High Performance

Chillers
Aquaflair
Uniflair chillers designed for technical
cooling applications in data centers,
buildings, and industrial processes

schneider-electric.com
1 • Schneider Electric • Aquaflair > Uniflair chillers
2 | Aquaflair chillers schneider-electric.com

Aquaflair
Combining cutting-edge technology with energy efficiency
and environmental protection is the basis of these units.
Uniflair™ chillers are designed to offer a complete solution
for mission-critical installations. High energy efficiency,
complete reliability, and total flexibility guarantee total cost
of ownership (TCO) reduction and the integration in Tier
III and IV data centers and mission-critical installations.

All the units are all-in-one for easy design and installation
and completely configurable to guarantee use in multiple
applications and environmental conditions for a continuous
and quiet operation.

The component selection includes excellent technologies


such as integrated automatic transfer switches,
scroll, screw, and oil-free compressors, variable
speed technology driven and monitored by the chiller
microprocessor control both for compressors and for pumps.

Schneider Electric™ policy is one of continuous technological innovation and the Company therefore reserves the right
to amend any data herein without prior notice. The images shown in this catalog are for descriptive purposes only.
They may therefore differ from specific models which are selected. Some of the features described may be available
only for some models or configurations. Please refer to the specific technical literature for further details. Technical
data here reported according to EN 14511 standard.
schneider-electric.com Aquaflair chillers | 3

Table of contents

The solution for IT mission-critical applications Page 6 — 7

The issue-free chiller solution for industrial Page 8 — 9



processes

Cooling and heating for innovative building systems Page 10 — 11

Integrated free-cooling system Page 14

Adiabatic cooling Page 15

Variable speed compressors Page 16

Acquaflair chillers with zero ambient impact Page 17


R1234ze refrigerant

Optimized management Page 18


Advanced control strategies Page 19
Acoustic impact Page 19
Prepackaged solutions Page 20
Variable speed driven onboard pumps Page 20
Prefabricated Data Center Modules Page 21
Aquaflair cooling portfolio Page 22 — 23
Technical data sheets From Page 24
SmartStruxure™ solution Page 72 — 73
Schneider Electric Cooling Services Page 74
Cooling for Datacenter interactive application Page 75
4 | Aquaflair chillers schneider-electric.com

Flexibility
Modular and tailored solutions for any application

Availability
Continuous operation to safeguard customers' business

Energy saving
Technological excellence for efficient performance
schneider-electric.com Aquaflair chillers | 5
6 | Aquaflair chillers schneider-electric.com

Maximum efficiency,
total availability
where no failure is allowed
schneider-electric.com Aquaflair chillers | 7

The solution for IT mission-critical applications

Total cost of ownership Availability


High performance technological solutions. Optimize Compressors. Scroll and screw compressors utilize few
the unit operation at any load or ambient condition, moving parts for increased reliability and life expectancy.
guaranteeing an extremely low power consumption. Oil-free solution. Centrifugal compressors which operate
Integrated free-cooling system. An efficient method without oil increase operational availability.
for reducing the energy consumption at low outside air Modulating compressors. Ease the mechanical and
temperatures to assist in data center or process cooling electrical stress on compressor start-up. Aquaflair chillers are
energy optimization. Redundant components. Single points of failure in designed combining
Modular strategy. Mechanical equipments combined the system have redundant components to maintain cutting-edge technology
with control devices allow a modular installation which availability and reliability. with extensive tests for
guarantees to follow the growth of the site, reducing the Dual A-B power inputs. Draws power from the energy efficiency and
continuous availability
CapEx and deferring the investment throughout the years. secondary line for power protection with dual feeds for
Optimized management. Connection between redundancy (optional). Energy savings, complete
the computer room air conditioners and the chillers Separate power input. Draws power from the external reliability, and total flexibility
guarantees energy maximization, based on real, UPS for mainboards and heaters to monitor and protect guarantee TCO reduction and
instantaneous load conditions. the unit even in complete power failure mode. integration in Tier III and IV
Quick restart. Full-load operation in less than three Quick restart. Full-load operation in less than three data centers.

minutes with specific settings permits undersizing of minutes with specific arrangements guarantees
The all-in-one design and
the storage tanks. continuous chilled water availability to the data center.
the complete configurability
Oil-free solution. Centrifugal compressors operating Active response controls. Monitors and actively adjusts allow easy installation and
without oil minimize the energy impact of the chiller. cooling capacity to ensure proper server inlet temperatures. tailored solutions to meet the
Tandem compressors. Quiet and efficient operation of Through the microprocessor controller, visibility into the specific needs of each critical
compressors, connected on a common circuit for staged operation and health of the unit is provided. application.
capacity control. Electronic expansion valve. Refrigerant flow
Integrated hydronics package. Includes all the optimization at any load and temperature conditions.
necessary components to make one connection to Continuous indirect refrigerant charge monitoring.
the chiller without the need of external connections to Wide range for ambient temperature design.
auxiliary equipment, such as pumps, thus increasing Guarantees continuous operation at ambient
the speed of deployment. temperatures from -25 °C up to 50 °C. Wider limits
Integrated pumps adjustment system. Onboard are available upon request.
variable speed drive (VSD) pumps are available for Tier III- and IV-ready. Units are able to be fully integrated
adaptation to changing conditions on-site or for into the latest generation of data centers for guaranteed
continuous adjustment of the available pressure (optional). continuous operation.

Serviceability Manageability
Operational service. Allows critical components to be Local area network. Creates a shared communication
maintained/replaced while the system is in operation. between all available units for energy optimization and
Easy service access. Allows for all serviceable management during emergency situations.
components to be replaced/maintained by easily Building management system integration. Units are Some of the features
accessible panels/doors. able to send alarms and data points to a single system described may be
Service monitoring. All the monitoring devices onboard in order to manage critical building infrastructure from a available only for some
the unit allow for preventative maintenance and general remote location. models or configurations.
service during system operation. Network interface. Provides management by connecting Please refer to the
the device directly to the network with a dedicated IP products' technical section
address, avoiding the need for a proxy such as a server. for details.
Monitoring is available via Web browser.

-30% 99.99%
of annual energy is the reliability of Tier III
consumption* and Tier IV* data centers
thanks to the integrated according to Uptime
free-cooling. Institute certification
* Average value in a medium standards.
DC in Europe. *Aquaflair chillers are Tier III-
and Tier IV-ready design.
8 | Aquaflair chillers schneider-electric.com

Protect the environment


and your investments
Focus on your core business
schneider-electric.com Aquaflair chillers | 9

The issue-free chiller solution for industrial processes

Multiple processes adaptability Dual A-B power inputs. Draws power from the
Wide range of operation features. Units are able to secondary line for power protection with dual feeds
adapt to a large variety of industrial processes at any for redundancy.
external conditions. Quick restart. Full-load operation in less than three minutes
Engineering-to-order design. Cooling system design with specific arrangements guarantees continuous chilled
can be adjusted to fit a specific application. water availability to the data center.
Multiple set point for water temperatures. Active response controls. Monitor and actively adjust
Guarantees different settings for multiple processes stages the cooling capacity to ensure proper temperatures. The use of chilled water
such as plastic manufacturing, healthcare equipment Through the microprocessor controller, visibility into the is essential in many
manufacturing, and food and beverage applications. operation and health of the unit is provided. industrial production and
Wide range for ambient temperature design. Current monitoring. Allows continuous monitoring of transformation
Guarantees continuous operation from -40 °C the current absorbed from the compressors to signal processes.
up to 50 °C. any difference from default values.
Needs vary from heat
Integrated hydronics package. Includes all the absorption to the necessity to
components required to make one connection to the Total cost of ownership keep components, rooms, and
chiller, thus increasing the speed of deployment. No waste of water. Thanks to the use of water in a working phases at controlled
High head pressure pumps. Are available to be closed circuit. temperature conditions.
integrated and managed by the chiller. High performance technological solutions. Optimizes
Integrated primary and secondary loop. Enables quick the unit operation at any load or ambient condition, Reliability and easy
adjustment of the cooling
and easy design and installation for all applications. guaranteeing extremely low power consumption.
system to the specific
Close control on water temperature. Enables the use Undersize for storage tanks. Quick restart allows application are key factors
on high-precision applications like laser manufacturing or full-load operation in less than three minutes with to ensure an uninterrupted
biomedical devices. specific settings. production and to optimize
Continuous load adaption. Is available on the whole Integrated free-cooling system. An efficient method the process reducing costs.
range to follow all phases of the manufacturing process. for reducing the energy consumption at low outside air
Non-ferrous materials. Available for water circuits where temperatures to assist in energy optimization.
ferrous materials must not be present.
Heat exchangers treatment. Protects air side heat Serviceability
exchangers in saline or aggressive environments. Reduced maintenance. Closed circuit operation, proven
technology, and design and test of all refrigeration circuits
Reliability reduces maintenance over the lifetime of the unit.
Safe and reliable design. Guarantees operation in Operational service. Critical components can be
the most varied working conditions thanks to the use maintained/replaced while the system is working.
of cutting-edge solutions and to the availability of a wide Service monitoring. All the onboard monitoring devices
range of accessories and options. allow preventive maintenance and check of the operation
Pretested and validated solution. All units are tested at while the system is working.
the end of the manufacturing process.
Compressors. Utilize few moving parts for increased Manageability
reliability and life expectancy. Easy to use. The local user terminal displays all unit
Redundant components. Redundancy is applied on settings and data points. The most used parameters
the critical sections of the units to maintain availability are visible on the main screen.
on 24/7 operating processes. Network interface. Provides management by connecting
Electrical panel. Units are equipped with double closure the device directly to the network or to the management
panels, certified for outdoor use and manufactured in system avoiding the need of a proxy such as a server.
compliance with all safety standards.

-10 °C +-0.2 °C
Water inlet temperature up Close control water
to 30 ° C and outlet temperature guarantees use
temperature in high-precision applications
down to -10 ° C allow like laser machineries or
application in many industrial biomedical devices.
processes.
10 | Aquaflair chillers schneider-electric.com

Smart buildings
With efficient, quiet,
and adaptative operation
schneider-electric.com Aquaflair chillers | 11

Cooling and heating for innovative building systems

Operative cost OpEx Investment optimization CapEx


High efficiency technological solutions. Optimize Low noise impact. Allows installation in different areas,
the unit operation at any load or ambient condition, limiting the expense for noise barriers or louvers.
guaranteeing an extremely low power consumption. Package solution. Includes all the necessary components
Excellent performance at any load or temperature to make one connection to the chiller without the need of
conditions. All the ranges, and particularly the modulating external connections to auxiliary equipment, such as pumps,
units, are characterized by high efficiency at part loads thus increasing the speed and reducing cost of deployment.
Aquaflair systems offer
or at low ambient conditions with a short payback time Underflow air distribution. Enables quick and low-cost
an efficient, quiet, and
compared to conventional chillers, reducing consistently modifications of the internal building layout. flexible solution for
the operational costs. Low starting current. VSD and oil-free technology on buidings.
Modulating compressors. VSD centrifugal compressors compressors allow for low starting currents. A soft starter
are able to modulate the cooling capacity to match is also possible to add to the unit. Where high performance
the actual thermal load, therefore minimizing energy Water heat recovery. Integrated to provide water for cooling is crucial, Uniflair long
experience on mission-critical
consumption of the chiller and requiring little to no backup sanitary uses without boilers or heaters.
installations guarantees
water tanks. Easy and quick installation. The units are totally investment optimization, short
Heat pumps. Allows 65 percent heating produced via assembled, cabled, and refrigerant and oil charged design and on-site operation,
renewable energy. Modulating heat pumps guarantee 30 in the factory. They are complete with all the control ease of maintenance,
percent reduction compared to a traditional solution. and protection devices necessary. Only electrical and complete flexibility, and quiet
Heat recovery. Optimize the energy usage in reheating hydraulic connections are made on-site. operation.

and heating systems. Reduced mandatory controls. Reduces the ordinary


Aquaflair units are usually
Geothermal applications. Are available for installation checks cost when compared to boilers or other.
installed in hospitals, hotels,
with complete renewable energies usage. Tax reduction. Is possible thanks to heat pumps and small and large buildings
Oil-free solution. Centrifugal compressors operating or renewable energies. designed for smart operation.
without oil minimize the energy impact of the chiller. Existing plant reconversion. Using high water temperature
User-friendly control system. Contains all necessary heat pumps (up to 55 °C water). Completely configurable
operating and safety controls with a simple interface and a units allow tailored solutions

large screen for quick and easy checks on unit operation Quiet operations to meet the specific needs of
each application.
and maintenance. Low noise operation. Both standard Low Noise and
Underflow air distribution. Is an efficient solution to optional Ultra-Low Noise versions guarantee very low
provide cooling and heating in the building. acoustic impact, guaranteeing a wide range of installations,
BMS integration. Units are able to send alarms and even where the noise restrictions are very tight (hospitals,
data points to a single system (natively integrated with hotels, etc.).
Schneider Electric SmartStruxure platform or using specific Oil-free solution. Magnetic bearing compressors allow
adaptor for other BMS platforms) in order to manage critical extremely quiet operation.
building infrastructure from a remote location. Variable speed fans. Variable speed fans reduce
Innovative defrosting system. Occurs only in noise impact during off-peak cooling periods. Benefits
necessary conditions, reducing the energy consumption are maximized with electronic commutated motor fans,
on heat pumps, and improves heating operation. available on all the range.
Chilled beams and radiant panels optimization. The Internal installation. Backward curved centrifugal fans
units are designed to operate with smart cooling and are available in the middle range allowing the possibility
heating systems, maximizing the efficiency at the typical to install the chiller inside building where the air is taken/
water set points for those applications. discharged through duct or plenums.
Integrated shifting set point system. Adapts the water
temperature to the ambient conditions with a consequent
reduction in energy consumption.

45 dB(A) -30%
Is the limit for most Is the annual energy
residential areas reduction allowed by
during night. variable speed technology
compared to traditional heat
pumps.
12 | Aquaflair chillers schneider-electric.com

Technological solutions Our experience and


are constantly evolving expertise in cooling.
and improving.
schneider-electric.com Aquaflair chillers | 13

100% state-of-the-
art technology
Many years of experience, combined with innovative technology, have enabled our
designers to make the technical and operational choices necessary to reach technical
excellence in our products and make them ideal in cutting-edge applications.
14 | Aquaflair chillers schneider-electric.com

Integrated free-cooling system

Free-cooling is an efficient method


to reduce energy consumption at low
outside air temperatures. It enhances
energy optimization in data center and
process cooling.

According to the ambient temperature, the chilled water


is partially or totally produced exploiting the thermal
exchange with the external air. This significantly reduces
the chillers' energy impact.

When the external air temperature is low enough, the


microprocessor control system activates the free-cooling
pump, which circulates water inside special heat exchange
coils. Water is cooled by external air brought in by the fans,
which, together with the pump, are the only components
that absorb energy.

Intelligent Glycol-free
free-cooling (IFC) installations
Designing a reliable system means choosing units Designed for applications where the use of glycol
which are both intrinsically reliable and including is not allowed in the data center, this solution uses
“N+1” or “N+N” redundancy logic. an intermediate heat exchanger to limit glycol in
free-cooling circuit only, while using water in the
With IFC, all the available units are connected
main circuit.
allowing chilled water to circulate through all the
free-cooling coils, thus increasing the free-cooling The careful selection and position of the
surface and the benefit in terms of thermal intermediate heat exchanger allows the installation
dissipation: of the onboard main pump too, to minimize the
efficiency losses typical of intermediate heat
on Schneider Electric exchangers.
+7% free-cooling*
delta T = 2 °C
+35% on traditional systems* in the heat exchanger*
* Average values. * Average values.

Schneider Electric free-cooling OpEx savings

-41%
Annual Absorbed Energy — [MWh]

1,600 STANDARD
STANDARD SE FREE-
FREE-
1,400 CHILLER COOLING
-6% Energy consumption kWh 1,424,766
COOLING

1,193,799 1,160,297
1,200
Standard Chiller

Energy saving % 0 19% 23%


Free-Cooling

Cost saving € 0 -25,406 -29,092


Traditional

1,000
Absorbed
Energy
Annual

Load: 750 kW
800 Location: Paris
€/kWh: 0.1
600 Design water temperature: 10 °C/15 °C
schneider-electric.com Aquaflair chillers | 15

Adiabatic cooling system


Adiabatic cooling is based on the natural process of water evaporation, to shift
average suction condensing and free-cooling coils air temperature to the wet bulb
conditions. As water evaporates, energy is dissipated by the air and temperature is
reduced, which means operating conditions are improved and energy efficiency is
maximized.
This, combined with high chilled water temperature, results in significant OPEX
reduction for next generation datacenters.
Schneider Electric applies these concepts on mid-large air-cooled and free-cooling
chillers.

Energy Saving
Paris -35% Moscow -27%

Beijing -23%


Buenos Aires -27% Sydney -23%

New Delhi -18%

Data comparing traditional free-cooling units at 18/24°C water temperature with free-cooling adiabatic chillers at
18/28°C water temperatures.

Main Benefits
•T
 he system is applicable on chillers and free-cooling • Extended free-cooling operation, (up to 3°C more
chillers (>300kW) economization hours)
• Improved cooling capacity with lower CAPEX (up to • Factory fitted and tested
10% cost saving) • Ready for standard ISO container shipping
• Increased efficiency in summer mode, lower OPEX • Easy maintenance
(between 10 to 15% less, depending on the climatic zone) • Completely accessible unit

How it’s made


• Nozzles: their position has been defined in order to • Protective filter: prevents non-evaporated water from
optimize the drops distribution damaging the internal components and the coils.
• Layout: the “V” shape arrangement for coils and free- • Embedded control system: controls and optimizes the
cooling coils allows for integrated installation unit operation, including adiabatic pre-cooling.

Control board
and human
interface

Water collect and


discharge system

Nozzies

Onboard pumping Protective filters


for adiabatic system

Baffles
16 | Aquaflair chillers schneider-electric.com

Variable speed compressors


Inverter scroll and oil-free centrifugal solutions

Variable speed compressors, normally driven by inverter, are among the most
interesting solutions that characterize modern chillers. There are different solutions
according to the application size, i.e., inverter-driven scroll or oil-free centrifugal
compressors, but all of them provide a high level of reliability and may be
implemented in a wide range of applications and operating parameters.

Main benefits of variable speed compressors


• Increased efficiency at partial loads thanks to •L
 imitation of the maximum absorbed current (LRA)
the continuous regulation of the cooling capacity since the inverter-driven compressor can always be
and installation of the compressors on the same started up at low speed.
cooling circuit. •L
 imitation of noise level.
• Energy efficiency is maintained even during mixed- • Increased system reliability thanks to the reduction in
mode operation by optimizing compressor usage in compressor inrush current, thus reducing mechanical
conjunction with free-cooling at full load. and electrical stress.
• Regulation of the cooling capacity over a wide •R
 eduction or elimination of water tanks on the
operating range, i.e., from 10% to 100% continuously. hydraulic lines.
• High precision on chilled water temperatures (±0.2 °C),
thanks to continuous regulation by means of an inverter.
Annual energy consumption [MW]

Screw
Compressor Screw
Compressor Oil-Free
Compressor Oil-Free
+ Free-Cooling
Compressor
+ Free-Cooling

Based on 1 MW free-cooling chillers at the climatic profile of Paris. Nominal conditions: water 10/15 °C, 20% glycol.

Type of chiller 100 Kw Paris Frankfurt Milan Madrid Comparison of annual


energy consumption of
Traditional unit kWh 57,271 56,524 57,261 58,095
a traditional unit and
Unit with inverter kWh 46,843 46,183 46,778 47,763
a unit equipped with a
% -18% -18.3% -18.3% -17.8% variable speed compressor
(note: traditional unit
has two ON/OFF scroll
Type of heat pump 100 Kw Paris Frankfurt Milan Madrid
compressors placed
Traditional unit kWh 24,184 33,853 16,154 29,572
on the same refrigerant
Unit with inverter kWh 16,252 24,377 11,226 20,163 circuit; modulating unit is
% -32.8% -28% -30.5% -31.8% equipped with two scroll
compressors, one of which is
variable speed, on the same
refrigerant circuit).
schneider-electric.com Aquaflair chillers | 17

Aquaflair chillers with zero ambient impact


R1234ze refrigerant
Adiabatic cooling is based on the natural process of water evaporation, to shift average suction
condensing and free-cooling coils air temperature to the wet bulb conditions. As water evaporates, energy
is dissipated by the air and temperature is reduced, which means operating conditions are improved and
energy efficiency is maximized. This, combined with high chilled water temperature, results in significant
OPEX reduction for next generation datacenters. Schneider Electric applies these concepts on mid-large
air-cooled and free-cooling chillers.
Europe: F-Gas regulation to reduce
average GWP2 forcing the replacement
of current refrigerants with low GWP ones China: announced in 2014 the management
and replacement of HFC refrigerants as part
of an energy conservation and emissions
reduction plan

North America: possible


ban of HFC refrigerants in
California: proposal to ban the sale 2025. Climate Action Plan
of all HFC refrigerants with high to reduce HFC emissions
GWP in 2020 and to ban new
stationary refrigeration equipment
using HFC with a GWP >150

Australia: new phase


down strategy for HFC-
refrigerants starting Jan
2018, reducing HFC
Switzerland: ban of R134a emissions by 85% by
on chiller units >400kW 2036

300 - 1000 kW BREC-BREF air-cooled


and free-cooling chillers with double screw
compressors and HFO refrigerant

What are the main requirements for the new


refrigerant?
• Compressors specifically manufactured for R1234ze use

• R1234ze belong to Safety Class A2L (Slightly flammable) and require:


- ATEX explosion proof components for compressors
- Refrigerant leakage sensors located in the electrical board and optional compressor
acoustical casing
- Ventilation system for compressor acoustical casing

Operation limits: R1234ze Vs R134a


• Zero ambient impact: GWP < 1

• High ambient temperature operation, up to 50°C (up to 55°C on request)

• High chilled water outlet temperature, up to 25°C at full load (up to 30°C on request)
18 | Aquaflair chillers schneider-electric.com

Optimized management

Management of the whole system


allows energy consumption to be
optimized and integrated control
strategies to be implemented, which
would otherwise not be possible.

All the Schneider Electric cooling resources can


therefore be linked* together in a network to maximize
the operating parameters and the current required.
Row and room cooling units communicate to the
chiller, reducing the energy requirement by means
of a “tracking logic” for the current thermal load.
The chilled water temperature varies dynamically to
minimize compressor consumption and maximize the
use of free-cooling, while maintaining the optimum
temperature in the data center.
* Specific configuration may be required.

How it works
25
6.0
20
Water temperature [°C]

5.0
Energy efficiency [%]

15
4.0

3.0
Medium 10
2.0
Min Load
Load Medium
Load Max Load 5
1.0 EER
Operating water temperature
0 0

Number of units ON

Energy saving improvement


SUMMER WINTER

With optimized management

+28%
Traditional

+39%
+20% +42%
0%
0%
EER

EER

Min Med Tot Load Min Med Tot Load

Comparison between a traditional Summer mode external Free-cooling external Load variation: 100 kW – 300 kW
solution and an optimized management temperature: 35 °C temperature: 8 °C Water set point: 12 °C
logic:
schneider-electric.com Aquaflair chillers | 19

Advanced control strategies


All the control software solutions for
the Aqualflair range are developed
by Schneider Electric and specifically
designed for each unit configuration. This
choice enables the company to equip
each machine with a tailor-made control
which manages all aspects of the unit.
• Precision: the units use advanced algorithms to
accurately control the chilled water temperature.
• Availability: all the monitoring devices onboard the unit
allow a preventive maintenance and a check of the
working operation while the system is functioning.
• Amperage monitoring permits continuous supervision of
the compressors' absorbed current to signal possible
discrepancies with the default values.
• Quick restart: chiller control software provides full
cooling capacity within three minutes* after power
failure, optimizing reliability and reducing the capital
expense thanks to the downsize of backup water tanks.
• Local area network: creates a shared control between
all the available resources for energy optimization and
management of emergency situations.
• Connectivity: the unit sends alarms and data points
to manage critical building infrastructure from a
single system.** Additional network interfaces provide
management by connecting the device directly to the
network with a dedicated IP address. This eliminates
the need for a proxy such as a server. Monitoring is
available via Web browser.**
• 7-inch, touch-screen LCD display interface.

Acoustic impact
Reduction in noise impact is one of the
most critical issues designers are called
on to solve when choosing plant systems.
Uniflair chillers offer low noise solutions with extremely
low acoustic impact thanks to:

• EC motor Acousti-Composite fans with high


efficiency and low acoustic impact.
• Completely isolated soundproofing enclosures
for compressors.
• Variable speed compressors, to adapt the noise
emission to the thermal load.
• Extremely quiet oil-free centrifugal solution*.
• Extra quiet regulation algorithms which control
the rotation speed of the fans.

* Available on large chillers only.


** With specific adaptor.
20 | Aquaflair chillers schneider-electric.com

Prepackaged solutions

Uniflair chillers are designed to integrate


the main electrical and hydraulic
components onboard the units. Free-
cooling circuit, primary pumps, VSDs,
water tanks, and automatic transfer
switches are available to be factory
installed which reduces the design and
installation phases and allows
a solution ready to be used.
Thanks to this logic, the availability level is further
increased since the usual single point of failure is
removed, for instance:

• The integrated ATS connects the unit to both the


redundant power supplies. According to the line
presence, the unit manages the connection while
the control board operates due to the Uniflair
backup system.
•A
 n additional external UPS* connection is available
for critical components protection.
•T
 he default network connection allows for group
management without a master or external device
which could represent a critical item.
•T
 he possibility to choose onboard pumps guarantees
better availability when compared to single external
pump group.

Variable speed driven onboard pumps


Choosing the best solution for pumps
is certainly one of the most important
challenges for the designer. Uniflair
chillers have an onboard pump group
which can be inverter-driven.
Variable speed driven pumps integrated in the units and
driven by the chiller controller allow:

• Increased efficiency due to the continuous speed


adaption on the pressure drops of the circuit.
• Increased flexibility and modularity. It is possible to change
and adapt the available head pressure from the chiller
terminal, guaranteeing on-site optimization and modular
installations.
• Reduction in capital expense, since a single-circuit
design can be easily applied, saving the extra cost
for the additional devices typical of primary/secondary
circuits and manifolds, tanks, and secondary pumps.

* Specific configurations may be required.


schneider-electric.com Aquaflair chillers | 21

Schneider Electric Prefabricated


Data Center Modules
Why go Prefabricated? Why Schneider Electric?
Predictable Performance 1. Experience - Schneider Electric has over 15
Prefabricated Modules are implemented as years of experience in prefabricated data center
designed, and are configured and tested in the manufacturing. Over 300 projects with 500+
factory prior to shipment. modules.

Faster Deployment 2. Broad offering of Prefabricated Modules


Prefabricated Modules simplify the planning, - Wide range of prefabricated options to meet
construction, and implementation, reducing the different applications
total time from concept to commissioning.
3. Global capabilities with local support -
Scalability Global supply chain with experts in your region to
Prefabrication gives you the flexibility to scale support with applications and engineering
your data centre growth at a more granular level,
4. StruxureWare for Data Centers - Modules
minimizing oversizing and up-front expenditures.
are fully instrumented and compatible with
Schneider’s DCIM software suite

5. Library of Reference designs – Pre-


engineered prefabricated reference designs in a
range of sizes and tier levels

New Build
Power IT Cooling
Acquiring

Start up

Engineer Civil works/


& purchase site preparation Construction Installation

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

Containerized Solution
Civil works/ Construction
Acquiring

Start up

Engineer site preparation


& purchase
Production in factory Delivery Install
TIME SAVED = 30%

Prefabricated IT Prefabricated Prefabricated


Power Chilled water systems
•A
 vailable in All-in-One, Single, Dual, • Enclosed power modules with UPS, •H
 ydronics Modules – Pumps, drives,
and Multi-Bay Configurations switchboards, fire suppression, valves, and controls for Tier II and
•C
 ontainerized Modules – easy monitoring, and security Tier III designs
international transport, ruggedized • Power skids for large-scale, indoor •C
 omplete portfolio of chillers with and
applications deployments without free cooling options
•P
 urpose-Built Modules for maximum • Ranges from 250kW-1200kW • Indirect and direct air economizer,
space and aesthetics chilled water, and direct expansion
•M
 odular Rooms – field-assembled, solutions optimized for prefabricated
combine benefits of modularity and modules
traditional IT space1
22 | Aquaflair chillers schneider-electric.com

Aquaflair cooling portfolio


Small Medium

Uniflair ERAC
Page 24 – 25

Cooling only Uniflair LRAC
Page 22 – 23
Uniflair ISAC
Page 26 – 27

Air-cooled
units
Uniflair ERAH
Page 24 – 25

Heat pumps Uniflair LRAH
Page 22 – 23
Uniflair ISAH
Page 26 – 27

Uniflair ERAF
Page 36 – 37
Free-cooling
units Cooling only
Uniflair ISAF
Page 38 – 39

Cooling only

Water-cooled
units

Heat pumps

Uniflair ERCC
Page 52 – 53

Cooling only
Uniflair ISCC
Page 54 – 55

Uniflair ERCH
Page 52 – 53

Units with
Heat pumps
ducted fans
Uniflair ISCH
Page 54 – 55

Uniflair ERCF
Page 56 – 57

Free-cooling
Uniflair ISCF
Page 58 – 59

Scroll compressors Screw compressors

Oil-free compressors Variable speed drive compressors


schneider-electric.com Aquaflair chillers | 23

Large Extra Large

Uniflair TRAC
Uniflair BREC
Uniflair BREC

Page 28 – 29 Page 30 – 33 Page 30 – 33

Uniflair TSAC Uniflair BCEC


Page 34 – 35
Page XX – XX

Uniflair TRAH
Page 28 – 29

Uniflair TRAF
Uniflair BREF
Uniflair BREF

Page 40 – 41 Page 42 – 45 Page XX – XX

Uniflair TSAF Uniflair BCEF


Page 46 – 47
Page XX – XX

Uniflair BRWC
Page 48 – 49

Uniflair BCWC
Page 50 – 51

Uniflair BRWH
Page 48 – 49

24 | Aquaflair chillers schneider-electric.com

Air-cooled water chillers and heat pumps with axial fans for outdoor installations

Uniflair LRAC/LRAH
Range
Cooling capacity: 6 ÷ 40 kW
Heating capacity: 7 ÷ 43 kW
Available versions
- Low noise
- Top operating performance
- Condensing version*
Refrigerant R410A
Scroll compressor/s

Standard features
• Designed with a minimal footprint. • Water flow differential pressure switch.
• Self-supporting frame in galvanized steel (color • Predisposition for cooling/heating systems
RAL9022) with panels varnished with epoxy with heating panels.
powders in compliance with the ASTM B117 norm. • Rubber anti-vibration feet.
• Between one to two hermetic scroll compressors with • Heat pumps complying with EU Regulation 811/2013
internal thermal protection and anti-vibration feet. (heat pumps up to 70kW).
• Crankcase heaters**.
• Ecological refrigerant: R410A.
Total operating performance
• Refrigerant circuit in compliance with EC norms (PED
• Electronic expansion valve driven by the
97/23/EC Directive) in copper tubes mainly including a
microprocessor control.
filter dryer, water flow switch, thermostatic valve with
external equalization (stainless steel made), and high • Advanced UPCOxs microprocessor control system
and low pressure switches. with specific algorithm to:
- Outlet water temperature regulation
• Metal grille panel to protect the air side heat exchanger.
- Advanced management of compressors run
• Cycle inversion on the refrigerant side with four-way through automatic set-point sensitivity regulation
reversing valve**. - Advanced management of the defrosting function
• Stainless steel, brazed plate heat exchanger insulated to minimize cycle inversions**
with closed cell, expanded polyurethane. - Advanced antifreeze protection on evaporator
• Antifreeze heater on evaporator**. - Integrated LAN card for local network connection
• Air side heat exchanger with aluminum fins and of a group of chillers (up to 10 units, with one or
mechanically expanded copper tubes. two standby units)
• Axial fans, statically and dynamically balanced, • Moreover, the microprocessor control system
with sickle blades and with safety protection grilles. enables:
- Remote cycle inversion**
• Soundproofing polymeric impeller for each fan.
- The set point adjustment by a 0 V – 10 V
• Condensation control including continuous regulation
external signal
of fan speed.
- The management and selection of double set point
• Electric panel conforming to EC Directive 2006/95/EC - Free contact for general alarm and two
and Directive EMC 2004/108/EC with auxiliary addressable alarms
12 V circuit, general cut-off switch, magneto-thermal - Remote ON-OFF control
protection cut-off switches. - The ability to interface with main external
• UTS microprocessor control system with local user control communications protocols: Modbus, BACnet,
and monitoring terminal with LCD display and LED signals LonWorks, Metasys, TCP/IP, and SNMP
for all working parameters: chilled/hot** water temperature
regulation, antifreeze protection, compressor timing and
protection, fan speed regulation, alarm code signalling,
centralization for general alarm control and remote ON-OFF * Optional for LRAC, when possible.
switch, and remote cycle inversion**. ** For LRAH.
schneider-electric.com Aquaflair chillers | 25

Technical Data 1. D
 ata refer to nominal
conditions: water
LRAC/LRAH Models 023B 032B 041B 054A 067A 090A 120A 137A 180A
temperature 12/7 °C,
Power supply V/ph/Hz 230/1/50 400/3 + N/50
external temperature
Compressors/circuits nr. x mod. 1/1 1/1 1/1 1/1 1/1 1/1 2/1 2/1 2/1 35 °C glycol 0%, refrigerant
Evaporator nr. x mod. 1 x brazed plate R410A, fouling factor
Fans nr. 1 1 1 1 2 2 2 3 4 0.0 m2 °C/W
LRAC 2. Data refer to total absorbed
Cooling capacity (1) kW 6 8 10 14 17 19 27 33 39 power (compressors and
Absorbed power (1)(2) kW 1,6 2,3 3,1 4,6 4,8 6,3 9,1 10,7 12,7 fans)
EER (1)(2) 3,6 3,5 3,3 3,1 3,3 3,1 3 3,1 3,1 3. D
 ata refer to nominal
LRAH conditions: Inlet/outlet
Heating capacity (3) 6 9 10 15 18 21 30 36 42 water temperature:
Absorbed power (3)(2) 1,8 2,5 2,9 4,3 5,3 6,1 9,1 10,7 13,4 40/45°C; external air dry
bulb temperature 7°C,
COP (3)(2) 3,33 3,60 3,45 3,49 3,40 3,44 3,30 3,36 3,13
external air wet bulb
Seasonal efficiency class temperature 6°C, glycol
A+ A+ A+ A+ A+ A+ A++ A++ A++
(Regulation (UE) 811/2013) 0%; refrigerant R410A,
LRAC / LRAH Noise pressure level fouling factor 0.0 m2 °C/W
Noise pressure level dBA 34 34 34 35 37 38 38 40 41 4. S
 easonal Coefficient of
LRAC / LRAH Dimensions Performance
Height mm 650 650 650 1271 1271 1271 1271 1271 1271 5. Data refer to free field at
Depth mm 458 458 458 458 458 458 615 615 615 10 meters from the unit
Width mm 1274 1274 1274 1273 1273 1273 2054 2054 2054 operating without pump at
nominal conditions, with
fans at nominal conditions,
coil side, Q=2 directional
factor. At different
conditions and with
different configurations,
noise values may vary

Construction options Options


• Onboard water tank and pump. • Remote user terminal for:
• High head pressure pump*. - Display/entering of commands
• Condensing unit*. - Display unit status and alarms

• Unit works down to -20 °C. • Chilled/hot water piping filter.

• Production of glycol water mixture at low temperatures


option (down to -10 °C).
• Antifreeze protection on evaporator, water tank,
and pump.
• RS485 serial adaptor used to communicate with Uniflair
supervisory system or to interface with external BMS.
• LON® FTT-10 serial adaptor used to communicate with
external BMS managed with LON protocol.
• Hot gas bypass disposal for a constant outlet water
temperature, even with 0 to 100% charge variation
(optional; only LRAC).
• TCP/IP serial adaptor used to interface with external BMS.
• Condensing coils equipped with safety grilles and filter.

* On request.
26 | Aquaflair chillers schneider-electric.com

Air cooled water chillers and heat pumps with axial fans for outdoor installations

Uniflair ERAC/ERAH
Range
Cooling capacity: 50 ÷ 110 kW
Heating capacity: 55 ÷ 120 kW
Available versions
- Basic
- Quiet
- UltraQuiet
Refrigerant R410A
Scroll compressors

Standard feature
• Self-supporting frame in galvanized steel with panels • Phase sequence control and phase presence monitoring,
varnished with epoxy powders (color RAL9022). minimum / maximum voltage protection and correct
• Access panel to the unit equipped with handles and fast phase balancing.
screws. • Anti-freeze heaters (ERAH only)
• Two hermetic scroll compressors with internal thermal • Microprocessor control system including:
protection, discharge gas thermal protection (ERAH), - Local human interface with external display and
phase sequence control, safety internal valve, non- accessible via an access hatch
return discharge valve, oil level glass, anti-vibration - Outlet chilled water / hot water (for ERAH) temperature
supports. regulation by means of an exclusive algorithm
• Compressor casing for noise reduction, safe operation, - Production of chilled water to -10 °C
and protection. - External motorized isolating valve management
• Single or double ( **22A model) refrigerant circuit* - Anti-freeze protection
conforming to EC Directives (PED 97/23/CE) in - Compressor timing and protection
copper tubing including filter dryer, liquid sight glass, - Compressor rotation based on FIFO logic
thermostatic valve with external equalization, high and - Pump rotation (if present) on a timed basis for equal
low pressure switches, and high and low pressure operation and start-up of the stand-by pump (with alarm
transducers. signal) in the event of a breakdown
- Integrated LAN card for connecting more than one unit
• Environmentally friendly refrigerant R410A.
to the local area network
• Water side brazed plate heat exchanger in stainless
- Main electrical data acquisition and management
steel insulated with closed cell expanded polyurethane
- Integrated clock card.
• Water flow differential pressure switch. - Management of double set-point from remote control
• Air side exchange coil with aluminium fins and - Free-contact for general alarm and 2 for addressable
mechanically expanded copper tubes. alarms
• Refrigerant side cycle inversion with four-way inversion - Remote ON-OFF switch
valve (ERAH). - Ability to interface with two separate BMSs with different
• Sickle-blade axial fans, statically and dynamically protocols
balanced and made from composite materials for high - Direct connection to serial BMSs with Modbus protocols
efficiency and low acoustic impact with internal and (integrated RS485 serial card)
external safety protection grilles. - Set-point variation based on external temperature or
signal (0-10V, 4-20mA or 0-20mA).
• Modulating condensation control with fan speed
• Heat pumps complying with EU Regulation 811/2013
regulation.
(heat pumps up to 70kW) and 813/3013 (heat pumps
• Electrical panel conforming to EC standards (2006/95/ from 70kW to 400kW).
EC and EMC 2004/108/EC) protection grade IP54
with maximum internal temperature control, auxiliary
transformer, general auxiliary cut-off switch, magneto-
thermal protection switches with trip alarm signal on
compressors, magneto thermal protection for fan speed *ERAC models with **22A suffix are available with two
control protection, safe-motor for pumps protection compressors on two circuits.
and remote control cut-off switches. Electrical board
equipped with an embedded contact for an external
230V isolating motorized valve.
schneider-electric.com Aquaflair chillers | 27

Technical Data 1. D
 ata refer to nominal
conditions: water
ERAC/ERAH Models 0521A 0621A 0721A 0821A 0921A 0922A 1021A 1022A 1221A 1222A
temperature 12/7 °C,
Power supply V/ph/Hz 400/3/50
external temperature
Circuits / Compressors nr. x mod. 2/1 2/1 2/1 2/1 2/1 2/2 2/1 2/2 2/1 2/2 35 °C glycol 0%, refrigerant
Evaporator nr. x mod. 1 x brazed plate R410A, fouling factor
Fans nr. 2 2 2 3 3 3 3 3 3 3 0.0 m2 °C/W
ERAC — Basic/Quiet version Unit equipped with EC fans

Cooling capacity (1) kW 46 54 63 72 80 81 94 94 108 108 2. Data refer to total absorbed


Absorbed power (1)(2) kW 14,9 18,5 20,5 23,3 27,1 27,2 30,8 30,8 35,8 35,8 power (compressors and
EER (1)(2) 3,08 2,91 3,07 3,09 2,95 2,97 3,05 3,05 3,01 3,01 fans)
Unit equipped with EC fans
ESEER (3) 4,08 4,07 4,34 4,15 4,10 3,37 4,49 3,44 4,49 3,59
IPLV (4) 4,51 4,49 4,77 4,57 4,49 3,71 4,98 3,83 4,96 3,99 3. E
 uropean seasonal energy
ERAC — UltraQuiet version efficiency ratio
Unit equipped with EC fans
Cooling capacity (1) kW 44 52 61 70 78 78 91 91 103 104
Absorbed power (1)(2) kW 14,8 18,7 20,9 23,3 27,4 27,5 31,5 31,5 37,1 37,1 4. Integrated partial load
EER (1)(2) 2,97 2,78 2,91 3,00 2,84 2,83 2,89 2,88 2,77 2,80 value
Unit equipped with EC fans
ESEER (3) 4,32 4,25 4,46 4,41 4,29 3,39 4,57 3,35 4,55 3,48
IPLV (4) 4,75 4,67 4,89 4,82 4,69 3,78 5,09 3,77 5,04 3,92 5. Data refer to nominal
conditions: Inlet/outlet
ERAH - Basic / Quiet version
water temperature:
Heating capacity (5) 53 62 73 83 92 - 110 - 125 -
40/45°C; external air dry
Absorbed power (5)(2) 16,0 19,1 21,5 25,0 28,3 - 32,9 - 37,6 - bulb temperature 7°C,
COP (5)(2) 3,31 3,24 3,39 3,32 3,25 - 3,34 - 3,32 - external air wet bulb
Seasonal efficiency class temperature 6°C, glycol
A+ A+ A++ * * - * - * -
(Regulation (UE) 811/2013) 0%; refrigerant R410A,
ERAH - UltraQuiet version fouling factor 0.0 m2 °C/W
Unit equipped with EC fans
Heating capacity (5) 53 62 73 83 92 - 110 - 125 -
Absorbed power (5)(2) 16,0 19,1 21,5 25,0 28,3 - 32,9 - 37,6 - 6. Data refer to free field
at 10 meters from the unit
COP (5)(2) 3,31 3,24 3,39 3,32 3,25 - 3,34 - 3,32 -
operating without pump at
Seasonal efficiency class
A+ A+ A++ * * - * - * - nominal conditions, with
(Regulation (UE) 811/2013)
fans at nominal conditions,
ERAC / ERAH Noise Pressure Levels coil side, Q=2 directional
Basic version (6) dB(A) 50.2 50.2 54.3 54.3 54.3 54.3 56.2 56.2 56.7 56.7 factor. At different
Quiet version (6) dB(A) 49.9 50.0 54.1 54.1 54.1 54.1 54.6 54.6 54.8 54.8 conditions and with
UltraQuiet version (6) dB(A) 44.9 45.1 46.7 46.7 46.7 46.7 49.2 49.2 49.9 49.9 different configurations,
noise values may vary
ERAC / ERAH Dimensions
Unit equipped with EC fans
Height (EC fans) mm 1600 1600 1600 1600 1600 1600 1910 1910 1910 1910
Depth mm 1214 1214 1219 1219 1219 1184 1272 1184 1272 1184 * Not applicable
Width mm 2026 2026 2821 2821 2821 2804 3088 3073 3088 3073

Construction options
• Quiet version with compressor soundproof casing. • Discharge shut-off valves.
• UltraQuiet version with fan speed reduction and • Power factor improvement compressors.
compressor soundproof casing. • Compressor soft start.
• Double power supply with automatic integrated • Cataphoresis treatment for the condensing coils.
management on the active line.
• Modification of the set point by external 0 V – 10 V signal.
• Acoustic-Composite fans with electronic commutated
motors (EC). Options
• Partial condensation heat recovery. The units can be supplied with the following external
• Total condensation heat recovery (ERAC**21A models accessories.
only). • Remote human interface PDG (up to 200 meters with
• Electronic expansion valve (**21A models only). shielded cable) for:
• Integrated hydronic system with one or two circulation - Entering of commands
pumps. - Display unit status of alarms

• Integrated hydronic system with one inverter driven • Metal filters for the condensing coils.
circulation pump. • Rubber or spring anti-vibration supports.
• Internal water tank. • Flanged type hydraulic connection.
• Internal water tank including a pump to manage the • Serial adaptor used to communicate with the main
primary circuit. external protocols: Modbus over IP, LONworks,
• Anti-freeze heaters option (standard for ERAH models): BacNET, Metasys, TCP/IP, SNMP, Trend, and KNX.
unit can operate down to -20 °C external temperature.
28 | Aquaflair chillers schneider-electric.com

Modulating air-cooled water chillers and heat pumps for outdoor installations

Uniflair ISAC/ISAH
Range
Cooling capacity: 60 ÷ 110 kW
Heating capacity: 65 ÷ 130 kW
Available versions
- Quiet
- UltraQuiet
Refrigerant R410A
Inverter-driven scroll compressors

Standard feature
• Self-supporting frame in galvanized steel with panels thermal protection switches with trip alarm signal on
varnished with epoxy powders (color RAL9022). compressors, magneto thermal protection for fan speed
• Access panel to the unit equipped with handles and fast control protection, safe-motor for pumps protection
screws. and remote control cut-off switches. Electrical board
equipped with an embedded contact for an external
• Inverter-driven hermetic Scroll compressor, equipped
230V isolating motorized valve.
with inverter speed control, oil by-pass valve and line,
integrated soft start, power factor correction condenser, • Phase sequence control and phase presence
integrated thermal protection, crankcase heaters and monitoring, minimum / maximum voltage protection and
inverter with oil heating function, anti-vibration supports, correct phase balancing.
and an inverter driver with IP54 protection grade • Anti-freeze heaters (ISAH only).
coupled with a specific compressor and positioned in a • Microprocessor control system including:
dedicated housing compartment. - Local human interface with external display and
• Compressor soundproof casing for noise reduction, safe accessible via an access hatch
operation, and protection (Quiet version). - Outlet chilled water / hot water (for ISAH) temperature
• Single refrigerant circuit conforming to EC Directives regulation by means of an exclusive algorithm
(PED 97/23/CE) in copper tubing including filter dryer, - Production of chilled water to -10 °C
liquid sight glass, thermostatic valve with external - External motorized isolating valve management
equalization, high and low pressure switches, and high - Anti-freeze protection
and low pressure transducers. - Compressor timing and protection
- Compressor rotation based on FIFO logic
• Environmentally friendly refrigerant R410A.
- Pump rotation (if present) on a timed basis for equal
• Electronic expansion valve.
operation and start-up of the stand-by pump (with
• Water side brazed plate heat exchanger in stainless alarm signal) in the event of a breakdown
steel insulated with closed cell expanded polyurethane - Integrated LAN card for connecting more than one unit
• Water flow differential pressure switch. to the local area network
• Air side exchange coil with aluminum fins and - Main electrical data acquisition and management
mechanically expanded copper tubes. - Integrated clock card.
• Refrigerant side cycle inversion with four-way inversion - Management of double set-point from remote control
valve (ISAH). - Free-contact for general alarm and 2 for addressable
alarms
• Sickle-blade axial fans, statically and dynamically
- Remote ON-OFF switch
balanced and made from composite materials for high
- Ability to interface with two separate BMSs with
efficiency and low acoustic impact with internal and
different protocols
external safety protection grilles.
- Direct connection to serial BMSs with Modbus
• Modulating condensation control with fan speed protocols (integrated RS485 serial card)
regulation. - Set-point variation based on external temperature or
• Electrical panel conforming to EC standards (2006/95/ signal (0-10V, 4-20mA or 0-20mA).
EC and EMC 2004/108/EC) protection grade IP54 • Heat pumps complying with EU Regulation 811/2013
with maximum internal temperature control, auxiliary (heat pumps up to 70kW) and 813/3013 (heat pumps
transformer, general auxiliary cut-off switch, magneto- from 70kW to 400kW).
schneider-electric.com Aquaflair chillers | 29

Technical Data 1. D ata refer to nominal


conditions: water
ISAC/ISAH 0621A 0921A 1221A
temperature 12/7 °C,
Power supply V/ph/Hz 400/3/50
external temperature
Compressors/circuits nr. x mod. 2/1 2/1 2/1 35 °C glycol 0%,
Evaporator nr. x mod. 1 x brazed plate refrigerant R410A, fouling
Fans nr. 2 3 3 factor 0.0 m2 °C/W
ISAC — Quiet version Unit equipped with EC
fans
Cooling capacity (1) kW 58 82 111
Absorbed power (1)(2) kW 18,9 26,3 36,7 2. Data refer to total absorbed
EER (1)(2) 3,06 3,11 3,02 power (compressors and
fans)
ESEER (3) 4,43 4,60 4,80
Unit equipped with EC fans
IPLV (4) 4,62 4,84 5,14
3. E
 uropean seasonal energy
ISAC — UltraQuiet version
efficiency ratio
Cooling capacity (1) kW 56 80 107
Unit equipped with EC fans
Absorbed power (1)(2) kW 19,1 26,5 37,9
4. n
 tegrated partial load
EER (1)(2) 2,93 3,01 2,82
value
ESEER (3) 5,51 4,66 4,89
Unit equipped with EC fans
IPLV (4) 4,71 4,93 5,27
5. Data refer to nominal
ISAH — Quiet version
conditions: Inlet/outlet
Heating capacity (5) kW 64 91 126 water temperature:
Absorbed power (5)(2) kW 20,2 28,0 37,8 40/45°C; external air dry
COP (5)(2) 3,16 3,23 3,32 bulb temperature 7°C,
Seasonal efficiency class external air wet bulb
A+ * * temperature 6°C, glycol
(Regulation (UE) 811/2013)
0%; refrigerant R410A,
ISAH — UltraQuiet version
fouling factor 0.0 m2 °C/W
Heating capacity (5) kW 64 91 126
Unit equipped with EC fans
Absorbed power (5)(2) kW 20,2 28,0 37,8
6. Data refer to free field
COP (5)(2) 3,16 3,23 3,32
at 10 meters from the unit
Seasonal efficiency class operating without pump at
A+ * *
(Regulation (UE) 811/2013) nominal conditions, with
ISAC / ISAH Noise Pressure Levels fans at nominal conditions,
Quiet version (6) dB(A) 53.9 56.1 57.0 coil side, Q=2 directional
UltraQuiet version (6) dB(A) 49.0 50.9 53.0 factor. At different
conditions and with
ISAC / ISAH Dimensions
different configurations,
Height (EC fans) mm 1600 1600 1910
noise values may vary
Depth mm 1214 1214 1276 Unit equipped with EC fans
Width mm 2009 2804 3067
* Not applicable

Construction options Options


• UltraQuite version with fan speed reduction and The units can be supplied with the following external
compressor soundproof casing. accessories.
• Double power supply with automatic integrated • Remote human interface PDG (up to 200 meters with
management on the active line. shielded cable) for:
• Acoustic-Composite fans with electronic commutated - Entering of commands
motors (EC). - Display unit status of alarms
• Partial condensation heat recovery. • Metal filters for the condensing coils.
• Integrated hydronic system with one or two circulation • Rubber or spring anti-vibration supports.
pumps. • Flanged type hydraulic connection.
• Integrated hydronic system with one inverterdriven • Serial adaptor used to communicate with the main
circulation pump. external protocols: Modbus over IP, LONworks,
• Discharge shut-off valves BacNET, Metasys, TCP/IP, SNMP, Trend, and KNX.
• Cataphoresis treatment for the condensing coils.
• Modification of the set point by external 0 V – 10 V
signal.
30 | Aquaflair chillers schneider-electric.com

Air-cooled water chillers and heat pumps for outdoor installations

Uniflair TRAC/TRAH
Range
Cooling capacity: 110 ÷ 400 kW
Heating capacity : 110 ÷ 370 kW
Available versions
- Basic
- UltraQuiet
Refrigerant R410A
Scroll Compressors

Standard features
• Self-supporting frame in galvanized steel with panels • Anti-condensation heaters for the electrical panel (standard
finished in epoxy powders (color RAL9022). only for TRAH).
• Access panel to the unit equipped with handles and fast • Phase sequence control and phase presence monitoring,
screws minimum / maximum voltage protection and correct phase
• Between two to four hermetic scroll compressors with balancing.
internal thermal protection, discharge gas thermal •M icroprocessor control system including:
protection, phase sequence control, safety internal valve, - 7inch. touch screen display interface
non-return discharge valve, oil level glass, anti-vibration - outlet chilled water / hot water (TRAH) temperature
supports and crankcase heaters (only TRAH). regulation by means of an exclusive PID algorithm
• Single (models **21A1) or double (models **42A1) - Production of chilled water down to -10°C
refrigerant circuit conforming to EC standards (PED 97/23/ - External motorized isolating valve management
CE) with copper tubing including: filter dryer, liquid sight - Anti-freeze protection
glass, expansion valve, discharge and suction taps on the - Compressor timing and protection
compressor, pressure switches, high and low pressure - Magneto-thermal protection switches with trip alarm
transducers. signal on compressors
- Compressor rotation based on FIFO logic
• Environmentally friendly refrigerant R410A.
- Pump rotation (if present) on a timed basis for equal
• Water side brazed plate heat exchanger in stainless steel
operation and start-up of the stand-by pump (with alarm
insulated with closed cell expanded polyurethane.
signal) in the event of a breakdown
• Water flow differential pressure switch. - Integrated LAN card for connecting more than one unit to
• Air side heat exchange coils: the local area network
- micro-channel condensing coils for TRAC models up to - Integrated USB on the touch screen display for data
260kW (1221A1 – 2842A1). downloading/firmware uploading
- coils with aluminum fins and mechanically-expanded - Integrated SNMP, Modbus TCP/IP communication
copper tubes for TRAH models (1221A1 – 4042A1) and protocol
TRAC models of 300kW and higher (3642A1 – 4142A1). - Main electrical data acquisition and management
• Electrical heaters for air-side heat exchanger protection in - Integrated clock card
heat pump mode (only TRAH). • Microprocessor control system, in addition, allows:
• Acousti-Composite fans: sickle-blade axial fans, statically - Management of double set-point from remote control
and dynamically balanced, made from composite materials - Free-contact for general alarm and 2 for addressable
for high efficiency and low acoustic impact, with safety alarms
protection grilles. - Remote ON-OFF switch
• Modulating condensation control with fan speed regulation. - Ability to interface with two separate BMSs with different
protocols
• Electrical panel conforming to EC Norms (Directive
- Compatibility with BMS by means the main protocols
2006/95/EC and EMC 2004/108/EC, IP54) with maximum/
- Full integration into a Data Center Infrastructure
minimum internal temperature control, auxiliary transformer,
Management (DCIM) System
general auxiliary cut-off switch, electric bars distribution
- Set-point variation based on external temperature or
for power supply, thermos-magnetic protection for
signal (0-10V, 4-20mA or 0-20mA).
compressors, fans and auxiliaries, safe-motor for pumps
protection and remote control cut-off switches. The
electrical board is equipped with embedded contact for an
externally fitted 230V isolating motorized valve.
schneider-electric.com Aquaflair chillers | 31

Technical Data 1. D
 ata refer to nominal
TRAC/TRAH 1221A1 1421A1 1742A1 2042A1 2342A1 2642A1 2842A1 3642A1 4042A1 4142A1 conditions: water
temperature 12/7 °C,
Power supply V/ph/Hz 400/3/50
external temperature
Circuits /Compressors nr. x mod. 2/1 2/1 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2 35 °C glycol 0%, refrigerant
Evaporator type nr. x mod. 1 x brazed plate R410A, fouling factor
Fans nr. 2 2 3 3 4 4 4 5 6 6 0.0 m2 °C/W
TRAC - Basic version Unit equipped with EC fans

Cooling capacity (1) kW 120 130 166 187 217 240 262 311 355 387 2. Data refer to total absorbed
Absorbed power (1)(2) kW 39,5 46,1 50,8 60,1 66,7 78,4 91,3 101,9 115,7 129,4 power (compressors and
EER (1)(2) 3,03 2,83 3,26 3,11 3,25 3,06 2,87 3,06 3,07 2,99 fans)
Unit equipped with EC fans
ESEER (3) 4,48 4,43 4,80 4,55 4,68 4,66 4,64 4,80 4,81 4,70
IPLV (4) 4,95 4,90 5,21 4,93 5,07 5,09 5,07 5,29 5,27 5,13 3. E
 uropean seasonal energy
TRAC - UltraQuiet version efficiency ratio
Unit equipped with EC fans
Cooling capacity (1) kW 113 122 158 177 207 226 243 293 334 359
Absorbed power (1)(2) kW 41,1 49,2 51,6 62,1 67,7 81,9 98,1 107,3 120,8 138,2 4. Integrated partial load
EER (1)(2) 2,75 2,48 3,06 2,84 3,05 2,76 2,48 2,73 2,76 2,60 value
Unit equipped with EC fans
ESEER (3) 4,47 4,38 4,81 4,55 4,68 4,64 4,60 4,78 4,79 4,66
IPLV (4) 4,97 4,87 5,24 4,97 5,09 5,12 5,07 5,32 5,28 5,13 5. Data refer to nominal
conditions: Inlet/outlet
TRAH - Basic version
water temperature:
Cooling capacity (1) kW 116 129 161 185 215 238 269 307 350 -
40/45°C; external air dry
Absorbed power (1)(2) kW 40,0 45,6 51,5 58,9 65,6 76,9 88,6 101,3 114,7 - bulb temperature 7°C,
EER (1)(2) 2,89 2,83 3,13 3,15 3,28 3,09 3,04 3,03 3,05 - external air wet bulb
Heating capacity (5) 120 137 171 191 223 248 281 330 372 - temperature 6°C, glycol
Absorbed power (5)(2) 38,5 43,7 50,3 57,6 66,8 77,2 86,5 99,7 112,4 - 0%; refrigerant R410A,
fouling factor 0.0 m2 °C/W
COP (5)(2) 3,12 3,14 3,39 3,32 3,34 3,22 3,25 3,31 3,31 -
Unit equipped with EC fans
TRAH - UltraQuiet version
Cooling capacity (1) kW 112 124 156 179 206 228 258 294 336 - 6. Data refer to free field at
10 meters from the unit
Absorbed power (1)(2) kW 40,7 47,0 51,6 59,9 66,0 78,9 90,6 104,3 117,3 -
operating without pump at
EER (1)(2) 2,74 2,64 3,01 2,99 3,12 2,90 2,84 2,82 2,87 -
nominal conditions, with
Heating capacity (5) 114 130 164 181 211 234 276 313 353 - fans at nominal conditions,
Absorbed power (5)(2) 36,7 41,8 47,3 54,6 62,7 73,1 84,3 94,8 106,1 - coil side, Q=2 directional
COP (5)(2) 3,11 3,11 3,46 3,32 3,37 3,20 3,28 3,31 3,33 - factor. At different
TRAC / TRAH Noise Pressure Levels conditions and with
different configurations,
Basic version (6) dB(A) 55,9 56,5 56,9 57,1 58,6 59,2 59,2 60,6 61,1 61,1
noise values may vary
UltraQuiet version (6) dB(A) 52,0 52,8 52,6 52,9 54,2 55,3 55,8 56,9 57,4 57,5
Unit equipped with EC fans
TRAC / TRAH Dimensions
Height (EC fans) mm 2236 2236 2236 2236 2236 2236 2236 2156 2156 2156
Depth mm 3162 3162 4612 4612 5562 5562 5562 5730 5730 5730
Width mm 1151 1151 1151 1151 1151 1151 1151 2204 2204 2204

Construction options • Adiabatic pre-cooling system (only for TRAC 3642A1-


• Double power supply with automatic integrated 4042A1-4142A1) composed by spray nozzles, pumping
management on the active line and integrated condenser station and polyurethanic protection panels.
for control board. • Air-side coils equipped with metal filters and protection
• Separate power supply 230/3/50Hz. grilles.
• Double power supply with automatic integrated • Later metal grilles for unit protection.
management on the active line and separate power supply • Electrolytic treatment for air-side coils to allow installation in
230/3/50Hz. corrosive atmosphere
• Fans with electronic commutated motors (EC). * Standard only for TRAH.
• Low ambient temperature option*: TRAC units can operate
down to -20°C outdoor temperature Options
• UltraQuiet version with soundproof casing, vibration The units can be supplied with the following external
absorbers for compressors and fan speed reduction. accessories:
• Electronic expansion valve (EEV) • Spring anti-vibration kit.
• Integrated hydronic system with one or two circulation • Victaulic type hydraulic connection.
pumps (1 + 1 standby), or one or two inverter-driven
• Flanged type hydraulic connection (for 3642A1, 4042A1
circulation pumps (1+1 standby) and pressure transducer.
and 4142A1 models).
• Internal water tank.
• RS485 serial adaptor used to communicate with external
• Partial and total (only TRAC) condensation heat recovery. BMS.
• Antifreeze protection on evaporator and pump/s group. • LON FTT-10 serial adaptor used to communicate with LON
• Suction shut-off valves on compressor. protocol.
• Power phase correction capacitors. • Additional TCP/IP serial adaptor used to communicate
• Soft starter for compressor to reduce the starting current. with external BMS managed with SNMP/Modbus TCP/IP
• Power meter for a continuous measurement of the unit protocol
power consumption and communication to the BMS. • BACnet MS/TP serial adaptor
• Refrigerant leak monitoring system that generates alarms in • Lifting kit
the event of leakages in the compressor housing.
32 | Aquaflair chillers schneider-electric.com

Air-cooled water chillers and heat pumps for outdoor installations

Uniflair TSAC
Range
Cooling capacity: 110 ÷ 330 kW
Available versions
- Quiet
- UltraQuiet
Refrigerant R410A
Inverter-driven scroll compressors

Standard features
• Self-supporting frame in galvanized steel with panels general auxiliary cut-off switch, electric bars distribution for
finished in epoxy powders (color RAL9022). power supply, thermos-magnetic protection for compressors,
• Access panel to the unit equipped with handles and fast fans and auxiliaries, safe-motor for pumps protection and
screws. remote control cut-off switches. The electrical board is
equipped with embedded contact for an externally fitted 230V
• Between two to four hermetic scroll compressors (one
isolating motorized valve.
inverter driven) with oil by-pass valve and line, integrated
soft start, power factor correction condenser, integrated •P
 hase sequence control and phase presence monitoring,
thermal protection and inverter with oil heating function, minimum / maximum voltage protection and correct phase
anti-vibration supports, and an inverter driver with IP54 balancing.
protection grade coupled with a specific compressor and •M icroprocessor control system including:
positioned in a dedicated housing compartment. - 7inch. touch screen display interface
• Compressors soundproofed protective housing for noise - outlet chilled water temperature regulation by means of an
impact reduction and safe operation and protection (Quiet exclusive PID algorithm
version). - Production of chilled water down to -10°C
- External motorized isolating valve management
• Single (model 1521A) or double (models **42A) refrigerant
- Anti-freeze protection
circuit conforming to EC standards (PED 97/23/ CE) with
- Compressor timing and protection
copper tubing including: filter dryer, liquid sight glass,
- Magneto-thermal protection switches with trip alarm signal on
electronic expansion valve, solenoid valve on the liquid line,
compressors
water-flow differential pressure switch and high and low
- Compressor rotation based on FIFO logic
pressure transducers.
- Pump rotation (if present) on a timed basis for equal operation
• Environmentally friendly refrigerant R410A.
and start-up of the stand-by pump (with alarm signal) in the
• Electronic expansion valve (EEV) entirely managed by the event of a breakdown
control system. - Integrated LAN card for connecting more than one unit to the
• Water side brazed plate heat exchanger in stainless steel local area network
insulated with closed cell expanded polyurethane. - Integrated USB on the touch screen display for data
• Water flow differential pressure switch. downloading/firmware uploading
• Air side condensing coils: - Integrated SNMP, Modbus TCP/IP communication protocol
- micro-channel condensing coils for TSAC models up to - Main electrical data acquisition and management
220kW (1521A – 2642A) - Integrated clock card.
- coils with aluminum fins and mechanically-expanded •M icroprocessor control system, in addition, allows:
copper tubes for TSAC models of 280kW and higher - Management of double set-point from remote control
(3642A – 4042A). - Free-contact for general alarm and 2 for addressable alarms
• Acousti-Composite fans with electronic commutated - Remote ON-OFF switch
motors (EC): sickle-blade axial fans, statically and - Ability to interface with two separate BMSs with different
dynamically balanced, made from composite materials protocols
for high efficiency and low acoustic impact, with safety - Compatibility with BMS by means the main protocols
protection grilles. - Full integration into a Data Center Infrastructure Management
(DCIM) System
• Modulating condensation control with fan speed regulation.
- Set-point variation based on external temperature or signal
• Electrical panel conforming to EC Norms (Directive (0-10V, 4-20mA or 0-20mA).
2006/95/EC and EMC 2004/108/EC, IP54) with maximum/
minimum internal temperature control, auxiliary transformer,
schneider-electric.com Aquaflair chillers | 33

Technical Data 1. D
 ata refer to nominal
conditions: water
TSAC Model 1521A 2042A 2642A 3642A 4042A
temperature 12/7 °C,
Power supply V/ph/Hz 400/3/50
external temperature
Compressors/circuits nr. x mod. 2/1 4/2 4/2 4/2 4/2 35 °C glycol 0%, refrigerant
Evaporator nr. x mod. 1 x brazed plate R410A, fouling factor 0.0
Fans nr. 2 3 4 5 6 m2 °C/W
Quiet version 2. Data refer to total absorbed
Cooling capacity (1) kW 127,8 152 206,3 290,6 324,2 power (compressors and
Absorbed power (1)(2) kW 38,1 45,6 61,5 86,7 96,8 fans)
EER (1)(2) 3,35 3,34 3,35 3,35 3,35 3. E
 uropean seasonal energy
ESEER (3) 5,27 4,82 4,91 4,98 4,86 efficiency ratio
IPLV (4) 5,78 5,33 5,50 5,58 5,42 4. I ntegrated partial load
UltraQuiet version value
Cooling capacity (1) kW 121,4 145,5 196,5 276,3 307,2 5. Data refer to free field at
Absorbed power (1)(2) kW 39,2 45,7 62 88,3 97,8 10 meters from the unit
EER (1)(2) 3,10 3,18 3,17 3,13 3,14 operating without pump at
ESEER (3) 5,24 4,82 4,90 4,96 4,85 nominal conditions, with
IPLV (4) 5,76 5,33 5,50 5,58 5,42 fans at nominal conditions,
coil side, Q=2 directional
Noise Pressure Levels
factor. At different
Quiet version (5) dB(A) 57,3 56,9 59,8 60,4 60,8 conditions and with
UltraQuiet version (5) dB(A) 53,5 53,9 54,8 55,8 56,2 different configurations,
Dimensions noise values may vary
Height (EC fans) mm 2236 2236 2236 2156 2156
Depth mm 4112 4612 5562 5730 5730
Width mm 1151 1151 1151 2204 2204

Construction options • Adiabatic pre-cooling system (3642A-4042A models)


• Double power supply with automatic integrated composed by spray nozzles, pumping station and
management on the active line and integrated polyurethanic protection panels.
condenser for control board. • Air-side coils equipped with metal filters and protection
• Separate power supply 230/3/50Hz. grilles.
• Double power supply with automatic integrated • Later metal grilles for unit protection.
management on the active line and separate power • Electrolytic treatment for air-side coils to allow installation
supply 230/3/50Hz. in corrosive atmosphere.
• Low ambient temperature option: TSAC units can
operate down to -20°C outdoor temperature. Options
• UltraQuiet version with soundproof casing, vibration The units can be supplied with the following external
absorbers for compressors and fan speed reduction. accessories:
• Integrated hydronic system with one or two circulation • Spring anti-vibration kit.
pumps (1 + 1 standby), or one or two inverter-driven • Victaulic type hydraulic connection.
circulation pumps (1+1 standby) and pressure • Flanged type hydraulic connection (for 3642A1, 4042A1
transducer. and 4142A1 models).
• Internal water tank (only TSAC3642A-4042A models). • RS485 serial adaptor used to communicate with external
• Partial condensation heat recovery. BMS.
• Antifreeze protection on evaporator and pump/s group. • LON FTT-10 serial adaptor used to communicate with
• Suction shut-off valves on compressor. LON protocol.
• Power phase correction capacitors. • Additional TCP/IP serial adaptor used to communicate
• Soft starter for compressor to reduce the starting with external BMS managed with SNMP/Modbus TCP/
current. IP protocol
• Power meter for a continuous measurement of the unit • BACnet MS/TP serial adaptor
power consumption and communication to the BMS. • Lifting kit
• Refrigerant leak monitoring system that generates
alarms in the event of leakages in the compressor
housing.
34 | Aquaflair chillers schneider-electric.com

Air-cooled water chillers for outdoor installations

Uniflair BREC
Range
Cooling capacity: 400 ÷ 700 kW
Available versions
- Basic
- Quiet
- UltraQuiet
Refrigerant R134a
Double screw compressors
Basic Offer

Standard features
• Self-supporting frame in galvanized steel with panels - Outlet chilled water temperature regulation by means
finished in epoxy powders (color RAL9022). of an exclusive PID algorithm
• Two semi-hermetic double screw compressors with - Electronic expansion valve managed by the control
internal thermal protection, discharge shut-off valve, system
oil heaters, and anti-vibration supports. - Refrigerant charge monitoring
- Monitoring of the absorbed current and checking of
• Operation possible with external temperature
possible malfunctions
up to 50 °C at full load.
- Advanced antifreeze protection on evaporator
• Two refrigerant circuits conforming to EC norms
- Production of chilled water to -10 °C
(PED 97/23/EC) in copper tubes including: filter dryer,
- External motorized isolating valve management
flow indicator, electronic expansion valve managed
- Anti-freeze protection
by the Uniflair control system, valve on the liquid line,
- Compressor timing and protection
pressure switches, transducers, and manometers of
- Pump rotation (if present) on a timed basis for equal
high and low pressure.
operation and start-up of the stand-by pump (with
• High efficiency shell and tube single passage
alarm signal) in the event of a breakdown
evaporator. The heat exchanger is insulated with
- Integrated LAN card to connect more than one unit to
UV resistant closed cell expanded neoprene.
the local area network
• Air side exchange coils with aluminum fins, internally
- Integrated USB connection for data downloading
grooved copper tubes and integrated subcooling circuit.
- Integrated RS4805 serial card data downloading
• Water flow differential pressure switch.
- Integrated clock card.
• Acousti-Composite fans: sickle-blade axial fans,
statically and dynamically balanced, made from • Microprocessor control system, in addition, allows:
composite materials for high efficiency and low - Limiting of absorbed current on preset value or
acoustic impact, with safety protection grilles. external signal
- Quick restart procedure to reach total cooling
• Modulating condensation control with fan
capacity within two or three minutes according to the
speed regulation.
configuration
•E
 lectrical panel conforming to EC Norms
- Management of double set-point from remote control
(Directive 2006/95/EC and EMC 2004/108/EC, IP54)
- Free-contact for general alarm and 2 for addressable
with general cut-off switch, electric bars distribution
alarms
for power supply, acquisition of absorbed current,
- Remote ON-OFF switch
maximum internal temperature control, magneto-thermal
- Ability to interface with two separate BMSs with
cut-off switch on the fans and auxiliaries, fuses for
different protocols
the compressors.
- Direct connection to serial BMSs with Modbus
• Sequence phase, minimum and maximum power protocols (integrated RS485 serial card)
supply monitoring. - Set-point variation based on external temperature or
• Microprocessor control system including: signal (0-10V, 4-20mA or 0-20mA).
- Human Machine Interface (HMI) with external display
and accessible via an access hatch
schneider-electric.com Aquaflair chillers | 35

Technical Data 1. D
 ata refer to nominal
conditions: water
BREC Model 1802A 2202A 2502A 2802A
temperature 12/7 °C,
Power supply V/ph/Hz 400/3/50
external temperature
Compressors/circuits nr. x mod. 2 x double screw 35 °C glycol 0%, refrigerant
Evaporator nr. x mod. 1 x shell and tube R134a, fouling factor
Fans nr. 6 8 8 8 0.0 m2 °C/W
Basic or Quiet version Unit equipped with EC fans

Cooling capacity (1) kW 440 503 531 651 2. Data refer to total absorbed
Absorbed power (1)(2) kW 142 158 170 211 power (compressors and
EER (1)(2) 3,10 3,19 3,13 3,09 fans)
Unit equipped with EC fans
ESEER (3) 4,22 4,29 4,25 4,30
IPLV (4) 4,66 4,74 4,70 4,73 3. E
 uropean seasonal energy
Basic or Quiet version with subcooling economizer efficiency ratio
Unit equipped with EC fans
Cooling capacity (1) kW 475 540 571 702
Absorbed power (1)(2) kW 155 176 186 246 4. I ntegrated partial load
EER (1)(2) 3,07 3,07 3,07 2,86 value
Unit equipped with EC fans
ESEER (3) 4,25 4,21 4,29 4,10
IPLV (4) 4,73 4,69 4,77 4,54 5. Data refer to free field at
10 meters from the unit
UltraQuiet version
operating without pump at
Cooling capacity (1) kW 407 475 498 613
nominal conditions, with
Absorbed power (1)(2) kW 148 161 175 220 fans at nominal conditions,
EER (1)(2) 2,75 2,96 2,85 2,79 coil side, Q=2 directional
ESEER (3) 4,13 4,27 4,18 4,19 factor. At different
IPLV (4) 4,64 4,75 4,71 4,70 conditions and with
different configurations,
UltraQuiet version with subcooling economizer
noise values may vary
Cooling capacity (1) kW 452 515 546 677
Unit equipped with EC fans
Absorbed power (1)(2) kW 166 186 197 261
6. Data refer to unit without
EER (1)(2) 2,73 2,77 2,78 2,60
chimneys
ESEER (3) 4,15 4,15 4,22 3,95
Unit equipped with EC fans
IPLV (4) 4,67 4,67 4,75 4,45
Noise Pressure Levels
Basic version (5) dB(A) 63,2 64,1 63,8 64,2
Quiet version (5) dB(A) 62,1 63,2 63,1 63,2
Quiet version with chimneys (5) dB(A) 54,4 55,0 54,4 55,1
UltraQuiet version (5) dB(A) 58,7 59,7 59,5 59,7
Dimensions
Height (EC fans) (6) mm 2531 2531 2531 2531
Depth mm 5005 6435 6435 6435
Width mm 2200 2200 2200 2200

Construction options • Condensing coils equipped with metal safety grilles


• Double power supply with automatic integrated and filters.
management on the active line and integrated • Coil manifolds protection panels.
condenser for control board. • Condensing coil cataphoresis or pre-painting treatment.*
• Fans with electronic commutated motors (EC).
• Power phase correction capacitors. * On request.
• Subcooling Economizer.
• Low external temperature: unit works down to -20 °C. Options
• Quite version with soundproof casing and vibration The units can be supplied with the following
absorbers for compressors. external accessories:
• Noise reduction chimneys for Quiet version*. • Remote user terminal UPDG1 (up to 200 meters
• UltraQuiet version with soundproof casing, vibration with shielded cable) for:
absorbers for compressors and fan speed reduction. - Entering of commands
• Production of glycol/water mixture at low temperatures - Display unit status of alarms.
(down to -10 °C). • Spring anti-vibration kit.
• Partial condensation heat recovery. • Flanged type hydraulic connection.
• Suction shut-off valves on compressor. • Additional RS485 serial adaptor used to communicate
• Integrated hydronic system with one or two circulation with external BMS.
pumps (1 + 1 standby). • LON FTT-10 serial adaptor used to communicate
• Integrated hydronic system with one or two (1+1 with external BMS managed with LON protocol.
standby) inverter-driven circulation pumps and pressure •T  CP/IP serial adaptor used to communicate with
transducers. external BMS managed with SNMP protocol.
• Antifreeze protection on evaporator and pump group. •L  ifting kit.
36 | Aquaflair chillers schneider-electric.com

Air-cooled water chillers for outdoor installations

Uniflair BREC
Range
Cooling capacity: 400 ÷ 1,300 kW
Available versions
- Basic
- Quiet
- UltraQuiet
Refrigerant R134a
Double screw compressors
Premium offer

Standard features
• Self-supporting frame in galvanized steel with panels - Electronic expansion valve managed by the control
finished in epoxy powders (color RAL9022). system
• Two semi-hermetic double screw compressors with - Refrigerant charge monitoring
internal thermal protection, discharge shut-off valve, - Monitoring of the absorbed current and checking of
oil heaters, and anti-vibration supports. possible malfunctions
- Advanced antifreeze protection on evaporator
• Two refrigerant circuits conforming to EC norms
- Production of chilled water to -10 °C
(PED 97/23/EC) in copper tubes including: filter dryer,
- External motorized isolating valve management
flow indicator, electronic expansion valve managed
- Anti-freeze protection
by the Uniflair control system, valve on the liquid line,
pressure switches, transducers, and manometers of - Compressor timing and protection
high and low pressure. - Pump rotation (if present) on a time basis for equal
• High efficiency shell and tube single passage operation and start-up of the stand-by pump (with
evaporator. The heat exchanger is insulated with alarm signal) in the event of a breakdown
UV resistant closed cell expanded neoprene. - Integrated LAN card to connect more than one unit to
• Air side exchange coils with aluminum fins, internally the local area network
grooved copper tubes and integrated subcooling circuit. - Integrated USB connection for data downloading
• Water flow differential pressure switch. - Integrated RS4805 serial card data downloading
• Acousti-Composite fans: sickle-blade axial fans, - Integrated clock card.
statically and dynamically balanced, made from • Microprocessor control system, in addition, allows:
composite materials for high efficiency and low - Limiting of absorbed current on preset value or
acoustic impact, with safety protection grilles. external signal
• Modulating condensation control with fan - Quick restart procedure to reach total cooling
speed regulation. capacity within two or three minutes according to the
•E
 lectrical panel conforming to EC Norms configuration
(Directive 2006/95/EC and EMC 2004/108/EC, IP54) - Management of double set-point from remote control
with general cut-off switch, electric bars distribution - Free-contact for general alarm and 2 for addressable
for power supply, acquisition of absorbed current, alarms
maximum internal temperature control, magneto-thermal - Remote ON-OFF switch
cut-off switch on the fans and auxiliaries, fuses for - Ability to interface with two separate BMSs with
the compressors. different protocols
- Direct connection to serial BMSs with Modbus
• Sequence phase, minimum and maximum power
protocols (integrated RS485 serial card)
supply monitoring.
- Set-point variation based on external temperature or
• Microprocessor control system including:
signal (0-10V, 4-20mA or 0-20mA).
- Human Machine Interface (HMI) with external display
and accessible via an access hatch
- Outlet chilled water temperature regulation by means
of an exclusive PID algorithm
schneider-electric.com Aquaflair chillers | 37

Technical Data 1. D
 ata refer to nominal
conditions: water
BREC Model 1812A 2212A 2512A 2812A 3212A 3612A 4212A 4812A 5612A
temperature 12/7 °C,
Power supply V/ph/Hz 400/3/50
external temperature
Compressors/circuits nr. x mod. 2 x double screw 35 °C glycol 0%, refrigerant
Evaporator nr. x mod. 1 x shell and tube R134a, fouling factor
Fans nr. 6 8 8 8 10 10 12 12 14 0.0 m2 °C/W
Basic or Quiet version Unit equipped with EC fans

Cooling capacity (1) kW 392 499 542 641 731 822 960 1054 1152 2. Data refer to total absorbed
Absorbed power (1)(2) kW 120 151 169 192 224 264 297 331 378,4 power (compressors and
EER (1)(2) 3,27 3,31 3,21 3,34 3,27 3,12 3,24 3,19 3,04 fans)
Unit equipped with EC fans
ESEER (3) 4,35 4,69 4,39 4,72 4,61 4,63 4,48 4,58 4,25
IPLV (4) 4,81 5,28 4,88 5,24 5,11 5,22 4,97 5,13 4,76 3. E
 uropean seasonal energy
Basic or Quiet version with subcooling economizer efficiency ratio
Unit equipped with EC fans
Cooling capacity (1) kW 419 533 581 687 782 887 1034 1141 1244
Absorbed power (1)(2) kW 134 168 184 218 253 294 336 370 422 4. I ntegrated partial load
EER (1)(2) 3,13 3,80 3,16 3,16 3,10 3,02 3,08 3,09 2,95 value
Unit equipped with EC fans
ESEER (3) 4,23 4,60 4,43 4,58 4,46 4,62 4,39 4,57 4,23
IPLV (4) 4,71 5,25 4,96 5,10 5,00 5,24 4,89 5,17 4,76 5. Data refer to free field at
UltraQuiet version 10 meters from the unit
operating without pump at
Cooling capacity (1) kW 365 471 506 599 680 772 899 994 1086
nominal conditions, with
Absorbed power (1)(2) kW 123 155 174 203 233 279 309 346 395
fans at nominal conditions,
EER (1)(2) 2,97 3,04 2,91 2,96 2,92 2,77 2,91 2,88 2,75 coil side, Q=2 directional
ESEER (3) 4,30 4,65 4,33 4,62 4,53 4,50 4,41 4,43 4,15 factor. At different
IPLV (4) 4,79 5,30 4,88 5,18 5,10 5,13 4,94 5,04 4,69 conditions and with
UltraQuiet version with subcooling economizer different configurations,
noise values may vary
Cooling capacity (1) kW 396 510 553 660 747 853 995 1106 1202
Unit equipped with EC fans
Absorbed power (1)(2) kW 143 179 195 236 269 317 355 392 445
EER (1)(2) 2,77 2,85 2,84 2,80 2,78 2,70 2,81 2,83 2,70 6. Data refer to unit without
chimneys
ESEER (3) 4,18 4,55 4,35 4,45 4,37 4,44 4,28 4,37 4,10
Unit equipped with EC fans
IPLV (4) 4,67 5,21 4,93 5,00 4,93 5,09 4,84 5,00 4,65
Noise Pressure Levels
Basic version (5) dB(A) 62,8 65,8 65,2 65,4 66,2 66,3 66,7 67,2 68,0
Quiet version (5) dB(A) 61,9 63,8 63,5 63,6 63,9 63,9 64,2 64,5 65,2
Quiet version with
dB(A) 58,4 60,9 60,5 60,6 61,2 61,3 61,7 62,1 62,8
chimneys (5)
UltraQuiet version (5) dB(A) 53,7 57,9 56,9 57,3 58,7 58,8 59,2 59,9 60,7
Dimensions
Height (EC fans) (6) mm 2531 2531 2531 2531 2531 2531 2531 2531 2531
Depth mm 4985 4985 6415 6415 9110 9110 10540 10540 11970
Width mm 2200 2200 2200 2200 2200 2200 2200 2200 2200

Construction options • Condensing coils equipped with metal safety grilles


• Double power supply with automatic integrated and filters.
management on the active line and integrated • Coil manifolds protection panels.
condenser for control board. • Condensing coil cataphoresis or pre-painting treatment.*
• Fans with electronic commutated motors (EC).
• Power phase correction capacitors. * On request.
• Subcooling Economizer.
• Operation possible with external temperature up to Options
50 °C at full load. The units can be supplied with the following
• Low external temperature: unit works down to -20 °C. external accessories:
• Quite version with soundproof casing and vibration • Remote user terminal UPGD1 (up to 200 meters
absorbers for compressors. with shielded cable) for:
• UltraQuiet version with soundproof casing, vibration - Entering of commands
absorbers for compressors and fan speed reduction. - Display unit status of alarms
• Noise reduction chimneys for Quiet version* • Spring anti-vibration kit.
• Production of glycol/water mixture at low temperatures • Flanged type hydraulic connection.
(down to -10 °C). • Additional RS485 serial adaptor used to communicate
• Partial condensation heat recovery. with external BMS.
• Suction shut-off valves on compressor. • LON FTT-10 serial adaptor used to communicate
• Integrated hydronic system with one or two circulation with external BMS managed with LON protocol.
pumps (1 + 1 standby). •T  CP/IP serial adaptor used to communicate with
• Power meter. external BMS managed with SNMP protocol.
• Integrated hydronic system with one or two (1+1 •L  ifting kit.
standby) inverter-driven circulation pumps and pressure
transducers.
• Antifreeze protection on evaporator and pump group.
38 | Aquaflair chillers schneider-electric.com

Air-cooled water chillers for outdoor installations

Uniflair BREC
Range
Cooling capacity: 300 ÷ 1,000 kW
Available versions
- Basic
- Quiet
- UltraQuiet
Refrigerant R1234ze
Double screw compressors – optimized solution
for R1234ze

Standard features
• Self-supporting frame in galvanized steel with panels • Microprocessor control system including:
finished in epoxy powders (color RAL9022). - Human Machine Interface (HMI) with external display and
• Two semi-hermetic double screw compressors with accessible via an access hatch
internal thermal protection located in the electrical - Outlet chilled water temperature regulation by means of an
board, discharge shut-off valve, oil heaters, and anti- exclusive PID algorithm
vibration supports. - Modulating condensation pressure control
- Electronic expansion valve managed by the control system
• Environmental friendly refrigerant R1234ze(E) featured
- Indirect and direct refrigerant charge monitoring
by low global warming potential GWP<1.
- Monitoring of the absorbed current and checking of
• Two refrigerant circuits conforming to EC norms (PED
possible malfunctions
97/23/EC) in copper tubes including: compressor
- Advanced antifreeze protection on evaporator
discharge shut-off valve, filter dryer, liquid sight glass,
- External motorized isolating valve management
electronic expansion valve managed by the control
- Anti-freeze protection
system, solenoid valve on the liquid line, high and
- Compressor timing and protection
low pressure transducers and high and low pressure
- Unloading to protect unit operation even with temperatures
gauges.
which exceed the maximum
• Operation possible with external temperature up to 50 - Pump rotation (if present) on a timed basis for equal
°C at full load and water temperature up to 25 °C. operation and start-up of the stand-by pump (with alarm
• High efficiency shell and tube single passage signal) in the event of a breakdown
evaporator. The heat exchanger is insulated with UV - Integrated LAN card to connect more than one unit to the
resistant closed cell expanded neoprene. local area network
• Air side exchange coils with aluminum fins and internally - Integrated USB connection for data downloading
grooved copper tubes and integrated subcooling circuit. - Integrated RS4805 serial card data downloading
• Water flow differential pressure switch. - Integrated clock card.

• Acousti-Composite fans: sickle-blade axial fans, • Microprocessor control system, in addition, allows:
statically and dynamically balanced, made from - Limiting of absorbed current on preset value or external
composite materials for high efficiency and low acoustic signal
impact, with safety protection grilles. - Quick restart procedure to reach total cooling capacity
• Modulating condensation control with fan speed within two or three minutes according to the configuration
regulation. - Management of double set-point from remote control
• Electrical panel conforming to EC Norms (Directive - Free-contact for general alarm and 2 for addressable
2014/35/UE and EMC 2014/30/UE, IP54) with general alarms
cut-off switch, electric bars distribution for power - Remote ON-OFF switch
supply, acquisition of absorbed current, maximum - Ability to interface with two separate BMSs with different
internal temperature control, magneto-thermal cut- protocols
off switch on the fans and auxiliaries, fuses for the
- Direct connection to serial BMSs with Modbus protocols
compressors and thermal protection for compressors.
(integrated RS485 serial card)
• Refrigerant leakage sensor located in the electrical
- Set-point variation based on external temperature or signal
board.
(0-10V, 4-20mA or 0-20mA).
• Sequence phase, minimum and maximum power supply
monitoring.
schneider-electric.com Aquaflair chillers | 39

1. D
 ata refer to nominal
Technical Data
conditions: water
BREC Model 1832A 2232A 2532A 2832A 3232A 3632A 4232A 4832A 5632A
temperature 12/7 °C,
Power supply V/ph/Hz 400/3/50 external temperature
Compressors/circuits nr. x mod. 2 x double screw 35 °C glycol 0%, refrigerant
Evaporator nr. x mod. 1 x shell and tube R134a, fouling factor
Fans nr. 6 8 8 8 10 10 12 12 14 0.0 m2 °C/W
Unit equipped with EC fans
Basic or Quiet version
Cooling capacity (1) kW 317 396 457 529 648 703 795 874 934 2. Data refer to total absorbed
Absorbed power (1)(2) kW 98 120 139 161 194 209 243 267 291 power (compressors and
fans)
EER (1)(2) 3,23 3,31 3,29 3,28 3,34 3,37 3,27 3,27 3,21
Unit equipped with EC fans
ESEER (3) 4,29 4,51 4,35 4,33 4,51 4,70 4,24 4,13 4,14
3. E
 uropean seasonal energy
IPLV (4) 4,61 4,84 4,66 4,62 4,83 5,09 4,53 4,38 4,43
efficiency ratio
UltraQuiet version
Unit equipped with EC fans
Cooling capacity (1) kW 299 379 432 493 608 656 745 813 871
4. I ntegrated partial load
Absorbed power (1)(2) kW 96 117 137 163 195 216 243 270 294
value
EER (1)(2) 3,11 3,23 3,15 3,04 3,11 3,04 3,06 3,01 2,96
Unit equipped with EC fans
ESEER (3) 4,28 4,50 4,33 4,30 4,47 4,65 4,22 4,10 4,11
IPLV (4) 4,60 4,84 4,65 4,61 4,81 5,04 4,53 4,37 4,43 5. Data refer to free field at
10 meters from the unit
Noise Pressure Levels
operating without pump at
Basic version (5) dB(A) 62,8 65,8 65,2 65,4 66,2 66,3 66,7 67,2 68,0
nominal conditions, with
Quiet version (5) dB(A) 61,9 63,8 63,5 63,6 63,9 63,9 64,2 64,5 65,2 fans at nominal conditions,
Quiet version with coil side, Q=2 directional
dB(A) 58,4 60,9 60,5 60,6 61,2 61,3 61,7 62,1 62,8
chimneys (5) factor. At different
UltraQuiet version (5) dB(A) 53,7 57,9 56,9 57,3 58,7 58,8 59,2 59,9 60,7 conditions and with
Dimensions different configurations,
noise values may vary
Height (EC fans) (6) mm 2531 2531 2531 2531 2531 2531 2531 2531 2531
Unit equipped with EC fans
Depth mm 5005 6435 6435 6435 9110 9110 10540 10540 11970
Width mm 2200 2200 2200 2200 2200 2200 2200 2200 2200 6. Data refer to unit without
chimneys
Unit equipped with EC fans

Construction options • Condensing coils equipped with metal safety grilles and
• Double power supply with automatic integrated filters.
management on the active line and integrated • Coil manifolds protection panels.
condenser for control board. • Condensing coil cataphoresis or pre-painting treatment.*
• Fans with electronic commutated motors (EC).
• Low external temperature: unit works down to -20 °C. * On request.
• Quiet version with soundproof casing fitted with
refrigerant leakage system and ventilation system and Options
vibration absorbers for compressors. Remote user terminal UPGD1 (up to 200 meters with
• UltraQuiet version with soundproof soundproof casing shielded cable) for:
fitted with refrigerant leakage system and ventilation • Remote user terminal UPGD1 (up to 200 meters
system, vibration absorbers for compressors and fan with shielded cable) for:
speed reduction. - Entering of commands
• Noise reduction chimneys for Quiet version*. - Display unit status of alarms
• Suction shut-off valves on compressor. • Spring anti-vibration kit.
• Power phase capacitors for compressors. • Flanged type hydraulic connection.
• Power meter. • RS485 serial adaptor used to communicate with
• Integrated hydronic system with one or two circulation external BMS.
pumps (1 + 1 standby). • LON FTT-10 serial adaptor used to communicate with
• Integrated hydronic system with one or two inverter- external BMS managed with LON protocol.
driven circulation pumps (1+1 standby) and pressure • TCP/IP serial adaptor used to communicate with
transducers. external BMS managed with SNMP protocol.
• Antifreeze protection on evaporator and pump group. • Lifting kit
40 | Aquaflair chillers schneider-electric.com

Modulating air-cooled water chillers for outdoor installations

Uniflair BCEC
Range
Cooling capacity: 300 ÷ 1,200 kW
Available versions
- Quiet
- UltraQuiet
Refrigerant R134a
Oil-free centrifugal compressors
with magnetic bearings

Standard features
•S
 elf-supporting frame in galvanized steel with panels • Modulating condensation control with continuous
finished in epoxy powders (color RAL9022). regulation of the fans speed.
• Between one to three oil-free centrifugal compressors • Electric panel conforming to EC standards (2006/95/EC
with magnetic bearings equipped with: and EMC 2004/108/EC Directives) with EMC integrated
- Internal thermal protection filter for protection of the harmonics, maximum internal
- Protection and control of the rotation axis position temperature control, absorbed current control, auxiliary
- Brushless synchronized DC motor transformer, general auxiliary cut-off switch, fuses on the
- Integrated control system compressors, and remote control cut-off switches.
- Speed control with inverter • Line reactance for each compressor to stabilize the
- Soft start start-up power supply.
- Phase sequence control • Phase sequence control and minimum/maximum power
- Pre-rotation valve supply and voltage.
- Temperature and pressure sensors
• Microprocessor control system including:
- Two centrifugal compression stages
- Continuous control of the cooling capacity by means
- Anti-vibration kit.
of an inverter and IGV (inlet guide vane)
•S
 oundproofing enclosures for compressor/s quiet - Local user terminal with external display
version. - Outlet chilled water temperature regulation by means
•C
 oil manifold protection panels. of an exclusive PID algorithm
• Single refrigerant circuit conforming to EC standards - Integrated LAN card for connecting more than one
(PED 97/23/CE) with copper tubing including: filter unit to the local area network
dryer, liquid sight glass, electronic expansion valve - Acquisition and management of main electrical data
controlled by a level sensor, discharge and suction - Direct decoding of all the compressor signals on the
taps on the compressor, pressure switches, high and human interface to simplify service operations
low pressure transducers, and gauges. - Clock card.
• The refrigerant circuit is covered by acoustic • Microprocessor control system, in addition, allows:
soundproofing insulation for noise reduction. - USB card for easy download of the operating parameters
•B
 ypass line for vacuum start-up with high-pressure ratio. - Management of double set point from remote control
- Fast restart procedure
•F
 looded evaporator featuring an integrated demister
- Free contact for general alarm and two for
to prevent the formation of droplets: the exchanger is
addressable alarms
insulated with closed cell expanded polyurethane.
- Remote ON-OFF switch
•A
 ir side exchange coils with aluminum fins, internally
- Integrated RS485 serial card for direct connection to
grooved copper tubes and integrated subcooling circuit.
external BMS
•D
 ifferential water pressure switch. - Direct interface with serial BMS with Modbus protocol
• Acoustic-Composite fans: sickle-blade axial fans, statically - Interface with main BMS protocols, such as BACnet,
and dynamically balanced, made from composite LonWorks, Trend, Metasys, SNMP/TCP-IP, and KNX.
materials for high efficiency and low acoustic impact,
with safety protection grilles.
schneider-electric.com Aquaflair chillers | 41

Technical Data 1. D
 ata refer to nominal
conditions: water
BCEC Model 0301A 0401A 0532A 0632A 0752A 0903A 1103A
temperature 12/7 °C,
Power supply V/ph/Hz 400/3/50
external temperature
Compressor/s nr. x mod. 1 x oil-free 2 x oil-free 3 x oil-free 35 °C glycol 0%, refrigerant
Cooling circuits nr. 1 R134a, fouling factor
Evaporator nr. x mod. 1 x flooded 0.0 m2 °C/W
Fans nr. 6 6 8 10 12 14 16 Unit equipped with EC fans

Quiet version 2. Data refer to total absorbed


Cooling capacity (1) kW 313 415 604 638 842 943 1252 power (compressors and
Absorbed power (1)(2) kW 96,8 121,4 183,3 189,3 243,2 281,5 362,8 fans)
Unit equipped with EC fans
EER (1)(2) 3,24 3,42 3,30 3,38 3,47 3,35 3,46
ESEER (3) 5,35 5,30 5,50 5,75 5,77 5,59 5,48 3. E
 uropean seasonal energy
efficiency ratio
IPLV (4) 6,02 6,28 6,08 6,37 6,73 6,24 6,50
Unit equipped with EC fans
UltraQuiet version
Cooling capacity (1) kW 291 382 541 589 773 862 1136 4. I ntegrated partial load
value
Absorbed power (1)(2) kW 88,5 117,3 167,5 174,2 234,0 258,4 351,7
Unit equipped with EC fans
EER (1)(2) 3,29 3,26 3,23 3,38 3,30 3,34 3,23
5. Data refer to free field at
ESEER (3) 5,44 5,28 5,38 5,49 5,69 5,67 5,69
10 meters from the unit
IPLV (4) 6,28 6,23 5,91 5,99 6,60 6,42 6,65
operating without pump at
Noise Pressure Levels nominal conditions, with
Quiet version (5) dB(A) 59,6 59,8 60,4 60,8 61,2 61,4 61,7 fans at nominal conditions,
Quiet version with chimneys (5) dB(A) 55,9 56,2 56,9 57,2 57,7 57,8 58,2 coil side, Q=2 directional
UltraQuiet version (5) dB(A) 51,8 52,9 53,5 53,5 54,4 54,2 55,1 factor. At different
conditions and with
Dimensions
different configurations,
Height (EC fans) (6) mm 2531 2531 2531 2531 2531 2531 2531
noise values may vary
Depth mm 5000 5000 6430 7860 9290 10720 12150 Unit equipped with EC fans
Width mm 2200 2200 2200 2200 2200 2200 2200
6. Data refer to unit without
chimneys
Unit equipped with EC fans
Construction options • Antifreeze protection on evaporator and pump/s group.
• Double power supply with automatic integrated • Condensing coils equipped with metal safety grilles
management on the active line and integrated and filters.
condenser for control. Quick restart included (full load
• Condensing coil cataphoresis or pre-painting treatment*.
capacity within 3 minutes).
• Separate power supply for control board and heaters
operation. Quick restart included (full load capacity * On request.
within 3 minutes).
• Double power supply with automatic integrated Options
management on the active line and additional separate The units can be supplied with the following
power supply for quick start procedure. external accessories:
• Power meter for a continuous measurement of the unit • Remote user terminal UPDG1 (up to 200 meters
power consumption and communication to the BMS. with shielded cable) for:
- Entering of commands
• Acoustic-Composite fans with electronic commutated
- Display unit status of alarms
motors (EC).
• Spring anti-vibration kit.
• Soundproof enclosures for compressors and fan speed
reduction (UltraQuiet version). • Flanged type hydraulic connection.
• Low external temperature option: unit can operate down • Additional RS485 serial adaptor used to communicate
to -20 °C external temperature. with external BMS.
• Modularity bypass valve designed to handle low load • LON FTT-10 serial adaptor used to communicate with
conditions. external BMS managed with LON protocol.
• Noise reduction chimneys for Quiet version*. • TCP/IP serial adaptor used to communicate with
external BMS managed with SNMP protocol.
• Integrated hydronic system with one or two
circulation pumps. • Lifting kit.
• Integrated hydronic system with one or two (1+1
standby) inverter-driven circulation pumps and pressure
transducers.
42 | Aquaflair chillers schneider-electric.com

Air cooled water chillers with axial fans and free-cooling system for outdoor installations

Uniflair ERAF
Range
Cooling capacity: 50 ÷ 120 kW
Available versions
- Basic
- Quiet
- UltraQuiet
Refrigerant R410A
Scroll compressors

Standard feature
• Exclusive free-cooling system completely managed by the • Electrical board an embeddedcontact for an externally
microprocessor control. fitted 230V isolating motorized valve.
• Self-supporting frame in galvanized steel with panels • Phase sequence control and phase presence monitoring,
varnished with epoxy powders (color RAL9022). minimum / maximum voltage protection and correct phase
• Access panel to the unit equipped with handles and fast balancing.
screws. • Anti-freeze heaters
• Two hermetic scroll compressors with internal thermal • Anti-condensation heaters for the electrical panel.
protection, discharge gas thermal protection (ERAH), • Microprocessor control system including:
phase sequence control, safety internal valve, non-return -L  ocal human interface with external display and
discharge valve, oil level glass, anti-vibration supports. accessible via an access hatch
• Compressor casing for noise reduction, safe operation, and -O  utlet chilled water temperature regulation by means of
protection an exclusive algorithm
• Single or double ( **22A model) refrigerant circuit* -F  ree-cooling and intelligent free-cooling management
conforming to EC Directives (PED 97/23/CE) in copper -M  ixed free-cooling operation
tubing including filter dryer, liquid sight glass, thermostatic -E  xternal motorized isolating valve management
valve with external equalization, high and low pressure -A  nti-freeze protection
switches, and high and low pressure transducers. -C  ompressor timing and protection
-C  ompressor rotation based on FIFO logic
• Environmentally friendly refrigerant R410A.
-P  ump rotation (if present) on a timed basis for equal
• Water side brazed plate heat exchanger in stainless steel
operation and start-up of the stand-by pump (with alarm
insulated with closed cell expanded polyurethane
signal) in the event of a breakdown
• Water flow differential pressure switch. - Integrated LAN card for connecting more than one unit to
• Air side exchange coil with aluminum fins and mechanically the local area network
expanded copper tubes. -M  ain electrical data acquisition and management
• Free-cooling air coils with aluminium fins and mechanically- - Integrated clock card.
expanded copper tubes. The coils are equipped with -M  anagement of double set-point from remote control
isolating solenoid valve to maximize the mixed free-cooling -F  ree-contact for general alarm and 2 for addressable
operation. alarms
• Sickle-blade axial fans, statically and dynamically balanced -R  emote ON-OFF switch
and made from composite materials for high efficiency -A  bility to interface with two separate BMSs with different
and low acoustic impact with internal and external safety protocols
protection grilles. -D  irect connection to serial BMSs with Modbus protocols
(integrated RS485 serial card)
• Modulating condensation control with fan speed regulation.
-S  et-point variation based on external temperature or
• Electrical panel conforming to EC standards (2006/95/ signal (0-10V, 4-20mA or 0-20mA).
EC and EMC 2004/108/EC) protection grade IP54 with
maximum and minimum internal temperature control,
auxiliary transformer, general auxiliary cut-off switch, *ERAF models with **22A suffix are available with two
magneto-thermal protection switches with trip alarm signal compressors on two circuits.
on compressors, magneto thermal protection for fan speed
control protection, safe-motor for pumps protection and
remote control cut-off switches.
schneider-electric.com Aquaflair chillers | 43

Technical Data 1. D
 ata refer to nominal
conditions: water
ERAF Model 0521A 0621A 0721A 0821A 0921A 0922A 1021A 1022A 1221A 1222A
temperature 15/10 °C,
Power supply V/ph/Hz 400/3/50
external temperature
Compressors/circuits nr. x mod. 2/1 2/1 2/1 2/1 2/1 2/2 2/1 2/2 2/1 2/2 35 °C, glycol 20%,
Evaporator nr. x mod. 1 x brazed plate refrigerant R410A, fouling
Fans nr. 2 2 2 3 3 3 3 3 3 3 factor 0.0 m2 °C/W
ERAF — Basic or Quiet version Unit equipped with EC fans

Cooling capacity (1) kW 49 58 68 77 85 86 102 101 114 115 2. Data refer to total
Absorbed power (1)(2) kW 15,7 19,6 21,4 24,6 28,7 28,8 32,3 32,3 37,9 38,0 absorbed power
EER (1)(2) 3,12 2,95 3,17 3,13 2,96 2,98 3,15 3,12 3,00 3,02 (compressors and fans)
Unit equipped with EC fans
Free-cooling capacity (3) kW 36 38 46 53 55 55 66 66 66 66
ERAF — UltraQuiet version 3. D
 ata refer to nominal
Cooling capacity (1) kW 47 56 66 75 82 83 97 97 109 110 conditions: inlet water
temperature 15 °C, external
Absorbed power (1)(2) kW 15,7 20,0 22,0 24,8 29,4 29,4 33,3 33,3 39,8 39,9
temperature 5 °C, glycol
EER (1)(2) 2,99 2,80 3,00 3,02 2,78 2,82 2,91 2,91 2,73 2,75 20%, refrigerant R134a,
Free-cooling capacity (3) kW 36 38 46 53 54 54 66 66 66 66 fouling factor 0.0 m2 °C/W
Noise pressure levels Unit equipped with EC fans
Basic version (5) dB(A) 50.2 50.2 54.3 54.3 54.3 54.3 56.2 56.2 56.7 56.7 4. D
 ata refer to total input
Quiet version (5) dB(A) 49.9 50.0 54.1 54.1 54.1 54.1 54.6 54.6 54.8 54.8 power (compressors, fans
UltraQuiet version (5) dB(A) 44.9 45.1 46.7 46.7 46.7 46.7 49.2 49.2 49.9 49.9 and free-cooling pump)
Dimensions 5. Data refer to free field at
Height (EC fans) mm 1600 1600 1600 1600 1600 1600 1910 1910 1910 1910 10 meters from the unit
Depth mm 1214 1214 1219 1219 1219 1184 1272 1184 1272 1184 operating without pump
Width mm 2026 2026 2821 2821 2821 2804 3088 3073 3088 3073 at minal conditions, with
fans at nominal conditions,
coil side, Q=2 directional
factor. At different
conditions and with
different configurations,
noise values may vary
Unit equipped with EC fans

Construction options • Power factor improvement compressors.


• Quiet version with compressor soundproof casing. • Compressor soft start.
• UltraQuiet version with fan speed reduction and • Cataphoresis treatment for the condensing coils.
compressor soundproof casing. • Modification of the set point by external 0 V – 10 V signal
• Double power supply with automatic integrated
management on the active line. Options
• Acoustic-Composite fans with electronic commutated The units can be supplied with the following external
motors (EC). accessories.
• Partial condensation heat recovery. • Remote human interface PDG (up to 200 meters with
• Electronic expansion valve (**21A models only) shielded cable) for:
• Intelligent free-cooling. -E
 ntering of commands
-D
 isplay unit status of alarms
• Integrated hydronic system with one or two circulation
pumps. • Metal filters for the condensing coils.
• Integrated hydronic system with one inverter driven • Rubber or spring anti-vibration supports.
circulation pump. • Flanged type hydraulic connection.
• Internal water tank. • Serial adaptor used to communicate with the main external
• Internal water tank including a pump to manage the protocols: Modbus over IP, LONworks, BacNET, Metasys,
primary circuit. TCP/IP, SNMP, Trend, and KNX.
• Discharge shut-off valves
44 | Aquaflair chillers schneider-electric.com

Modulating air-cooled water chillers with free-cooling system for outdoor installations

Uniflair ISAF
Range
Cooling capacity: 60 ÷ 120 kW
Available versions
- Quiet
- UltraQuiet
Refrigerant R410A
Inverter-driven scroll compressors

Standard features
•E
 xclusive free-cooling system completely managed by maximum and minimum internal temperature control,
the microprocessor control. auxiliary transformer, general auxiliary cut-off switch,
•S
 elf-supporting frame in galvanized steel with panels magneto-thermal protection switches with trip alarm
varnished with epoxy powders (color RAL9022). signal on compressors, magneto thermal protection
for fan speed control protection, safe-motor for
•A
 ccess panel to the unit equipped with handles and fast
pumps protection and remote control cut-off switches.
screws.
Electrical board equipped an embedded contact for an
• Inverter-driven hermetic Scroll compressor, equipped
externally fitted 230V isolating motorized valve.
with inverter speed control, oil by-pass valve and line,
• Phase sequence control and phase presence
integrated soft start, power factor correction condenser,
monitoring, minimum / maximum voltage protection and
integrated thermal protection, crankcase heaters and
correct phase balancing.
inverter with oil heating function, anti-vibration supports,
and an inverter driver with IP54 protection grade • Anti-freeze heaters
coupled with a specific compressor and positioned in a • Anti-condensation heaters for the electrical panel.
dedicated housing compartment. • Microprocessor control system including:
•C
 ompressor soundproof casing for noise reduction, safe - Local human interface with external display and
operation, and protection accessible via an access hatch
•S
 ingle refrigerant circuit conforming to EC Directives - Outlet chilled water temperature regulation by means
(PED 97/23/CE) in copper tubing including filter dryer, of an exclusive algorithm
liquid sight glass, thermostatic valve with external - Free-cooling and intelligent free-cooling management
equalization, high and low pressure switches, and high - Mixed free-cooling operation
and low pressure transducers. - External motorized isolating valve management
- Anti-freeze protection
•E
 nvironmentally friendly refrigerant R410A.
- Compressor timing and protection
•E
 lectronic expansion valve
- Compressor rotation based on FIFO logic
•W
 ater side brazed plate heat exchanger in stainless - Pump rotation (if present) on a timed basis for equal
steel insulated with closed cell expanded polyurethane operation and start-up of the stand-by pump (with
•W
 ater flow differential pressure switch. alarm signal) in the event of a breakdown
•A
 ir side exchange coil with aluminum fins and - Integrated LAN card for connecting more than one unit
mechanically expanded copper tubes. to the local area network
•F
 ree-cooling air coils with aluminium fins and - Main electrical data acquisition and management
mechanically-expanded copper tubes. The coils are - Integrated clock card.
equipped with isolating solenoid valve to maximize the - Management of double set-point from remote control
mixed free-cooling operation. - Free-contact for general alarm and 2 for addressable
alarms
•S
 ickle-blade axial fans, statically and dynamically
- Remote ON-OFF switch
balanced and made from composite materials for high
- Ability to interface with two separate BMSs with
efficiency and low acoustic impact with internal and
different protocols
external safety protection grilles.
- Direct connection to serial BMSs with Modbus
•M
 odulating condensation control with fan speed protocols (integrated RS485 serial card)
regulation. - Set-point variation based on external temperature or
•E
 lectrical panel conforming to EC standards (2006/95/ signal (0-10V, 4-20mA or 0-20mA).
EC and EMC 2004/108/EC) protection grade IP54 with
schneider-electric.com Aquaflair chillers | 45

Technical Data 1. D
 ata refer to nominal
conditions: water
ISAF Model 0621A 0921A 1221A
temperature 15/10 °C,
Power supply V/ph/Hz 400/3/50
external temperature
Compressors/circuits nr. x mod. 2/1 2/1 2/1 35 °C, glycol 20%,
Evaporator nr. x mod. 1 x brazed plate refrigerant R410A, fouling
Fans nr. 2 3 3 factor 0.0 m2 °C/W
ISAF — Quiet version Unit equipped with EC fans

Cooling capacity (1) kW 61 88 120 2. Data refer to total absorbed


Absorbed power (1)(2) kW 20,1 28,0 38,9 power (compressors and
EER (1)(2) 3,08 3,14 3,08 fans)
Unit equipped with EC fans
Free-cooling capacity (3) kW 38 53 71
ISAF — UltraQuiet version 3. D
 ata refer to nominal
Cooling capacity (1) kW 59 84 115 conditions: inlet water
temperature 15 °C, external
Absorbed power (1)(2) kW 20,7 28,6 40,0
temperature 5 °C, glycol
EER (1)(2) 2,84 2,93 2,88 20%, refrigerant R134a,
Free-cooling capacity (3) kW 37 53 71 fouling factor 0.0 m2 °C/W
ISAF Noise Pressure Levels Unit equipped with EC fans
Quiet version (5) dB(A) 53.9 56.1 57.0 4. D
 ata refer to total input
UltraQuiet version (5) dB(A) 49.0 50.9 53.0 power (compressors, fans
ISAF Dimensions and free-cooling pump)
Height (EC fans) mm 1600 1600 1910 5. Data refer to free field at
Depth mm 1214 1214 1276 10 meters from the unit
Width mm 2009 2804 3067 operating without pump
at minal conditions, with
fans at nominal conditions,
coil side, Q=2 directional
factor. At different
conditions and with
different configurations,
noise values may vary
Unit equipped with EC fans

Construction options Options


• UltraQuiet version with fan speed reduction and The units can be supplied with the following external
compressor soundproof casing. accessories.
• Double power supply with automatic integrated • Remote human interface PDG (up to 200 meters with
management on the active line. shielded cable) for:
• Acoustic-Composite fans with electronic commutated - Entering of commands
motors (EC). - Display unit status of alarms
• Partial condensation heat recovery. • Metal filters for the condensing coils.
• Intelligent free-cooling. • Rubber or spring anti-vibration supports.
• Integrated hydronic system with one or two circulation • Flanged type hydraulic connection.
pumps. • Serial adaptor used to communicate with the main
• Integrated hydronic system with one inverterdriven external protocols: Modbus over IP, LONworks,
circulation pump. BacNET, Metasys, TCP/IP, SNMP, Trend, and KNX.
• Discharge shut-off valves.
• Cataphoresis treatment for the condensing coils.
• Modification of the set point by external 0 V – 10 V
signal.
46 | Aquaflair chillers schneider-electric.com

Air-cooled water chillers with free-cooling system for outdoor installations

Uniflair TRAF
Range
Cooling capacity: 120 ÷ 420 kW
Available versions
- Basic
- UltraQuiet
Refrigerant R410A
Scroll compressors

Standard features
•E
 xclusive Uniflair free-cooling system completely managed compressors, fans and auxiliaries, safe-motor for pumps
by the microprocessor control. protection and remote control cut-off switches. The electrical
•S
 elf-supporting frame in galvanized steel with panels board is equipped with embedded contact for an externally
finished in epoxy powders (color RAL9022). fitted 230V isolating motorized valve.
•A
 ccess panel to the unit equipped with handles and fast • Anti-condensation heaters for the electrical panel.
screws. • Phase sequence control and phase presence monitoring,
•B
 etween two to four hermetic scroll compressors with minimum / maximum voltage protection and correct phase
internal thermal protection, discharge gas thermal balancing
protection, phase sequence control, safety internal valve, • Microprocessor control system including:
non-return discharge valve, oil level glass, anti-vibration - 7inch. touch screen display interface
supports and crankcase heaters. - outlet chilled water / hot water (TRAH) temperature regulation
•S
 ingle (models **21A1) or double (models **42A1) by means of an exclusive PID algorithm
refrigerant circuit conforming to EC standards (PED 97/23/ - Free-cooling and intelligent free-cooling management
CE) with copper tubing including: filter dryer, liquid sight - Mixed free-cooling operation
glass, expansion valve, discharge and suction taps on the - External motorized isolating valve management
compressor, pressure switches, high and low pressure - Anti-freeze protection
transducers. - Compressor timing and protection
- Magneto-thermal protection switches with trip alarm signal on
•E
 nvironmentally friendly refrigerant R410A.
compressors
•W
 ater side brazed plate heat exchanger in stainless steel
- Compressor rotation based on FIFO logic
insulated with closed cell expanded polyurethane.
- Pump rotation (if present) on a timed basis for equal operation
•W
 ater flow differential pressure switch. and start-up of the stand-by pump (with alarm signal) in the
•A ir side condensing coils: event of a breakdown
- micro-channel condensing coils for TRAF models up to - Integrated LAN card for connecting more than one unit to the
260kW (1221A1 – 2842A1). local area network
- coils with aluminum fins and mechanically-expanded - Integrated USB on the touch screen display for data
copper tubes for TRAF models of 300kW and higher downloading/firmware uploading
(3642A1 – 4142A1). - Integrated SNMP, Modbus TCP/IP communication protocol
•F
 ree-cooling air coils with aluminum fins and mechanically- - Main electrical data acquisition and management
expanded copper tubes. The coils are equipped with - Integrated clock card
isolating solenoid valve to maximize the mixed free-cooling •M
 icroprocessor control system, in addition, allows:
operation. - Management of double set-point from remote control
•F
 ree-cooling pump driven by microprocessor control. - Free-contact for general alarm and 2 for addressable alarms
•A
 cousti-Composite fans: sickle-blade axial fans, statically - Remote ON-OFF switch
and dynamically balanced, made from composite materials - Ability to interface with two separate BMSs with different
for high efficiency and low acoustic impact, with safety protocols
protection grilles. - Compatibility with BMS by means the main protocols
•M
 odulating condensation control with fan speed regulation. - Full integration into a Data Center Infrastructure Management
(DCIM) System
•E
 lectrical panel conforming to EC Norms (Directive
- Set-point variation based on external temperature or signal
2006/95/EC and EMC 2004/108/EC, IP54) with maximum/
(0-10V, 4-20mA or 0-20mA).
minimum internal temperature control, auxiliary transformer,
general auxiliary cut-off switch, electric bars distribution
for power supply, thermos-magnetic protection for
schneider-electric.com Aquaflair chillers | 47

Technical Data 1. D
 ata refer to nominal
conditions: water
TRAF 1221A1 1421A1 1742A1 2042A1 2342A1 2642A1 2842A1 3642A1 4042A1 4142A1
temperature 15/10 °C,
Power supply V/ph/Hz 400/3/50 external temperature
Compressors/circuits nr. x mod. 2/1 2/1 4/2 4/2 4/2 4/2 4/2 4/2 4/2 4/2 35 °C, glycol 20%,
Evaporator nr. x mod. 1 x brazed plate refrigerant R410A, fouling
Fans nr. 2 2 3 3 4 4 4 5 6 6 factor 0.0 m2 °C/W
TRAF - Basic version Unit equipped with EC fans

Cooling capacity (1) kW 127,7 138,9 176,2 198,3 229,8 253,2 275,3 329,2 373,6 406,4 2. Data refer to total absorbed
Absorbed power (1)(2) kW 41,3 48,2 52,8 62,7 70,1 82,6 96,5 107,3 122,6 137,4 power (compressors and
fans)
EER (1)(2) 3,09 2,88 3,34 3,16 3,28 3,07 2,85 3,07 3,05 2,96
Unit equipped with EC fans
EER in free-cooling
°C 9,29 9,20 10,00 9,37 12,51 12,22 9,86 10,33 10,77 9,74
mode (3)(4) 3. D
 ata refer to nominal
TRAF - UltraQuiet version conditions: inlet water
temperature 15 °C, external
Cooling capacity (1) kW 119,4 131,1 166,5 186,3 216,8 235,5 259,4 307,8 350,7 382,9
temperature 5 °C, glycol
Absorbed power (1)(2) kW 43,4 50,8 54,1 65,2 72,0 87,4 102,1 113,9 128,5 144,8
20%, refrigerant R410A,
EER (1)(2) 2,75 2,58 3,08 2,86 3,01 2,70 2,54 2,70 2,73 2,64 fouling factor 0.0 m2 °C/W
EER in free-cooling Unit equipped with EC fans
°C 9,42 9,33 10,11 9,27 13,03 11,04 9,53 10,27 10,56 9,38
mode (3)(4)
4. D
 ata refer to total input
TRAF Noise Pressure Levels power (compressors, fans
Basic version (5) dB(A) 55,9 56,5 56,9 57,1 58,6 59,2 59,2 60,6 61,1 61,1 and free-cooling pump)
UltraQuiet version (5) dB(A) 52,0 52,8 52,6 52,9 54,2 55,3 55,8 56,9 57,4 57,5
5. Data refer to free field at
TRAF Dimensions 10 meters from the unit
Height (EC fans) mm 2236 2236 2236 2236 2236 2236 2236 2156 2156 2156 operating without pump
Depth mm 3162 3162 4612 4612 5562 5562 5562 5730 5730 5730 at minal conditions, with
Width mm 1151 1151 1151 1151 1151 1151 1151 2204 2204 2204 fans at nominal conditions,
coil side, Q=2 directional
factor. At different
conditions and with
different configurations,
noise values may vary
Construction options • Refrigerant leak monitoring system that generates alarms in Unit equipped with EC fans
• Double power supply with automatic integrated the event of leakages in the compressor housing.
management on the active line and integrated condenser • Adiabatic pre-cooling system (3642A1-4042A1-4142A1
for control board. models) composed by spray nozzles, pumping station and
• Separate power supply 230/3/50Hz. polyurethanic protection panels.
• Double power supply with automatic integrated • Air-side coils equipped with metal filters and protection
management on the active line and separate power supply grilles.
230/3/50Hz. • Later metal grilles for unit protection.
• Fans with electronic commutated motors (EC). • Electrolytic treatment for air-side coils to allow installation in
• Intelligent free-cooling option (1+1 and 2+1) to leverage on corrosive atmosphere.
the stand-by unit to increase the free-cooling capacity.
• Glycol free arrangement to avoid glycol inside the primary * Standard feature for TRAH models.
circuit.
• UltraQuiet version with soundproof casing, vibration Options
absorbers for compressors and fan speed reduction.
The units can be supplied with the following external
• Electronic expansion valve (EEV) accessories:
• Integrated hydronic system with one or two circulation • Spring anti-vibration kit.
pumps (1 + 1 standby).
• Victaulic type hydraulic connection.
• Integrated hydronic system with one or two inverter-driven
• Flanged type hydraulic connection (for 3642A1, 4042A1
circulation pumps (1+1 standby) and pressure transducers.
and 4142A1 models).
• Internal water tank.
• RS485 serial adaptor used to communicate with external
• Partial condensation heat recovery. BMS.
• Antifreeze protection on evaporator and pump/s group. • LON FTT-10 serial adaptor used to communicate with LON
• Suction shut-off valves on compressor. protocol.
• Power phase correction capacitors. • Additional TCP/IP serial adaptor used to communicate
• Soft starter for compressor to reduce the starting current. with external BMS managed with SNMP/Modbus TCP/IP
• Power meter for a continuous measurement of the unit protocol.
power consumption and communication to the BMS. • BACnet MS/TP serial adaptor.
• Lifting kit.
48 | Aquaflair chillers schneider-electric.com

Air-cooled water chillers and heat pumps for outdoor installations

Uniflair TSAF
Range
Cooling capacity: 130 ÷ 350 kW
Available versions
- Quiet
- UltraQuiet
Refrigerant R410A
Inverter-driven scroll compressors

Standard features
• Exclusive Uniflair free-cooling system completely managed by • Electrical panel conforming to EC Norms (Directive 2006/95/EC
the microprocessor control. and EMC 2004/108/EC, IP54) with maximum/minimum internal
• Self-supporting frame in galvanized steel with panels finished temperature control, auxiliary transformer, general auxiliary cut-off
in epoxy powders (color RAL9022). switch, electric bars distribution for power supply, thermos-
magnetic protection for compressors, fans and auxiliaries, safe-
• Access panel to the unit equipped with handles and fast
motor for pumps protection and remote control cut-off switches.
screws.
The electrical board is equipped with embedded contact for an
• Between two to four hermetic scroll compressors (one
externally fitted 230V isolating motorized valve.
inverter driven) with oil by-pass valve and line, integrated soft
• Anti-condensation heaters for the electrical panel.
start, power factor correction condenser, integrated thermal
protection and inverter with oil heating function, anti-vibration • Phase sequence control and phase presence monitoring, minimum
supports, crankcase heaters and an inverter driver with IP54 / maximum voltage protection and correct phase balancing.
protection grade coupled with a specific compressor and • Microprocessor control system including:
positioned in a dedicated housing compartment. - 7inch. touch screen display interface
• Compressors soundproofed protective housing for noise - outlet chilled water temperature regulation by means of an
impact reduction and safe operation and protection (Quiet exclusive PID algorithm
version). - Free-cooling and intelligent free-cooling management
- Mixed free-cooling operation
• Single (model 1521A) or double (models **42A) refrigerant
- Production of chilled water down to -10°C
circuit conforming to EC standards (PED 97/23/ CE) with
- External motorized isolating valve management
copper tubing including: filter dryer, liquid sight glass,
- Anti-freeze protection
electronic expansion valve, solenoid valve on the liquid line,
- Compressor timing and protection
water-flow differential pressure switch and high and low
- Magneto-thermal protection switches with trip alarm signal on
pressure transducers.
compressors
• Possibility of operation with external temperatures down to
- Compressor rotation based on FIFO logic
-25 °C in free-cooling mode.
- Pump rotation (if present) on a timed basis for equal operation and
• Environmentally friendly refrigerant R410A. start-up of the stand-by pump (with alarm signal) in the event of a
• Electronic expansion valve (EEV) entirely managed by the breakdown
control system. - Integrated LAN card for connecting more than one unit to the local
• Water side brazed plate heat exchanger in stainless steel area network
insulated with closed cell expanded polyurethane. - Integrated USB on the touch screen display for data downloading/
• Water flow differential pressure switch. firmware uploading
- Integrated SNMP, Modbus TCP/IP communication protocol
• Air side condensing coils:
- Main electrical data acquisition and management
- micro-channel condensing coils for TSAF models up to
- Integrated clock card
220kW (1521A – 2642A)
- coils with aluminum fins and mechanically-expanded copper • Microprocessor control system, in addition, allows:
tubes for TSAF models of 280kW and higher (3642A – - Management of double set-point from remote control
4042A). - Free-contact for general alarm and 2 for addressable alarms
• Free-cooling air coils with aluminum fins and mechanically- - Remote ON-OFF switch
expanded copper tubes. The coils are equipped with isolating - Ability to interface with two separate BMSs with different protocols
solenoid valve to maximize the mixed free-cooling operation.
- Compatibility with BMS by means the main protocols
• Free-cooling pump driven by microprocessor control.
- Full integration into a Data Center Infrastructure Management
• Acousti-Composite fans with electronic commutated motors (DCIM) System
(EC): sickle-blade axial fans, statically and dynamically
- Set-point variation based on external temperature or signal (0-10V,
balanced, made from composite materials for high efficiency
4-20mA or 0-20mA).
and low acoustic impact, with safety protection grilles.
• Modulating condensation control with fan speed regulation.
schneider-electric.com Aquaflair chillers | 49

Technical Data 1. D
 ata refer to nominal
conditions: water
TSAF Model 1521A 2042A 2642A 3642A 4042A
temperature 15/10 °C,
Power supply V/ph/Hz 400/3/50
external temperature
Compressors/circuits nr. x mod. 2/1 4/2 4/2 4/2 4/2 35 °C, glycol 20%,
Evaporator nr. x mod. 1 x brazed plate refrigerant R410A, fouling
Fans nr. 2 3 4 5 6 factor 0.0 m2 °C/W
Quiet version 2. Data refer to total absorbed
Cooling capacity (1) kW 136,8 162,3 219 308,5 344 power (compressors and
Absorbed power (1)(2) kW 39,7 47,3 64,3 90,8 101,7 fans)
EER (1)(2) 3,44 3,43 3,41 3,40 3,38 3. D
 ata refer to nominal
EER in free-cooling mode (3)(4) °C 10,77 10,64 13,58 12,35 11,57 conditions: inlet water
UltraQuiet version temperature 15 °C, external
temperature 5 °C, glycol
Cooling capacity (1) kW 128,3 154,2 206,8 289,4 320,8
20%, refrigerant R410A,
Absorbed power (1)(2) kW 41,2 47,8 65,6 93,6 104,4
fouling factor 0.0 m2 °C/W
EER (1)(2) 3,11 3,23 3,15 3,09 3,07
4. D
 ata refer to total input
EER in free-cooling mode (3)(4) °C 10,85 10,58 13,79 11,92 11,12
power (compressors, fans
Noise Pressure Levels
and free-cooling pump)
Quiet version (5) dB(A) 57,3 56,9 59,8 60,4 60,8
5. Data refer to free field at
UltraQuiet version (5) dB(A) 53,5 53,9 54,8 55,8 56,2
10 meters from the unit
Dimensions operating without pump
Height (EC fans) mm 2236 2236 2236 2156 2156 at minal conditions, with
Depth mm 4112 4612 5562 5730 5730 fans at nominal conditions,
Width mm 1151 1151 1151 2204 2204 coil side, Q=2 directional
factor. At different
Note: Refer to the Schneider Electric selection software for data related to units equipped with AC fans conditions and with
different configurations,
noise values may vary

Construction options •  Refrigerant leak monitoring system that generates


•  Double power supply with automatic integrated alarms in the event of leakages in the compressor
management on the active line and integrated housing.
condenser for control board. •  Adiabatic pre-cooling system (3642A-4042A models)
•  Separate power supply 230/3/50Hz. composed by spray nozzles, pumping station and
•  Double power supply with automatic integrated polyurethanic protection panels.
management on the active line and separate power •  Air-side coils equipped with metal filters and protection
supply 230/3/50Hz. grilles.
•  Intelligent free-cooling option (1+1 and 2+1) to leverage •  Later metal grilles for unit protection.
on the stand-by unit to increase the free-cooling •  Electrolytic treatment for air-side coils to allow installation
capacity. in corrosive atmosphere.
•  Glycol free arrangement to avoid glycol inside the
primary circuit. Options
•  UltraQuiet version with soundproof casing, vibration The units can be supplied with the following external
absorbers for compressors and fan speed reduction. accessories:
•  Integrated hydronic system with one or two circulation • Spring anti-vibration kit.
pumps (1 + 1 standby), or one or two inverter-driven • Victaulic type hydraulic connection.
circulation pumps (1+1 standby) and pressure • Flanged type hydraulic connection (for 3642A1, 4042A1
transducer. and 4142A1 models).
•  Internal water tank (only TSAC3642A-4042A models). • RS485 serial adaptor used to communicate with external
•  Partial condensation heat recovery. BMS.
•  Antifreeze protection on evaporator and pump/s group. • LON FTT-10 serial adaptor used to communicate with
•  Suction shut-off valves on compressor. LON protocol.
•  Power phase correction capacitors. • Additional TCP/IP serial adaptor used to communicate
•  Soft starter for compressor to reduce the starting with external BMS managed with SNMP/Modbus TCP/
current. IP protocol.
•  Power meter for a continuous measurement of the unit • BACnet MS/TP serial adaptor.
power consumption and communication to the BMS. • Lifting kit.
50 | Aquaflair chillers schneider-electric.com

Air-cooled water chillers with free-cooling system for outdoor installations

Uniflair BREF
Range
Cooling capacity: 400 ÷ 700 kW
Available versions
- Basic
- Quiet
- UltraQuiet
Refrigerant R134a
Double screw compressors
Basic offer

Standard features
•E
 xclusive Uniflair free-cooling system completely • Free-cooling pump regulated by microprocessor control.
managed by the microprocessor control. • Microprocessor control system including:
•S
 elf-supporting frame in galvanized steel with panels - Human Machine Interface (HMI) with external display
finished in epoxy powders (color RAL9022). and accessible via an access hatch
•T
 wo semi-hermetic double screw compressors with - Outlet chilled water temperature regulation by means
internal thermal protection, discharge shut-off valve, of an exclusive PID algorithm
oil heaters, and anti-vibration supports. - Electronic expansion valve managed by the control
system
• Operation possible with external temperature
- Refrigerant charge monitoring
up to 50 °C at full load.
- Monitoring of the absorbed current and checking of
• Two refrigerant circuits conforming to EC norms
possible malfunctions
(PED 97/23/EC) in copper tubes including: filter dryer,
- Advanced antifreeze protection on evaporator
flow indicator, electronic expansion valve managed
- External motorized isolating valve management
by the control system, electrovalve on the liquid line,
- Anti-freeze protection
pressure switches, transducers, and manometers of
- Compressor timing and protection
high and low pressure.
- Pump rotation (if present) on a time basis for equal
•P
 ossibility of operation with external temperatures down
operation and start-up of the stand-by pump (with
to -25 °C.
alarm signal) in the event of a breakdown
•H
 igh efficiency shell and tube single passage
- Integrated LAN card for connecting more than one unit
evaporator. The heat exchanger is insulated with
to the local area network
UV resistant closed cell expanded neoprene.
- Integrated USB connection for data downloading
•A
 ir side exchange coils with aluminum fins, internally
- Integrated RS4805 serial card for data downloading
grooved copper tubes and integrated subcooling circuit.
- Integrated clock card.
•W
 ater flow differential pressure switch.
• Microprocessor control system, in addition, allows:
• Acousti-Composite fans: sickle-blade axial fans, statically
- Limiting of absorbed current on preset value or
and dynamically balanced, made from composite
external signal
materials for high efficiency and low acoustic impact
- Quick restart procedure to reach total cooling
with safety protection grilles.
capacity within two or three minutes according to unit
•M
 odulating condensation control with fan
configuration
speed regulation.
- Management of double set-point from remote control
• Electrical panel conforming to EC norms (Directive - Free-contact for general alarm and 2 for addressable
2006/95/EC and EMC 2004/108/EC, IP54) with general alarms
cut-off switch, power supply electic bars distribution, - Remote ON-OFF switch
acquisition of absorbed current, minimum and - Ability to interface with two separate BMSs with
maximum internal temperature control, magneto-thermal different protocols
cut-off switch on the fans and auxiliaries, fuses for
- Direct connection to serial BMSs with Modbus
the compressors.
protocols (integrated RS485 serial card)
•S
 equence phase, minimum and maximum power
- Set-point variation based on external temperature or
supply monitoring.
signal (0-10V, 4-20mA or 0-20mA).
schneider-electric.com Aquaflair chillers | 51

Technical Data 1. D
 ata refer to nominal
conditions: water
BREF Model 1802A 2202A 2502A 2802A
temperature 15/10 °C,
Power supply V/ph/Hz 400/3/50
external temperature
Compressors/circuits nr. x mod. 2 x double screw 35 °C, glycol 20%,
Evaporator nr. x mod. 1 x shell and tube refrigerant R134a, fouling
Fans nr. 6 8 8 8 factor 0.0 m2 °C/W
Basic or Quiet version Unit equipped with EC fans

Cooling capacity (1) kW 477 545 576 689 2. Data refer to total absorbed
Absorbed power (1)(2) kW 149 165 178 221 power (compressors and
EER (1)(2) 3,12 3,31 3,24 3,12 fans)
Unit equipped with EC fans
Free-cooling capacity (3) kW 272 299 312 386
Basic or Quiet version with subcooling economizer 3. D
 ata refer to nominal
conditions: inlet water
Cooling capacity (1) kW 512 582 618 743
temperature 15 °C, external
Absorbed power (1)(2) kW 161 181 193 251
temperature 5 °C, glycol
EER (1)(2) 3,19 3,22 3,21 2,97 20%, refrigerant R134a,
Free-cooling capacity (3) kW 286 313 327 409 fouling factor 0.0 m2 °C/W
UltraQuiet version Unit equipped with EC fans
Cooling capacity (1) kW 446 508 540 653 4. D
 ata refer to free field at
Absorbed power (1)(2) kW 155 169 183 228 10 meters from the unit
EER (1)(2) 2,88 3,01 2,96 2,87 operating without pump
Free-cooling capacity (3) kW 262 282 295 369 at minal conditions, with
fans at nominal conditions,
UltraQuiet version with subcooling economizer
coil side, Q=2 directional
Cooling capacity (1) kW 491 557 593 720
factor. At different
Absorbed power (1)(2) kW 171 191 203 261 conditions and with
EER (1)(2) 2,88 2,92 2,93 2,76 different configurations,
Free-cooling capacity (3) kW 278 303 316 391 noise values may vary
Noise Pressure Level Unit equipped with EC fans

Basic version (4) dB(A) 63,2 64,1 63,8 64,2 5. Data refer to unit without
Quiet version (4) dB(A) 62,1 63,2 63,1 63,2 chimneys
Quiet version with chimneys (4) dB(A) 54,4 55,0 54,4 55,1
UltraQuiet version (4) dB(A) 58,7 59,7 59,5 59,7
Dimensions
Height (EC fans) (5) mm 2531 2531 2531 2531
Depth mm 5005 6435 6435 6435
Width mm 2200 2200 2200 2200

Construction options • Condensing and free-cooling coils equipped with metal


• Double power supply with automatic integrated safety grilles and filters.
management on the active line and integrated • Coil manifolds protection panels.
condenser for control board. • Condensing and free-cooling coil cataphoresis
• Fans with electronic commutated motors (EC). or pre-painting treatment*.
• Power phase correction capacitors.
• Subcooling Economizer. Options
• Quite version with soundproof casing and vibration The units can be supplied with the following
absorbers for compressors. external accessories:
• UltraQuiet version with soundproof casing, vibration • Remote user terminal UPGD1 (up to 200 meters
absorbers for compressors and fan speed reduction. with shielded cable) for:
• Noise reduction chimneys for Quiet version*. - Entering of commands
- Display unit status of alarms
• Intelligent free-cooling for an increase in efficiency
with unit in standby. • Spring anti-vibration kit.
• Free-cooling operation down to -40°C. • Flanged type hydraulic connection.
• Glycol-free version*. • Additional RS485 serial adaptor used to communicate
with external BMS.
• Partial condensation heat recovery.
• LON FTT-10 serial adaptor used to communicate
• Suction shut-off valves on compressor.
with external BMS managed with LON protocol.
• Power meter.
•T
 CP/IP serial adaptor used to communicate with
• Integrated hydronic system with one or two
external BMS managed with SNMP protocol.
circulation pumps (1+1 standby).
•L
 ifting kit.
• Integrated hydronic system with one or two (1+1
standby) inverter-driven circulation pumps and pressure
transducers. * On request.
52 | Aquaflair chillers schneider-electric.com

Air-cooled water chillers with free-cooling system for outdoor installations

Uniflair BREF
Range
Cooling capacity: 400 ÷ 1,300 kW
Available versions
- Basic
- Quiet
- UltraQuiet
Refrigerant R134a
Double screw compressors
Premium offer

Standard features
•E
 xclusive Uniflair free-cooling system completely • Microprocessor control system including:
managed by the microprocessor control. - Human Machine Interface (HMI) with external display
•S
 elf-supporting frame in galvanized steel with panels and accessible via an access hatch
finished in epoxy powders (color RAL9022). - Outlet chilled water temperature regulation by means
of an exclusive PID algorithm
•T
 wo semi-hermetic double screw compressors with
- Electronic expansion valve managed by the control
internal thermal protection, discharge shut-off valve,
system
oil heaters, and anti-vibration supports.
- Refrigerant charge monitoring
• Two refrigerant circuits conforming to EC norms
- Monitoring of the absorbed current and checking of
(PED 97/23/EC) in copper tubes including: filter dryer,
possible malfunctions
flow indicator, electronic expansion valve managed
- Advanced antifreeze protection on evaporator
by the control system, electrovalve on the liquid line,
- External motorized isolating valve management
pressure switches, transducers, and manometers of
- Anti-freeze protection
high and low pressure.
- Compressor timing and protection
•P
 ossibility of operation with external temperatures down
- Pump rotation (if present) on a time basis for equal
to -25 °C in free cooling mode.
operation and start-up of the stand-by pump (with
•H
 igh efficiency shell and tube single passage alarm signal) in the event of a breakdown
evaporator. The heat exchanger is insulated with
- Integrated LAN card to connect more than one unit to
UV resistant closed cell expanded neoprene.
the local area network
•A
 ir side exchange coils with aluminum fins, internally
- Integrated USB connection for data downloading
grooved copper tubes and integrated subcooling circuit.
- Integrated RS4805 serial card data downloading
•W
 ater flow differential pressure switch.
- Integrated clock card.
• Acousti-Composite fans: sickle-blade axial fans, statically
• Microprocessor control system, in addition, allows:
and dynamically balanced, made from composite
- Limiting of absorbed current on preset value or
materials for high efficiency and low acoustic impact
external signal
with safety protection grilles.
- Quick restart procedure to reach total cooling
•M
 odulating condensation control with fan
capacity within two or three minutes according to unit
speed regulation.
configuration
• Electrical panel conforming to EC norms (Directive - Management of double set-point from remote control
2006/95/EC and EMC 2004/108/EC, IP54) with general - Free-contact for general alarm and 2 for addressable
cut-off switch, power supply electic bars distribution, alarms
acquisition of absorbed current, minimum and - Remote ON-OFF switch
maximum internal temperature control, magneto-thermal - Ability to interface with two separate BMSs with
cut-off switch on the fans and auxiliaries, fuses for different protocols
the compressors.
- Direct connection to serial BMSs with Modbus
•S
 equence phase, minimum and maximum power protocols (integrated RS485 serial card)
supply monitoring.
- Set-point variation based on external temperature or
•F
 ree-cooling pump regulated by microprocessor control. signal (0-10V, 4-20mA or 0-20mA).
schneider-electric.com Aquaflair chillers | 53

1. D
 ata refer to nominal
Technical Data
conditions: water
BREF Model 1812A 2212A 2512A 2812A 3212A 3612A 4212A 4812A 5612A
temperature 15/10 °C,
Power supply V/ph/Hz 400/3/50 external temperature
Compressors/circuits nr. x mod. 2 x double screw 35 °C, glycol 20%,
Evaporator nr. x mod. 1 x shell and tube refrigerant R134a, fouling
Fans nr. 6 8 8 8 10 10 12 12 14 factor 0.0 m2 °C/W
Unit equipped with EC fans
Basic or Quiet version
Cooling capacity (1) kW 428 543 593 685 788 891 103 1139 1224 2. Data refer to total
Absorbed power (1)(2) kW 127 157 177 201 233 277 313 350 395 absorbed power
(compressors and fans)
EER (1)(2) 3,38 3,46 3,36 3,41 3,39 3,22 3,31 3,26 3,10
Unit equipped with EC fans
Free-cooling capacity (3) kW 256 299 318 385 409 493 598 619 676
Basic or Quiet version with subcooling economizer 3. D
 ata refer to nominal
conditions: inlet water
Cooling capacity (1) kW 454 577 634 731 842 959 1112 1232 1320
temperature 15 °C, external
Absorbed power (1)(2) kW 141 173 192 228 263 312 350 395 440 temperature 5 °C, glycol
EER (1)(2) 3,22 3,34 3,31 3,21 3,21 3,08 3,18 3,12 3,00 20%, refrigerant R134a,
Free-cooling capacity (3) kW 265 312 333 401 429 520 618 649 710 fouling factor 0.0 m2 °C/W
UltraQuiet version Unit equipped with EC fans
Cooling capacity (1) kW 394 507 552 648 737 842 977 1084 1162 4. D
 ata refer to free field at
Absorbed power (1)(2) kW 132 162 182 211 241 290 322 361 408 10 meters from the unit
EER (1)(2) 2,99 3,13 3,04 3,08 3,06 2,91 3,04 3,01 2,85 operating without pump
at minal conditions, with
Free-cooling capacity (3) kW 241 283 303 372 394 471 566 584 648
fans at nominal conditions,
UltraQuiet version with subcooling economizer
coil side, Q=2 directional
Cooling capacity (1) kW 430 551 605 707 806 929 1076 1201 1284 factor. At different
Absorbed power (1)(2) kW 152 185 202 242 276 330 365 411 458 conditions and with
EER (1)(2) 2,83 2,98 3,00 2,93 2,93 2,82 2,95 2,93 2,80 different configurations,
Free-cooling capacity (3) kW 254 301 322 393 418 501 601 610 682 noise values may vary
Unit equipped with EC fans
Noise Pressure Levels
Basic version (4) dB(A) 62,8 65,8 65,2 65,4 66,2 66,3 66,7 67,2 68,0 5. Data refer to unit without
Quiet version (4) dB(A) 61,9 63,8 63,5 63,6 63,9 63,9 64,2 64,5 65,2 chimneys

Quiet version with


dB(A) 58,4 60,9 60,5 60,6 61,2 61,3 61,7 62,1 62,8
chimneys (4)
UltraQuiet version (4) dB(A) 53,7 57,9 56,9 57,3 58,7 58,8 59,2 59,9 60,7
Dimensions
Height (EC fans) (5) mm 2531 2531 2531 2531 2531 2531 2531 2531 2531
Depth mm 4985 4985 6415 6415 9110 9110 10540 10540 11970
Width mm 2200 2200 2200 2200 2200 2200 2200 2200 2200

Construction options •C
 ondensing and free-cooling coils equipped with metal
• Double power supply with automatic integrated safety grilles and filters.
management on the active line and integrated •C
 oil manifolds protection panels.
condenser for control board. •C
 ondensing and free-cooling coil cataphoresis or pre-
• Fans with electronic commutated motors (EC). painting treatment*.
• Power phase correction capacitors.
• Subcooling Economizer. Options
• Operation possible with external temperature up to The units can be supplied with the following
50 °C at full load. external accessories:
• Quite version with soundproof casing and vibration • Remote user terminal UPGD (up to 200 meters
absorbers for compressors. with shielded cable) for:
• UltraQuiet version with soundproof casing, vibration - Entering of commands
absorbers for compressors and fan speed reduction. - Display unit status of alarms
• Noise reduction chimneys for Quiet version*. • Spring anti-vibration kit.
• Intelligent free-cooling for an increase in efficiency • Flanged type hydraulic connection.
leveraging on the unit in standby. • Additional RS485 serial adaptor used to communicate with
• Free-cooling operation down to -40°C external BMS.
• Glycol-free version*. • LON FTT-10 serial adaptor used to communicate
• Partial condensation heat recovery. with external BMS managed with LON protocol.

• Suction shut-off valves on compressor. •T


 CP/IP serial adaptor used to communicate with
external BMS managed with SNMP protocol.
• Power meter.
•L
 ifting kit.
• Integrated hydronic system with one or two
circulation pumps (1+1 standby).
• Integrated hydronic system with one or two (1+1 * On request.
standby) inverter-driven circulation pumps and pressure
transducers.
54 | Aquaflair chillers schneider-electric.com

Air-cooled water chillers with free-cooling system for outdoor installations

Uniflair BREF
Range
Cooling capacity: 300 ÷ 1,000 kW
Available versions
- Basic
- Quiet
- UltraQuiet
Refrigerant R1234ze
Double screw compressors – optimized solution
for R1234ze

Standard features
•E
 xclusive Uniflair free-cooling system completely • Free-cooling pump regulated by microprocessor control.
managed by the microprocessor control. • Microprocessor control system including:
•S
 elf-supporting frame in galvanized steel with panels - Human Machine Interface (HMI) with external display and
finished in epoxy powders (color RAL9022). accessible via an access hatch
•T
 wo semi-hermetic double screw compressors with - Outlet chilled water temperature regulation by means of
internal thermal protection located in the electrical board, an exclusive PID algorithm
discharge shut-off valve, oil heaters, and anti-vibration - Modulating condensation pressure control
supports. - Electronic expansion valve managed by the control
system
•E
 nvironmental friendly refrigerant R1234ze(E) featured by
- Indirect and direct refrigerant charge monitoring
low global warming potential GWP<1
- Monitoring of the absorbed current and checking of
•T
 wo refrigerant circuits conforming to EC norms (PED
possible malfunctions
97/23/EC) in copper tubes including: compressor
- Advanced antifreeze protection on evaporator
discharge shut-off valve, filter dryer, liquid sight glass,
- External motorized isolating valve management
electronic expansion valve managed by the control
- Anti-freeze protection
system, solenoid valve on the liquid line, high and low
- Compressor timing and protection
pressure transducers and high and low pressure gauges.
- Unloading to protect unit operation even with
•O
 peration possible with external temperature up to 50 °C temperatures which exceed the maximum
at full load and water temperature up to 25 °C. - Pump rotation (if present) on a timed basis for equal
•P
 ossibility of operation with external temperatures down operation and start-up of the stand-by pump (with alarm
to -25 °C in free-cooling mode. signal) in the event of a breakdown
•H
 igh efficiency shell and tube single passage evaporator. - Integrated LAN card to connect more than one unit to the
The heat exchanger is insulated with UV resistant closed local area network
cell expanded neoprene. - Integrated USB connection for data downloading
•A
 ir side exchange coils with aluminum fins and internally - Integrated RS4805 serial card data downloading
grooved copper tubes and integrated subcooling circuit. - Integrated clock card

•W
 ater flow differential pressure switch. • Microprocessor control system, in addition, allows:
- Limiting of absorbed current on preset value orexternal
•A
 cousti-Composite fans: sickle-blade axial fans, statically
signal
and dynamically balanced, made from composite
- Quick restart procedure to reach total cooling capacity
materials for high efficiency and low acoustic impact with
within two or three minutes according to the configuration
safety protection grilles.
- Management of double set-point from remote control
•M
 odulating condensation control with fan speed - Free-contact for general alarm and 2 for addressable
regulation. alarms
•E
 lectrical panel conforming to EC Norms (Directive - Remote ON-OFF switch
2014/35/UE and EMC 2014/30/UE, IP54) with general - Ability to interface with two separate BMSs with different
cut-off switch, electric bars distribution for power supply, protocols
acquisition of absorbed current, maximum internal - Direct connection to serial BMSs with Modbus protocols
temperature control, magneto-thermal cut-off switch on (integrated RS485 serial card)
the fans and auxiliaries, fuses for the compressors and - Set-point variation based on external temperature or
thermal protection for compressors signal (0-10V, 4-20mA or 0-20mA).
•R
 efrigerant leakage sensor located in the electrical board.
•S
 equence phase, minimum and maximum power supply
monitoring.
schneider-electric.com Aquaflair chillers | 55

1. D
 ata refer to nominal
Technical Data
conditions: water
BREF Model 1832A 2232A 2532A 2832A 3232A 3632A 4232A 4832A 5632A
temperature 15/10 °C,
Power supply V/ph/Hz 400/3/50 external temperature
Compressors/circuits nr. x mod. 2 x double screw 35 °C, glycol 20%,
Evaporator nr. x mod. 1 x shell and tube refrigerant R1234ze,
Fans nr. 6 8 8 8 10 10 12 12 14 fouling factor 0.0 m2 °C/W
Unit equipped with EC fans
Basic or Quiet version
Cooling capacity (1) kW 353 434 499 577 707 763 864 949 1018 2. Data refer to total
Absorbed power (1)(2) kW 104 124 144 170 201 218 256 281 305 absorbed
EER (1)(2) 3,40 3,50 3,45 3,40 3,51 3,51 3,38 3,38 3,34 power (compressors and
fans)
Free-cooling capacity (3) kW 170 201 219 262 288 336 401 421 463
Unit equipped with EC fans
UltraQuiet version
3. D
 ata refer to nominal
Cooling capacity (1) kW 329 413 469 532 659 709 803 887 940
conditions: inlet water
Absorbed power (1)(2) kW 101 122 144 173 205 227 258 285 311
temperature 15 °C, external
EER (1)(2) 3,24 3,37 3,25 3,08 3,22 3,12 3,12 3,12 3,02 temperature 5 °C, glycol
Free-cooling capacity (3) kW 163 194 210 248 280 319 381 401 437 20%, refrigerant R1234ze,
Noise Pressure Levels fouling factor 0.0 m2 °C/W
Basic version (4) dB(A) 62,8 65,8 65,2 65,4 66,2 66,3 66,7 67,2 68,0 Unit equipped with EC fans

Quiet version (4) dB(A) 61,9 63,8 63,5 63,6 63,9 63,9 64,2 64,5 65,2 4. D
 ata refer to free field at
Quiet version with 10 meters from the unit
dB(A) 58,4 60,9 60,5 60,6 61,2 61,3 61,7 62,1 62,8 operating without pump
chimneys (4)
at minal conditions, with
UltraQuiet version (4) dB(A) 53,7 57,9 56,9 57,3 58,7 58,8 59,2 59,9 60,7
fans at nominal conditions,
Dimensions
coil side, Q=2 directional
Height (EC fans) (5) mm 2531 2531 2531 2531 2531 2531 2531 2531 2531 factor. At different
Depth mm 5005 6435 6435 6435 9110 9110 10540 10540 11970 conditions and with
Width mm 2200 2200 2200 2200 2200 2200 2200 2200 2200 different configurations,
noise values may vary
Unit equipped with EC fans

5. Data refer to unit without


chimneys

Construction options • Coil manifolds protection panels.


• Double power supply with automatic integrated • Condensing and free-cooling coil cataphoresis or
management on the active line and integrated prepainting treatment*.
condenser for control board.
• Fans with electronic commutated motors (EC). * On request.
• Quiet version with soundproof casing fitted with
refrigerant leakage system and ventilation system and
Options
vibration absorbers for compressors.
The units can be supplied with the following external
• UltraQuiet version with soundproof soundproof casing
accessories:
fitted with refrigerant leakage system and ventilation
• Remote user terminal UPGD1 (up to 200 meters with
system, vibration absorbers for compressors and fan
shielded cable) for:
speed reduction.
- Entering of commands
• Noise reduction chimneys for Quiet version*.
- Display unit status of alarms
• Intelligent free-cooling for an increase in efficiency
• Spring anti-vibration kit.
leveraging on the unit in standby.
• Flanged type hydraulic connection.
• Glycol-free version*.
• RS485 serial adaptor used to communicate with
• Suction shut-off valves on compressor.
external BMS.
• Power phase capacitors for compressors.
• LON FTT-10 serial adaptor used to communicate with
• Power meter. external BMS managed with LON protocol.
• Integrated hydronic system with one or two circulation • TCP/IP serial adaptor used to communicate with
pumps (1+1 standby). external BMS managed with SNMP protocol.
• Integrated hydronic system with one or two inverter- • Lifting kit.
driven circulation pumps (1+1 standby) and pressure
transducers.
• Antifreeze protection on evaporator and pump group.
• Condensing and free-cooling coils equipped with metal
safety grilles and filters.
56 | Aquaflair chillers schneider-electric.com

Modulating air-cooled water chillers with free-cooling system for outdoor installations

Uniflair BCEF
Range
Cooling capacity: 300 ÷ 1,200 kW
Available versions
- Quiet
- UltraQuiet
Refrigerant R134a
Oil-free centrifugal compressors
with magnetic bearings

Standard features
•E
 xclusive Uniflair free-cooling system completely • Modulating condensation control with continuous
managed by the microprocessor control. regulation of the fans speed.
•S
 elf-supporting frame in galvanized steel with panels • Electric panel conforming to EC standards
finished in epoxy powders (color RAL9022). (2006/95/EC and EMC 2004/108/EC Directives) with
•B
 etween one to three oil-free centrifugal compressors EMC integrated filter for protection of the harmonics,
with magnetic bearings equipped with: maximum internal temperature control, absorbed
- Internal thermal protection current control auxiliary transformer, general auxiliary
- Protection and control of the rotation axis position cut-off switch, fuses on the compressors, and remote
- Brushless synchronized DC motor control cut-off switches.
- Integrated control system • Line reactance for each compressor to stabilize the
- Speed control with inverter power supply.
- Soft start start-up • Phase sequence control and minimum/maximum
- Phase sequence control power supply and voltage.
- Pre-rotation valve • Free-cooling pump regulated by microprocessor control.
- Temperature and pressure sensors
• Microprocessor control system including:
- Two centrifugal compression stages
- Continuous control of the cooling capacity by means
- Anti-vibration kit
of an inverter and IGV (inlet guide vane)
•S
 oundproofing enclosures for compressor/s (quiet - Local user terminal with external display
version). - Outlet chilled water temperature regulation by means
•C
 oil manifold protection panels. of an exclusive PID algorithm
•S
 ingle refrigerant circuit conforming to EC standards - Integrated LAN card for connecting more than one unit
(PED 97/23/CE) with copper tubing including: filter to the local area network
dryer, liquid sight glass, electronic expansion valve - Acquisition and management of main electrical data
controlled by a level sensor, discharge and suction - Direct decoding of all compressor signals on the
taps on the compressor, pressure switches, high human interface to simplify service operations
and low pressure transducers, and gauges. - Clock card
•T
 he refrigerant circuit is covered by acoustic soundproof • Microprocessor control system, in addition, allows:
insulation for noise reduction. - USB card for easy download of the operating parameters
•B
 ypass line for vacuum start-up with - Management of double set point from remote control
high-pressure ratio. - Fast restart procedure
•F
 looded evaporator featuring an integrated demister - Free contact for general alarm and two for
to prevent the formation of droplets: the exchanger addressable alarms
is insulated with closed cell expanded polyurethane. - Remote ON-OFF switch
- Integrated RS485 serial card for direct connection
•D
 ifferential water pressure switch.
to external BMS
•A
 ir side exchange coils with aluminum fins, internally
- Direct interface with serial BMS with Modbus protocol
grooved copper tubes and integrated subcooling circuit.
- Interface with main BMS protocols, such as BACnet,
• Acoustic-Composite fans: sickle-blade axial fans, LonWorks, Trend, Metasys, SNMP/TCP-IP, and KNX.
statically and dynamically balanced, made from
composite materials for high efficiency and low
acoustic impact, with safety protection grilles.
schneider-electric.com Aquaflair chillers | 57

Technical Data 1. D
 ata refer to nominal
conditions: water
BCEF Model 0301A 0401A 0532A 0632A 0752A 0903A 1103A
temperature 15/10 °C,
Power supply V/ph/Hz 400/3/50
external temperature
Compressor/s nr. x mod. 1 x oil-free 2 x oil-free 3 x oil-free 35 °C, glycol 20%,
Cooling circuits nr. 1 refrigerant R134a, fouling
Evaporator nr. x mod. 1 x flooded factor 0.0 m2 °C/W
Fans nr. 6 6 8 10 12 14 16 Unit equipped with EC fans

Quiet version 2. Data refer to total absorbed


Cooling capacity (1) kW 332 444 642 684 909 1010 1350 power (compressors and
fans)
Absorbed power (1)(2) kW 99 124 184 191 251 283 374
Unit equipped with EC fans
EER (1)(2) 3,38 3,57 3,50 3,59 3,63 3,57 3,62
Free-cooling capacity (3) kW 235 279 380 407 587 682 783 3. Data refer to nominal
conditions: inlet water
UltraQuiet version
temperature 15 °C, external
Cooling capacity (1) kW 306 407 584 629 835 915 1240
temperature 5 °C, glycol
Absorbed power (1)(2) kW 87,9 117,8 167,8 172,9 236,4 254,9 355,0 20%, refrigerant R134a,
EER (1)(2) 3,48 3,46 3,48 3,64 3,53 3,59 3,49 fouling factor 0.0 m2 °C/W
Free-cooling capacity (3) kW 245 325 445 452 658 758 886 Unit equipped with EC fans
Noise Pressure Levels 4. D
 ata refer to free field at
Quiet version (4) dB(A) 59,6 59,8 60,4 60,8 61,2 61,4 61,7 10 meters from the unit
Quiet version with chimneys (4) dB(A) 55,9 56,2 56,9 57,2 57,7 57,8 58,2 operating without pump
UltraQuiet version (4) dB(A) 51,8 52,9 53,5 53,5 54,4 54,2 55,1 at minal conditions, with
fans at nominal conditions,
Dimensions
coil side, Q=2 directional
Height (EC fans) (5) mm 2531 2531 2531 2531 2531 2531 2531 factor. At different
Depth mm 5000 5000 6430 7860 9290 10720 12150 conditions and with
Width mm 2200 2200 2200 2200 2200 2200 2200 different configurations,
noise values may vary
Unit equipped with EC fans

5. Data refer to unit without


chimneys
Construction options • Integrated hydronic system with one or two (1+1 standby)
• Double power supply with automatic integrated inverter-driven circulation pumps and pressure
management on the active line. Quick restart included transducers.
(full load capacity within 3 minutes). • Coil manifolds protection panels.
• Separate power supply for control board and heaters •C
 ondensing coil cataphoresis or pre-painting treatment*.
operation. Quick restart included (full load capacity
within 3 minutes).
* On request.
• Double power supply with automatic integrated.
Options
management on the active line and additional separate
The units can be supplied with the following external
power supply for quick start procedure.
accessories:
• Power meter for a continuous measurement of the unit
• Remote user terminal UPGD1 (up to 200 meters with
power consumption and communication to the BMS.
shielded cable) for:
• Acoustic-Composite fans with electronic commutated
- Entering of commands
motors (EC).
- Display unit status of alarms
• Soundproof enclosure for compressor/s and fan speed
• Spring anti-vibration kit.
reduction.
• Flanged type hydraulic connection.
• Intelligent free-cooling.
• Additional RS485 serial adaptor used to communicate
• Modulating bypass valve designed to handle low load
with external BMS.
conditions.
• LON FTT-10 serial adaptor used to communicate with
• Free-cooling operation to -40°C.
LON protocol.
• Glycol-free arrangement*.
• TCP/IP serial adaptor used to communicate with
• Integrated hydronic system with one or two circulation external BMS managed with SNMP protocol.
pumps (1 + 1 standby).
• Lifting kit.
58 | Aquaflair chillers schneider-electric.com

Water-cooled water chillers and heat pumps for indoor installations

Uniflair BRWC/BRWH
Range
Cooling capacity: 300 ÷ 1,200 kW
Heating capacity: 370 ÷ 1,370 kW
Available versions
- Basic
- Sea water condensers*
- High condensing water temperature**
Refrigerant R134a
Double screw compressors

Standard features

•S
 elf-supporting frame in galvanized steel with panels • UPC1m microprocessor control system including:
finished in epoxy powders (color RAL9022). - mP20II local user terminal visible externally and
• Two semi-hermetic double screw compressors accessible through a door panel
with internal thermal protection, oil heaters, and - Chilled water/hot discharge water
anti-vibration supports. temperature regulation
- Advanced start-up management with eight partialization
•T
 wo refrigerant circuits conforming to EC standards
steps with automatic set-point regulation and compressor
(PED 97/23/CE) in copper tubing including: filter dryer,
rotation with FIFO logic (runtime counter, inrush counter,
liquid sight glass, electronic expansion valve, discharge
and counter threshold for programmed maintenance)
shut-off valve, pressure gauges, pressure switches, and
- Advanced evaporator antifreeze protection
high and low pressure transducers.
- Integrated LAN card for connection to the local
•S
 hell and tube evaporator insulated with closed cell
network of a group of chillers (up to 10 units with one
expanded neoprene.
or two in reserve)
•S
 hell and tube condenser. - Modulating condensation control (with kit: see options)
•W
 ater flow differential pressure switch for the evaporator - Clock card
and condensers. • The microprocessor control system also includes:
•E
 lectric panel conforming to EC standards - External evaporator pump group management
(2006/95/EC and EMC 2004/108/EC Directives) - Set point adjustment from external 0 V – 10 V signal
with maximum internal temperature control, auxiliary - Double set-point management with contact selection
transformer, auxiliary general cut-off switch, fuses for - General alarm contact and two addressable alarms
compressors, cut-off switches. - ON-OFF remote control
•P
 hase sequence and minimum/maximum - Ability to interface with Modbus protocol directly on
voltage control. RS485 serial card
- Ability to interface with main external communication
protocols: BACnet, LonWorks, Metasys,
TCP/IP, and SNMP.

* On request.
**Available only for 2202A, 3202A models.
schneider-electric.com Aquaflair chillers | 59

Technical Data 1. D
 ata refer to nominal
conditions: evaporator
BRWC / BRWH MODEL 1602A 1802A 2202A 2802A 3202A 4202A
in/out temperature
Power supply V/ph/Hz 400/3/50 12/7 °C, condenser
Compressors/circuits nr. x mod. 2 x double screw in/out temperature
Evaporator nr. x mod. 1 x shell and tube 30/35 °C, glycol 0%,
Condensers nr. x mod. 2 x shell and tube refrigerant R134a, fouling
Cooling only unit (BRWC) factor 0.0 m2 °C/W

Cooling capacity (1) kW 379 425 545 688 806 1037 2. D


 ata refer to total
Absorbed power (1)(2) kW 79,8 93,1 110,8 141 164,8 218,3 absorbed power
EER (1)(2) 4,75 4,57 4,92 4,87 4,89 4,75 3. European seasonal energy
ESEER (3) kW 5,11 4,67 5,35 5,26 5,15 5,03 efficiency ratio
IPLV (4) °C 5,52 5,00 5,88 5,68 5,63 5,50 4. I ntegrated partial load
Heat pump unit (BRWH) value
Heating capacity (1) kW 429 485 623 779 910 1177
5. Data refer to nominal
Absorbed power (1)(2) kW 95,2 109,2 136,3 170 196,2 259,0 conditions: evaporator
EER (1)(2) 4,50 4,45 4,57 4,58 4,64 4,54 in/out temperature
Noise Pressure Levels 12/7 °C, condenser
Basic version (6) dB(A) 73,7 73,8 79,5 79,6 77,3 76,3 in/out temperature
40/45 °C, glycol 0%,
Low noise version (6) dB(A) 73,7 64,6 69,6 72,4 69,3 71,8
refrigerant R134a, fouling
Dimensions
factor 0.0 m2 °C/W
Height mm 2038 2038 2043 2043 2340 2340
6. Data refer to free field
Depth mm 860 860 860 860 1485 1485
at 1 meter from the unit
Width mm 3874 3874 4234 4234 4300 4300
operating without pump
at nominal conditions,
Q=2 directional factor.
At different conditions
and with different
configurations, noise
values may vary

Construction options Options


• Low noise version with soundproofed housing for • Pressostatic two-way valve with integrated control
the compressors. for control software.
• Low external temperature version with anti-condensation •R
 emote control panel which allows:
heater for the electrical panel and heaters for the - Display/modification of settings
evaporator and condensers. - Display of activated alarms
• Condensers for sea water*. • Spring anti-vibration anti-seismic supports.
• High condensation temperature version**. • Neoprene anti-vibration supports.
• Partial/total integrated condensation heat recovery.
• Low temperature glycol/water mixture production
(down to -10 °C).
• RS485 serial card for connection an external BMS.
• LON FFT-10 serial card for connection to an external
BMS with LON protocol.
• Power phase correction condensers.
• Unit predisposed for outdoor installation*.

* On request.
**Available only for 2202A, 3202A models.
60 | Aquaflair chillers schneider-electric.com

Modulating water-cooled water chillers for indoor installation

Uniflair BCWC

Range
Cooling capacity: 300 ÷ 1,300 kW
Available versions
- Basic
- Sea water condersers*
Refrigerant R134a
Oil-free centrifugal compressors
with magnetic bearings

Standard features
•S
 elf-supporting metal frame in galvanized steel finished • Electric panel conforming to EC standards.
in epoxy powders (color RAL9022). (2006/95 /EC and EMC 2004/108/EC Directives) with EMC
•B
 etween one and four oil-free centrifugal compressors integrated filter for protection of the harmonics, maximum
with magnetic bearings equipped with: internal temperature control, auxiliary transformer, general
- Internal thermal protection auxiliary cut-off switch, fuses on the compressors, and
- Protection and control of the rotation axis position remote control cut-off switches.
- Brushless synchronized DC motor • Line reactance for each compressor to stabilize the
- Integrated control system power supply.
- Speed control with inverter • Phase sequence control and minimum/maximum power
- Soft start start-up supply and voltage.
- Phase sequence control • Microprocessor control system including:
- Pre-rotation valve - Continuous control of the cooling capacity by means
- Temperature and pressure sensors of an inverter and IGV (inlet guide vane)
- Two centrifugal compressor stages - Local user terminal with external display
- Anti-vibration supports. - Outlet chilled water temperature regulation by means
•S
 ingle refrigerant circuit conforming to EC standards of an exclusive PID algorithm
(PED 97/23/CE Directive) with copper tubing including: - Integrated LAN card for connecting more than one unit
filter dryer, liquid sight glass, electronic expansion valve to the local area network
controlled by a level sensor, discharge and suction taps - Acquisition and management of main electrical data
on the compressor, pressure switches, high and low - Direct decoding of all the compressor signals on the
pressure transducers, and gauges. human interface to simplify service operations
•B
 ypass line for vacuum start-up with high pressure ratio. - Clock card.
•S
 hell and tube evaporator featuring an integrated • Microprocessor control system, in addition, allows:
demister to prevent the formation of droplets: - USB card for easy download of the operating
the exchanger is insulated with closed cell parameters
expanded polyurethane. - Management of double set point from remote control
•D
 ifferential water pressure switch for the evaporator - Fast restart procedure
and the condenser. - Free contact for general alarm and two for addressable
•S
 hell and tube condenser. alarms
- Remote ON-OFF switch
- Integrated RS485 serial card for direct connection to
* On request. external BMS
- Direct interface with serial BMS with Modbus protocol
- Interface with main BMS protocols, such as BACnet,
LonWorks, Trend, Metasys, SNMP/TCP-IP, and KNX.
schneider-electric.com Aquaflair chillers | 61

Technical Data 1. D
 ata refer to nominal
conditions: evaporator
BCWC Model 0320A 0630A 0950A 1250A
in/out temperature
Power supply V/ph/Hz 400/3/50
12/7 °C, condenser
Compressors nr. x mod. 1 x centrifugal 2 x centrifugal 3 x centrifugal 4 x centrifugal in/out temperature
Evaporator nr. x mod. 1 x flooded 30/35 °C, glycol 0%,
Condensers nr. x mod. 1 x shell and tube refrigerant R134a, fouling
Cooling only unit (BCWC) factor 0.0 m2 °C/W

Cooling capacity (1) kW 320 630 950 1250 2. Data refer to total absorbed
Absorbed power (1)(2) kW 67,5 133,8 198,0 258,3 power
EER (1)(2) 4,74 4,71 4,80 4,84 3. Data refer to free field
Noise Pressure Levels at 1 meter from the unit
Noise pressure level (3) dB(A) 67,3 70,3 72,1 73,3 operating without pump
Dimensions at nominal conditions,
Q=2 directional factor.
Height mm 2028 2130 1924 1924
At different conditions
Depth mm 1061 1022 1544 1505 and with different
Width mm 2640 2940 3294 4591 configurations, noise
values may vary

* Data are currently under


revision and must be
confirmed by Schneider
Electric

Construction options Options


• Separate power supply for control board and heaters The units can be supplied with the following external
/ Quick restart included (full load capacity within 3 accessories:
minutes) • Remote user terminal PDG1 (up to 200 meters with
• Double power supply with automatic integrated shielded cable) for:
management on the active line and integrated - Entering of commands
condenser for control. /Quick restart included (full load - Display unit status of alarms
capacity within 3 minutes) • Additional RS485 serial adaptor used to communicate
• Condenser for sea water use*. with external BMS.
• RS485 serial card for connection to Uniflair supervision • LON FTT-10 serial adaptor used to communicate with
system or an external BMS. external BMS managed with LON protocol.
• LON FFT-10 serial card for connection to an external • TCP/IP serial adaptor used to communicate with
BMS with LON protocol. external BMS managed with SNMP protocol.
• Neoprene anti-vibration supports.
* On request.
62 | Aquaflair chillers schneider-electric.com

Air cooled water chillers and heat pumps with backward curved bladed fans for outdoor/indoor installations

Uniflair ERCC/ERCH
Range
Cooling capacity: 50 ÷ 110 kW
Available versions
- Basic
- Quiet
Refrigerant R410A
Scroll compressors

Standard features
•S
 elf-supporting frame in galvanized steel with panels control protection, safe-motor for pumps protection
varnished with epoxy powders (color RAL9022). and remote control cut-off switches. Electrical board
•A
 ccess panel to the unit equipped with handles and fast equipped an embedded contact for an externally fitted
screws. 230V isolating motorized valve.
•T
 wo hermetic scroll compressors with internal thermal • Phase sequence control and phase presence
protection, discharge gas thermal protection (ERCH), monitoring, minimum / maximum voltage protection and
phase sequence control, safety internal valve, non- correct phase balancing.
return discharge valve, oil level glass, anti-vibration • Anti-freeze heaters (ERCH only)
supports. • Microprocessor control system including:
•C
 ompressor casing for safe operation, and protection - Local human interface with external display and
•S
 ingle (**21A model) or double ( **22A model) accessible via an access hatch
refrigerant circuit* conforming to EC Directives (PED - Outlet chilled water / hot water (for ERAH) temperature
97/23/CE) in copper tubing including filter dryer, liquid regulation by means of an exclusive algorithm
sight glass, thermostatic valve with external equalization, - Production of chilled water to -15 °C
high and low pressure switches, and high and low - External motorized isolating valve management
pressure transducers. - Anti-freeze protection
- Compressor timing and protection
•E
 nvironmentally friendly refrigerant R410A.
- Compressor rotation based on FIFO logic
•W
 ater side brazed plate heat exchanger in stainless
- Pump rotation (if present) on a timed basis for equal
steel insulated with closed cell expanded polyurethane
operation and start-up of the stand-by pump (with
•W
 ater flow differential pressure switch. alarm signal) in the event of a breakdown
•A
 ir side exchange coil with aluminium fins and - Integrated LAN card for connecting more than one unit
mechanically expanded copper tubes. to the local area network
•R
 efrigerant side cycle inversion with four-way inversion - Main electrical data acquisition and management
valve (ERCH). - Integrated clock card.
•S
 ingle suction backward curved blade centrifugal fans. - Management of double set-point from remote control
The external tri-phase rotary electric motor is directly - Free-contact for general alarm and 2 for addressable
coupled and has an IP54 Class F equipped with alarms
internal thermal protection (Klixon). The fan impeller is - Remote ON-OFF switch
dynamically and statically balanced and the cushions - Ability to interface with two separate BMSs with
are sealed and lubricated for life. different protocols
- Direct connection to serial BMSs with Modbus
•M
 odulating condensation control with fan speed
protocols (integrated RS485 serial card)
regulation.
- Set-point variation based on external temperature or
•E
 lectrical panel conforming to EC standards (2006/95/ signal (0-10V, 4-20mA or 0-20mA).
EC and EMC 2004/108/EC) protection grade IP54
• Heat pumps complying with EU Regulation 811/2013
with maximum internal temperature control, auxiliary
(heat pumps up to 70kW) and 813/3013 (heat pumps
transformer, general auxiliary cut-off switch, magneto-
from 70kW to 400kW)
thermal protection switches with trip alarm signal on
compressors, magneto thermal protection for fan speed *ERCC models with **22A suffix are available with two
compressors on two circuits.
schneider-electric.com Aquaflair chillers | 63

Technical Data 1. D
 ata refer to nominal
conditions: water
ERCC / ERCH Noise
0521A 0621A 0721A 0821A 0921A 0922A 1021A 1022A 1221A 1222A temperature 12/7 °C,
Pressure Levels
external temperature
Power supply V/ph/Hz 400/3/50
35 °C, external static
Compressors/circuits nr. x mod. 2/1 2/1 2/1 2/1 2/1 2/2 2/1 2/2 2/1 2/2 pressure 50Pa, glycol 0%,
Evaporator nr. x mod. 1 x brazed plate refrigerant R410A, fouling
Fans nr. 2 2 2 2 2 2 3 3 3 3 factor 0.0 m2 °C/W
ERCC - Basic / Quiet version Unit equipped with EC fans
Cooling capacity (1) kW 44 52 60 70 77 78 90 90 107 107 2. Data refer to total absorbed
Absorbed power (1)(2) kW 17,3 21,1 23,5 27 30,9 31 35,3 35,3 40,3 40,4 power (compressors and
EER (1)(2) 2,54 2,46 2,55 2,59 2,49 2,52 2,55 2,55 2,66 2,65 fans)
Unit equipped with EC fans
ESEER (3) 3,07 3,14 3,32 3,11 3,15 2,62 3,48 2,69 3,32 2,77
IPLV (4) 3,51 3,56 3,75 3,57 3,56 2,86 3,92 2,97 3,82 3,02 3. E
 uropean seasonal energy
efficiency ratio
ERCH - Basic / Quiet version
Unit equipped with EC fans
Heating capacity (5) 52 62 71 82 91 - 108 - 126 -
Absorbed power (5)(2) 18,2 21,3 23,9 28,4 31,6 - 36,3 - 42,9 - 4. I ntegrated partial load
value
COP (5)(2) 2,86 2,91 2,97 2,89 2,88 - 2,98 - 2,94 -
Unit equipped with EC fans
Seasonal efficiency class
B A A+ * * - * - * - 5. Data refer to nominal
(Regulation (UE) 811/2013)
conditions: Inlet/outlet
ERCC / ERCH Noise Pressure Levels
water temperature:
Basic version (6) dB(A) 65,2 65,3 65,3 66,8 66,8 66,8 69,9 69,9 71,2 71,2
40/45°C; external air dry
Quiet version (6) dB(A) 63,1 63,2 63,2 64,7 64,7 64,7 65,3 65,3 66,6 66,6 bulb temperature 7°C,
ERAC / ERAH Dimensions external air wet bulb
Height (EC fans) mm 1836 1836 1836 1836 1836 1836 2146 2146 2146 2146 temperature 6°C, external
Depth mm 1213 1213 1220 1220 1220 1184 1272 1184 1272 1184 static pressure 50Pa,
glycol 0%; refrigerant
Width mm 2026 2026 2821 2821 2821 2804 3088 3073 3088 3073
R410A, fouling factor 0.0
m2 °C/W
Unit equipped with EC fans

6. Data refer to free field at


10 meters from the unit
Construction options Options operating without pump at
• Quiet version with compressor soundproof casing. The units can be supplied with the following external nominal conditions, with
fans at nominal conditions,
• Double power supply with automatic integrated accessories.
coil side, Q=2 directional
management on the active line. • Remote human interface PDG (up to 200 meters with factor. At different
• Acoustic-Composite fans with electronic commutated shielded cable) for: conditions and with
motors (EC). - Entering of commands different configurations,
- Display unit status of alarms noise values may vary
• Partial condensation heat recovery. Unit equipped with EC fans
•  recovery (ERCC**21A models • Metal filters for the condensing coils.
• Total condensation heat
only). • Rubber or spring anti-vibration supports. * Not applicable

• Electronic expansion valve (**21A models only) • Flanged type hydraulic connection.
• Integrated hydronic system with one or two circulation • Serial adaptor used to communicate with the main
pumps. external protocols: Modbus over IP, LONworks,
BacNET, Metasys, TCP/IP, SNMP, Trend, and KNX.
• Integrated hydronic system with one inverter driven
circulation pump.
• Internal water tank.
• Internal water tank including a pump to manage the
primary circuit.
• Anti-freeze heaters option (standard for ERAH models):
unit can operate down to -20 °C external temperature.
• Discharge shut-off valves
• Power factor improvement compressors.
• Compressor soft start.
Cataphoresis treatment for the condensing coils.
• Modification of the set point by external 0 V – 10 V
signal.
64 | Aquaflair chillers schneider-electric.com

Modulating air-cooled water chillers and heat pumps with backward curved blade fans for indoor/outdoor installations

Uniflair ISCC/ISCH
Range
Cooling capacity: 60 ÷ 120 kW
Heating capacity: 65 ÷ 130 kW
Available versions
- Quiet
- UltraQuiet
Refrigerant R410A
Inverter-driven scroll compressors

Standard features
•S
 elf-supporting frame in galvanized steel with panels magneto-thermal protection switches with trip alarm
varnished with epoxy powders (color RAL9022). signal on compressors, magneto thermal protection
•A
 ccess panel to the unit equipped with handles and fast for fan speed control protection, safe-motor for
screws. pumps protection and remote control cut-off switches.
Electrical board equipped with an embedded contact
• Inverter-driven hermetic Scroll compressor, equipped
for an externally fitted 230V isolating motorized valve.
with inverter speed control, oil by-pass valve and line,
integrated soft start, power factor correction condenser, • Phase sequence control and phase presence
integrated thermal protection, crankcase heaters and monitoring, minimum / maximum voltage protection and
inverter with oil heating function, anti-vibration supports, correct phase balancing.
and an inverter driver with IP54 protection grade • Anti-freeze heaters
coupled with a specific compressor and positioned in a • Microprocessor control system including:
dedicated housing compartment. - Local human interface with external display and
•C
 ompressor soundproof casing for noise reduction, safe accessible via an access hatch
operation, and protection - Outlet chilled water / hot water (for ISAH) temperature
•S
 ingle refrigerant circuit* conforming to EC Directives regulation by means of an exclusive algorithm
(PED 97/23/CE) in copper tubing including filter dryer, - Production of chilled water to -15 °C
liquid sight glass, thermostatic valve with external - External motorized isolating valve management
equalization, high and low pressure switches, and high - Anti-freeze protection
and low pressure transducers. - Compressor timing and protection
- Compressor rotation based on FIFO logic
•E
 nvironmentally friendly refrigerant R410A.
- Pump rotation (if present) on a timed basis for equal
•E
 lectronic expansion valve
operation and start-up of the stand-by pump (with
•W
 ater side brazed plate heat exchanger in stainless alarm signal) in the event of a breakdown
steel insulated with closed cell expanded polyurethane - Integrated LAN card for connecting more than one unit
•W
 ater flow differential pressure switch. to the local area network
•A
 ir side exchange coil with aluminum fins and - Main electrical data acquisition and management
mechanically expanded copper tubes. - Integrated clock card.
•R
 efrigerant side cycle inversion with four-way inversion - Management of double set-point from remote control
valve (ISCH). - Free-contact for general alarm and 2 for addressable
alarms
•S
 ingle suction backward curved blade centrifugal fans.
- Remote ON-OFF switch
The external tri-phase rotary electric motor is directly
- Ability to interface with two separate BMSs with
coupled and has an IP54 Class F equipped with
different protocols
internal thermal protection (Klixon). The fan impeller is
- Direct connection to serial BMSs with Modbus
dynamically and statically balanced and the cushions
protocols (integrated RS485 serial card)
are sealed and lubricated for life.
- Set-point variation based on external temperature or
•M
 odulating condensation control with fan speed signal (0-10V, 4-20mA or 0-20mA).
regulation.
• Heat pumps complying with EU Regulation 811/2013
•E
 lectrical panel conforming to EC standards (2006/95/ (heat pumps up to 70kW) and 813/3013 (heat pumps
EC and EMC 2004/108/EC) protection grade IP54 with from 70kW to 400kW).
maximum and minimum internal temperature control,
auxiliary transformer, general auxiliary cut-off switch,
schneider-electric.com Aquaflair chillers | 65

Technical Data 1. D
 ata refer to nominal
conditions: water
ISCC/ISCH Models 0621A 0921A 1221A
temperature 12/7 °C,
Power supply V/ph/Hz 400/3/50
external temperature
Compressors/circuits nr. x mod. 2/1 2/1 2/1 35 °C, external static
Evaporator nr. x mod. 1 x brazed plate pressure 50Pa, glycol 0%,
Fans nr. 2 2 3 refrigerant R410A, fouling
ISCC — Quiet version factor 0.0 m2 °C/W
Unit equipped with EC fans
Cooling capacity (1) kW 58 86 114
Absorbed power (1)(2) kW 21,4 30,0 41,4 2. Data refer to total absorbed
EER (1)(2) 2,71 2,73 2,70 power (compressors and
fans)
ESEER (3) 4,01 4,21 4,32
Unit equipped with EC fans
IPLV (4) 4,00 4,29 4,46
3. E
 uropean seasonal energy
ISCH — Quiet version
efficiency ratio
Heating capacity (5) kW 62 91 122
Unit equipped with EC fans
Absorbed power (5)(2) kW 20,2 28,0 38,1
COP (5)(2) 3,16 3,25 3,30 4. I ntegrated partial load
value
Seasonal efficiency class
B * * Unit equipped with EC fans
(Regulation (UE) 811/2013)
ISCC / ISCH Noise Pressure Levels 5. Data refer to nominal
Quiet version (6) dB(A) 65,3 66,8 71,2 conditions: Inlet/outlet
water temperature:
ISCC / ISAH Dimensions
40/45°C; external air dry
Height (EC fans) mm 1836 1836 2146
bulb temperature 7°C,
Depth mm 1214 1214 1276 external air wet bulb
Width mm 2003 2804 3073 temperature 6°C, external
static pressure 50Pa,
glycol 0%; refrigerant
R410A, fouling factor 0.0
m2 °C/W
Unit equipped with EC fans

6. Data refer to free field


at 10 meters from the unit
operating without pump at
nominal conditions, with
fans at nominal conditions,
coil side, Q=2 directional
factor. At different
conditions and with
different configurations,
noise values may vary
Unit equipped with EC fans

Construction options Options


• Double power supply with automatic integrated The units can be supplied with the following external
management on the active line. accessories.
• Acoustic-Composite fans with electronic commutated • Remote human interface PDG (up to 200 meters with
motors (EC). shielded cable) for:
• Partial condensation heat recovery. - Entering of commands
- Display unit status of alarms
• Integrated hydronic system with one or two circulation
pumps. • Metal filters for the condensing coils.
• Integrated hydronic system with one inverterdriven • Rubber or spring anti-vibration supports.
circulation pump. • Flanged type hydraulic connection.
• Discharge shut-off valves • Serial adaptor used to communicate with the main
• Cataphoresis treatment for the condensing coils. external protocols: Modbus over IP, LONworks,
BacNET, Metasys, TCP/IP, SNMP, Trend, and KNX.
• Modification of the set point by external 0 V – 10 V
signal.
66 | Aquaflair chillers schneider-electric.com

Air cooled water chillers with backward curved bladed fans and free-cooling system for outdoor/indoor installations

Uniflair ERCF
Range
Cooling capacity: 50 ÷ 120 kW
Available versions
- Basic
- Quiet
Refrigerant R410A
Scroll compressors

Standard features
•E
 xclusive free-cooling system completely managed by • Modulating condensation control with an embedded
the microprocessor control. contact for an externally fitted 230V isolating motorized
•S
 elf-supporting frame in galvanized steel with panels valve.
varnished with epoxy powders (color RAL9022). • Electrical board equipped with control and 230V power
•A
 ccess panel to the unit equipped with handles and fast supply for external motorized isolating valve.
screws. • Phase sequence control and phase presence
•T
 wo hermetic scroll compressors with internal thermal monitoring, minimum / maximum voltage protection and
protection, discharge gas thermal protection (ERCH), correct phase balancing.
phase sequence control, safety internal valve, non- • Anti-freeze heaters
return discharge valve, oil level glass, anti-vibration • Anti-condensation heaters for the electrical panel.
supports. • Microprocessor control system including:
•C
 ompressor casing for safe operation, and protection - Local human interface with external display and
(basic version) accessible via an access hatch
•S
 ingle or double ( **22A model) refrigerant circuit* - Outlet chilled water temperature regulation by means of
conforming to EC Directives (PED 97/23/CE) in an exclusive algorithm
copper tubing including filter dryer, liquid sight glass, - Free-cooling and intelligent free-cooling management
thermostatic valve with external equalization, high and - Mixed free-cooling operation
low pressure switches, and high and low pressure - External motorized isolating valve management
transducers. - Anti-freeze protection
•E
 nvironmentally friendly refrigerant R410A. - Compressor timing and protection
- Compressor rotation based on FIFO logic
•W
 ater side brazed plate heat exchanger in stainless
- Pump rotation (if present) on a timed basis for equal
steel insulated with closed cell expanded polyurethane
operation and start-up of the stand-by pump (with alarm
•W
 ater flow differential pressure switch.
signal) in the event of a breakdown
•A
 ir side exchange coil with aluminium fins and - Integrated LAN card for connecting more than one unit
mechanically expanded copper tubes. to the local area network
•F
 ree-cooling air coils with aluminium fins and - Main electrical data acquisition and management
mechanically-expanded copper tubes. The coils are - Integrated clock card.
equipped with isolating solenoid valve to maximize the - Management of double set-point from remote control
mixed free-cooling operation. - Free-contact for general alarm and 2 for addressable
•S
 ingle suction backward curved blade centrifugal fans. alarms
The external tri-phase rotary electric motor is directly - Remote ON-OFF switch
coupled and has an IP54 Class F equipped with - Ability to interface with two separate BMSs with different
internal thermal protection (Klixon). The fan impeller is protocols
dynamically and statically balanced and the cushions - Direct connection to serial BMSs with Modbus protocols
are sealed and lubricated for life. (integrated RS485 serial card)
•E
 lectrical panel conforming to EC standards (2006/95/ - Set-point variation based on external temperature or
EC and EMC 2004/108/EC) protection grade IP54 with signal (0-10V, 4-20mA or 0-20mA).
maximum and minimum internal temperature control,
auxiliary transformer, general auxiliary cut-off switch, *ERCC models with **22A suffix are available with two
magneto-thermal protection switches with trip alarm compressors on two circuits.
signal on compressors, magneto thermal protection
for fan speed control protection, safe-motor for pumps
protection and remote control cut-off switches.
schneider-electric.com Aquaflair chillers | 67

Technical Data 1. D
 ata refer to nominal
conditions: water
ERCF Model 0521A 0621A 0721A 0821A 0921A 0922A 1021A 1022A 1221A 1222A
temperature 15/10 °C,
Power supply V/ph/Hz 400/3/50
external temperature
Compressors/circuits nr. x mod. 2/1 2/1 2/1 2/1 2/1 2/2 2/1 2/2 2/1 2/2 35 °C, external static
Evaporator nr. x mod. 1 x brazed plate pressure 50Pa, glycol 20%,
Fans nr. 2 2 2 2 2 2 3 3 3 3 refrigerant R410A, fouling
ERCF — Basic/Quiet version factor 0.0 m2 °C/W
Unit equipped with EC fans
Cooling capacity (1) kW 49 58 67 77 85 86 100 100 118 119
Absorbed power (1)(2) kW 17,8 21,7 24,2 27,8 31,9 31,9 36,3 36,3 41,5 41,5 2. Data refer to total absorbed
EER (1)(2) 2,75 2,67 2,77 2,77 2,66 2,70 2,75 2,75 2,84 2,87 power (compressors and
fans)
Free-cooling capacity (3) kW 36 38 43 53 55 55 63 63 74 74
Unit equipped with EC fans
ERCF Noise Pressure Levels
Basic version (5) dB(A) 65,2 65,3 65,3 66,8 66,8 66,8 69,9 69,9 71,2 71,2 3. D
 ata refer to nominal
conditions: inlet water
Quiet version (5) dB(A) 63,1 63,2 63,2 64,7 64,7 64,7 65,3 65,3 66,6 66,6
temperature 15 °C, external
ERCF Dimensions temperature 5 °C, external
Height (EC fans) mm 1836 1836 1836 1836 1836 1836 2146 2146 2146 2146 static pressure 50Pa,
Depth mm 1213 1213 1220 1220 1220 1184 1272 1184 1272 1184 glycol 20%, refrigerant
Width mm 2026 2026 2821 2821 2821 2804 3088 3073 3088 3073 R134a, fouling factor 0.0
m2 °C/W
Unit equipped with EC fans

4. D
 ata refer to total input
power (compressors, fans
and free-cooling pump)

5. Data refer to free field


at 1 meter from the unit
operating without pump at
nominal conditions, with
fans at nominal conditions,
dicharge air side, Q=2
directional factor. At
different conditions
and with different
configurations, noise
values may vary
Unit equipped with EC fans
Construction options Options
• Quiet version with compressor soundproof casing. The units can be supplied with the following external
• Double power supply with automatic integrated accessories.
management on the active line. • Remote human interface PDG (up to 200 meters with
• Acoustic-Composite fans with electronic commutated shielded cable) for:
motors (EC). - Entering of commands
- Display unit status of alarms
• Partial condensation heat recovery.
• Metal filters for the condensing coils.
• Electronic expansion valve (**21A models only)
• Rubber or spring anti-vibration supports.
• Intelligent free-cooling.
• Flanged type hydraulic connection.
• Integrated hydronic system with one or two circulation
pumps. • Serial adaptor used to communicate with the main
external protocols: Modbus over IP, LONworks,
• Integrated hydronic system with one inverter driven
BacNET, Metasys, TCP/IP, SNMP, Trend, and KNX.
circulation pump.
• Internal water tank.
• Internal water tank including a pump to manage the
primary circuit.
• Discharge shut-off valves
• Power factor improvement compressors.
• Compressor soft start.
• Cataphoresis treatment for the condensing coils.
• Modification of the set point by external 0 V – 10 V
signal.
68 | Aquaflair chillers schneider-electric.com

Modulating air-cooled water chillers and heat pumps with BCF and free-cooling system for indoor/outdoor installations

Uniflair ISCF
Range
Cooling capacity: 60 ÷ 120 kW
Available versions
- Quiet
Refrigerant R410A
Inverter-driven scroll compressors

Standard features
•E
 xclusive free-cooling system completely managed by maximum and minimum internal temperature control,
the microprocessor control. auxiliary transformer, general auxiliary cut-off switch,
•S
 elf-supporting frame in galvanized steel with panels magneto-thermal protection switches with trip alarm
varnished with epoxy powders (color RAL9022). signal on compressors, magneto thermal protection
for fan speed control protection, safe-motor for
•A
 ccess panel to the unit equipped with handles and fast
pumps protection and remote control cut-off switches.
screws.
Electrical board equipped with an embedded contact
• Inverter-driven hermetic Scroll compressor, equipped
for an externally fitted 230V isolating motorized valve.
with inverter speed control, oil by-pass valve and line,
• Phase sequence control and phase presence
integrated soft start, power factor correction condenser,
monitoring, minimum / maximum voltage protection and
integrated thermal protection, crankcase heaters and
correct phase balancing.
inverter with oil heating function, anti-vibration supports,
and an inverter driver with IP54 protection grade • Anti-freeze heaters
coupled with a specific compressor and positioned in a • Anti-condensation heaters for the electrical panel.
dedicated housing compartment. • Microprocessor control system including:
•C
 ompressor soundproof casing for noise reduction, safe - Local human interface with external display and
operation, and protection (quiet version). accessible via an access hatch
•S
 ingle refrigerant circuit conforming to EC Directives - Outlet chilled water temperature regulation by means
(PED 97/23/CE) in copper tubing including filter dryer, of an exclusive algorithm
liquid sight glass, thermostatic valve with external - Free-cooling and intelligent free-cooling management
equalization, high and low pressure switches, and high - Mixed free-cooling operation
and low pressure transducers. - External motorized isolating valve management
- Anti-freeze protection
•E
 nvironmentally friendly refrigerant R410A.
- Compressor timing and protection
•E
 lectronic expansion valve
- Compressor rotation based on FIFO logic
•W
 ater side brazed plate heat exchanger in stainless - Pump rotation (if present) on a timed basis for equal
steel insulated with closed cell expanded polyurethane operation and start-up of the stand-by pump (with
•W
 ater flow differential pressure switch. alarm signal) in the event of a breakdown
•A
 ir side exchange coil with aluminum fins and - Integrated LAN card for connecting more than one unit
mechanically expanded copper tubes. to the local area network
•F
 ree-cooling air coils with aluminium fins and - Main electrical data acquisition and management
mechanically-expanded copper tubes. The coils are - Integrated clock card.
equipped with isolating solenoid valve to maximize the - Management of double set-point from remote control
mixed free-cooling operation. - Free-contact for general alarm and 2 for addressable
alarms
•S
 ingle suction backward curved blade centrifugal fans.
- Remote ON-OFF switch
The external tri-phase rotary electric motor is directly
- Ability to interface with two separate BMSs with
coupled and has an IP54 Class F equipped with
different protocols
internal thermal protection (Klixon). The fan impeller is
- Direct connection to serial BMSs with Modbus
dynamically and statically balanced and the cushions
protocols (integrated RS485 serial card)
are sealed and lubricated for life.
- Set-point variation based on external temperature or
•M
 odulating condensation control with fan speed signal (0-10V, 4-20mA or 0-20mA).
regulation.
•E
 lectrical panel conforming to EC standards (2006/95/
EC and EMC 2004/108/EC) protection grade IP54 with
schneider-electric.com Aquaflair chillers | 69

Technical Data 1. Data refer to nominal


conditions: water
ISCF Model 0621A 0921A 1221A
temperature 15/10 °C,
Power supply V/ph/Hz 400/3/50
external temperature
Compressors/circuits nr. x mod. 2/1 2/1 2/1 35 °C, external static
Evaporator nr. x mod. 1 x brazed plate pressure 50Pa, glycol 20%,
Fans nr. 2 2 3 refrigerant R410A, fouling
ISCF — Quiet version factor 0.0 m2 °C/W
Unit equipped with EC fans
Cooling capacity (1) kW 63 89 122
Absorbed power (1)(2) kW 22,0 30,8 42,5 2. Data refer to total absorbed
EER (1)(2) 2,86 2,88 2,87 power (compressors and
fans)
Free-cooling capacity (3) kW 38 53 72
Unit equipped with EC fans
ISCF Noise Pressure Levels
Quiet version (5) dB(A) 65,3 66,8 71,2 3. D
 ata refer to nominal
conditions: inlet water
ISCF Dimensions
temperature 15 °C, external
Height (EC fans) mm 1836 1836 2146 temperature 5 °C, external
Depth mm 1214 1214 1276 static pressure 50Pa,
Width mm 2003 2804 3073 glycol 20%, refrigerant
R134a, fouling factor 0.0
m2 °C/W
Unit equipped with EC fans

4. D
 ata refer to total input
power (compressors, fans
and free-cooling pump)

5. Data refer to free field


at 1 meter from the unit
operating without pump at
nominal conditions, with
fans at nominal conditions,
dicharge air side, Q=2
directional factor. At
different conditions
and with different
configurations, noise
values may vary
Unit equipped with EC fans

Construction options Options


• Double power supply with automatic integrated • Remote human interface PDG (up to 200 meters with
management on the active line. shielded cable) for:
• Acoustic-Composite fans with electronic commutated - Entering of commands
motors (EC). - Display unit status and alarms
• Partial condensation heat recovery. • Metal filters for the condensing coils.
• Intelligent free-cooling. • Rubber or spring anti-vibration supports.
• Integrated hydronic system with one or two circulation • Flanged type hydraulic connection.
pumps. • Serial adaptor used to communicate with the main external
• Integrated hydronic system with one inverterdriven protocols: Modbus over IP, LONworks, BacNET, Metasys,
circulation pump. TCP/IP, SNMP, Trend, and KNX.
• Discharge shut-off valves
• Cataphoresis treatment for the condensing coils.
• Modification of the set point by external 0 V – 10 V
signal.
70 | Aquaflair chillers schneider-electric.com

Prefabricated Chilled Water System

PFMHE module
Range
250 ÷ 500kW
500kW ÷ 1000 kW
Available versions
Tier II and Tier III for mechanical and electrical
Optional internal UPSs for pumps and controller
Optional storage tanks

Schneider Electric’s prefabricated chilled water systems offer a simple way to design and install a complete cooling
system for today’s critical data centers. The system features a series of prefabricated chilled water systems which are
pre-designed to meet Tier II or Tier III requirements, and can be customized to meet customer specifications. Each
module is shipped complete with pumps, valves, piping, controls, and electrical system pre-assembled at factory and
delivered on-site for simple and fast installation.

Standard features
•S
 elf supporting and isolated enclosure to protect The module is complete with Management and Control
mechanical and electrical systems (color RAL9003) System
• IP55* electrical room including main components to • Features SmartStruxure controls and ATV61 series
control and drive the system variable speed drives
•F
 ire Suppression System* for Electrical Room and • Pump Speed based on delta-P as Primary Pump
Ventilation Fan for Piping Room Variable Speed System or Fixed Flow Rate System
•C
 omplete hydraulic circuits fitted with Expansion Tank, • System By-Pass Control in two different ways
Strainers, Chemical Dosing Pot and Pressurization Unit - Chiller Fail Bypass: To isolate Chiller Loop to use
• Isolation valves for service to meet Tier level Thermal Storage Tank for continuously Cooling
requirements (II& III) - System Low Flow Bypass: This is for Chiller Evaporator
•3
 variable speed driven pumps in 2+1 logic anti-frozen protection
•S
 ystem By-Pass to adapt to rapid changes in load and • Continuous cooling control during power loss via the
low load conditions thermal storage and pump UPS backup
•S
 eparate central electrical and mechanical zones • Chiller Optimization resets water temperature based on
•S
 ecurity and Access Control to Module operating conditions: the controller detects IT Room
Dew Point, and then resets Chiller Supply Water Temp
•E
 xternal Door access monitoring
Set Point to keep Sensible Ratio as high as possible.
•O
 verhead lighting, exit signs, convenience outlets

* Options based on customer requirements.


schneider-electric.com Aquaflair chillers | 71

Technical Data 1. D
 ata refer to nominal
conditions: water
PFMHE Model 0500EB*U 0500EB*N 0500EB*E 1000EB*U 1000EB*N 1000EB*E
temperature 15/20,6°C,
Power supply V/ph/Hz 400/3/50
external temperature 35°C,
Fans internal without external internal without external propylene glycol 30%.
TIER II version
2. Data refer to both onboard
Total chiller load requirement (1) kW 544 1088 pumps running at full speed.
Water flow (1) Ih 90709 181418 The module is fitted with
Available head pressure kPa 230 245 three pumps in 2+1 logic.
Absorbed Power (1)(2) kW 15 30 3. D
 ata refer to empty unit
Height mm 2896 2896 2896 2896 2896 2896
4. E
 xternally fitted
Lenght mm 10657 10224 10224 11583 10668 10668
Width mm 2438 2438 2438 2438 2438 2438
Weight (2) Kg 16400 14600 14600 20600 17700 12900
TIER III version
Total chiller load requirement (1) kW 544 1088
Water flow (1) Ih 90709 181418
Available head pressure kPa 230 245
Absorbed Power (1)(2) kW 15 30
Height mm 2896 2896 2896 2896 2896 2896
Lenght mm 13189 11878 12328 15252 13388 13838
Width mm 2438 2438 2438 2438 2438 2438
Weight (2) Kg 16400 14600 14600 20600 17700 17900
TIER III version
Run-through time, 5 minutes m3 8417 16833
Run-through time, 10 minutes m3 16883 33667
Run-through time, 15 minutes m3 25250 50500
Run-through time, 20 minutes m3 33667 67333

Example Design
(Variations Based on Code and Electrical Requirements)

Main Input Power and Control Cabinet

Piping and Isolation Valves


based on Tier Level
Integrated Fire
Suppression System

Pumps with
Suction Guide x 3

Maintenance
walkway and
Chemical access floor
Pump UPS for continuous cooling Feeder Not Shown:
(Optional) Piping to IT - Hoist for Pump Removal
Load Circuit 1 - Service door for pump maintenance
Expansion and 2
Tank
72 | Aquaflair chillers schneider-electric.com

Building management systems

SmartStruxure solution

SmartStruxure solution enables you to monitor, measure, and optimize your building’s
performance throughout its life cycle — saving energy while saving money. Because
you can’t control what you don’t measure, SmartStruxure solution facilitates the
exchange and analysis of data from energy, lighting, fire safety, and HVAC.

The intelligent energy TCP/IP offers a variety of


management approach networking
Your complex energy challenges require a stronger and architecture options
more efficient collaboration between your organization’s key Using TCP/IP, SmartStruxure host workstations can
stakeholders. They demand comprehensive solutions that communicate across the Internet and existing commercial
include enterprise-wide management of power, IT, HVAC, WAN/LANs.
and security, with a level of intelligence that involves system
dynamics across segments, platforms, and providers.
The SmartStruxure flexible
Schneider Electric SmartStruxure platform integrates architecture makes it highly
multiple systems on one network to reduce training, scalable
operations, maintenance, and energy costs, which improves
comfort and increases productivity. SmartStruxure is well suited for any building management
application, regardless of the size, the business, number
of buildings, or what distances separate the buildings.
Combining industry-standard technology with an easy-
SmartStruxure manages multicampus applications
to-use interface, SmartStruxure produces an integrated
just as efficiently as single, small sites.
building management solution that is reliable, flexible, and
cost-effective. Full integration of environmental control
as well as facility and energy management in a single Aquaflair range is natively
software package allows you to customize SmartStruxure integrated with Schneider Electric
for any building and security management application.
SmartStruxure
Uniflair chillers allow a complete and easy integration into
Integrated and intelligent systems SmartStruxure. Units are able to send alarms and data
deliver choices points to the system in order to manage and optimize any
SmartStruxure gives customers the freedom to select critical infrastructure from a local or remote location.
products from a wide range of suppliers, yielding true
vendor independence. SmartStruxure runs on Microsoft®
Windows® with standard LAN communication on Ethernet
or fiber optics using TCP/IP and standard network
equipment. Field bus communication features open
LonWorks, Modbus, and/or BACnet technology, which are
used by more than 3,000 vendors worldwide.
schneider-electric.com Aquaflair chillers | 73

Data center infrastructure


management (DCIM)
Good design and quality construction alone do not ensure a highly available
and efficient data center. Data centers require ongoing monitoring and
management to ensure the facility lives up to its design intent. StruxureWare™
for Data Centers is a software management suite designed to collect and
manage data about a data center’s assets, resource use, and operational
status throughout the life cycle of the facility. This information is then
distributed, integrated, and applied in ways that help managers optimize the
data center’s performance and meet IT, business, and service-oriented goals.
From IT assets to racks, rows, rooms, and buildings, StruxureWare for Data
Centers delivers the right information to the right users at the right time.

Control level
Experts, on-site or remotely, can control process performance
and ensure business continuity in real time, while tracking energy
consumption in a highly critical and secure environment.

Operations level
Functional managers can optimize operations, energy, and assets
through smart analytical tools, often spanning multiple sites.

Enterprise level
C-level executives can drive their sustainability strategy efficiently,
choosing the best scenario that meets their business objective to
conserve enterprise-wide resources.

StruxureWare for Data Centers allows for flexibility when requirements


and implementation strategies change over time. StruxureWare
software applications and suites simplify integration time, improve
reliability, enhance visibility to energy information, and streamline
operational efficiency.

Visit www.apc.com/software to learn more


about StruxureWare for Data Centers!
74 | Aquaflair chillers schneider-electric.com

Schneider Electric
Cooling Services

Schneider Electric offers service solutions for all of our cooling customers.
These services are customized to best meet your cooling service needs.
Proper care is essential to ensure your solution is operating at its peak performance,
and thereby prolonging the life of your critical cooling equipment.

Why choose Schneider Electric


as your Cooling Specialist? ew
Ren
Schneider Electric provides quality service and solutions
from trained and trusted HVAC professionals.

Pl
an
Our best-in-class service organization ensures your
How doI What are
receiving the highest quality service from Schneider renew my my options?
Electric certified engineers. Our global cooling service solution?
organization is there to support you from commissioning
to maintaining your critical applications.
Opt imize

Whether you are planning, installing, or operating a facility,


Schneider Electric has the expertise and services
to support you throughout the many phases of its life Life Cycle
cycle. How doI Services How doI
optimize? install and
Plan: Our experts can help you plan, define, and design commission?
the right solution for increased efficiency and availability.

Install: Convert your plan into an efficient, reliable,


and safe solution with project management, installation, How doI

all
and integration services from Schneider Electric to ensure operate and

st
maintain?
In
quick and efficient implementation of your equipment.

Operate: Maximize your solution uptime Op


era
and performance with Advantage Plan service packages te
that keep your equipment running efficiently and maintain
maximum availability, while protecting your investment.

Optimize: Our solution experts and remote monitoring


systems will provide proactive and tailored
recommendations to reduce risk and improve solution’s
performance and reliability.

Renew: Schneider Electric enables you to increase


performance and flexibility, while controlling the costs
of aging infrastructure.
schneider-electric.com Aquaflair chillers | 75

Cooling for Datacenter interactive


application
To learn more about Schneider Electric cooling solutions,
download the interactive application “Cooling for Data
Center”, available for iPad®
April 2017
35 rue Joseph Monier

www.schneider-electric.com
92500 Rueil-Malmaison, France
Schneider Electric Industries SAS
©2017 Schneider Electric. All Rights Reserved. Schneider Electric, Uniflair, SmartStruxure, and Make the most of your energy are trademarks owned by
Schneider Electric Industries SAS or its affiliated companies. All other trademarks are property of their respective owners.