Professional Documents
Culture Documents
1. SPECIFICATIONS
Description Specification
Heater Core size (mm²) 200 x 165.5 x 25
Capacity (kcal/h) 4,700
Evaporator Core size (mm²) 254.8 x 196.7 x 60
Capacity (kcal/h) 4,700
Blower Supplied power (W) 240 + 10% Max (at12V)
Fan speed (rpm) 2900 ± 200
Supply voltage (V) 12.0
PTC Supply power (W) 900~1,050
Compressor Capacity (cc/rev) 170
Diameter of pulley (mm) 120
Max. speed (rpm) 8,000
Supply voltage (V) 12.0
Power consumption (A) 2.2
Discharge pressure (kgf/cm²G) 8~10
Power transistor Supply voltage (V) 12.0
Operating temperature (℃) -30℃~60℃
Resistance Hi-Low (Ω) 2.0 Ω ± 10%
Hi-ML (Ω) 0.9 Ω ± 10%
Hi-MH (Ω) 0.4 Ω ± 10%
01-4
2. MAJOR CHANGES
Console rear duct
Poam pad
Bracket
Console rear duct bracket removed and upper part's appearance changed due to changed cup
holder/poam pad used
6810-01 01-5
3. COMPONENTS
1. Compressor Assy-A/CON
2. Condenser Assy
3. Receiver Drier & Brkt Assy
4. Hose Assy-Discharge & Suction
5. Pipe Assy-Joint
6. Pipe Assy-Liquid No1
7. Pipe Assy-Liguid No2
8. Hose Assy-Liguid
9. Hose Assy-Heater Inlet
10.Hose Assy-Heater Outlet
11.Hose-Drain
6810-01 01-7
4. TROUBLESHOOTING
1) Overview
The FATC has a self-diagnosis function that can diagnose the system by itself. Before checking a
component, be sure to check the fault code by using the self-diagnosis function. The self-diagnosis
consists of 6 steps. The temperature control dial (step 2 to 5) and fan speed dial (step 6) are used to
enter each step of the self-diagnosis. The 6 steps of the self-diagnosis are:
▶ Step 1
- The VFD and all LED segments are checked for proper illumination.
▶ Step 2
- The sensors and air mix door are checked for proper operation.
▶ Step 3
- The position and condition of the air source door and mode door are checked.
▶ Step 4
- The actuator door position, fan speed and compressor operation are checked. Pressing the
defroster switch after entering step 4 changes the diagnosis mode as follows: 41 -> 42 -> 43 ->
44 -> 45 -> 46 -> 41.
6810-01 01-9
▶ Step 5
- You can check that the temperature value from each temperature sensor is displayed properly in
this step. Pressing the defroster switch changes the temperature value that appears on the
display in the order as follows:
▶ Step 6
- To enter the step 6 from 5, turn the fan speed dial lightly toward the right not using the
temperature control dial. In this step, you can decrease or increase by up to 3 degrees from the
temperature set on the A/C controller.
2) Self-diagnosis step
(1) Step 1
Turn the ignition ON and press the OFF switch for 5 sec. or more within 10 sec.
Then the first step of the self-diagnosis is started as shown in the below figure.
(2) Step 2
The sensors and air mix door are checked for proper operation in this step. When the step 2 is started,
the number "2", which indicates that the system is in the step 2, apprears on the display and the check
for sensors is performed. Once the check is done (for 10 to 20 sec.), the one digit number between 0
and 8 is added behind "2". "20" means there is no fault code. For the meaning of the rest of the
numbers, refer to the description below.
10 to 20
sec.
Refer to the following table for the meaning of the fault code.
6810-01 01-11
(3) Step 3
In this step, you can check the position and condition of the air source door and mode door. To start step
3, turn the temperature control dial lightly toward the right and confirm that the number 3 appears on the
display. It takes several tens of seconds to finish the check. If there is no fault code, "30" is displayed.
And if there is a malfunction, the corresponding fault code is added as described in the step 2.
Refer to the following table for the meaning of the fault code.
01-12
(4) Step 4
In this step, the door position of each actuator, fan speed and operation of the compressor are checked.
To enter this step, turn the temperature dial to the right in the step 3. The number, "41", appears on the
display as soon as the step 4 is started. Press the defroster switch to change the diagnosis mode.
Press Press
1. Turn temperature dial lightly
toward right to enter step 4
Below table describes the detailed diagnosis items performed for each number. Check the
corresponding component for proper operation according to the table. The voltage values listed in the
table are the output voltage to operate the blower motor. The higher the voltage, the faster the fan speed
is.
6810-01 01-13
(5) Step 5
In this step, the system checks the temperature sensors used to control the A/C. To enter this step, turn
the temperature dial to the right in the step 4. The ambient temperature appears on the display first and
the interior temperature appears next and the intake air temperature last. The display changes the
temperature value each time the defroster switch is pressed.
(6) Step 6
You can increase or decrease by up to 3 degrees from the set temperature. When entering the step 6
from 5, turn the fan speed dial.
1. Turn fan
2. Turn speed dial
temperature to enter
control dial to step 6
adjust
temperature
3) Trouble Diagnosis
(1) Duct Temperature Sensor
If the fault code for the duct temperature sensor (DTC 3) appears on the display, check the sensor as
follows:
A. Remove the duct temperature sensor and measure the resistance between the terminals of the
connector (specification: approx. 2.2 kW at 25℃). If the resistance value is extremely high or
low, replace the duct temperature sensor.
B. If the result is not as specified, replace the duct temperature sensor. If the result is as specified,
proceed to the next step.
C. Turn the ignition switch to ON position and measure the voltage between the connector of the FATC
controller and the duct temperature sensor (specification: approx. 2 V at 25℃).
D. If the voltage cannot be measured, check the wiring for open circuit. If the result is as specified,
replace the FATC controller.
D. If the voltage is out of specified value, check the wiring for open circuit. If the wiring is intact, replace
the power transistor.
A. Remove the thermo AMP and measure the voltage between the terminals no. 1 and 2 of the
connector.
B. Check if the voltage is approx. 12 V when the output is ON and 0 V when the output is OFF.
C. If the voltage value is not as specified, replace the thermo AMP. If the value is as specified, proceed
to the next step.
D. Turn the ignition switch to ON position and turn on the A/C by pressing the A/C button. And measure
the voltage between the terminals A12 and A11 of the FATC controller connector (specification:
approx. 12 V).
E. If the voltage cannot be measured, check the wiring for open circuit. If the result is not as specified,
replace the thermo AMP.
01-16
Sun-load sensor
A/C controller
Thermo AMP
3. VENTILATION SYSTEM
1) Vent Ports Location - Interior
4. A/C MODULE
1) Components
2) Configuration
A/C filter
Air source door
case Blower unit
(upper) case
Blower unit
(lower) case
Evaporator
Power
Duct temperature Transistor A/C cable
sensor assembly
Thermo AMP
Mode door
Mode door
Mode door
actuator
link assembly
6810-01 01-23
3) Wiring Layout
Power transistor
Main wiring
connector
Thermo AMP
Blower motor
Interior
temperature
sensor
A/C controller unit
01-24
1) System Flow
- "Compression -> Condensation -> Expansion -> Evaporation"
2) Functions
(1) Compressor
- Condition: Gas
- Function: Circulates the refrigerant and increases the pressure and temperature for easier
evaporation.
(2) Condenser
- Condition: Gas/Liquid
- Function: Cools and condenses the refrigerant by using ambient air to liquefy it under high pressure.
3) Blower