Inspection clarification points - PGCIL - Dtd. 20.03.

2021
As built
B sheet Observation by PGCIL inspector CGL offer CGL Remarks As per Scematic/Approved Drawings
Item. No.
As per PGCIL Specifications and approved schematic
drg no.GS0019-A-11_4 & GTP
As per approved schematic GS0019-A-11_4 & GTP
Spring charging motor voltage -110V or 230V not CGPISL provided spring charging motor voltage - But due to oversight it was mentioned 230V AC in
1A CGPISL has provided spring charging motor voltage -
matching with approved Bsheet. 110V DC. Bshhet.
110V DC.
B sheet updated with 110V DC as per requirements.
Refer attached sheet -1,2
As per commented drawings schematic drawing no.
Trip circuit unhealthy ind. provided.in place of GS0019-A-11_4. customer required Trip ckt unhealthy As per Approved schematic drawing no. GS0019-A-
2.4 CGPISL provided Trip circuit unhealthy ind.
Healthy indiaction ind. 11_4.CGPISL has provided Trip ckt unhealthy ind.
Refer attached sheet - 3,4,5.

Master trip relay not provided. Hence Auto trip indication


Auto trip indication lamp missing in as built Auto trip indiation lamp not required as master not required. As per comments tripping required through As per Approved schematic drawing no. GS0019-A-
*
drawings. trip relay not available. numerical relay, Bsheet updated as per requirements 11_4.CGPISL has provided Trip ckt unhealthy ind.
Refer attached sheet - 6,7

As per PGCIL Specifications and approved schematic


drg no.GS0019-A-11_4 & GTP.
As per approved schematic GS0019-A-11_4 & GTP
Timer auxillary voltage not matching as per CGPISL provided Timer with 110V DC Aux But due to oversight it was mentioned 230V AC in
7 CGPISL has provided Timer for spring charging motor
approved Bsheet Voltage Bshhet.
voltage - 110V DC.
B sheet updated with 110V DC as per requirements.
Refer attached sheet -1,2
As per approved schematic panel illumination lamp
CGPISL provided LED type panel illumination CGPISL provided LED type panel illumination lamp
8 CFL-type panel illumination lamp not provided mentioed in drawing. - CFL/LED Type mentioned in
lamp which Illuminate more light than CFL.
Bsheet.
CGPISL has provided MCB for main AC/DC supply and As per approved schematic drawing GS0019-A-
CGPISL has provided MCB for main AC/DC
MCB/Rotary switch required for Heater Toggle switch for local ON/OFF for heater/ socket. 31/SHEET 10 of 15 - Toggle switch for HSW/SSW
supply and Toggle switch for local ON/OFF for
Refer attached sheet - 8 provided.
13 heater/ socket.
As per PGCIL approved technical sheet drawing no.
GT0019-A-00_1 , disconnecting type TB shall be As per approved schematic drawing GS0019-A-
Disconnecting type TB for CT & PT ckt , non CGPISL provided disconnecting type TB for
29 provide for CT & PT ckt and stud type TB for other ckt. 31/SHEET 2 ,3 of 15 - Disconnecting type terminal
disconnecting type TB required CT/PT circuit.
Offered Disconnecting TB's are better for terminal block block provided.
shoring during calibaration of instuments.
In approved Bsheet Qty of cable termination kit was
Cable termination kit qty mentioned in set in as 12 set of cable termination kit provided (1 set As per approved Bsheet Qty specified in Numbers in
32 mentioned in numbers.(One set consists of 3 no.s.)
built drawing in place of numbers. consist of 3 no.) place of Sets.
(12x3) = 36 no.s which is equivalent to 12 SET.
In approved Bsheet Qty of cable termination kit
2 set i.e. 6 Nos cable termination kit insulating insulating cap was mentioned in numbers.(One set As per approved Bsheet Insulating CAP was part of
32 Cable termination kit insulating cap
cap provided (1 set consist of 3 no.) consists of 3 no.s.) (2x3) = 6 no.s which is equivalent to termination kit. Not mentioned seperately.
2 SET.
CGPISL has provided mimic diagram on each Mimic diagram is a part of panel,so it is not called in
Blank Mimic diagram Not mentioed In approved Bsheet, as it is part of Panel.
panel. Bsheet.
It is part of Ethernate switch. Hence not mentioned in B
CGPISL will provide CAT- V cable from Relay to sheet.
38 LAN/ FO cable Not mentioed In approved B'sheet.
ethernate switch. LAN/FO cable for substation is not in CGPISL'S Scope