RATING : 40 / 50 MVA 66 / 11.5 kV
CUSTOMER: M/s. MUNDRA SOLAR TECHNOLOGY LIMITED , DISTRICT KUTCH, GUJARAT, INDIA
PROJECT NAME: 2GW WAFER & INGOT PLANT, MUNDRA, KUTCH
W.O.No.: 5964 Date & Rev.No.: 04.11.2022 & R0
LOSS DETAILS
Submit calculation
Guaranteed No-load losses = 25 kW (Max)
Guaranteed Load losses at Nor tap at 50MVA(ONAF) = 125 kW (Max)
Calculated Load losses at Min tap at 50MVA(ONAF) = 135 kW (Max)
Total losses at Min tap at 50MVA(ONAF) (NLL+LL@min tap) = 25 + 135 kW
= 160 kW
Load losses at Min tap at 40MVA(ONAN) = 135x (40/50) ^2
= 86.4 kW
Total losses at Min tap at 40MVA(ONAN) (NLL+LL@min tap) = 25 + 86.4 kW
= 111.4 kW
As per internal design manual watts/m2 dissipated by MS tank is 750W. We consider full
dissipation by tank cover as cover surface is fully exposed to embrace air contact where as
67% dissipation by side walls is considered in view of obstructed air flow caused by mouting
of radiators/control boxes(marshalling box,FCC),etc.
ALL INFORMATION IN THIS DOCUMENT IS CONFIDENTIAL AND SHOULD NOT BE USED WITHOUT PRIOR CONSENT OF INDO TECH TRANSFORMERS LIMITED
Top Oil Rise = Average Oil Rise + T2
T2 (Top header oil rise - Bottom header oil rise) = 14 x Losses at min. tap ^0.5
2 Thermal head
= 6
T2 (Top header oil rise - Bottom header oil rise) = 14 x Losses at min. tap ^0.5
2 Thermal head
= 7.2
Air flow required for dissipating 160 kW = 0.97 x160 / 14.4 m3/sec
= 10.78
ALL INFORMATION IN THIS DOCUMENT IS CONFIDENTIAL AND SHOULD NOT BE USED WITHOUT PRIOR CONSENT OF INDO TECH TRANSFORMERS LIMITED
Fan selected (900 rpm 24 inches) = 10450 m3/hr air flow
= 10450/3600 m3/sec air flow
= 2.9 m3/sec air flow
No. of fans requried = 10.78 / 2.9 no's
= 3.72 fans
ALL INFORMATION IN THIS DOCUMENT IS CONFIDENTIAL AND SHOULD NOT BE USED WITHOUT PRIOR CONSENT OF INDO TECH TRANSFORMERS LIMITED
HOTSPOT CALCULATION
where,
ALL INFORMATION IN THIS DOCUMENT IS CONFIDENTIAL AND SHOULD NOT BE USED WITHOUT PRIOR CONSENT OF INDO TECH TRANSFORMERS LIMITED