You are on page 1of 5

Study of Different Components and Their Functions

of an Air Circuit Braker (ACB)


Md. Abdullah Nabil Sadman Sakib Rafat Raisa Tabassum Tasin
Electrical Electronics Engineering Electrical Electronics Engineering Electrical Electronics Engineering
American International University- American International University- American International University-
Bangladesh Bangladesh Bangladesh
Dhaka,Bangladesh Dhaka,Bangladesh Dhaka,Bangladesh
nabilabdullah12@gmail.com sakib75@gmail.com raisatasin715@gmail.com

Lia Moni Tahmina Akter Urmi


Electrical Electronics Engineering Electrical Electronics Engineering
American International University- American International University-
Bangladesh Bangladesh
Dhaka,Bangladesh Dhaka,Bangladesh
liamoni982@gmail.com tahminaurmi99@gmail.com

Abstract—The overall purpose of power system protection is extinguished at the current zero of AC wave.Air break circuit
to detect any faults or abnormal conditions that could cause the breakers are employed in DC circuits and Ac circuits up to
system to malfunction or create a full power outage and isolate 12,000 voltages. Such breakers are usually of indoor type and
them from the healthy portion. Protecting the critical power installed on vertical panels or indoor draw out switch gear.
system equipment will require analysis. A circuit breaker is
AC circuit breakers are widely employed indoor medium
used to break circuits during faulty conditions such as short
circuits or over current manually or remotely. These devices are voltage and low voltage switchgear. [2] Based on the arc
mainly used to protect the system. Few devices namely relays, quenching medium circuit breakers are classified into several
switches, fuses and many more can be connected to protect the types. Air circuit breaker is one of the types. In ACB air is
electrical systems along with circuit breakers. ACB play an used to clear arc from the arcing zone. In this experiment
important part in ensuring that electrical safety devices are construction of ACB is examined properly and following
properly protected. This lab study highlights the manual and things are observed:
automatic contact closing operations, as well as the tripping 1. Observe the contact closing operation manually
mechanism and the under voltage shunt tripping mechanism. 2. Observe the contact closing operation automatically
Keywords— Power system protection, ACB, Faulty conditions.
3. Observe the tripping mechanism
4. Observe the under voltage shunt tripping mechanism [7]
II. THEORY
I. INTRODUCTION
A. Defination and Types of ACB
ACB is the short form for Air Circuit Breaker. Air circuit
breakers (ACB) are used for the protection of circuits which Air Circuit breaker /ACB is an electrical switching device
used to protect electrical circuits from overcurrent, under
have current of about 800 Amperes to 10-kilo Amperes
voltage and short circuits. These devices are generally used in
flowing through them. The ACB provides the circuit
low voltage applications and operate in the air as an arc
protection against the short circuit and the overcurrent extinguishing medium considering the atmospheric pressure.
condition in an electrical circuit. The air circuit breakers ACBs have a large capacity and a steel frame with parts
(ACB’s) are used in the circuits where the voltage range of installed inside.[3]
the circuit is below 450 Volts. The ACB trip is described as
when the current or voltage in a circuit in which the current
between 800A to 10kA is flowing gets greater than the
predefined values the ACB gets opened and the flow of
current and voltage in the circuit is stopped. Similarly, ACB
is opened in case of a short circuit and it prevents the circuit
from more damage. The main function of the ACB is to
quench the arching during overloading. [1]
In the air break, circuit breaker the contact separation and arc
extinction take place in air at atmospheric pressure. In air
break circuit breaker high resistance principle is employed.
In this circuit breaker arc is expanded by the mean of arc
runners, arc chutes, and arc resistance is increased by
splitting, cooling and lengthening.The arc resistance is
increased to such an extent that the voltage drop across the
arc becomes more than the system voltage, and the arc gets
Fig. 1: Air Circuit Breaker [4]

XXX-X-XXXX-XXXX-X/XX/$XX.00 ©20XX IEEE


There are different types of ACB. These are- for low and medium voltage circuits is shown in the figure
1)Plain Break type ACB. below. There are two sets of contacts called the main contacts
2)Magnetic Blowout Type ACB. and arcing or auxiliary contacts. Main contacts are usually of
3)Air Chute ACB. copper and conduct the current in the closed position of the
4)Air Blast Circuit Breaker [4] breakers. They have low contact resistance and are silver
Plain Break Type Air Break Circuit Breaker: It is the simplest plated.
one in which contacts are made in the shape of two horns. The The arcing contacts are hard, heat resistant and usually of
air initially strikes across the shortest distance between the copper alloy. Arcing contacts are used to relieve the main
horns and is driven steadily upwards by the convection contacts from damage due to arcing. The arcing contacts are
currents caused by heating of air during arcing and the easily renewable when required. The auxiliary and arcing
interaction of the magnetic and the electric fields. The arc contacts close before and open after the main contacts during
extends from one tip to the other when the horns are fully the operation.
separated resulting in lengthening and cooling arc. Here the blowouts consist of a steel insert in the arcing
The relative slowness of the process and the possibility of arc chutes. These are so arranged that the magnetic field induced
spreading of adjacent metal works limits the application of in them by the current in the arc moves it upwards still faster.
about 500V and too low power circuits. The steel plates divide the arc into a number of arcs in the
Magnetic Blow-Out Type Air Break Circuit Breaker: Some series.
air circuit breakers are used in the circuits having voltage up The distribution of voltage along the arc length is not linear,
to 11 KV, the arc extinction is accomplished using magnetic but it is accompanied by a rather large anode and cathode
field provided by the current in blowout coils connected in drops. In case the total sum of anode and drops of all the short
series with the circuit being interrupted. Such coils are called arcs in series exceeds the system voltage, conditions for the
blow out the coil. The magnetic field itself does not quick extinction of the arc are automatically established.
extinguish the arc. It simply moves the arc into chutes where When the contact has come in contact with the relatively cool
the arc is lengthened, cooled and extinguished. The arc surfaces of the steel plants gets rapidly and effectively cooled.
shields prevent arc spreading to an adjacent network. The movement of the arc may be naturally or aided by a
magnetic blowout. Thus, the arc is extinguished by lightening
and increasing the power loss of the arc. [2]

B. Ratings of ACB
Air circuit breakers come in with different ratings as different
circuits utilize different current and voltage ratings. However
the standard ratings of the ACB’s lie in the range of 400A to
1600A. Similarly, another class of ACB lies in 2000A to
5000A rating. The standard current ratings of the ACB are
these however, the voltage, the physical ratings of the ACB
vary from manufacturer to manufacturer. [4]

Fig. 2: Magnetic Blow-Out Type Air Break Circuit Breaker

It is important to connect the coils at correct polarity so that


the arc is directed upwards. As the breaking action becomes
more effective with large currents, this principle has resulted
in increasing the rupturing capacities of such breakers to
higher values.
Arc chute is an efficient device for arc extinction in air and
performs the following three interrelated functions
1. It confines the arc within a restricted space. Fig. 3: ACB Rating [4]
2. It provides magnetic control over the arc movement so as
to make arc extinction within the devices.
3. It provides for the rapid cooling of arc gasses to ensures III. WORKING PRINCIPLE
arc extinction by deionization. Air circuit breakers operate with their contacts in free air.
Air Chute Air Break Circuit Breaker: The normal Their method of arc quenching control is entirely different
arrangement of air-chute air break circuit breaker employed from that of oil circuit-breakers. They are always used for a
low-voltage interruption and now tends to replace high- avoid rust and enhance reliability. The coordination of
voltage oil breakers. The below-shown figure illustrates the components within the frame allows ACBs to perform
principle of air breaker circuit operation. different functions and also consists of an electrical switch to
Air Circuit breakers generally have two pairs of contacts. The obtain stable performance.
main pair of contacts (1) carries the current at normal load 4.The rated current and shell rating of ACB is higher
and these contacts are made of copper metal. The second pair compared to other circuit breakers. This also means that the
is the arcing contact (2) and is made of carbon. When the allowable current value of ACB is also higher and can be used
circuit breaker is being opened, the main contacts open first. to protect the motor. [3]
When the main contacts opened the arcing contacts are still
in touch with each other. As the current gets a parallel low
resistive path through the arcing contact. During the opening V. CONSTRACTION & MAINTAINANCE OF ACB
of main contacts, there will not be any arcing in the main The construction of an air circuit breaker can be done by
contact. The arcing is only initiated when finally the arcing using different internal and external parts like the following.
contacts are separated. The each of the arc contacts is fitted The external parts of ACB mainly include the ON & OFF
with an arc runner which helps. The arc discharge to move button, an indicator for the position of the main contact, an
upward due to both thermal and electromagnetic effects as indicator for the mechanism of energy storage, LED
shown in the figure. As the arc is driven upward it enters in indicators, RST button, controller, rated nameplate, handle
the arc chute, consisting of splatters. for energy storage, displays, shake, fault trip rest button,
The arc in the chute will become colder, lengthen and split rocker repository, etc. [6]
hence arc voltage becomes much larger than the system
voltage at the time of operation of air circuit breaker, and
therefore the arc is extinguished finally during the current
zero.
The air brake circuit box is made of insulating and fireproof
material and it is divided into different sections by the barriers
of the same material, as shown above,. At the bottom of each
barrier is a small metal conducting element between one side
of the barrier and the other. When the arc, driven upwards by
the electromagnetic forces, enters the bottom of the chute, it
is split into many sections by the barriers, but the each metal
piece ensures electrical continuity between the arcs in each
section, the several arcs are consequently in the series.
When the oscillation starts between C and L as described
for the idealised circuit breaker shown in Figure below, this
resistance damps the oscillation heavily. Certainly, it is
usually so heavy that the damping is critical, the oscillation
cannot then take place at all, and the restriking voltage, Fig. 4: Construction of ACB [6]
instead of appearing as a high-frequency oscillation, rises
dead-beat to its eventual value of peak generator voltage. [5] The internal parts of ACB mainly include supporting
structure with steel sheet, the current transformer used to
protect the trip unit, pole group insulating box, horizontal
IV. CHARECTARISTICS & FUNCTIONS OF ACB terminals, arcing chamber, trip unit for protection, terminal
ACBs are used in power systems including transformers, box, closing springs, CB opening & closing control, plates to
power distribution stations, industrial and mining enterprises move arcing and main contacts, plates for fixed main &
due to its multiple advantages such as high sectional arcing contacts. [5]
capability, perfect function, compact structure and excellent
performance. ACBs work like circuit protection devices for an extensive
1.When the incident of current overload or failure happens, range of low voltage applications up to 600V AC like UPS,
ACB will instantly cut off the circuit acting as a combination generators, mini power stations, MCCB distribution boards,
of a fuse switch and an overheating relay. Under-voltage etc and their sizes range from 400A to 6300A otherwise
protection, and short-circuit protection are effective in larger.In this circuit breaker, nearly 20% of failures in the
solving the problems of power equipment and lines. power distribution system occur due to less maintenance,
2.ACBs control the electrical circuits to operate electrical tough grease, dust, corrosion & frozen parts. So maintenance
equipment normally by cutting off and connecting the load of circuit breaker is the ideal choice to ensure consistent
circuit. These devices are compact due to their small size and operation as well as expand the lifetime. The air circuit
lightweight. Industrial, mining, power transformers, breaker maintenance is very important. For that, it should be
distribution stations, and in many more places ACBs are used turned off first, and then separated from both faces by
as they match the requirements of the industry and are easy opening the required electrical isolator. The circuit breaker
to install. should be worked at this no isolated condition for restricted
3.Insulation plates are used in ACBs as a protective measure and distant areas in every year. The circuit breaker must be
on both sides to separate the conductors while ensuring safety worked electrically from restricted and isolated after that
in daily operation. The parts are placed within the frame to mechanically from restricted. This kind of process will make
the breaker more consistent by detaching any outside layer routine tests of a circuit breaker are a trip test, insulation
developed among sliding faces. [6] resistance, connection, contact resistance, overload tripping,
instantaneous magnetic tripping, etc.
For testing a circuit breaker, different kinds of test equipment
VI. APPARATUS are used to verify the condition of the circuit breaker in any
To do this lab we must need some equipment that are power system. This testing can be performed through
required for conduct lab. The required apparatus are- different test methods as well as kinds of testing equipment.
1. ACB The testing devices are analyzer, micro ohmmeter, primary
2. DC source injection tester with high current, etc. There are some benefits
3. Clamp Meter [7] of circuit breaker testing like the following.
1.The performance of the circuit breaker can be enhanced.
2.The circuit can be checked on load or offload.
VII. EXPERIMENTAL PRESIDURE 3.Recognizes requirement of maintenance
For energizing the charging motor, closing the contacts, 4.Issues can be avoided
opening the contacts and under voltage tripping, the terminals 5.Early indications of faults can be identified [6]
of control circuits for the motor are connected as shown in
the diagram. One incandescent lamp is connected across one
of the three phases of the contacts and the neutral. [7] IX. ADVANTAGE & DISADVANTAGE OF ACB
The advantages of an air circuit breaker include the
following.
1. High-speed re-closures facility
2. Used for frequent operation
3. Need less maintenance
4. High-speed operation
5. Fire risk can be eliminated not like in oil circuit breakers
6. Consistent and short arcing time, so burning of contacts is
less.
The disadvantages of air circuit breaker include the
following.
1.A drawback of the arc chute principle is its inefficiency at
low currents where the electromagnetic fields are weak.
2.The chute itself is not necessarily less efficient in its
lengthening and de-ionizing action than at high currents, but
the arc movement into the chute tends to become slower, and
high-speed interruption is not necessarily obtained. [6]
Fig. 4: Implementation of experimental circuit [7]

X. APPLICATIONS
When the ON switch is pushed the contacts will be closed and
the lamp will glow and when the “OFF” switch is pushed the Air Circuit Breakers are used for controlling the power
contacts will be opened and the lamp will stop glowing. It is station auxiliaries and industrial plants. They offer protection
important to keep in mind that the voltage across the under to industrial plants, electrical machines like transformers,
voltage coil (i.e D1 and D2) should be maintained at about capacitors, and generators.
220 V (ac) otherwise contacts cannot be closed by pushing 1.They are mainly used for the protection of plants, where
the ON switch. If the voltage across the under voltage coil is there are possibilities of fire or explosion hazards.
reduced below 200 V (approax.) the breaker will 2.The air brake principle of the air breaker circuit arc is used
automatically be tripped. [7] in DC circuits and AC circuits up to 12KV.
3.The air circuit breakers have high resistance power that
helps in increasing the resistance of the arc by splitting,
VIII. TESTING PROCEDURE cooling, and lengthening.
Circuit Breaker Testing is mainly used to check each 4.An air circuit breaker is also used in the Electricity sharing
switching system operation as well as the programming of the system and NGD about 15kV [6]
complete tripping construction. So, testing is very essential
for any kind of circuit breaker to ensure secure and consistent
XI. REPORT QUESTION AND ANSWER
performance. As compared to other devices, performing
testing is more challenging. Suggest a protection scheme for a 10HP motor.
When a malfunction occurs in a circuit breaker then it can Answer: The amount of protection and its type, used for a
lead to a short circuit within the coils, incorrect behavior, motor is a compromise between factors such as the
damage the mechanical connections, etc. Thus, circuit importance of the motor, the potential dangers, the type of
breakers need to test regularly to overcome all these faults. duty and the requirements of protection coordination against
Different types of tests performed in circuit breaker mainly the cost of the protection scheme.The protection schemes that
include mechanical, thermal, dielectric, short circuit, etc. The are illustrated represent common practise and international
recommendations for the protection of motors of different XII. DISCUSSION
powers, and are divided into 4 categories: The air circulates the circuit breaker's magnetic coil, where it
1.Protection of low power motors (less than 100 HP); acts as an ARC quenching medium. It is very simplistic in
2.Protection of motors up to 1 000 HP; construction. Circuit breakers smaller than normal are
3.Protection of motors greater than 1 000 HP; associated with air circuit breakers. The length of the distance
4.Additional protection for synchronous motors. between the contacts should be wide because if we use it in
Protection of low power motors: Low power motors are high voltage the ARC needs to be extinguished with no
normally protected by fuses associated with thermal overload particular arrangement. The air circuit breaker doesn't need
relays incorporating bimetallic elements (Figure 5) – the an arc control system because it is set to run at 1KV. The only
fuses protecting against short circuits. perfect alternatives in the case of severe fault current and low
voltage are those that use ABCs with an appropriate arc
control system (low voltage level above 1 KV).

XIII. CONCLUSION
Due to the present pandemic situation as our university is
closed we can not observe the above equipment in hand. But
our honorable faculty did his at best to understood us about
all the functions, characteristics and specifications of those
equipment. To make our understanding more convenience
our faculty shows us a video which helps us more to
understand all the features. The main objective of this
experiment was to get familiar with different kinds of
insulators, fuses and Miniature circuit breaker and we have
Fig.5: Schematic of fuse protection for low power motors [8] understood all the specifications very well which is required
to fulfill this lab objective. So we can say, the lab was
Or low voltage breakers plus thermal overload relays (Figure successfully achieved.
6) when the breaker should have a magnetic element to
trip instantaneously under short circuit conditions. [8
REFERENCES
[1] https://www.electgo.com/acb-trip/
[2] https://circuitglobe.com/air-break-circuit-breaker.html
[3] https://www.micronovaimpex.com/how-acb-works/
[4] https://www.electgo.com/what-is-acb/
[5] https://electricalswitchboards.com.au/air-circuit-breaker-works/
[6] https://www.elprocus.com/air-circuit-breaker-acb-working-principle-
application/
[7] aiub lab menual
[8] https://electrical-engineering-portal.com/protection-schemes-of-
generators-and-motors

Fig. 6: Schematic of low voltage breaker protection for low power motor
[8]

You might also like