You are on page 1of 1

SPECIFICQSqATION FOR SPECIFICATION NUMBER

VACUUM : - 0
TEST PRESSURE (kg/cm2g) / (barg) : 9 0
DESIGN TEMP (0C) : 200 0
FLOWING MEDIUM : Gas 0
DENSITY (kg/m3) : 0.40 0
FLOW DIRECTION : VERTICAL 0
VELOCITY (m/sec) : - 0
BELLOWS REQUIREMENT :
TYPE : TIED BELLOW WITH TIE ROD 0
BELLOW MATERIAL : SS 304 0
MATERIAL END & CENTRE PIECE 0
BELLOW DESIGN PRESSURE (kg/cm2g) / (barg) : 11 / FV 0
BELLOWS DUTY : (mm)
AXIAL : SELF EXPANSION * 0
LATERAL1 : (±) 14 0
LATERAL 2 ( TO 1) (±) 14 0
NO OF CYCLES : 7000 0
MAX. SPRING RATE :
AXIAL : (N/cm) 391 * 0
LATERAL : (N/cm) 889 * 0
END CONNECTION :
FLANGED : WELDING END : FLANGED ENDS 0
RATING : 150 # 0
FLG MATERIAL : ASTM A 240 F 304 * 0
THERMAL INSULATION THK (mm) : 50 0
INTERNAL SLEEVES : YES 0
MAXIMUM INSTALLATION LENGTH (mm) : 460 * 0
PLY MULTI PLY 0

* VENDOR TO CONFIRM
SPECIAL NOTE :- 1) BELLOW TO BE DESIGNED AS PER EJMA & ASME SEC. VIII. FOR FULL VACUUM SERVICE & 4-5 (Kg/cm2) MORE THAN INTERNAL
DESIGN PRESSURE OF PIPE.
2) ORDER TO BE PLACED ONLY AGAINST APPROVAL OF VENDOR TECHNICAL QUOTATION WITH G.A.
3) ALL PRESSURE THRUST DEVELOPED FOR 11 KG/CM 2 PRESSURE AND FULL VAC.TO BE ABSORBED BY BELLOW TIE RODS &LUGS.
4) VENDOR TO MARK FLOW ARROW ON BELLOW.
5) VENDOR TO PROVIDE VACUUM TEST PROCEDURE.
6) THIS SPECIFICATION IS PREPARED BASED ON CURRENT LINE ROUTING. IF ANY CHANGE IN LINE ROUTING WILL CAUSE CHANGE
IN BELLOW SPEC.
REVISION NO. 0
ISSUED FOR ENQUIRY
PREPD. BY / DATE
CHKD. BY / DATE
APPD. BY / DATE

You might also like