CUSTOMER SHAMA POWER INDIA LIMITED A/C AIIMS AEGCL

PROJECT CONSTRUCTION OF 132/33KV, 1X25 MVA SUB-STATION AT AIIMS


CAMPUS (CHANGSARI) , GUWAHATI, ALONG WITH ASSOCIATED
TRANSMISSION LINE
TITLE 132/33KV CRP
CONSULTANT
VENDOR L&T ELECTRICAL & AUTOMATION – RELAY & INTEGRATION SOLUTION
DOCUMENT NO ESE-R&IS-CRP-235-2009-00
REVISION NO 00

REVISION HISTORY
SL No Reason for change Rev No Made by Date
01 BOQ and quotation for CR Panels are prepared based 00 SN 16.09.20
on technical specification.
02
03
04
05
06

INDEX
SL No Title Page No
01 132KV LINE BAYS 02
02 132KV TRANSFORMER BAY 03
03 132KV BUSCOUPLER BAY 04
04 33KV LINE BAY 05
05 33KV TRANSFORMER I/C PROTECTION CONTROL PANEL 06
06 TECHNICAL SPECIFICATION 07

Sr No Description Quantity

1 132KV LINE BAYS 3


2 132KV Transformer Bay 2
3 132KV BUSCOUPLER BAY 1
4 33KV line control panel 3
5 33KV Transformer I/C Protection control panel 1

Electrical Systems & Equipment

shailesh.nar@lntebg.com
01 132KV LINE BAYS
SL No Description Make QTY
Panel Fabrication
01 Relay protection panel (H x W x D) : 2315 x 800 x 800 L&T E&A 2
Control panel (H x W x D) : 2315 x 800 x 800
02 SIEMENS/ABB/
Numerical Relay: 21,79 1
SCHNEIDER/GE
SIEMENS/ABB/
03 Back up protection (67,67N,50,51,50N,51N) 1
SCHNEIDER/GE
04 SIEMENS/ABB/
BCU+25 1
SCHNEIDER/GE
05 Relay Test Terminal Block JVS / EQUIVALENT
3
06 Relay Test Plug JVS / EQUIVALENT
1
07 Trip ckt supervision ALSTOM/EQUIVALENT
2
08 Three Phase Trip Relays (Group A, B, Auto reclose lock out) ALSTOM/ EQUIVALENT
3
09 Single Phase Trip Relays ALSTOM/ EQUIVALENT
6
10 Voltage Selection relay ALSTOM / EQUIVALENT
2
11 DC Supply Supervision ABB/ EQUIVALENT
2
12 Power Diode with heat sink SILICON
16
13 ABT tariff meter CLIENT SCOPE
1
14 Test Terminal Block for meters JVS 1
TNC Switch, spring return type, 25A ,4 Way,3 Position for SALZER
15 4
isolators + breaker
16 Single Pole Toggle Switch, 10A KAYCEE 2
17 DC supply Selector switch , A/R in/out switch SALZER 2
18 Limit Switch, Contact : 1 C/O KAYCEE 2
19 MCB's L&T E&A 25
20 Fuse, and neutral links + Fuse base L&T E&A 38
21 LED Indication Lamp, Cluster Type ESBEE 20
22 Thermostat ; Range 25-75 deg, Voltage 240V,50 Hz APT 2
23 Panel Space Heater: 240V AC, 150W VILECO 2
24 Domestic type Socket with Piano type switch, 5A/15A, 230V AC ANCHOR 2
25 Panel illumination Lamp Holder with CFL ANCHOR 2
Black' colored Flush head (Non-illu) Push button with add on ESBEE
26 4
contact
27 RJ45 patch chords Iveonet 6
*Make of components is subject to change during detail engineering

SHAMA POWER INDIA LIMITED A/C AIIMS


Customer
AEGCL
CONSTRUCTION OF 132/33KV, 1X25 MVA ESE-R&IS-CRP-
Electrical Systems & Equipment
SUB-STATION AT AIIMS CAMPUS 235-2009-00
Project
(CHANGSARI) , GUWAHATI, ALONG WITH
ASSOCIATED TRANSMISSION LINE
Consultant PAGE 2 OF 7
PREP. SN DATE 16.09.20
CHKD TECHNICAL OFFER FOR CRP Panel REV 00
SN APPD. BM
.
This document is the property of L&T Electrical & Automation and must not be copied or lent without their permission in writing.
R&IS_F_3
02 132KV TRANSFORMER BAY
SL No Description Make QTY
Panel Fabrication
01 Relay protection panel (H x W x D) : 2315 x 800 x 800 L&T E&A 2
Control panel (H x W x D) : 2315 x 800 x 800
02 Main 1 Numerical Relay: Transformer Differential (87T+64R) SIEMENS/ABB/
1
SCHNEIDER/GE
03 Back up protection ( 67.67N, 50,51,50N,51N) SIEMENS/ABB/
1
SCHNEIDER/GE
04 BCU SIEMENS/ABB/
1
SCHNEIDER/GE
05 Relay Test Terminal Block JVS / EQUIVALENT
3
06 Relay Test Plug JVS / EQUIVALENT
1
07 Trip ckt supervision ALSTOM/EQUIVALENT
2
08 Three Phase Trip Relays (Group A, B) ALSTOM/ EQUIVALENT
2
09 Voltage Selection relay ALSTOM/ EQUIVALENT
2
10 DC Supply Supervision ABB / EQUIVALENT
2
11 Power Diode 16A,110V DC, with heat sink SILICON
16
12 Auxiliary Relays for Mechanical Protections ALSTOM/ EQUIVALENT
3
13 ABT tariff meter CLIENT SCOPE
1
14 Test Terminal Block for meters JVS 1
TNC Switch, spring return type, 25A ,4 Way,3 Position for SALZER
15 4
isolators + breaker
16 Single Pole Toggle Switch, 10A KAYCEE 2
17 DC supply Selector switch , SALZER 1
18 Limit Switch, Contact : 1 C/O KAYCEE 2
19 Selector switches SALZER 2
20 MCB's L&T E&A 25
21 Fuse, and neutral links + Fuse base L&T E&A 38
22 LED Indication Lamp, Cluster Type, Red ESBEE 20
23 Thermostat; Range 25-75 deg, Voltage 240V,50 Hz APT 2
24 Panel Space Heater: 240V AC, 150W VILECO 2
25 Domestic type Socket with Piano type switch, 5A/15A, 230V AC ANCHOR 2
26 Panel illumination Lamp Holder with CFL ANCHOR 2
Black' colored Flush head (Non-illu) Push button with add on ESBEE
27 3
contact
28 RJ45 patch chords Iveonet 6
*Make of components is subject to change during detail engineering

SHAMA POWER INDIA LIMITED A/C AIIMS


Customer
AEGCL
CONSTRUCTION OF 132/33KV, 1X25 MVA ESE-R&IS-CRP-
Electrical Systems & Equipment
SUB-STATION AT AIIMS CAMPUS 235-2009-00
Project
(CHANGSARI) , GUWAHATI, ALONG WITH
ASSOCIATED TRANSMISSION LINE
Consultant PAGE 3 OF 7
PREP. SN DATE 16.09.20
CHKD TECHNICAL OFFER FOR CRP Panel REV 00
SN APPD. BM
.
This document is the property of L&T Electrical & Automation and must not be copied or lent without their permission in writing.
R&IS_F_3
03 132KV BUSCOUPLER BAY
SL No Description Make QTY
01 Panel Fabrication
L&T E&A 1
Relay & control panel (H x W x D) : 2315 x 800 x 800
02 SIEMENS/ABB/
Numerical relay (50,51,50N,51N) 1
SCHNEIDER/GE
03 BCU+25 SIEMENS/ABB/
1
SCHNEIDER/GE
04 Relay Test Terminal Block JVS / Equivalent
2
05 Relay Test Plug JVS / Equivalent
1
06 Trip ckt supervision Alstom/Equivalent
2
07 Three Phase Trip Relays (protection trip A &B) Alstom/ Equivalent
2
08 Duplicate DC supply with changeover arrangement and ABB/ Equivalent
2
monitoring
09 Contactors for contact multiplications Siemens Contactors 5
10 Power Diode with heat sink SILICON 16
11 TNC Switch, spring return type, 25A ,4 Way,3 Position for SALZER
3
isolators + Breaker
12 Single Pole Toggle Switch, 10A KAYCEE 2
13 DC supply Selector switch , SALZER 1
14 Limit Switch, Contact : 1 C/O KAYCEE 2
15 Selector switches SALZER 1
16 MCB's L&T E&A 15
17 Fuse, and neutral links + Fuse base L&T E&A 30
18 LED Indication Lamp, Cluster Type, Red ESBEE 25
19 Thermostat; Range 25-75 deg, Voltage 240V,50 Hz APT 1
20 Panel Space Heater: 240V AC, 150W VILECO 1
21 Domestic type Socket with Piano type switch, 10A, 230V AC ANCHOR 1
22 Panel illumination Lamp Holder with CFL LAMP ANCHOR 1
Black' colored Flush head (Non-illu) Push button with add on ESBEE
23 3
contact
24 Ethernet switch L&T E&A 2
25 RJ45 patch chords Iveonet 4
*Make of components is subject to change during detail engineering

SHAMA POWER INDIA LIMITED A/C AIIMS


Customer
AEGCL
CONSTRUCTION OF 132/33KV, 1X25 MVA ESE-R&IS-CRP-
Electrical Systems & Equipment
SUB-STATION AT AIIMS CAMPUS 235-2009-00
Project
(CHANGSARI) , GUWAHATI, ALONG WITH
ASSOCIATED TRANSMISSION LINE
Consultant PAGE 4 OF 7
PREP. SN DATE 16.09.20
CHKD TECHNICAL OFFER FOR CRP Panel REV 00
SN APPD. BM
.
This document is the property of L&T Electrical & Automation and must not be copied or lent without their permission in writing.
R&IS_F_3
04 33KV LINE BAY
SL No Description Make QTY
Control & relay Panel Dimensions (H x W x D)
01 2315 x 800 x 800 mm
L&T E&A 1
Schneider/
02 Numerical Relay : 50 + 51+ 50N + 51N
Siemens/GE/ABB
1
Schneider/
03 BCU ( Per two bay)
Siemens/GE/ABB
1

04 Trip relays (Electrical Reset) Ashida / Equivalent 1


05 Trip ckt supervision relay ABB / Equivalent 2
Siemens contactors/ OEN
06 AC/DC supervision relays
relays
4
Siemens contactors/ OEN
07 Contactors for contact multiplications
relays
3

08 Test terminal blocks for metering circuits DAV 1


09 Tariff meter Client Scope 1
10 Breaker control switch, Salzer 2
11 LED indication lamp other than blue and white Esbee 8
12 LED indication blue and white Esbee 5
13 Space Heater VILECO 1
14 Thermostat Apt 1
15 Illumination lamp holder with CFL lamp Anchor 1
16 Socket type:-domestic make piano type switch 10A Anchor 1
17 Black colour pushbutton with NO contact Esbee 6
18 MCBs L&T E&A 10
19 Add on contact for MCB L&T E&A 4
20 Fuse with link and base L&T E&A 10
21 RJ45 patch chords Iveonet 4
*Make of components is subject to change during detail engineering

SHAMA POWER INDIA LIMITED A/C AIIMS


Customer
AEGCL
CONSTRUCTION OF 132/33KV, 1X25 MVA ESE-R&IS-CRP-
Electrical Systems & Equipment
SUB-STATION AT AIIMS CAMPUS 235-2009-00
Project
(CHANGSARI) , GUWAHATI, ALONG WITH
ASSOCIATED TRANSMISSION LINE
Consultant PAGE 5 OF 7
PREP. SN DATE 16.09.20
CHKD TECHNICAL OFFER FOR CRP Panel REV 00
SN APPD. BM
.
This document is the property of L&T Electrical & Automation and must not be copied or lent without their permission in writing.
R&IS_F_3
05 33KV TRANSFORMER I/C PROTECTION CONTROL PANEL
SL No Description Make QTY
Control & relay Panel Dimensions (H x W x D)
01 2315 x 800 x 800 mm
L&T E&A 1
Schneider/Siemens/
02 Trafo differential relay + REF
GE/ABB
1
Schneider/Siemens/
03 Numerical Relay : 50 + 51+ 50N + 51N( for LV side and HV side)
GE/ABB
2
Schneider/Siemens/
04 BCU
GE/ABB
1

05 Trip relays (Electrical Reset) Ashida/Equivalent 3


06 Trafo Aux relays Ashida/Equivalent 4
07 Trip ckt supervision relay ABB/Equivalent 4
Siemens contactors/OEN
08 AC/DC supervision relays
relays
4
Siemens contactors/OEN
09 Contactors for contact multiplications
relays
3

10 Test terminal blocks for metering circuits Dav 1


11 Tariff meter client scope 1
12 Breaker control switch Salzer 2
13 LED indication lamp other than blue and white Esbee 8
14 LED indication blue and white Esbee 5
15 Space Heater VILECO 1
16 Thermostat Apt 1
17 Illumination lamp holder with CFL lamp Anchor 1
18 Socket type:-domestic make piano type switch 10A Anchor 1
19 Black colour pushbutton with NO contact Esbee 6
20 MCBs L&T E&A 10
21 Add on contact for MCB L&T E&A 4
22 Fuse with link and base L&T E&A 10
23 Ethernet switch L&T E&A 2
24 RJ45 patch chords Iveonet 10
*Make of components is subject to change during detail engineering

SHAMA POWER INDIA LIMITED A/C AIIMS


Customer
AEGCL
CONSTRUCTION OF 132/33KV, 1X25 MVA ESE-R&IS-CRP-
Electrical Systems & Equipment
SUB-STATION AT AIIMS CAMPUS 235-2009-00
Project
(CHANGSARI) , GUWAHATI, ALONG WITH
ASSOCIATED TRANSMISSION LINE
Consultant PAGE 6 OF 7
PREP. SN DATE 16.09.20
CHKD TECHNICAL OFFER FOR CRP Panel REV 00
SN APPD. BM
.
This document is the property of L&T Electrical & Automation and must not be copied or lent without their permission in writing.
R&IS_F_3
06 Technical Consideration
Indoor simplex design having swing frame, glass door, no rear access with bottom cable entry
1
is considered
Breakers for line feeder are considered as pole operated whereas breakers for buscoupler is
2
assumed to be gang operated.
Numerical relays and BCU are offered with IEC61850 protocol with dual RJ45/FO port for
3
communication with SCADA
Separate control & relay panel considered for 132KV line bay whereas single protection cum
4
control panel is considered for 132 buscoupler bay and 33KV bays
5 Mimic and semaphore indicators are not considered.
MFM, voltmeter, ammeter are not considered. For ABT meter, we will provide the cut-out. The
6
scope of supply of tariff meter is in client scope
7 Annunciator window, bell, hooter is not considered, as same is not mentioned in TS
8 Aux supply is considered as 110V DC.
9 for 33KV bays, individual BCU is considered.
10 Redundant Ethernet Switches and communication patch chords are considered.
Supply of any electrical and communication cables with necessaries accessories outside
11
Panel with connectors are not in our scope of supply.
Control cable laying and termination between breaker and control relay panel is not included
12
in scope.
13 Training and site commissioning on per diem basis.
Relays Settings and parameterisation is not in scope of supply. It can be provided with extra
14
price
15 Future / Spares are not considered in offer.

SHAMA POWER INDIA LIMITED A/C AIIMS


Customer
AEGCL
CONSTRUCTION OF 132/33KV, 1X25 MVA ESE-R&IS-CRP-
Electrical Systems & Equipment
SUB-STATION AT AIIMS CAMPUS 235-2009-00
Project
(CHANGSARI) , GUWAHATI, ALONG WITH
ASSOCIATED TRANSMISSION LINE
Consultant PAGE 7 OF 7
PREP. SN DATE 16.09.20
CHKD TECHNICAL OFFER FOR CRP Panel REV 00
SN APPD. BM
.
This document is the property of L&T Electrical & Automation and must not be copied or lent without their permission in writing.