76 Life is On | Schneider Electric


TECHNICAL DATA
1
Gross cooling
capacities; fans must
IDEV MODEL 1511A 2022A 2922A
be deduced to obtain
Fan type EC Backward-curved centrifugal motor fan
net cooling data.
Power supply V/ph/Hz 400/3/50Hz
Fans Nr. 2 2 3 2
Data refers to nominal
Airflow m3/h 16800 17000 26000 conditions: Room at 24
N° of fixed speed compressors - 1 1 °C-50% RH, inlet/outlet
N° of variable speed compressors 1 1 1 water temperatures
Refrigerant circuits 2 2 2 30/36°C, 0% glycol
Gross total cooling capacity1,2 kW 55,4 64,1 100,3 and ESP = 20 Pa
Gross sensible cooling capacity1,2 kW 51,1 55,9 85,0
DIMENSIONS
Height mm 2150 2150 2150
Length mm 1777 2082 2650
Depth mm 900 900 900
IUEV MODEL 1511A 2022A 2922A
Fan type EC Backward-curved centrifugal motor fan
Power supply V/ph/Hz 400/3/50Hz
Fans Nr. 2 2 2
Airflow m3/h 16800 17000 26000
N° of fixed speed compressors - 1 1
N° of variable speed compressors 1 1 1
Refrigerating circuits 2 2 2
Gross total cooling capacity1,2 kW 55,4 64,1 100,3
Gross sensible cooling capacity1,2 kW 51,1 55,9 85,0
DIMENSIONS
Height mm 1950 1950 1950
Length mm 1777 2082 2650
Depth mm 900 900 900

• Control software design to provide a highly accurate Construction options


real-time control of room conditions and the complete
unit management such as: • Double power supply with automatic integrated
management on the active line to provide redundancy
- electronic expansion valve complete management
and ensure a constant power supply
- advanced interactivity with the installation
• Standard, cleanable or low conductibility humidifier
environment
with immersed-electrodes for modulating steam
- dehumidification operating mode managed by production available as an option for units equipped
means of EEV with devised algorithm which with cooling and humidification configuration
maintains constant air flow
• Condensate drain pump
- double set-point with digital input selection
• Electrical heaters with aluminum-finned heating
- emergency operation elements complete with safety thermostat (for manual
• The design of the IT J-Controller allows to physically resetting) to cut off the power supply in the event of
isolate the internal connections from the external overheating
connections. The external connections on the upper • High efficiency EU5 pleated air filters. Downflow units
level offer a wide variety of accessibility options: have filters housed in a dedicated plenum box.
- External CAN and Group CAN • Power phase correction capacitors for compressors
- Isolated 2-wire and 4-wire RS485 ports • Active Flow Control to improve the balance of airflow
- NetBotz universal sensor ports between the cooling structure and IT equipment.
- Alarm/Shutdown Contacts • Energy meter and CO2 emission calculator
- USB ports (Host, Device) • Motorized damper on the air return side
- Ethernet
- HDMI display interface Accessories
- Modbus The units can be supplied with the following
- Remote shutdown input external accessories:
• Ability to interface with most common external • Suction / discharge plenums
BMS on communication protocols and boosting on • Direct free-cooling plenums
connection towards Schneider monitoring systems:
• Floor stands with or without motorized damper
- Modbus/RTU RS485
• Height adjustable base frame
- SNMP
• Room temperature and humidity sensor
- Modbus Over IP
• Smoke and fire sensors
- StruxureWare
• Water leak detectors
- StruxureON
- Cooling Tuner as service diagnostic tool

Life is On | Schneider Electric 77


Direct-expansion energy-saving units with backward-curved fans equipped with EC motor

Uniflair LE
IXEV

Range
Cooling capacity: 60 ÷ 150 kW
1 VSD compressor and 1 fixed speed compressor
Refrigerant R-410A
EC fans
Available versions
• Underfloor (IXEV)

Standard features
• Underfloor configuration with top return and multiple • Single (**11A models) or double (**22A models)
fan module configurations: refrigerant circuit each equipped with a scroll
- bottom discharge compressor (one fixed-speed and one brushless
inverter driven, except the 2311A model that is
- rear discharge
equipped with only one brushless inverter driven
- front discharge scroll compressor)
- front and side discharge • Refrigerant circuits complying with Pressure
- fully open discharge Equipment Directive 2014/68/EU (PED) including:
liquid refrigerant receiver, filter-dryer and liquid sight
• Metal structural frame and inside part made with
glass, electronic expansion valve, high-pressure
hot-dip zinc-plated sheet steel
pressostats with manual reset.
• External panels coated with RAL9003 epoxy-polyester
• New generation of hermetic scroll compressor:
paint and internally lined with heat- and sound-proofing
insulation to class 1 according to Class B1 according - Fixed-speed compressors with Intermediate
to DIN 4102, BS 476 part 7,VO according to UL94, Discharge Valves (IDVs), built-in thermal protection
ASTM E84, class M1 according to NFP92-501 and anti-vibration feet
• Internal panels for shutting-off the compartments - Variable speed scroll compressors with a brushless
affected by the airflow, made with hot-dip zinc-plated Interior Permanent Magnet (IPM) and dedicated
sheet steel and captive screws variable speed drive designed to provide maximum
efficiency across the full operating range
• High efficiency EU4 pleated air filters are contained
in a metal frame and equipped with a dirty filter • Refrigerant R410A
differential pressure switch and a low airflow differential • Electronic Expansion Valve (EEV) to provide accurate
pressure switch. Air filters are housed in a dedicated control of the refrigerant superheat ensuring high
plenum box. energy efficiency also at low external temperatures.
• The units are equipped with the latest generation • Energy saving units are equipped with a new patent
Radical EC Fans for efficiency maximization. Impellers pending solution. The 3-way valve is replaced by three
are made of high-tech compound material with flow control devices designed to maximize efficiency
optimized flow control, combined with highly efficient and minimize water side pressure drops.
GreenTech EC motors. These fans are designed to
• Electrical panel complying with Machinery Directive
have easier serviceability with quick removability kit.
2006/42/EC (MD) and Electromagnetic compatibility
• Low airflow differential pressure switch Directive 2014/30/EU (EMC), Regulation (EU)
• Cooling coil, mounted upstream of the fans, No 517/2014 on fluorinated greenhouse gases
constructed of copper tubes expanded into (F-GAS), housed- in a compartment isolated from the
hydrophilic aluminum fins, complete with stainless airflow and including 24V control circuit transformer,
steel tray and a flexible condensate drain hose metal isolating screen for protection from live
components, mains switch, thermomagnetic
• Brazed plate water-cooled condenser made from
circuit-breakers, terminal board for no-voltage signal
stainless steel.
and control contacts.

78 Life is On | Schneider Electric


TECHNICAL DATA
1
Gross cooling
capacities; fans must
IXEV MODEL 2322A 2622A 4022A
be deduced to obtain
Fan type EC Backward-curved centrifugal motor fan
net cooling data.
Power supply V/ph/Hz 400/3/50Hz
Fans Nr. 2 2 3 2
Data refers to nominal
Airflow m3/h 18800 23400 30000 conditions: Room at 24
N° of fixed speed compressors 1 1 1 °C-50% RH, inlet/outlet
N° of variable speed compressors 1 1 1 water temperatures
Refrigerating circuits 2 2 2 30/36°C, 0% glycol and
Gross total cooling capacity1,2 kW 57,8 98,3 135,1 ESP = 20 Pa.
Gross sensible cooling capacity1,2 kW 56,5 80,9 108,4
DIMENSIONS
Height mm 1950 1950 1950
Fan module height mm 565 565 565
Length mm 1777 2082 2650
Depth mm 900 900 900

• 7 inch. IT Touch Screen display interface that allows Construction options


to set operating parameters, monitor the trend of
the main working parameters, and read any • Double power supply with automatic integrated
alarm messages. management on the active line to provide redundancy
and ensure a constant power supply
• Schneider Electric IT J-Controller (J5 18 DIN),
complying with Machinery Directive 2006/42/EC (MD) • Standard, cleanable or low conductibility humidifier
and Electromagnetic compatibility Directive 2014/30/ with immersed-electrodes for modulating steam
EU (EMC), Regulation (EU) No 517/2014 on fluorinated production available as an option for units equipped
greenhouse gases (F-GAS), where are connected with cooling and humidification configuration
analogical and digital inputs necessary for control of • Condensate drain pump
the unit.
• Electrical heaters with aluminum-finned heating
• Control software design to provide a highly accurate elements complete with safety thermostat (for
real-time control of room conditions and the complete manual resetting) to cut off the power supply in
unit management such as: the event of overheating
- electronic expansion valve complete management • High efficiency EU5 pleated air filters. Air filters are
- advanced interactivity with the installation environment housed in a dedicated plenum box.
- dehumidification operating mode managed by • Power phase correction capacitors for compressors
means of EEV with devised algorithm which • Active Flow Control to improve the balance of airflow
maintains constant air flow between the cooling structure and IT equipment.
- double set-point with digital input selection • Energy meter and CO2 emission calculator
- emergency operation • Motorized damper on the air return side
• The design of the IT J-Controller allows to physically
isolate the internal connections from the external Accessories
connections. The external connections on the upper
level offer a wide variety of accessibility options: The units can be supplied with the following
- External CAN and Group CAN external accessories:

- Isolated 2-wire and 4-wire RS485 ports • Suction / discharge plenums

- NetBotz universal sensor ports • Direct free-cooling plenums

- Alarm/Shutdown Contacts • Fan module shipped separately from the upper unit

- USB ports (Host, Device) • Height adjustable legs kit

- Ethernet • Room temperature and humidity sensor

- HDMI display interface • Smoke and fire sensors

- Modbus • Water leak detectors

- Remote shutdown input


• Ability to interface with most common external BMS on
communication protocols and boosting on connection
towards Schneider monitoring systems:
- Modbus/RTU RS485
- SNMP
- Modbus Over IP
- StruxureWare
- StruxureON
- Cooling Tuner as service diagnostic tool

Life is On | Schneider Electric 79


Air-cooled remote condensers

Uniflair CAP
Range
Cooling capacity: 7 ÷ 160 kW
Refrigerant R-410A

Standard features Accessories


• R-410A refrigerant. • Shut off valves
• Low noise axial fans with IP54 class F electric motor. • Leg support kit
• Fan speed pressure switch regulator with protection grade IP55. • Manifold kit to make the unit single circuit
• Safety protection grills. • Coil protection treatment for use
• Copper and aluminum condensing coil. in aggressive environments
• Low noise levels. • Low temperature versions down to
• Outdoor installation. -40 °C with high-resilience steel liquid
• High-efficiency, EU4-pleated air filter housed in a metal frame and filter differential receiver and flooding valve to control
pressure switch. the condensing temperature
• Vertical or horizontal installation.
• Welded refrigeration connections for rapid and safe connection.
• Condensers are powered by the internal unit to grant operation at
208 – 230 V with a tolerance of +/-10%.

80 Life is On | Schneider Electric


TECHNICAL DATA
1
With external
temperature
CAP MODEL 251 331 361 511 611 801 1011 1301
35 °C and 50 °C
Fan type Axial
R-410A condensing
Power supply V/ph/Hz 208 – 230/1/50 temperature.
Performance capacity1 kW 8,2 9,8 12,8 16,6 20,2 27,6 33,7 44,5
Airflow rate at 0.08 in.w (20 Pa) m3/h 3050 2750 3300 6100 9150 9150 8250 10980
2
Measured in free
field conditions at
Number of circuits 1 1 1 1 1 1 1 1
5 meters from
Noise level2 dB(A) 51 50,5 51,5 53,2 52,6 54,6 54,1 54,6
the unit.
DIMENSIONS
Height mm 732 732 1067 1227 1227 1877 1877 2277
Width mm 350 350 350 350 350 350 350 350
Depth mm 700 700 700 700 700 700 700 700
CAP MODEL 1802 2002 3002 4002 5002 6002 7002
Fan type Axial
Power supply V/ph/Hz 208 – 230/1/50
Performance capacity1 kW 61,3 67 88,7 96,4 127,9 145,8 166,7
Airflow rate at 0.08
m /h
3
17500 16900 27500 26250 35000 45000 42250
in.w (20 Pa)
Number of circuits 2 2 2 2 2 2 2
Noise level2 dB(A) 61 61 63 63 64 65 65
DIMENSIONS
Height mm 2217 2217 3217 3217 4217 5217 5217
Width mm 400 400 400 400 400 400 400
Depth mm 700 700 700 700 700 700 700

Life is On | Schneider Electric 81


Air-cooled remote condensers

Uniflair OCC

Range
Heat dissipation: 40 ÷ 200 kW
Refrigerant R-410A
AC or EC fans

Standard features Construction options and accessories


• R-410A refrigerant • Versions with electronically commutated (EC) motor to
• Low-speed axial fans compliant with Ecodesign reduce the sound pressure level
and Energy Labelling Directive 2009/125/EC • Shut-off valves
• Fan speed regulator works exclusively via • Leg support kit
Modbus commands • Coil protection treatment for use in aggressive
• Copper and aluminum condensing coil environments (optional)
• Outdoor installation • Low temperature versions down to -40 °C with high-
• Vertical or horizontal installation resilience steel liquid receiver and flooding valve to
control the condensing temperature. The kit is shipped
• High-efficiency, EU4-pleated air filter housed in a
separately from the OCC LT condenser, and must be
metal frame and filter differential pressure switch.
installed on site.

TECHNICAL DATA
1
Gross cooling
capacities; fans must
OCC - ONE CIRCUIT 1701 2101 2401 2601 3101 3301 3901
be deduced to obtain
Fan Type AC / EC axial fans
net cooling data.
Power supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 400/3/50 400/3/50
Fans Nr. 2 2 2 2 3 2 3 2
Measured in free field
Airflow Nr. 2 2 2 3 3 2 2 conditions at 10 meters
Heat dissipation1 m3/h 17227 16313 15216 22275 23372 32700 29525 from the unit.
Noise level2 kW 45,8 55,5 62,1 69,7 81,9 87,9 102
Refrigerating circuits dB(A) 45 45 45 47 47 51 51
DIMENSIONS
Height mm 1150 1150 1150 1150 1150 1250 1250
Length mm 2380 2380 2380 2660 2660 2660 2660
Depth mm 800 800 800 800 800 800 800
IUAV MODEL 3502 4202 4702 5302 6202 6702 7702
Fan type AC / EC axial fans
Power supply V/ph/Hz 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 400/3/50 400/3/50
Fans Nr. 4 4 4 6 6 4 4
Airflow m3/h 34453 32625 30431 44550 46744 65400 59050
Heat dissipation1 kW 91,6 111,0 124,2 139,4 163,8 175,8 204,0
Noise level2 dB(A) 48 48 48 50 50 54 54
DIMENSIONS
Height mm 2253 2253 2253 2253 2253 2453 2453
Length mm 2380 2380 2380 2660 2660 2660 2660
Depth mm 800 800 800 800 800 800 800

82 Life is On | Schneider Electric


High-density cooling solutions

Active floor
Range
Cooling capacity: 6 ÷ 15 kW

Standard features
• Active floor is a flexible and modular system for cooling
data centers with medium- and high-density loads.
Integrated within a modular access floor in front of the
intake section of the rack, the Active Floor fits exactly
into a modular access floor panel measuring 600 mm
x 600 mm. The cold air produced by the close control
perimeter units is directly channeled to the source of the
thermal load thanks to the advanced adjustment of the
direction of the airflow. The active floor creates a high-
density bubble of air, which is maintained at a constant
temperature along the whole intake section of the rack,
guaranteeing operation at the nominal design conditions.
The airflow varies according to the actual thermal load
and is detected by two sensors placed on the discharge
section of the servers.
• Active floor employs variable speed EC, motor-driven
fans to minimize energy consumption.
• This solution may be used in stand-alone applications as
well as with perimeter close control units equipped with
underfloor pressure control.
• The active floor guarantees optimum operation
of high-density equipment for loads installed in each
module of 25 kW and 40 kW with solutions featuring
the two modules certified by TUV.

TECHNICAL DATA
ACTIVE FLOOR
Power supply V/ph/Hz 220/1+N/60
N° of fans/motor 1/E.C
Max airflow m³/h/CFM 4988/2936
Nominal airflow m³/h/CFM 2880/1650
Min airflow m³/h/CFM 1698/999
DIMENSIONS
Height mm/inch 230/9.1
Width mm/inch 600/23.6
Depth mm/inch 600/23.6

Life is On | Schneider Electric 83


Mobile telecom air conditioners
Modern telephone technology uses equipment that is Connection to supervision systems
usually housed in shelters or in small- to medium-sized
rooms. These sites form effective technological rooms All the units can be connected to a RS485 serial line by
with common needs from which a series of particular using an additional card, ensuring complete monitoring
requirements arise. of the system. This allows for:

Around-the-clock operation every day of the year • Control through the Uniflair Netvisor
supervision system
• Highly reliable equipment
• Connection to a centralized supervision system
• Reduced running costs

Furthermore, all the units are fitted with digital alarm


High breakdown costs
outputs (between three and six depending on the
• Rapid intervention model), which make it easier to control the status
• Avoidance of critical conditions of the cooling unit and the connection to the external
control PLC.
Expensive equipment
• Guaranteed control of environmental conditions Intelligent free-cooling
• Management of critical situations
• Long life for the system The microprocessor control continuously monitors
the room temperature and the outside environmental
conditions: if these conditions allow the dissipation
Unmanned sites
of the thermal load, free-cooling is then activated.
• Autonomous control of emergencies
• Elimination only of the sensible heat Unlike traditional systems, the free-cooling
start-up temperature varies as the thermal
Reduced space load in the conditioned room varies.

• High density of thermal loads


COOLING MECHANICAL FREE-COOLING MIXED
• Protection of the space dedicated to the instruments
Compressor ON OFF OFF
Evaporator fan ON ON ON
Applications in various environments
Condenser fan ON OFF ON
• Easy installation Damper Closed Open Modulating
• Adaptable for any site
Minimal discharge air temperature with modulating damper.
To satisfy these needs, Schneider Electric has designed
various product families to ensure:

• Operational accuracy
• Continuous service
• Flexibility
• Low running costs

Uniflair Mobile telecom air conditioners provide


the features of the most advanced cooling units.

84 Life is On | Schneider Electric


Continuous operation during emergencies Stand-by control
Telephone shelters are constructed to guarantee Up to 10 units can be installed in each shelter, which
continuous operation even during power failures. are linked to each other through the local LAN network,
The free-cooling damper, microprocessor control, offering the following benefits:
and evaporator fan can also be powered by the UPS
in the shelter. During power failures the room is cooled • Equal wear to the units that are rotated
by the outside air through the free-cooling damper. on a timed basis
Without air conditioning, the temperature in the racks • The stand-by unit turns on if there is
rises from 45 °C to 70 °C in less than 15 minutes. an alarm in the working unit
• Automatic power turns on if there is
an exceptional thermal load
• Control of the combined operating phases
with excellent energy savings

Mobile telecom offer overview

Monoblock wall-mounted external


Monoblock internal installation units Splitted units
installation units

Upflow Downflow Upflow Downflow Ceiling mounted Wall mounted

Uniflair WM Uniflair WM Uniflair MB Uniflair MB Uniflair SP Uniflair SP


WMA-WMF WDA-WDF XMA-XMF XDA-XDF UCA-UCF UWA-UWF

Life is On | Schneider Electric 85


Monoblock wall-mounted units for external installation with downflow air discharge

Uniflair WM
WDA – WDF

Range
Cooling capacity: 6 ÷ 15 kW
Refrigerant R407C
Available versions
• Without direct free-cooling (WDA)
• With direct free-cooling (WDF)

Standard features
• Monoblock conditioning units can be installed on the outside wall of the air • The double external paneling is available in galvanized,
conditioned room. painted sheet steel and gives separate access to the fan
• Built-in air condenser is included. The units can be supplied completely assembled compartment and electric board compartments. This
and filled with refrigerant; all the components are set in the factory for normal enables maintenance and regulation to be carried out
working conditions and the electrical and cooling functions are tested. Installation without having to turn the unit off.
only requires simple electrical wiring and mechanical fixing to the shelter, even by • Power supply:
nonspecialized personnel. - 400 V/3+N/50 Hz standard on request
• The direct free-cooling units (WMF) are supplied with a motorized damper. During - 230 V/1/50 Hz on 221 and 341 models
free-cooling the excess air is expelled from the room through the condenser section - Main power supply + UPS 48 VDC (evaporator DC fan/s)
without using any extra overpressure dampers. • Microprocessor control.
• Complete access to all the components allows servicing entirely from the outside, • Scroll compressor.
without having to enter the room which is normally protected by controlled access. • EU4 filter (optional).
• The external screws are stainless steel, antitamper and can only be removed using • Modulating condenser fan/s speed control.
special tools.
• Free-cooling metal pre-filter.

TECHNICAL DATA
1
Data refers to
mechanical operation:
WDA – WDF MODEL WDF0221A WDF0341A WDF0481A WDF0501A
Ambient temperature:
Power supply V/ph/Hz 400/3+N/50
27 °C/40% RH,
Mechanical cooling1 external temperature
Sensible cooling capacity kW 6,0/6,0 9,0/9,0 12,0/12,0 15,0/15,0 35 °C/R407C
Airflow m³/h 1650 2350 2900 4200 (data consider
inlet and outlet
COMPONENT FEATURES
evaporating coil),
N° of evaporator fans 1 2 2 2 and Maximum external
N° of condenser fans 1 1 1 1 temperature 45 °C.
Compressor power
kW 1,25 1,94 3,56 3,78
consumption1
DIMENSIONS
Height mm 1800 1800 1800 1800
Width mm 950 950 950 1120
Depth mm 650 650 650 650

86 Life is On | Schneider Electric


Monoblock wall-mounted units for external installation with upflow air discharge

Uniflair WM
WMA – WMF

Range
Cooling capacity: 3.9 ÷ 16.9 kW
Refrigerant R407C
Available versions
- Without direct free-cooling (WMA)
- With direct free-cooling (WMF)

Standard features
• Monoblock conditioning units are installed on the outside wall of the air conditioned room. • Power supply:
• Air condenser is built in. The units can be supplied completely assembled - 230 V/1/50 Hz or 400 V/3+N/50 Hz
and filled with refrigerant. (standard, according to the model)
• All the components are set in the factory for normal working conditions. Electrical - Main power supply + UPS 230 V
and cooling functions are all tested. Installation only requires simple electrical wiring - Main power supply + UPS
and mechanical fixing to the shelter, even by nonspecialized personnel. - 48 VDC (evaporator DC-fan/s)
• The direct free-cooling units (WMF) are supplied with a motorized damper. • Microprocessor control.
During free-cooling the excess of air is expelled from the room through • Scroll compressor (rotary for 0121 model) housed
the condenser section without using extra overpressure dampers. in compartment isolated from the airflow.
• Complete access to all the components so that servicing can be entirely done from the • EU4 filter (optional).
outside, without having to enter the room which is normally protected by controlled access. • Modulating condenser fan/s speed control.
• The external screws are stainless steel, antitamper and can only be removed using • Free-cooling metal pre-filter.
special tools.
• The double external paneling is available in galvanized, painted sheet steel and gives
separate access to the fan compartment and electric board compartments. This enables
maintenance and regulation to be carried out without having to turn the unit off.

TECHNICAL DATA
1
Room: 26 °C/40% RH;
external temperature:
WMA – WMF MODELS 0121 0181 0251 0281 0331 0551 0661
35 °C; R407C.
Power supply V/ph/Hz 230/1/50 400/3+N/50
Mechanical cooling1 2
Room: 26 °C; external
Sensible cooling capacity kW 3,9/3,9 5,4/5,4 7,4/7,4 8,2/8,2 9,6/9,6 15,2/15,2 16,9/16,9 temperature:
Airflow m³ / h 1240 1460 2240 2240 2670 4580 4580 14 °C; R407C.
WMF MODEL
3
ARI standard.
Free-cooling2
Sensible cooling capacity kW 5,0 5,8 8,5 8,5 9,2 17,4 17,4 4
Optional.
Airflow m³/h 1230 1430 2100 2100 2280 4310 4310
5
Measurements taken
COMPONENT FEATURES
at 1 meter above the
N° of evaporator fans 1 1 2 2 2 1 1 floor and at a distance
N° of condenser fans 1 1 1 1 2 1 1 of 5 meters from
Air filter efficiency EU2 EU2 EU2 EU2 EU2 EU2 EU2 the unit in free field,
Nominal compressor power3 kW 1,2 1,8 2,2 2,5 3,0 4,4 5,2 mechanical cooling.

Electric heating4 kW 2,6 4,0 4,0 4,0 6,0 6,0 6,0


Noise pressure level5 dB(A) 40,5 44,0 45,5 45,5 49,0 50,0 54,0
DIMENSIONS
Height mm 1790 1790 1940 1940 1940 2250 2250
Width mm 650 650 930 930 930 1050 1050
Depth mm 400 400 450 450 450 625 625

Life is On | Schneider Electric 87


Monoblock units for internal installations

Uniflair MB
XMA – XMF – XDA – XDF

Range
Cooling capacity: XM* 5.7 ÷ 12.3 kW XD* 6.3-15.0 kW
Refrigerant R407C
Available versions
• Upflow (XMA)
• Upflow with free-cooling (XMF)
• Downflow (XDA)
• Downflow with free-cooling (XDF)

Standard features
• Monoblock conditioning units are installed inside • Cooling circuit includes:
the installation. These units are ideal when the required - Filter and flow sight glass
solution is easy to install with all the refrigerant - Thermostatic expansion valve
components already installed. - High- and low-pressure pressostats
• The unit has a self-supporting steel structure - Scroll compressor with thermal protection
finished in epoxy powder and external panels in steel - Ecological refrigerant R407C
finished in epoxy powder; it’s lined internally - Modulating condenser fan speed regulation.
with abrasion-resistant, self-extinguishing material • The microprocessor control manages the unit
for noise and heat insulation. autonomously and the free-cooling function
• Units are supplied ready for installation, completely and can be integrated with the most common BMSs.
assembled and filled with refrigerant in the factory, The control includes:
where they are calibrated and the electric and cooling - Microprocessor control board and user terminal
systems are tested.
- Room temperature sensor
• Easy installation and connection to the outside
- Mixed air temperature sensor (X*F version only)
is provided using rigid or flexible pipes that are fitted
- External temperature sensor (X*F version only)
to the window.
• Power supply:
• The air filtration is provided with an EU2-efficiency air
- 230 V/ 1/ 50 Hz or 400 V/3+N/50 Hz
filter in self-extinguishing material and a rigid metal
(Standard, according to the model)
frame; the free-cooling version is available with
an additional free-cooling metal pre-filter. EU4 filters - Main power supply + UPS 230 V
are available as an option. - Main power supply + UPS 48 VDC
• The evaporating and condensing fans are made (evaporator DC fan/s, available only for XMF)
of in galvanized steel. Double-inlet centrifugal fan(s) • Microprocessor control.
with forward-curved blower are keyed directly • Scroll compressor with low noise level.
to motor shaft. • EU4 filter (optional).
• The electrical panel is housed in a compartment • Modulating condenser fan/s speed control.
isolated from the airflow, complying with Machinery • Free-cooling metal pre-filter.
Directive 2006/42/EC (MD), Regulation (EU)
No 517/2014 on fluorinated greenhouse gases
(F-GAS). Separate power supply for fans and
microprocessor is available as an option.

88 Life is On | Schneider Electric


TECHNICAL DATA
1
Room: 26 °C/40% RH;
external temperature:
XDA – XDF MODELS 0221 0281 0341 0481 0501
35 °C; R407C.
Power supply V/ph/Hz 230/1/50 400/3+N/50
Mechanical cooling1 2
Room: 26 °C;
Total/sensible cooling external temperature:
1.058 6,3/5,8 7,0/6,4 9,0/9,0 12,0/12,0 14,9/14,9
capacity 14 °C; R407C.

Airflow m³/h 2230 2230 2900 3920 3920 3


Optional.
Free-cooling2
Sensible cooling capacity kW 9 9 11,7 15,8 15,8
COMPONENT FEATURES
N° of evaporator fans 1 1 1 1 1
N° of condenser fans 1 1 2 2 2
Air filter efficiency EU2 EU2 EU2 EU2 EU2
Electric heating3 kW 2 2 4 4 4
DIMENSIONS
Height mm 1970 1970 2130 2130 2130
Width mm 850 850 1160 1160 1160
Depth mm 450 450 650 650 650
XMF MODELS 0221 0281 0341 0401 0491 0555
Power supply V/ph/Hz 230/1/50 400/3+N/50
Mechanical cooling1
Total/sensible cooling
kW 5,7/5,7 7,1/7,1 8,4/8,4 10,8/10,8 12,3/12,3 16,5/16,5
capacity
Airflow m³/h 1500 2000 2200 3700 3700 3710
Free-cooling2
Sensible cooling capacity kW 6,1 8,1 8,9 15 15 15
COMPONENT FEATURES
N° of evaporator fans 1 1 1 2 2 2
N° of condenser fans 1 1 1 2 2 2
Air filter efficiency EU2 EU2 EU2 EU2 EU2 EU2
Electric heating3 kW 2 2 4 4 4 4
DIMENSIONS
Height mm 1960 1960 1960 1960 1960 1960
Width mm 1200 1200 1200 1200 1200 1200
Depth mm 600 600 600 600 600 600

Life is On | Schneider Electric 89


Spilt units for internal installations

Uniflair SP
UCA – UCF – UWA – UWF

Range
Cooling capacity: 5,9 ÷ 14,5 kW
Refrigerant R407C
Available versions
• Ceiling mounted (UCA)
• Ceiling mounted with direct free-cooling (UCF)
• Wall mounted (UWA)
• Wall mounted with direct free-cooling (UWF)

Standard features
• Units are made of two separate sections: the evaporation section, which is installed inside the • Internal and external units
conditioned room (UCA – UCF – UWA – UWF), and the condensation section (MRA), which is are powered separately.
installed on the outside. • Power supply:
• The evaporator is designed to be fixed to the ceiling or a wall and, with advanced microprocessor - 230 V/1/0 Hz or 400 V/3+N/50 Hz
control, it is very precise in maintaining the set parameters inside the conditioned room. (Standard, according to the model)
• Servicing is very simple as different access is given to the electrical board, the technical • Main power supply + UPS
compartment, and the servomotor for the free-cooling damper. - 48 VDC (evaporator DC-fan/s)
• There is a special panel for the fan compartment, which means calibration and servicing can be • Evaporator sections are equipped with:
carried out safely without having to turn the unit off. - Microprocessor control
• UCF units have free-cooling that intakes air from the back of the unit through a connection - EU4 filter (optional)
that can be made using either rigged ducting or flexible piping. - Scroll compressor
• The user terminal (on request) is fitted to the wall for the ceiling units and onboard - Modulating condenser fan/s speed control
for the wall fitted units, and gives complete control for the unit regarding changing
and displaying the operating parameters.

TECHNICAL DATA 1
Room: 26 °C/45% RH;
MODELS CEILING UCA – UCF WALL UWA – UWF external temperature:
0341 0401 0481 0341 0401 0481 35 °C; R407C.
Power supply V/ph/Hz 230/1/50 230/1/50 2
Room: 26 °C; external
Mechanical cooling1
temperature: 14 °C;
Sensible cooling cap. kW 5,9/5,9 7,1/7,1 8,1/8,1 10,4/10,4 14,5/14,5 5,9/5,9 7,1/7,1 8,1/8,1 10,4/10,4 14,5/14,5 R407C.
Airflow m³/h 1850 1850 220 2600 3900 1850 1850 2200 2600 3900
UCF-UWF 0341 0401 0481 0341 0401 0481
3
ARI standard.

Free-cooling2
Sensible cooling cap. kW 6,7 6,7 6,9 9,5 14 6,7 6,7 6,9 9,5 14
Airflow m³/h 1850 1850 220 2600 3900 1850 1850 2200 2600 3900
DIMENSIONS
Height mm 330 330 330 410 410 1200 1200 1200 1300 1300
Width mm 950 950 950 1150 1150 980 980 980 1150 1150
Depth mm 1050 1050 1050 1300 1300 330 330 330 410 410
EXTERNAL UNIT MRA 0221 0281 0341 0401 0611 0211 0281 0341 0401 0611
Power supply V/ph/Hz 230/1/50 400/3+N/50 230/1/50 400/3+N/50
Nominal compressor
kW 1,7 2,1 2,6 3,1 4,6 1,7 2,1 2,6 3,1 4,6
power3
Airflow m³/h 1800 2990 2990 6290 6290 1800 2990 2990 6290 6290
DIMENSIONS
Height mm 610 610 610 1230 1230 610 610 610 1230 1230
Width mm 850 850 850 1200 1200 850 850 850 1200 1200
Depth mm 345 345 345 80 80 345 345 345 480 480

90 Life is On | Schneider Electric


Life is On | Schneider Electric 91
Schneider Electric Industries SAS

35 rue Joseph Monier


92500 Rueil-Malmaison, France

schneider‑electric.com.

March 2019

©2019 Schneider Electric. All Rights Reserved. Schneider Electric | Life Is On is a trademark
and the property of Schneider Electric SE, its subsidiaries, and affiliated companies.
998-20086951_GMA-US_A