8 10A, 2 Pole 2 Way without off Local / Remote Selector Switch KAYCEE 1
9 R-Y-B Indication Lamp, LED Type, 240V AC. L&T 3
10 On (R) /Off (G) /Trip (A) /Spring Charge (B) Indication Lamp, L&T 4
LED Type, 240V AC.
11 16A, T-N-C Switch for breaker control (2C + 2T) KAYCEE 1
12 Electronic on delay timer with 2 C/O contact, 240V AC EAPL/L&T 1
13 6A TPN MCB, 10KA ABB/L&T/SIEMENS/ 2
SCHNEIDER
14 16A DP MCB, 10KA ABB/L&T/SIEMENS/ 1
SCHNEIDER
15 6A DP MCB, 10KA ABB/L&T/SIEMENS/ 6
SCHNEIDER
16 2.5sq. mm. control terminal ELMEX 25
17 Disconnecting type Terminals, 2 BA size, stud type ELMEX 10
LINE PT 2 1 6A TP MCB, 10KA ABB/L&T/SIEMENS/ 1
SCHNEIDER
2 6A TPN MCB, 10KA ABB/L&T/SIEMENS/ 1
SCHNEIDER
3 0-500V AC Digital Voltmeter, 96 Sq mm, Cl : 1.0, PT sec. : 110V AC, Aux. SCHNEIDER/L&T 1
supply 240V AC
4 16A, 3 position (RY-YB-BR) With -off Voltmeter selector switch KAYCEE 1
5 415V/√3: 110V/√3 AC 3Phase Fixed type Potential Transformer, INDUSREE 3
Secondary Winding Cl. : 1.0, 33.3 VA for PH.
BUS- 1 1 1000A 4P EDO ACB, 50KA with Micro-processor based release for O/C, ABB/L&T/SIEMENS/ 1
COUPLER S/C & E/F protection, Sp. Chgd. Motor : 240V AC, Closing Coil : 240V SCHNEIDER
AC, St. Coil : 240V AC, U/V Coil : 240V AC, trip signaling common micro
switch, Spring charge limit sw, Frame earthing contact, Service & test
position limit switch, Automatic safety shutters with 4 NO + 4 NC Aux-
Contact
2 Aux-Contactor with 2 NO + 2 NC contact, 240V AC ABB/L&T/SIEMENS/ 6
SCHNEIDER
3 10A, 2 Pole 2 Way without off Local / Remote Selector Switch KAYCEE 1
4 On (R) /Off (G) /Trip (A) /Spring Charge (B) Indication Lamp, LED Type, L&T 4
240V AC.
5 16A, T-N-C Switch for breaker control (2C + 2T) KAYCEE 1
6 16A DP MCB, 10KA ABB/L&T/SIEMENS/ 1
SCHNEIDER
7 6A DP MCB, 10KA ABB/L&T/SIEMENS/ 7
SCHNEIDER
8 2.5sq. mm. control terminal ELMEX 25
INTERLOCK 1 1 Electro-mechanical Interlock Between two Incomer & one Bus-coupler PCE 1
180KW DOL 4 1 500A TP MCCB, 50KA with microprocessor based release for O/C, S/C & ABB/L&T/SIEMENS/ 1
STARTER for E/F Protection. Extended Door drive kit & spreader with 1NO + 1NC Aux. SCHNEIDER
main pump- switch
1,2,3 & spare 2 CBCT Operated earth leakage relay, 240V AC L&T (GIC) 1
3 500A TP Air Break Contactor (AC-3) with 2 NO + 2 NC contact, 240V AC ABB/L&T/SIEMENS/ 1
SCHNEIDER
4 400/5A Bar Primary type C.T, Class: 1.0, 10VA (Resin Cast) KAPPA 3
5 400/5A Bar Primary type C.T, Class: 5P10, 10VA (Resin Cast) KAPPA 3
6 400/5A Bar Primary type C.T, Class: 1.0, 10VA (Resin Cast) for remote KAPPA 1
Ammeter
7 Microprocessor based motor protection relay, auxiliary supply : 240V ABB / SCHNEIDER 1
AC, 2 C/O output contact, CT Secondary : 5A with RS 485 Port (AREVA)
8 0-400A Digital Ammeter, 96Sq mm, Cl : 1.0, CT sec : 5A, Aux. supply 240V SCHNEIDER/L&T 1
AC
9 16A, 3 position (R-Y-B) With -off Ammeter selector switch KAYCEE 1
10 16A, 2 Pole 2 Way without off L/R selector switch KAYCEE 1
11 Flush mounting type high speed tripping relay, 240V AC, Contact: 3 NO AREVA 1
+1 NC HR, 1/4N Vert. Case VAJH-13
12 On (R)/ Off (G) / Trip (A) Indication Lamp, LED Type, 240V AC. L&T 3
13 Start (G) /Stop (R) Push Button with Spring return type actuator with 1 NO L&T 2
/ 1 NC Contact
14 Aux-Contactor with 2 NO + 2 NC contact, 240V AC ABB/L&T/SIEMENS/ 3
SCHNEIDER
15 6A TPN MCB, 10KA ABB/L&T/SIEMENS/ 1
SCHNEIDER
16 6A DP MCB, 10KA ABB/L&T/SIEMENS/ 2
SCHNEIDER
17 2.5sq. mm. control terminal ELMEX 25
18 3 Way power terminals DESUN 1
250A MCCB 2 1 250A TP+N MCCB (TP MCCB with manually isolated neutral link), 50KA ABB/L&T/SIEMENS/ 1
FEEDER for with Thermo-magnetic release for O/C & S/C protection with spreader SCHNEIDER
APFC with 1NO + 1NC Aux. sw. & 1 No Alarm switch, S/T Coil : 240V AC
8 0-400A Digital Ammeter, 96Sq mm, Cl : 1.0, CT sec : 5A, Aux. supply 240V SCHNEIDER/L&T 1
AC
9 16A, 3 position (R-Y-B) With -off Ammeter selector switch KAYCEE 1
10 16A, 2 Pole 2 Way without off L/R selector switch KAYCEE 1
11 Flush mounting type high speed tripping relay, 240V AC, Contact: 3 NO AREVA 1
+1 NC HR, 1/4N Vert. Case VAJH-13
12 On (R)/ Off (G) / Trip (A) Indication Lamp, LED Type, 240V AC. L&T 3
13 Start (G) /Stop (R) Push Button with Spring return type actuator with 1 NO L&T 2
/ 1 NC Contact
14 Aux-Contactor with 2 NO + 2 NC contact, 240V AC ABB/L&T/SIEMENS/ 3
SCHNEIDER
15 6A TPN MCB, 10KA ABB/L&T/SIEMENS/ 1
SCHNEIDER
16 6A DP MCB, 10KA ABB/L&T/SIEMENS/ 2
SCHNEIDER
17 2.5sq. mm. control terminal ELMEX 25
18 3 Way power terminals DESUN 1
250A MCCB 2 1 250A TP+N MCCB (TP MCCB with manually isolated neutral link), 50KA ABB/L&T/SIEMENS/ 1
FEEDER for with Thermo-magnetic release for O/C & S/C protection with spreader SCHNEIDER
APFC with 1NO + 1NC Aux. sw. & 1 No Alarm switch, S/T Coil : 240V AC
8 0-400A Digital Ammeter, 96Sq mm, Cl : 1.0, CT sec : 5A, Aux. supply 240V SCHNEIDER/L&T 1
AC
9 16A, 3 position (R-Y-B) With -off Ammeter selector switch KAYCEE 1
10 16A, 2 Pole 2 Way without off L/R selector switch KAYCEE 1
11 Flush mounting type high speed tripping relay, 240V AC, Contact: 3 NO AREVA 1
+1 NC HR, 1/4N Vert. Case VAJH-13
12 On (R)/ Off (G) / Trip (A) Indication Lamp, LED Type, 240V AC. L&T 3
13 Start (G) /Stop (R) Push Button with Spring return type actuator with 1 NO L&T 2
/ 1 NC Contact
14 Aux-Contactor with 2 NO + 2 NC contact, 240V AC ABB/L&T/SIEMENS/ 3
SCHNEIDER
15 6A TPN MCB, 10KA ABB/L&T/SIEMENS/ 1
SCHNEIDER
16 6A DP MCB, 10KA ABB/L&T/SIEMENS/ 2
SCHNEIDER
17 2.5sq. mm. control terminal ELMEX 25
18 3 Way power terminals DESUN 1
250A MCCB 2 1 250A TP+N MCCB (TP MCCB with manually isolated neutral link), 50KA ABB/L&T/SIEMENS/ 1
FEEDER for with Thermo-magnetic release for O/C & S/C protection with spreader SCHNEIDER
APFC with 1NO + 1NC Aux. sw. & 1 No Alarm switch, S/T Coil : 240V AC
8 0-400A Digital Ammeter, 96Sq mm, Cl : 1.0, CT sec : 5A, Aux. supply 240V SCHNEIDER/L&T 1
AC
9 16A, 3 position (R-Y-B) With -off Ammeter selector switch KAYCEE 1
10 16A, 2 Pole 2 Way without off L/R selector switch KAYCEE 1
11 Flush mounting type high speed tripping relay, 240V AC, Contact: 3 NO AREVA 1
+1 NC HR, 1/4N Vert. Case VAJH-13
12 On (R)/ Off (G) / Trip (A) Indication Lamp, LED Type, 240V AC. L&T 3
13 Start (G) /Stop (R) Push Button with Spring return type actuator with 1 NO L&T 2
/ 1 NC Contact
14 Aux-Contactor with 2 NO + 2 NC contact, 240V AC ABB/L&T/SIEMENS/ 3
SCHNEIDER
15 6A TPN MCB, 10KA ABB/L&T/SIEMENS/ 1
SCHNEIDER
16 6A DP MCB, 10KA ABB/L&T/SIEMENS/ 2
SCHNEIDER
17 2.5sq. mm. control terminal ELMEX 25
18 3 Way power terminals DESUN 1
250A MCCB 2 1 250A TP+N MCCB (TP MCCB with manually isolated neutral link), 50KA ABB/L&T/SIEMENS/ 1
FEEDER for with Thermo-magnetic release for O/C & S/C protection with spreader SCHNEIDER
APFC with 1NO + 1NC Aux. sw. & 1 No Alarm switch, S/T Coil : 240V AC
8 0-500A Digital Ammeter, 96Sq mm, Cl : 1.0, CT sec : 5A, Aux. supply 240V SCHNEIDER/L&T 1
AC
9 16A, 3 position (R-Y-B) With -off Ammeter selector switch KAYCEE 1
10 16A, 2 Pole 2 Way without off L/R selector switch KAYCEE 1
11 Flush mounting type high speed tripping relay, 240V AC, Contact: 3 NO AREVA 1
+1 NC HR, 1/4N Vert. Case VAJH-13
12 On (R)/ Off (G) / Trip (A) Indication Lamp, LED Type, 240V AC. L&T 3
13 Start (G) /Stop (R) Push Button with Spring return type actuator with 1 NO L&T 2
/ 1 NC Contact
14 Aux-Contactor with 2 NO + 2 NC contact, 240V AC ABB/L&T/SIEMENS/ 3
SCHNEIDER
15 6A TPN MCB, 10KA ABB/L&T/SIEMENS/ 1
SCHNEIDER
16 6A DP MCB, 10KA ABB/L&T/SIEMENS/ 2
SCHNEIDER
17 2.5sq. mm. control terminal ELMEX 25
18 3 Way power terminals DESUN 1
315A MCCB 2 1 315A TP+N MCCB (TP MCCB with manually isolated neutral link), 50KA ABB/L&T/SIEMENS/ 1
FEEDER for with Thermo-magnetic release for O/C & S/C protection with spreader SCHNEIDER
APFC with 1NO + 1NC Aux. sw. & 1 No Alarm switch, S/T Coil : 240V AC
2 Valve Opening Push Button with spring return actuator type with 2NO contact L&T 1
3 Emergency STOP push button, murshroom head type press to lock and trun to L&T 1
release, lockable type with 2 NC contact
4 Indication Lamp, LED type, 240V AC for Motor ON L&T 1
5 Indication Lamp, LED type, 240V AC for Valve Open L&T 1
6 Indication Lamp, LED type, 240V AC for Valve Close L&T 1
7 10A, 2 Pole 2 Way without off Local / Remote Selector Switch KAYCEE 1
8 6A DP MCB, 10KA for Control ABB/L&T/SIEMENS/S 1
CHNEIDER
9 2.5Sq. mm. Control Terminals ELMEX 25
LPBS FOR BOOSTER PUMP FOR PUMP HOUSE (3Nos. for each location)
SL. NO. FEEDER COMPONENTS MAKE QTY
1 Start Push Button with spring return type actuator 2NO contact L&T 1
2 Emergency STOP push button, murshroom head type press to lock and trun to L&T 1
release, lockable type with 2 NC contact
3 0-400/1000A Digital Ammeter, 96Sq mm, CT sec : 5A, SCHNEIDER/SECUR 1
E
4 10A, 2 Pole 2 Way without off Local / Remote Selector Switch KAYCEE 1
5 6A DP MCB, 10KA for Control ABB/L&T/SIEMENS/S 1
CHNEIDER
6 2.5Sq. mm. Control Terminals ELMEX 20
19
65 KVAR APFC PANEL AT MATHURAPUR-1 SITE
FEEDER QTY FEEDER COMPONENTS MAKE QTY
NAME
CAP. BANK 1 1 250A TP MCCB, 50KA with thermal magnetic based release for O/C ABB/L&T/SIEMENS 1
INCOMER: & S/C protection, Extended type door drive kit with spreader with /SCHNEIDER
1NO + 1NC Aux. contact & 1NO alarm contact
2 250/5A Bar Primary type C.T., CL-1.0, 10VA (CAST RESIN) KAPPA 3
3 0-250A Digital Ammeter, 96Sq mm, Cl : 1.0, CT sec : 5A, Aux. supply SCHNEIDER/L&T 1
240V AC
4 0-500V AC Digital Voltmeter, 96 Sq mm, Cl : 1.0, Aux. supply 240V AC SCHNEIDER/L&T 1
20
75 KVAR APFC PANEL AT MATHURAPUR-II SITE
FEEDER QTY FEEDER COMPONENTS MAKE QTY
NAME
CAP. BANK 1 1 250A TP MCCB, 50KA with thermal magnetic based release for O/C ABB/L&T/SIEMENS 1
INCOMER: & S/C protection, Extended type door drive kit with spreader with /SCHNEIDER
1NO + 1NC Aux. contact & 1NO alarm contact
2 250/5A Bar Primary type C.T., CL-1.0, 10VA (CAST RESIN) KAPPA 3
3 0-250A Digital Ammeter, 96Sq mm, Cl : 1.0, CT sec : 5A, Aux. supply SCHNEIDER/L&T 1
240V AC
4 0-500V AC Digital Voltmeter, 96 Sq mm, Cl : 1.0, Aux. supply 240V AC SCHNEIDER/L&T 1
21
95 KVAR APFC PANEL AT MOGRAHAT-1 SITE
FEEDER QTY FEEDER COMPONENTS MAKE QTY
NAME
CAP. BANK 1 1 315A TP MCCB, 50KA with thermal magnetic based release for O/C ABB/L&T/SIEMENS 1
INCOMER: & S/C protection, Extended type door drive kit with spreader with /SCHNEIDER
1NO + 1NC Aux. contact & 1NO alarm contact
2 300/5A Bar Primary type C.T., CL-1.0, 10VA (CAST RESIN) KAPPA 3
3 0-300A Digital Ammeter, 96Sq mm, Cl : 1.0, CT sec : 5A, Aux. supply SCHNEIDER/L&T 1
240V AC